87740140 SEL 387 Training Notes
-
Upload
bala-murugan -
Category
Documents
-
view
47 -
download
1
Transcript of 87740140 SEL 387 Training Notes
-•• ~'~~S~ •.•..
',,"v British Columbia Transmission,-7 fjo-\.(::l:> -77<11.)
Maintenance StandardProtection and ControlCORPORATION
Subject SEL 387Title: SEL 387 Relay .~.0 -$ -(,
Supplementary Training Notes Number 42.87.732-8
1. Introduction
The SEL 387 relay provides four-input variable-percentage current differential protection andovercurrent protection associated with each input. The relay includes
• three restrained and unrestrained differential elements. The restrained differentialelement has two settable percentage restraint slope characteristics and can be blocked bysecond or fifth harmonic blocking elements. The unrestrained element can be used toquickly clear high magnitude internal faults.
• eleven overcurrent elements for each of the 4 three-phase current inputs. Each group iscomprised of nine torque-controlled elements (one instantaneous, definite time, andinverse-time for phase, negative sequence, and residual currents), and two phasesegregated elements for targeting of level sensing.
• four combined overcurrent elements which operate on the sum of phase currents from tworelay terminals.
2. Overcurrent Protection
Phase overcurrent elements operate on the maximum phase current of A-,B-, or C-phase currents atany time.
Negative sequence elements respond to 312current, where 312= Ia + Ib(1I240) + Ic(1/120).
Residual current elements respond to 310current, where 310= Ia + Ib + Ie.
3. Differential Protection
3.1 Differential Element Logic
Figure 1 illustrates how the SEL 387 relay compares input winding currents IWICI throughIWIC4. These quantities are the result of input currents scaled by the value of their associated TAPsetting and then compensated for the given transformer / CT connection configuration (see 3.2below). Resultant quantities are then added
vectorially (phasor sum) to provide lOP
and
magnitudinally (scalar sum) and divided by two to provide IRT
See Figure 1, following
I Recommended By: PDS I Approved By: DB M I Issue Date 04 Jan 2007 I Pig3 1 d 13Prepared By: PDS
95Jan20
r~~ .
~ritish ColumbiaTransmissionCORPORATION
Maintenance Standard".•.
Protection and ControlSubject: SEL 387Title: SEL 387 Relay
Supplementary Training Notes Number 42.87.732-8
E87WlIIWICI ~o--
E87W2IIW2Cl -if 0-
E87W3 ~ ..II W3C1 ~C:r--t-t+--\ru I ~ II w.ci] 1-------- IOPl
E87W4
llW4Cl ~o- ~ I II W 1C 1 I 1---------,.
YI IIW2C111-------7( ~~IIIW3C11r----~
'---~ I II W4C 1111----~
+2 t---lRTl
IOP= IIW1La + IW2L~ + IW3L8 + IW3L~ I if a = ~+ 180°and 8 = ~ = ~then lOP = IIW11 -IIW21-1 IW31-1 IW41
IRT=(IIW11 + IIW21 + IIW31 + IIW41 )/2
Figure 1 - Differential Element Operate (lOP) and Restraint (IRT) Quantities
3.2 Transformer and CT Connections (Relay Compensation)
The SEL 387 relay utilizes CT Connection Compensation Matrices for each winding to adjust fortransformer and CT connection phase shifts.
Connecting a transformer in a delta-wye or wye-delta configuration shifts secondary voltages andcurrents 30° with respect to comparable, primary quantities. Conventionally, connecting associatedCTs in an opposite configuration compensates for this phase shift, i.e. CTs are connected delta-wyefor a wye-delta connected power transformer.
See Figure 2, following
Prepared By: PDS I Recommended By: PDS I Approved By: DB M I Issue Date 04 Jan 2007 I P<y> 2 d 13
95Jan20
Title:
British Columbia TransmissionCGRPORATION .
Maintenance StandardProtection and Control
SEL 387 Relay Subject: SEL 387
Supplementary Training Notes
f-oQ)
~I
Q)
~..c-.~
Number 42.87.732-8
Recommended By: PDS Issue Date: 04 Jan 2007
NOJc'6c~
< :)1 - VI> < - Ifl _ 81< N N
t> o o" < < 81 - :)1 N 0 0
> o s sn 0< s '" _4.
I1 :II_0
,....-- ,....-- r-'--
~I~ ~I~ ~I~
T T '---
0 -<{ co, ,<{ m o
uouesusduro-j uouoauuorjJ.8/JeWJOJSUBJJ.
>-CO
IIIQ)0::: Iy~ ~~
I'-- 4cor+
C")
~....J....J Y Y ....J Y Y Y I ....JY YY '--I ~
III l lI
uouasusduron uouosuuooJ.8/JeUJJOJSUBJJ.
<{ co o , ,....-- ,--- -'--
~I~ ~I~ ~I~'--- '--,-- '--,--
I
J <l-J "I ~ T Io IP- O ~ ~
< s o o< 0 0
<I--' > _0 s s~ < :)1 , m _4.-< 81
If I
•....Q)
E•.....E enen CC 0co~•....uf-Q)•....CQ) C
~8o,CO-Q)oI
Q)
~
OJ.£"0c~
Prepared By: PDS
95Jan20
Approved By: 0 B M ~3d 13
~:e,"'British Columbia Transmission
CORPORATION
Maintenance Standard..,.
Protection and Control
\'\
Subject SEL 387Title: SEL 387 Relay
Supplementary Training Notes Number 42.87.732-8
With reference to Figure 2, note that the SEL 387 relay provides the option of using wye-wyeconnected CTs with wye-delta or delta-wye connected power transformers.
The compensation matrix required to compensate for this phase shift is specified by settingWnCTC=m,
where n = winding number, 1-4, and
m = 0, 1, 2, ... , 12, where m = the number of increments of 30 degrees that a balanced, ABCrotating system is rotated in a counter-clockwise direction.
Assume that a power transformer is connected wye-delta and that the delta connection is an "A-C"style, i.e., A0 polarity is connected to C0 non-polarity; associated CTs are connected wye-wye.
v : DACA-ph -::::=~~~l
B-ph -+----+~+--+-~
C-ph A-ph'
In Ie' Ib' la'
-C C'
\ N
<:N .A
IB 8' A'
Issue Date: 04 Jan 2007Prepared By PDS Recommended By: PDS Approved By: 0 B M P<gl4d13
95Jan20
Maintenance StandardProtection and ControlBritish Columbia Transmission
CORPORATION
Title: Subject: SEL 387SEL 387 Relay
Supplementary Training Notes Number 42.87.732-8
Note that for the above example, A' lags A by 30°. Since the compensation matrices rotate phasorsin the counter-clockwise direction, aligning these vectors requires A' rotation of 30° or A rotationof 330°.
1 1 -1 0 1 1 -2 1CTC1= - 0 1 -1 CTC2= - 1 1 -2
/3 -1 0 1 3 -2 1 1
1 0 -1 1 1 -1 -1 2CTC3= - 1 0 -1 CTC4= - 2 -1 -1
/3 -1 1 0 3 -1 2 -1
1 -1 0 1 1 -2 1 1CTC5= - 1 -1 0 CTC6= - 1 -2 1
J3 0 1 -1 3 1 1 -2
1 -1 1 0 1 -1 2 -1CTC7= - 0 -1 1 CTC8= - -1 -1 2
/3 1 0 -1 3 2 -1 -1
1 0 1 -1 1 1 1 -2CTC9= - -1 0 1 CTCI0= - -2 1 1
/3 1 -1 0 3 1 -2 1
1 1 0 -1 1 2 -1 -1CTCH= - -1 1 0 CTC12 = - -1 2 -1
/3 0 -1 1 3 -1 -1 2
Figure 3: Compensation Matrices (m = 1 to 12)
As previously outlined, the compensation matrices rotate a balanced set of currents with ABC phaserotation in 30 degree increments in a counter-clockwise direction. CTC(O) creates no changes andsimply multiplies the currents by an identity matrix. Similarly, CTC(12) produces no phase shift butdoes remove zero-sequence components from the winding currents, as do all other matrices where m:;t: O.
For the above example, arbitrarily choose Winding 1 as the reference. Apply CTC(12) to Winding 1to remove zero-sequence:
1 2 -1 -1CTCI2=- -1 2 -1
3 -1 -1 2
I Recommended By: PDS I Approved By: DBM I Issue Date: 04 Jan 2007 I P<ga 5 d 13Prepared By: PDS
95Jan20
I ..
~.:&....~.,.,.,....- British Columbia Transmission
CORPORATION
Maintenance StandardProtection and Control
Title: Subject: SEL 387SEL 387 Relay
Supplementary Training Notes Number: 42.87.732-8
Therefore, the relay calculates the following currents for Winding 1 using CTC(12):
Iar, = 1/3 [2Ia, - Ib, - Ic.]
Ibr, = 1/3 [-la, + 21b, - Ic.]
Icr, = 1/3 [-la, - Ib, + 2 Ic.]
where Iar, Ibr., and Icr, are internally calculated relay currents
for externally applied currents Ia, Ib, and Ic,
The 387 relay is tested on a single-phase basis to minimize the amount oftest equipment required fortesting. Therefore, ifIa, is arbitrarily applied to Winding 1 of the relay and Ib, = Ic, = 0, then
Iar, = 1/3 [2Ia, - 0 - 0]
Ibr, = 1/3 [-la, + 0 - 0]
Icr. = 1/3 [-la, - 0 + 0]
Note that Ibr, and Icr, are produced internally in the relay despite external currents Ib, = Ic, = o.
Apply compensation matrix CTC(1) to Winding 2 to effectively shift Winding 2 current in phasewith Winding 1. This results in a 30° phase shift of Winding 2 currents in the counter-clockwisedirection.
1 -1 0o 1 -1-1 0 1
1CTC1=-
Iar, = 1/ -J3 [la2 - Ib2 + 0] -./3
Ibr, = 1/ -J3 [0 + Ib2 - IcJ
and
where Iar., Ibr., and Icr, are internally calculated relay currents
for externally applied currents Ia., Ib2, and Ie2
lfphase A current (Ia2) is again arbitrarily applied to Winding 2 of the relay and Ib, = Ic, = 0, then
Iar, = 1/ -J3 [Ia, - 0 + 0]
n-, = 1/-J3 [0 + 0 - 0]
Icrj= 1/-J3 [-la2+O+O]
A comparison of the internally calculated relay currents for Winding 1 and Winding 2 shows that"A" phase current appears in each of the calculated currents, Iarj, Ibr, and Icrj, of Winding 1 butonly appears in Iar-, and Icr- of Winding 2.
I Recommended By: PDS I Approved By DB M I Issue Date 04 Jan 2007 I F'<g3 6 ri 13Prepared By: PDS
95Jan20
Maintenance StandardProtection and ControlBritish Columbia Transmission
CORPORATION
Title: Subject: SEL 387SEL 387 Relay
Supplementary Training Notes Number 42.87.732-8
Therefore, in order to "match" these calculated currents for testing purposes, "-Ia2" must beconnected to "B" phase of Winding 2. Applying the same current into "A" phase, (Ia2), and out of"B" phase, (-Ia2), of Winding 2 then generates 2Ia2 in the Iar, calculation and -Ia2 in the Ibr,calculation.
Finally, to adjust scalar quantities such that Iar, = Iar., multiply Ia, by 3/2 and multiply Ia, by J3 /2.Therefore, Iar, = Iar., Ibr, = Ibr., and Icr, = Icr., and testing may proceed.
3.3 Relay Current Taps
The relay will automatically calculate current taps, TAPn, provided setting MVA-:;t.OFF. Tapsettings are limited to a range of 0.1 (IN) to 31(IN) and the tap ratio TAPmax/TAPmin:::;7.5. IN isthe nominal current rating of the relay and is equal to either 1A or 5A.
Tap settings can be manually calculated using the formula
TAPn= (MV A) (1OOO)(C)(J3 )(VWDGn)(CTRn)
Where: n = Winding number
C = 1, ifWnCT setting = Y (wye-connected cts)
C = J3 ,ifWnCT setting = D (delta-connected cts)
MV A = Maximum power transformer capacity in MV A
VWDGn = Winding line-to-line voltage setting in KV
CTRn = Current Transformer ratio setting
3.4 Percentage Restrained Differential Element
Refer to Figure 4: Percentage Restraint Differential Characteristic
Restrained, differential operation of the relay is based on a composite characteristic made up ofthree "regions". These regions are created by four different settings:
• 087P (restrained element operating current pickup set in per unit of TAP)
• SLP 1 (restraint slope 1, set in percentage)
• IRS 1 (restraint current, slope 1 limit, set in per unit of TAP)
• SLP2 (restraint slope 2, set in percentage)
I Recommended By: PDS I Approved By 0 B M I Issue Date: 04 Jan 2007 I f><;g3 7 ri 13Prepared By: PDS95Jan20
II ~~
-'British Columbia TransmissionCORPORATION
Maintenance Standard-~Protection and Control
Title: SEL 387 Relay Subject SEL 387
Supplementary Training Notes Number 42.87.732-8
Region 1 Region 2 Region 3lOP(PerUnit)
lOP = 087P lOP = (SLP2)(IRT) - (IRS1)(SLP2-SLP1)
100
Operati
087P
IRT(Per Unit)
Figure 4 Percentage Restraint Differential Characteristic
3.4.1 087P
The 087P setting is the minimum lOP (per unit operate current) level required for operation.
Therefore, region 1 operation is given by
lOP = 087P087P
forIRT~ SLPI X 100
3.4.2 SLP1
Setting SLPI provides the first restraint slope percentage ofthe relay and defines "region 2"operation. This is a linear characteristic that can be extrapolated through the origin of the lOP vs.IRT (per unit restraint current) graph. Therefore, basic algebra results in the line equation
Approved By DB M Issue Date: 04 Jan 2007 F"Y' 8 d 13Prepared By: PDS Recommended By: PDS
95Jan201----
'1 •••
~Varitish ColumbiaTransmission- CORPORATION
Maintenance StandardProtection and Control
Subject SEL 387Title: SEL 387 Relay
Supplementary Training Notes Number 42.87.732-8
lOP = (SLP1)(IRT)100
087P -for SLP 1 X 100 ~ IRT ~ IRS 1 setting
3.4.3 IRS1
The IRS 1 setting is the IRT limit of the slope 1 setting and is the boundary current between theSLPI characteristic (region 2) and the SLP2 characteristic (region 3).
The IRS 1 setting is not used if SLP2 = OFF
3.4.4 SLP2
The setting, SLP2, provides the second restraint slope percentage of the relay and defines "region3" operation. This is a linear characteristic offset from the origin of the lOP vs. IRT graph.Therefore, basic linear algebra results in the line equation
(SLP2)(IR T) - (IRS 1)(SLP2 - SLP 1)lOP =
100for IRT ;:: IRS 1
3.4.5 Determining Winding Input Currents for Testing
As outlined above, the typical restrained differential operating characteristic has three distinct"regions" .
. 087P• Region 1 occurs for IRT~ SLP1 X 100 and lOP = 087P
087P (SLP1)(IRT)• Region 2 occurs for -- X 100 ~ IRT ~ IRS 1 setting and lOP =
SLP1 100
R . 3 c. IR IRS d lOP (SLP2)(IRT) - (IRS1)(SLP2 - SLP1)• egion occurs lor T;:: 1an =100
Testing the differential characteristic has been arbitrarily set at four distinct points to verify thethree regions of the differential characteristic. These points have been chosen at
1) 95% of the region 1 boundary.
2) 125% ofthe region 1 boundary.
3) 95% of the IRS 1 setting.
4) 150% of the IRS 1 setting.
I Recommended By: PDS I Approved By: DB M I Issue Date: 04 Jan 2007 I ~ 9 d 13Prepared By PDS
95Jan20
~~,VBrilish ColumbiaTransmission
CORPORATION
Maintenance Standard..• '
Protection and Control'Title: SEL 387 Relay Subject· SEL 387
Number 42.87.732-8Supplementary Training Notes
3.4.5.1 Case 1: 95% of the Region 1 Boundary
lRT =(.95) (087P}100)SLPI
and lRT = (HWl] + IlW21)/2
therefore uwu = (.95{ 087P) (200) - IlW21SLPI
substituting for IlW21
IlWll = (.95)(087P) (200) - IlWll + 087PSLPI
= 087P (~+!)SLPI 2
and IlW21 = IlW11- 087P
= 087P (~-!)SLP1 2
lOP = 087P
and lOP = IlW11- IlW21
therefore IlW21 = IlW11- 087P
where lWl and lW2 are the per unit input currents into Windings 1 and 2, respectively.
Therefore, actual input winding currents for winding 1 (IWDG 1) and winding 2 (IWDG2) on asingle phase basis are
IWDGI = 087P c.:x TAP1 x l/A (where "A" is the W1CTC matrix scalar)SLP1 2
IWDG2 = ·087P (~-!) x TAP2 x liB (where"B" is the W2CTC matrix scalar)SLPI 2
and
3.4.5.2 Case 2: 125% of the Region 1 Boundary
lRT = (1.25)(087P)(100)SLP1
lOP = (lRT)(SLP1)100
and lOP = IlW11- IlW21
therefore IlW21= IlW11- (lRT{Sl~~l)
substituting for lR T
and lRT = (llW11 + IlW21)12
therefore IlW11= (1.25{ ~~;~) (200) - IlW21
substituting for IlW21
Prepared By PDS I Recommended By: PDS I Approved By: DBM I Issue Date 04 Jan 2007 I Pew 10 d 13
r95Jan20
rI
British Columbia TransmissionCORPORATION
Maintenance StandardProtection and Control
Title: SEL 387 Relay Subject SEL 387
Number 42.87.732-8Supplementary Training Notes
IIW11 = (1.25)(~~;:)(200) - \IW1\+1.25(087P)
( 100 1)= 1.25(087P) SLP1 +'2 .
and IIW21= IIW11- 1.25(087P)
= 1.25(087P) (~-!)SLP12
IIW21= IIW11- 1.25(087P)
where IWt and IW2 are the per unit input currents into Windings 1 and 2, respectively.
Therefore, actual input winding currents for winding 1 (IWDG 1) and winding 2 (IWDG2) on asingle phase basis are
IWDGI = 1.25(087P) (~+!) x TAP1 x 1/A (where "A" is the W1CTC matrix scalar)SLPI 2
(100 1) .and IWDG2 = 1.25(087P) SLP1 -'2 x TAP2 x liB (where "B" IS the W2CTC matrix scalar)
3.4.5.3 Case 3: 95% of IRS1 Setting
IRT = .95(IRS1)
and IRT = (IIW11+ IIW2D/2
therefore IIW11= (2)(.95)(IRS1) -IIW21
substituting for IIW21
IIW11= (2)(.95)(IRS1) -\IW1\ + (.95)( Sl~~l) (IRS 1)
. (SLPl)= .95(IRS 1) 1+ 200
and IIW21= IIW11- (.95{Sl~~1}IRS1)
lOP = (IRT)(SLP1)100
and lOP = IIW11- IIW21
therefore IIW21 = IIW11_ (IRT{ SLP1)100
substituting for IRT
II\v21 = IIW11- (.95) (SLP1) (IRS 1)100
Prepared By: PDS I Recommended By:· PDS I Approved By DBM I Issue Date 04 Jan 2007 I f>'Y' 11 ri 13
95Jan20
~~'-'British ColumbiaTransmission
CORPORATION
Maintenance Standard,'" '
Protection and ControlSubject: SEL 387Title: SEL 387 Relay
Supplementary Training Notes Number 42.87.732-8
= .95(IRS 1)(1- SLP1)200
where IW1 and IW2 are the per unit input currents into Windings 1 and 2, respectively.
Therefore, actual input winding currents for winding 1 (IWDG 1) and winding 2 (IWDG2) on asingle phase basis are
( SLP1)IWDGI = .95(IRS1) 1+ 200 x TAP 1 x l/A (where "A" is the W1CTC matrix scalar)
( SLP1)and IWDG2 = .95(IRS 1) 1- 200 x TAP2 x liB (where "B" is the W2CTC matrix scalar)
3.4.5.4 Case 4: 150% of IRS1 Setting
IRT = 1.5(IRS1)SLP2(IR T) - IRS 1(SLP2 - SLP 1)
lOP =100
and IRT = (IIW11+ IIW21)/2 and lOP = IIW11- IIW21
SLP2(IRT) - IRS1(SLP2- SLP1)therefore IIW21= IIW11- 100
substituting for IRT1.5(IRS 1)SLP2 - IRS 1(SLP2 - SLP1)
IW2 = IIW11- 100
therefore IIW11= (2)(1.5)(IRSl) -IIW21
substituting for IIW21
and
1.5(IRS 1)SLP2 - IRS 1(SLP2 - SLP 1)IW1 = (2)(1.5)(IRS1) -IIW11 + 100
_ ( S)( SLP1 + (.5)SLP2)- 1.5 IR 1 1+ (1.5)(200)
1.5(IRS1)SLP2 - IRS 1(SLP2 - SLP1)IIW21= IIW11- 100
= 1.5(IRS0(1- SLP1 + (.5)SLP2). (1.5)(200)
where IW1 and IW2 are the per unit input currents into Windings 1 and 2, respectively.
I Recommended By: PDS I Approved By: DB M I Issue Date 04 Jan 2007 I Pi:g3 12 d 13Prepared By: PDS
95Jan20
,--t••~,~ British Columbia Transmission
CORPORATION
Maintenance StandardProtection and Control
Number 42.87.732-8
Subject SEL 387Title: SEL 387 Relay
Supplementary Training Notes
Therefore, actual input winding currents for winding 1 (IWDG 1) and winding 2 (IWDG2) on asingle phase basis are
. ( SLP1 + (.S)SLP2) . .IWDGI = l.S(IRS1) 1+ (1.S)(200) x TAP1 x l/A (where "A" IS the W1CTC matnx scalar)
and
(SLP1 + (.S)SLP2) .
IWDG2 = l.S(rRS1) 1- (1.S)(200) x TAP2 x liB (where "B" IS the W2CTC matrix scalar)
3.4.6 Harmonic Blocking
The percentage-restrained differential element can be blocked by either second and/or fifthharmonic using the PCT2 and/or PCTS settings, respectively. Set these settings to "OFF" ifblocking is not required.
Transformer magnetizing inrush current contains a significant amount of second harmonic. If theratio of second harmonic to fundamental current (IF2/IF1) is greater than PCT2 setting, blockingoccurs.
Transformer overexcitation produces odd order harmonics. A fifth harmonic componentexceeding PCTS setting enables restrained-differential blocking.
Harmonic blocking can be either "Independent" or "Common". Independent Harmonic Blocking(IHBL = Y) blocks differential operation of a particular phase if the harmonic content of thatphase exceeds the pickup level. Common Harmonic Blocking (IHBL = N) blocks all differentialelements if anyone phase exceeds the pickup level.
3.5 Instantaneous Unrestrained Differential Element
The instantaneous unrestrained differential element responds to fundamental frequency only and isnot affected by SLP1, SLP2, IRS1, PCT2, PCTS, or IHBL settings.
I Recommended By PDS I Approved By: DB M I Issue Date 04 Jan 2007 I PaJ3 13 ri 13Prepared By: PDS
95Jan20