70072-0188-00(1)
-
Upload
hiteshkela -
Category
Documents
-
view
224 -
download
0
Transcript of 70072-0188-00(1)
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 1/14
70072-0188-00TECHNICAL NOTE 12/2007
PowerLogic, ION, ION Enterprise,MeterM@il, WebMeter andModbus are either trademarks orregistered trademarks ofSchneider Electric.
Electrical equipment should beinstalled, operated, serviced, andmaintained only by qualified
personnel. No responsibility isassumed by Schneider Electric forany consequences arising out ofthe use of this material.
© 2007 Schneider Electric. All rights reserved.
www.powerlogic.com
Troubleshooting Meter WiringThis document outlines wiring troubleshooting procedures for ION7300 series, ION7550 / ION7650, ION8600, and ION8800 meters. Troubleshooting your meter’s
wiring before commissioning can save you time and money.
D ANGER
During normal operation of ION devices, hazardous voltages are present which can cause severe injury
or death. Only qualified, properly trained personnel should perform installation, servicing and operation.
NOTE
In this Technical Note, the three phases are referred to as A, B and C. The meter input terminals are
marked 1, 2 and 3 for the voltage and current phase inputs. Positive phase rotation is seen as anti-
clockwise, with positive phase sequence A, B, C.
In This Document
Checking Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Checking PT and CT Polarity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Checking Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Checking Wiring using the Real‐Time Phasor Viewer . . . . . . . . . . . . . . . . . . . . . . . 3
Using CT Shorting Test Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Using PT Secondary Winding Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Types of Wiring Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Diagnosing Wiring Issues using the Phasor Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Appendix A: Manual Power Calculations to Determine Wiring Errors . . . . . . 7WYE Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DELTA Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 2/14
Checking Wiring Diagrams Troubleshooting Meter Wiring
Page 2 © 2007 Schneider Electric. All rights reserved.
Checking Wiring Diagrams Study the meter wiring diagrams in your meter’s installation guide to ensure
that the wiring method is correct in your site installation diagrams.
Check all meter wiring to ensure that it is correct and as shown on the site
installation diagrams. Do not rely solely on vector diagrams to determine correct wiring. The wiring should be marked with unique numbers or color coded. This
makes installation and checking easier. If the wiring is incorrect, the meter
displays incorrect readings.
Checking PT and CT Polarity Potential transformer (PT) and current transformer (CT) polarity is normally
indicated by markings at the device terminals. In rare situations, these can be
incorrectly marked. Test to verify that the PT and CT polarities are correct as
marked, especially if protection relays are installed in the secondary circuits of the
PTs
and
CTs.
Incorrect
operation
will
occur
if
the
polarities
are
incorrectly
marked.
CTsPolarity can be tested using the flick test. Connect an analog ammeter (hand‐held
multi‐meter) to the secondary terminals of the CT, meter positive to X1 and
negative to X2. Using a suitable low‐voltage battery, connect the negative terminal to H2 of the CT. While watching the analog ammeter, apply a current pulse to the
CT by connecting and disconnecting the battery positive to H1 of the CT. If the
polarity is correct, the meter needle gives a positive flick on closing and a negative
flick on breaking the circuit.
PTsTest PT polarity in the same way as the CT (connecting the battery to the primary
side) or by applying a low voltage (for example, 120 VAC) to the primary winding
and comparing primary and secondary voltages on a dual trace oscilloscope.
Checking WiringTest all wiring by ringing out and mark the conductors with wire numbers as
indicated on the drawing. The conductors or cabling should be disconnected from
terminals at both ends. Ringing out is best done using an audible continuity tester. Connect the tester between a wire and ground. At the other end, short wires to
ground one by one until the correct conductor is located. Mark the tested
conductor at both ends.
C AUTION
Do not ring out conductors that are energized.
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 3/14
Troubleshooting Meter Wiring Checking Wiring using the Real-Time Phasor Viewer
© 2007 Schneider Electric. All rights reserved. Page 3
Checking Wiring using the Real-Time Phasor ViewerION Setup version 2.1 and higher has a real‐time Phasor Viewer available for some
meters. The Phasor Viewer provides detailed harmonics calculations for a voltage
or current input on a meter. This information is valuable for power quality
analysis, selecting properly rated transformers, and fault detection. For more
details regarding
the
Phasor
Viewer,
refer
to
the
ION Setup User Guide.
NOTE
The Phasor Viewer in ION Setup is configured by default to display correctly for the meter installer. Users
can change the display to rotate clockwise or counterclockwise using the Phasor Rotation option located
on the Conventions tab under ION Setup Tools Options.
To access the Phasor Viewer:
1. Log on to ION Setup and connect to your meter in Basic Mode.
2. In the Setup Assistant, go to the Verification screen and click the Wiring tab.
3. Select Phasor Viewer, then click Confirm.
The Phasor Viewer appears, containing both voltage and current phasors on the
Combined and Side by Side tabs. The combined view also contains power readings.
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 4/14
Using CT Shorting Test Blocks Troubleshooting Meter Wiring
Page 4 © 2007 Schneider Electric. All rights reserved.
Using CT Shorting Test BlocksA current transformer (CT) develops a very high voltage across its secondary
winding if the secondary circuit is open circuited while current is flowing in the
primary winding. This could damage the CT and cause electric shock. It is
recommended that you use a CT shorting device in the secondary circuit. If the
metering circuit
needs
future
maintenance,
you
can
safely
short
the
CT
secondary
to perform maintenance without switching off the primary system.
Using PT Secondary Winding FusesThe PT secondary circuit should be fitted with fuses as shown in the meterʹs
technical documentation. A practical choice of fuse rating is 2A. The fuses should
be properly coordinated with any other fuses on the same circuit. When the fuses
are removed, the meter is isolated from the PT and maintenance can be done
safely.
Additional tests could include:
CT magnetization curve
PT phasing check
Ratio check
Check CT polarity back to meter terminals
Inject meter from test terminal
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 5/14
Troubleshooting Meter Wiring Types of Wiring Issues
© 2007 Schneider Electric. All rights reserved. Page 5
Types of Wiring IssuesIf you suspect a wiring problem, first check that the meter is programmed properly
with the correct PT and CT ratios and that the Volts Mode setting is correct.
Depending on the configuration, there can be 3 CT and 3 PT secondary windings
(12 conductor ends) that need to be applied to the meter with the correct polarity. Without proper commissioning testing, these could be connected incorrectly, causing the meter to display false readings. Possible wiring errors can include:
Swapped current phases
Incorrect current polarities
Swapped voltage phases
Incorrect voltage polarities
For most of the above wiring errors, the meter displays correct values for voltage
and current while the W, VA, VAR and power factor values are incorrect (for
example, when
metering
a load,
a negative
kW
value
indicates
incorrect
polarities).
Diagnosing Wiring Issues using the Phasor ToolDownload the phasor tool from the Support area of the powerlogic website. The
phasor tool is a Microsoft Excel spreadsheet. You must enable macros in Microsoft Excel for the phasor tool to work.
Before using the phasor tool, verify the following:
Your meter’s Volts Mode setting (Delta or Wye).
Your meter’s
frequency
matches
the
frequency
of
the
system
you
are
metering.
Your loads are balanced and non‐distorted (THD ~0).
You must enter the per‐phase power parameters as read by your meter, either kW
and PF or voltage and current angles.
If your meter is configured for Wye Volts Mode, note the power parameters for phase A, B and C from the front panel display, through the Vista component of ION Enterprise or from the real‐time data screens in ION Setup.
If your meter is configured for Delta Volts Mode, temporarily switch the meter
to 4‐Wire Wye Volts Mode. Read the per‐phase power parameters for phase A
and phase C from the front panel display, through the Vista component of ION
Enterprise or
in
the
real
‐time
data
screens
in
ION
Setup.
Ignore
phase
B
information. Return the meter to Delta Volts Mode.
Open the phasor tool spreadsheet in Microsoft Excel, enable macros, and
acknowledge the disclaimer. Follow the instructions on the spreadsheet to
generate actual and corrected phasors to determine meter wiring errors. Refer to
the example document that accompanies the phasor tool for examples.
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 6/14
Diagnosing Wiring Issues using the Phasor Tool Troubleshooting Meter Wiring
Page 6 © 2007 Schneider Electric. All rights reserved.
Refer to “Appendix A: Manual Power Calculations to Determine Wiring Errors”
on page 7 for more information.
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 7/14
Troubleshooting Meter Wiring Appendix A: Manual Power Calculations to Determine Wiring Errors
© 2007 Schneider Electric. All rights reserved. Page 7
Appendix A: Manual Power Calculations to Determine Wiring Errors
You can confirm correct wiring with the following steps:
1. Determine the load characteristics: You need to know rough estimates of the VA or W rating and power factor. If the plant is not running at full load, this
can have an effect on the power factor. Induction motors have poor power factors when operating at less than full load.
2. Perform Power Calculations: Perform calculations to determine the expected
power parameters for your application, using the voltage, current, and power
values displayed on the meter.
When calculating power parameters, use a simplified model. Visualize the meter’s
input circuits as 3 separate voltmeters with a common connection brought out to
the VREF (V4) terminal. Current inputs operate like 4 separate ammeters.
Using the above model of the meter makes it easier to understand the various
configurations and voltage modes.
NOTE
Some ION meters do not have VREF (V4) or I4 terminals.
V1 V2 V3 A1 A2 A3 A4
V1 V2 V3 VREF I11 I12 I21 I22 I31 I32 I41 I42
Meter
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 8/14
WYE Mode Troubleshooting Meter Wiring
Page 8 © 2007 Schneider Electric. All rights reserved.
WYE ModeWhen the meter is set for WYE mode, each of the phases can be seen to be metered
by a separate power meter. Each phase can therefore be checked independently
(see figure below).
Power Calculations:For a balanced and non‐distorted (THD approaches 0%) load, the power parameter totals can be calculated as below:
kW = 3* | Vln | * | I | *power factor
kVA = 3* | Vln | * | I |
kVAR = SQRT(kVA*kVA
‐kW*kW)
Check each of the power parameters on a per phase basis. In WYE mode, the per‐
phase power parameters should be one third of the totals if the load is balanced. If your meter does not display power values per phase, you can do the following:
1. Remove the fuses for V2 and V3, isolating these inputs from the meter. Check
that the meter displays zero readings for VBN and VCN. The meter now uses
the voltage applied to V1 and the current applied to I1 to determine the power
parameters for the A phase. The meter should display kW, kVAR and kVA
readings that are 1/3 of the total values calculated.
2. Perform the same check for B phase by removing the V1 and V3 fuses.
3. Perform the same check for C phase by removing the V1 and V2 fuses.
NOTE
The readings obtained by performing the above check are only accurate if the meter’s system frequency
matches the frequency of the system being monitored.
Table 1 and 2 show how the power parameters (kVA, kW and kVAR) are affected
by incorrect connection of the voltage and current wiring. Only single error
V A0º
VC
120º
VB
240º
IC
100º
IBI A
220º
340º
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 9/14
Troubleshooting Meter Wiring WYE Mode
© 2007 Schneider Electric. All rights reserved. Page 9
situations are shown; there are many more possible multiple‐error combinations. The power values shown are normalized values, based on the correct values. The
tables are shown for a load with lagging power factor of about 86%.
Normalized Power Parameters (Volts Mode = WYE)
Table
1:
Current
connections
correct,
with
voltage
connections
as
shown:
kVA kW kVAR
Va,Vb,Vc n/a n/a n/a
Va,Vc,Vb 0 0 0
Vb,Va,Vc 0 0 0
Vc,Vb,Va 0 0 0
-Va,-Vb,-Vc n/a -1 -1
-Va,Vb,Vc 0.3 0.3 0.3
Va,-Vb,Vc 0.3 0.3 0.3
Va,Vb,-Vc 0.3 0.3 0.3
Vb,Vc,Va n/a 0 -2
Vc,Va,Vb n/a -1 n/a
Table 2: Voltage connections correct, with current connections as shown:
kVA kW kVAR
Ia, Ib, Ic n/a n/a n/a
Ia, Ic, Ib 0 0 0
Ib, Ia, Ic 0 0 0
Ic, Ib, Ia 0 0 0
-Ia, -Ib, -Ic n/a -1 -1
-Ia, Ib, Ic 0.3 0.3 0.3
Ia, -Ib, Ic 0.3 0.3 0.3
Ia, Ib, -Ic 0.3 0.3 0.3
Ib, Ic, Ia n/a -1 n/a
Ic, Ia, Ib n/a 0 -2
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 10/14
DELTA Mode Troubleshooting Meter Wiring
Page 10 © 2007 Schneider Electric. All rights reserved.
Example
You have just installed an ION meter. The known good power values for the
installation site and the measured values from the meter are shown below:
The meter values are obviously incorrect, and you suspect incorrect wiring of the
current and/or voltage inputs.
Dividing the meter values by the known values gives you the normalized values
as used in Tables 1 and 2:
normalized kVA = 0.333
normalized kW = 0.334 normalized kVAR = 0.332
Inspecting the tables, you can see that your meter may have either of:
any one current phase connection reversed
any one voltage phase connection reversed
This method reduces the list of possible wiring errors and can be used to confirm
a suspected wiring error.
DELTA ModeIn DELTA mode, the measurement is performed using the two wattmeter method. The meter needs only VAB (applied to V1), VCB (applied to V3), I1 and I3 to
measure the total power. VCA is calculated and IB is measured. Both are displayed
but are not used by the meter for the power calculations in DELTA mode.
If all voltages are approximately the same magnitude, then the polarities of VAB
and VCB are either both correct or both incorrect
Checking the Two Wattmeter ValuesFor troubleshooting purposes only, temporarily change your meter from DELTA
mode to WYE mode. In WYE mode, the two wattmeter values are seen on phases
A and C. Ignore any values on phase B. Once you have determined the two
wattmeter values, reset your meter back to DELTA mode.
If your meter does not display per‐phase power values in WYE mode, you can do
the following:
Power Values
ApparentPower Real Power Reactive Power
Known Values 1035 kVA 896.3 kW 517.5 kVAR
Meter Values 345 kVA 300 kW 172 kVAR
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 11/14
Troubleshooting Meter Wiring DELTA Mode
© 2007 Schneider Electric. All rights reserved. Page 11
Remove the fuse for V3, isolating that input from the meter. The meter now uses
the voltage applied to V1 and the current applied to I1 to determine the power parameters for the phase A (wattmeter #1).
Perform the same check for phase C by removing the fuse for V1. The meter now
uses the voltage applied to V3 and the current applied to I3 to determine the
power parameters for phase C (wattmeter #2).
The power values seen for phases A and C differ depending on the power factor
of the system. The following equations can be used to calculate the power values
for wattmeters #1 and #2:
Wattmeter #1:
kW = VLILcos (30o+phi)
kVA = SQRT(kW2 + kVAR2)
kVAR = VLILsin (30o+phi)
Wattmeter #2:
kW = VLILcos (30o‐phi)
kVA = SQRT(kW2 + kVAR2)
kVAR = VLILsin (30o‐phi)
phi = load power factor angle, or angle associated with load impedance
Examples (assuming a balanced, non-distorted load)
System power factor is unity:
kW values have equal magnitude and sign.
kVAR
values
have
equal
magnitude,
but
phase
A
is
positive
and
phase
C
is
negative.
kVA values are the same for phases A and C.
0º
120º
I A
V AB30º
90º
VCB
IC
240º
IB
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 12/14
DELTA Mode Troubleshooting Meter Wiring
Page 12 © 2007 Schneider Electric. All rights reserved.
System power factor is 86% lagging:
kW value for phase C is the same as kVA value, the value for phase A is half of that.
kVAR value for phase A is half of the total kVA value, the value for phase C is
zero.
kVA values are the same for phases A and C.
System power factor is 86% leading:
kW value for phase C is small, value for phase A is same as kVA value.
kVAR value for phase C is large, value for phase A is zero.
kVA values are the same for phases A and C.
Table 3 and Table 4 show how the power parameters (kVA, kW and kVAR) are
affected by incorrect connection of the voltage and current wiring. Only single
error situations are shown. There are many more possible multiple‐error
combinations. The power values shown are normalized values, based on the
correct values. The tables are shown for a load with lagging power factor of about 86%. See the corresponding information in the “WYE Mode” section for an
example of how to use the tables; use the equations for wattmeters #1 and #2.
0º
330º
I A
V AB30º
90º
VCB
IC
210º
IB
0ºI A
V AB30º
90º
VCB
IC
270º
IB
150º
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 13/14
Troubleshooting Meter Wiring DELTA Mode
© 2007 Schneider Electric. All rights reserved. Page 13
Normalized Power Parameters (Volts Mode = DELTA)
Table 3: Current connections correct, with voltage connections as shown
kVA tot kW tot kVAR tot
V1, V3 n/a n/a n/a
V3, V1 0 0 0
V1, -V3 0.6 -0.3 n/a
-V1, V3 0.6 0.3 -1
-V1, -V3 n/a -1 -1
Table 4: Voltage connections correct, with current connections as shown
kVA tot kW tot kVAR tot
Ia, Ib, Ic n/a n/a n/aIa, Ic, Ib 0 0 0
Ib, Ia, Ic 0 0 0
Ic, Ib, Ia 0 0 0
-Ia, -Ib, -Ic n/a -1 -1
-Ia, Ib, Ic 0.6 0.3 -1
Ia, -Ib, Ic n/a n/a n/a
Ia, Ib, -Ic 0.6 -0.3 n/a
Ib, Ic, Ia n/a -1 n/a
Ic, Ia, Ib n/a 0 -2
8/13/2019 70072-0188-00(1)
http://slidepdf.com/reader/full/70072-0188-001 14/14
DELTA Mode Troubleshooting Meter Wiring
Page 14 © 2007 Schneider Electric. All rights reserved.