5Power Cable Specs Set 2.cdr

16
Cables E LECTRICAL E L E C T R I C A L

Transcript of 5Power Cable Specs Set 2.cdr

Page 1: 5Power Cable Specs Set 2.cdr

CablesELECTRICALE L E C T R I C A L

Page 2: 5Power Cable Specs Set 2.cdr

April 24, 2007

CONDUMEX INCORPORATED

WIRE & CABLE PRODUCT INDEX

!

!

!

MTW/THHN/THWN 600 VOLTS COPPER 14 AWG SOLID 750 MCMSTRANDED UL 83XHHW-2 600 VOLTS COPPER 14 AWG 1000 MCM STRANDED UL 44RHH-RHW-USE 600 VOLTS COPPER (XLP) 6 AWG 1000 MCM STRANDED UL 44

BUILDING WIRE

!

!

TYPE TC/THHN 600 VOLTS COPPER 14 AWG STRANDED 750 MCMSTRANDED, 3 AND/OR 4 CONDUCTOR, WITH OR WITHOUT BAREGROUND WIRE (SIZES 8 AWG AND LARGER), UP TO 16 CONDUCTORFOR SIZES 14, 12 AND 10 AWG UL 1277TYPE TC/XHHW-2 600 VOLTS COPPER 14 AWG STRANDED 750 MCMSTRANDED, 3 AND/OR 4 CONDUCTOR, WITH OR WITHOUT BAREGROUND WIRE (SIZES 8 AWG AND LARGER), UP TO 16 CONDUCTORFOR SIZES 14, 12 AND 10 AWG UL 1277

TRAY CABLE

POWER CABLE

!

!

!

!

!

PRIMARY URD CABLES, 15 KV 35 KV, 100% & 133% INSULATIONLEVELS, COPPER OR ALUMINUM CONDUCTOR, EPR OR TR-XLPINSULATION, CONCENTRIC COPPER WIRE NEUTRAL, WITH OR WITHOUTENCAPSULATING JACKET OVERALLSPECIFICATIONS: ICEA S-94-649 & AEIC CS8TYPE MV-90 & MV-105 (EPR INSULATION ONLY FOR MV-105) POWER CABLE, 5 KV - 35KV, 100% & 133% INSULATION LEVELS, COPPER CONDUCTOR, EPR OR XLPINSULATION, COPPER DRAIN WIRE OR COPPER TAPE METALLIC SHIELD, BLACK PVCSUNLIGHT RESISTANT JACKET. SINGLE CONDUCTOR CONSTRUCTION.LISTED UL 1072; SPECIFICATIONS: ICEA S-93-639 & AEIC CS8TYPE MC ARMORED CABLES, 600 VOLTS, 5 KV - 15 KV, MULTI-CONDUCTORSTRANDED COPPER, EPR OR XLP INSULATION, ALUMINUM OR GALVANIZED STEELINTERLOCKED ARMOR, PVC SUNLIGHT RESISTANT JACKET OVERALL. UL 1569HIGH VOLTAGE POWER CABLES UP TO 138 KV, COPPER OR ALIMINUM CONDUCTOR,XLP UNSULATION, METALLIC SHIELD,PVC JACKET.SPECIFICATION: AEIC Cs7BARE OVERHEAD CONDUCTORS, TYPES AAC AND ACSR, PER ASTM B230 & B232

SPECIAL PURPOSE CABLES

! TYPE RHH-RHW 2000 VOLTS, (DLO), SINGLE CONDUCTOR TINNED COPPER, ROPE-LAYSTRANDED, EPR INSULATION, SEPARATOR, BLACK CSPE JACKET. CONDUCTOR SIZES4 AWG 1 AWG UL LISTED AS VW-1; SIZES 1/0 AWG 929.2 MCM UL LISTED FOR “CTUSE”, CSA LISTED AS FT4. SIZE 1111 MCM IS PER ICEA S-68-516.

Page 3: 5Power Cable Specs Set 2.cdr

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947302-06

TYPE THHN OR THWN 600 VOLTS

1) Annealed bare solid (14-10 AWG),

annealed bare stranded class C

concentric round (14-2 AWG),

DESCRIPTION

compressed stranding class B

(1 AWG - 1000 MCM) copper conductor.

2) Polyvinyl chloride (PVC insulation)

3) Nylon overall protective jacket.

123

Dimension and weights shown are nominal, unless otherwise indicated, and subject to

14

12

10

14

12

10

8

6

4

3

2

1

1/0

2/0

3/0

4/0

250

300

350

400

500

600

750

1000

1 Solid

1 Solid

1 Solid

19

19

19

19

19

19

19

19

19

19

19

19

19

37

37

37

37

37

61

61

61

4.1

6.5

10.3

4.1

6.5

10.3

16.5

26.2

41.7

52.6

66.3

83.7

106

133

168

211

0.06

0.08

0.10

0.07

0.09

0.11

0.15

0.18

0.23

0.26

0.29

0.32

0.37

0.41

0.47

0.52

0.57

0.62

0.67

0.72

0.80

0.88

0.98

1.14

15

15

20

15

15

20

30

30

40

40

40

50

50

50

50

50

60

60

60

60

60

70

70

70

5

5

5

5

5

5

5

6

6

7

7

7

8

8

8

8

9

9

9

9

9

10

10

10

0.10

0.12

0.15

0.12

0.14

0.17

0.23

0.26

0.34

0.36

0.39

0.45

0.50

0.54

0.59

0.65

0.72

0.78

0.83

0.87

0.96

1.06

1.15

1.27

16

23

37

17

26

40

65

99

157

197

241

306

380

472

587

729

870

1033

1196

1359

1685

2023

2454

3347

SizeAWG/kcmil

Numberof

Strands

ConductorAreakcmil

ConductorDiameter

mils

InsulationThickness

mils

JacketThickness

mils

OverallDiameter

inch

NetWeightlb/mft

manufacturing tolerances.

VINANEL Nylon, solid or stranded type®

General use in commercial and industrial

SPECIFICATIONS

construction, and installations where

resistance against oils and gasoline is

APPLICATION

75° CIn oil (Oil resistant II)

6) Superior abrasion and mechanical

properties.

7) Sizes 1/0 and larger are marked "For

CT use", and are approved for installation

overload exists.

in cable trays. Sunlight resistant in

Accordance with NEC Article 318.

manufacturing process.

4) Flame retardant, UL listed as VW-1.

5) Smooth nylon jacket aids in easier

pulling.

1) Good resistance to moisture, heat, oil,

gasoline, chemicals and grease.

2) Suitable for installation where thermal

3) Strict quality control during

FEATURES

MAXIMUM CONDUCTOR TEMPERATURE

Dry locations (THHN)

Dry and wet locations (THWN)

90° C

75° C

MAXIMUM OPERATING VOLTAGE

600 volts

required. May be used for power and

gases, gasoline and chemicals. Also

suitable as machine tool and switchboard

control circuits in recognized raceways, in

wet or dry locations, and in presence of

wiring.

UL-83

HOW TO ORDER

NATIONAL ELECTRICAL CODE REFERENCE

Ampacities

Switchboard wiring

Conduit fill tables

Article 3 10-15

Article 384

Chapter 9

THHN or THWN, 600 volts, size, color and length

11

Page 4: 5Power Cable Specs Set 2.cdr

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947303-06

THHN/THWN 600 VOLTS

POWER CABLE TYPE TC

DESCRIPTION

2) Polyvinyl Chloride (PVC) thermoplastic

insulation.

1) Annealed bare Class C concentric

strand copper conductors.

3) Nylon protective covering.

4) Binder tape over core.

5) Overall flame retardant PVC jacket.

Dimension and weights shown are nominal, unless otherwise indicated, and subject to

Size

AWG

Numberof

Strands

Numberof

Conductors

JacketThickness

mils

OverallDiameterinches

NetWeightlb/Mft

14

12

10

19

19

19

2

3

4

5

7

9

12

16

2

3

4

5

7

9

12

16

2

3

4

5

7

9

12

45

45

45

45

45

60

60

60

45

45

45

45

60

60

60

60

45

45

60

60

60

60

80

0.34

0.36

0.40

0.43

0.46

0.56

0.63

0.67

0.38

0.40

0.43

0.46

0.55

0.64

0.71

0.76

0.45

0.47

0.55

0.60

0.65

0.75

0.89

68

87

109

130

167

234

285

335

90

119

154

173

247

326

400

485

139

180

247

178

367

480

637

manufacturing tolerances.

FEATURES

Wet or DryDry

75° C90° C

APPLICATION

Electrical Code

Condumex Type TC cable may be used for power,

messenger. Type TC cable may be used in wet or

dry locations and in the presence of oil and most

lighting, control, signal and communcation circuits,

in raceways, direct burial in earth, or in

SPECIFICATIONS

S-73-532 (table E-2 or Method S/B 4.)

7) Circuit identification; color coded per ICEA

UL 1277 and UL 83

HOW TO ORDER

chemicals in accordance with the National

MAXIMUM OPERATING VOLTAGE

600 volts

MAXIMUM CONDUCTOR TEMPERATURE

Condumex Tray Cable Type TC/THHN,

600 volts, number and size of conductors.

1) UL listed for direct burial.

2) Flame retardant, (passes UL 1277, 70,000

BTU flame test.3) Sunlight resistant; can be installed outdoors.

4) UL listed as Type TC for power and control

Electrical Code.

tray cable used in accordance with the National

Resistant I.

5) PVC jacket is UL rated 90 C and listed OilO

required metallic sheathed cables.

substantial cost savings over the previously

Location Applications. Type TX offers

6) Acceptable for Class I, Division 2, Hazardous

7a) Other color coding methods are available,

based on ICEA S-73-532

2

245 13

Page 5: 5Power Cable Specs Set 2.cdr

5) Binder tape over core

750 kcmil) copper conductors.

6) Overall flame retardant PVC jacket.

DESCRIPTION

3) Nylon protective covering.4) Fillers

1) Annealed bare Class C (8-2 AWG)compressed stranded Class B (1/0 AWG-

2) Polyvinyl Chloride thermoplastic insulation

36 145 2

POWER CABLE TYPE TC

THHN/THWN 600 VOLTS

Size

AWG/kcmil

Numberof

Conductors

GroundConductor

AWG

InsulationThickness

mils

JacketThickness

mils

OverallDiameter

inch

NetWeightlb/Mft

8

6

4

2

1/0

2/0

3/0

4/0

250

350

500

750

1/0

2/0

4/0

350

500

750

3

3

3

3

3

3

3

3

3

3

3

3

4

4

4

4

4

4

10

8

6

6

6

6

4

4

4

3

2

1

6

6

4

3

2

1

30/5

30/5

40/7

40/7

50/8

50/8

50/8

50/8

60/9

60/9

60/9

70/10

50/8

50/8

50/8

60/9

60/9

70/10

60

60

80

80

80

80

80

80

80

110

110

110

80

80

110

110

110

140

0.638

0.698

0.884

1.015

1.223

1.320

1.428

1.549

1.760

1.980

2.260

2.967

1.350

1.457

1.773

2.188

2.502

3.057

338

448

693

1012

1495

1858

2297

2791

3374

4526

6230

8845

1913

2311

3597

5754

8018

11716

Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.

MAXIMUM OPERATING VOLTAGE

UL 1277 and UL 83

7) Circuit identification; color coded per ICEA

MAXIMUM CONDUCTOR TEMPERATURE

Wet or DryDry

75° C90° C

required metallic sheathed cables.

3) Sunlight resistant; can be installed outdoors.

tray cable use in accordance with the National

Electrical Code.

APPLICATION

in accordance with the National Electrical Code.

6) Acceptable for Class I, Division 2, Hazardous

4) UL listed as Type TC for power and control

600 volts

5) PVC jacket is UL rated 90° C and listed Oil

Resistant I.

1) UL listed for direct burial.

2) Flame retardant, (passes UL 1277, 70,000

BTU flame test.)

FEATURES

Condumex Type TC cable may be used for

cable may be used in wet or dry locationsand in the presence of oil and most chemicals

power, lighting, control, signal andcommunication circuits, in raceways, direct

HOW TO ORDER

600 volts, number and size of conductors.Condumex Tray Cable Type TC/THHN,

SPECIFICATIONS

S-73-532 (table E-2 or Method S/B 4.)

Location Applications. Type TC offers

substantial cost savings over the previously

7a) Other color coding methods are available,

based on ICEA S-73-532

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947303-06

3

Page 6: 5Power Cable Specs Set 2.cdr

1) Annealed bare stranded class B compact

copper conductor.

DESCRIPTION

3) Ethylene propylene (EPR) or cross-linked

polyethylene (XLPE) insulation.

4) Polyvinyl chloride (PVC) protective jacket.

2) Extruded semiconducting strand shield.

VULCANEL®

MEDIUM VOLTAGE

WET OR DRY POWER CABLE 5 KV

XLPE OR EPR NON-SHIELDED

24 13

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

SizeAWG/kcmil

Numberof

Strands

ConductorDiameter

inch

InsulationThickness

inch

InsulationDiameter

inch

JacketThickness

mils

OverallDiameter

Inch XLPE EPR

Net WeightLb/Mft

8

6

4

2

1/0

2/0

3/0

4/0

250

350

500

750

1000

7

7

7

7

19

19

19

19

37

37

37

61

61

0.14

0.17

0.22

0.27

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.06

125

125

125

125

125

125

125

125

140

140

140

155

155

0.43

0.47

0.52

0.57

0.64

0.68

0.73

0.78

0.87

0.96

1.08

1.29

1.44

80

80

80

80

80

80

95

95

110

110

110

125

125

0.60

0.64

0.68

0.74

0.80

0.85

0.92

0.97

1.09

1.19

1.31

1.55

1.70

190

234

298

394

539

639

788

944

1143

1496

2014

2950

3799

201

245

310

409

557

658

808

966

1171

1527

2030

2998

3854

manufacturing tolerances.

5kV 133% Insulation Level, 115 mils Insulation Thickness

Dimension and weights shown are nominal, unless otherwise indicated, and subject to

cable, voltage and insulation level, conductor

Ampacities

Cable Trays

Type MV

ICEA S-66-524, AEIC CS-S (XLP)

extrusion) results in a virtually perfect

cable core.

- Very low dielectric loss

Normal Operation 105° C130° CEmergency Overload

VULCANEL® 5kv Non-shielded power cables

adequate for proper termination of the shielding.

1) Simultaneous extrusion of strand shield,

250° CShort Circuit

UL 1072

326

318

310-15

National Electrical Code References:

VULCANEL®EPR/XLPE Non-Shielded power

size and type, length and reel dimensions.

SPECIFICATIONS

are ideally suited for use in industrial and

utility applications where shields cannot be

APPLICATION

abrasion, ozone and moisture.

- Electrical stability under stress

- Low dielectric loss- Chemical resistance

FEATURES

3) Easy-stripping insulation shield4) The external PVC jacket is resistant to

EPR insulation offers:- Excellent heat, moisture and corona

2) XLPE insulation offers:- Low moisture absorption.

- Good resistance to chemicals.

insulation and insulation shield (triple

accordance with the National ElectricalCode.

5) UL listed as MV-105, sunlight resistant,direct burial. Optional marking "For CTuse" available on single conductor in

HOW TO ORDER

resistance.

MAXIMUM CONDUCTOR TEMPERATURE

Page 1 of 2

ICEA S-68-516, AEIC CS-6-87 (EPR)

4

Page 7: 5Power Cable Specs Set 2.cdr

VULCANEL®

MEDIUM VOLTAGE

WET OR DRY POWER CABLE 5 KV

XLPE OR EPR NON-SHIELDED

Page 2 of 2

SizeAWG/kcmil

Numberof

Strands

ConductorDiameter

inch

InsulationThickness

inch

InsulationDiameter

inch

JacketThickness

mils

OverallDiameter

Inch XLPE EPR

Net Weightlb/Mft

8

6

4

2

1/0

2/0

3/0

4/0

250

350

500

750

1000

7

7

7

7

19

19

19

19

37

37

37

61

61

0.14

0.17

0.22

0.27

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.06

125

125

125

125

125

125

125

125

140

140

140

155

155

0.43

0.47

0.52

0.57

0.64

0.68

0.73

0.78

0.87

0.96

1.08

1.29

1.44

80

80

80

80

80

80

95

95

110

110

110

125

125

0.60

0.64

0.68

0.74

0.80

0.85

0.92

0.97

1.09

1.19

1.31

1.55

1.70

190

234

298

394

539

639

788

944

1143

1496

2014

2950

3799

201

245

310

409

557

658

808

966

1171

1527

2030

2998

3854

25kV 100% Insulation Level, 260 mils Insulation Thickness

8

6

4

2

1/0

2/0

3/0

4/0

250

350

500

750

1000

7

7

7

7

19

19

19

19

37

37

37

61

61

0.14

0.17

0.22

0.27

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.06

125

125

125

125

125

125

125

125

140

140

140

155

155

0.43

0.47

0.52

0.57

0.64

0.68

0.73

0.78

0.87

0.96

1.08

1.29

1.44

80

80

80

80

80

80

95

95

110

110

110

125

125

0.60

0.64

0.68

0.74

0.80

0.85

0.92

0.97

1.09

1.19

1.31

1.55

1.70

190

234

298

394

539

639

788

944

1143

1496

2014

2950

3799

201

245

310

409

557

658

808

966

1171

1527

2030

2998

3854

35kV 100% Insulation Level, 345 mils Insulation Thickness

Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.

8

6

4

2

1/0

2/0

3/0

4/0

250

350

500

750

1000

7

7

7

7

19

19

19

19

37

37

37

61

61

0.14

0.17

0.22

0.27

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.06

125

125

125

125

125

125

125

125

140

140

140

155

155

0.43

0.47

0.52

0.57

0.64

0.68

0.73

0.78

0.87

0.96

1.08

1.29

1.44

80

80

80

80

80

80

95

95

110

110

110

125

125

0.60

0.64

0.68

0.74

0.80

0.85

0.92

0.97

1.09

1.19

1.31

1.55

1.70

190

234

298

394

539

639

788

944

1143

1496

2014

2950

3799

201

245

310

409

557

658

808

966

1171

1527

2030

2998

3854

15kV 133% Insulation Level, 220 mils Insulation Thickness

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

15

Page 8: 5Power Cable Specs Set 2.cdr

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

VULCANEL®

MEDIUM VOLTAGE EPR

SHIELDED POWER CABLES 5, 15, 25, 35 KV

346 125

DESCRIPTION

1) Annealed bare stranded class B compactcopper conductor.

2) Extruded semiconducting strand shield.3) Ethylene propylene rubber (EPR) insulation.4) Extruded semiconducting insulation shield.5) Annealed copper tape shield (25% overlap

6) Polyvinyl chloride (PVC) protective jacket.minimum).

Three-phase electrical distribution systems.

trays.

Suitable for use in overhead installations,recognized raceways, direct burial or cable

APPLICATION

voltage and insulation level, conductor

Ampacities

Cable TraysType MV

- Chemical resistance

5) The external PVC jacket is resistant to

- Electrical stability under stress

MAXIMUM CONDUCTOR TEMPERATURE

SPECIFICATIONS

use" available on single conductor in

accordance with the National Electrical

Code.

abrasion, ozone and moisture.

6) UL listed as MV-105, sunlight resistant,

direct burial. Optional marking "For CT

3) Easy-stripping insulation shield

4) Tape shield provides high short circuit

capabilities and uniform shield impedance.

- Low dielectric loss

UL 1072

size and type, length and reel dimensions.

ICEA S-68-516, AEIC CS6-87

326

318

310-15National Electrical Code References:

VULCANEL® EPR shielded power cable,

2) EPR insulation offers:

- Excellent heat, moisture and corona

resistance.

insulation and insulation shield (triple

extrusion) results in a virtually perfect

cable core.

250 °CShort Circuit

1) Simultaneous extrusion of strand shield,

Normal Operation 105 °C130 °CEmergency Overload

FEATURES

SPECIFICATIONS

HOW TO ORDER

Page 1 of 2

Size

AWG/kcmil

Numberof

Strands

ConductorDiameter

Inch

InsulationThickness

inch

Insul. Shld.Diameter

inch

JacketThickness

mils

OverallDiameter

Inch

NetWeightlb/Mft

6

4

2

1/0

2/0

3/0

4/0

250

350

500

750

1000

7

7

7

19

19

19

19

37

37

37

61

61

0.17

0.22

0.27

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.11

0.45

0.49

0.55

0.62

0.66

0.71

0.76

0.81

0.91

1.03

1.21

1.36

0.53

0.57

0.63

0.70

0.74

0.79

0.84

0.90

0.99

1.13

1.32

1.46

60

60

60

80

80

80

80

80

80

80

80

80

0.67

0.71

0.74

0.85

0.92

0.97

1.02

1.07

1.17

1.32

1.50

1.64

290

357

478

668

775

933

1071

1226

1560

2150

3027

3845

5kV 133% Insulation Level, 115 mils Insulation Thickness

2

1/0

2/0

3/0

4/0

250

350

500

750

1000

7

19

19

19

19

37

37

37

61

61

0.27

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.11

0.67

0.74

0.78

0.83

0.88

0.94

1.03

1.16

1.34

1.36

0.75

0.82

0.86

0.91

0.96

1.02

1.14

1.26

1.44

1.59

80

80

80

80

80

80

80

80

80

110

0.93

1.00

1.04

1.09

1.14

1.20

1.32

1.44

1.62

1.83

570

736

849

1010

1190

1330

1753

2280

3142

5794

5kV 100% Insulation Level, 175 mils Insulation Thickness

Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.

6

Page 9: 5Power Cable Specs Set 2.cdr

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

Page 2 of 2

VULCANEL®

MEDIUM VOLTAGE EPR

SHIELDED POWER CABLES 5, 15, 25, 35 KV

Size

AWG/kcmil

Numberof

Strands

ConductorDiameter

Inch

InsulationThickness

inch

Insul. Shld.Diameter

inch

JacketThickness

mils

OverallDiameter

Inch

NetWeightlb/Mft

6

4

2

1/0

2/0

3/0

4/0

250

350

500

750

1000

7

7

7

19

19

19

19

37

37

37

61

61

0.17

0.22

0.27

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.11

0.45

0.49

0.55

0.62

0.66

0.71

0.76

0.81

0.91

1.03

1.21

1.36

0.53

0.57

0.63

0.70

0.74

0.79

0.84

0.90

0.99

1.13

1.32

1.46

60

60

60

80

80

80

80

80

80

80

80

80

0.67

0.71

0.74

0.85

0.92

0.97

1.02

1.07

1.17

1.32

1.50

1.64

290

357

478

668

775

933

1071

1226

1560

2150

3027

3845

15kV 133% Insulation Level, 220 mils Insulation Thickness

1/0

2/0

3/0

4/0

250

350

500

750

1000

19

19

19

19

37

37

37

61

61

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.11

0.92

0.96

1.00

1.06

1.11

1.21

1.33

1.51

1.66

1.00

1.04

1.11

1.16

1.22

1.31

1.43

1.61

1.80

80

80

80

80

80

80

80

110

110

1.18

1.22

1.29

1.34

1.40

1.49

1.61

1.85

2.04

894

1009

1181

1394

1537

1936

2516

3620

4543

25kV 100% Insulation Level, 260 mils Insulation Thickness

1/0

2/0

3/0

4/0

250

350

500

750

1000

19

19

19

19

37

37

37

61

61

0.34

0.38

0.43

0.48

0.52

0.62

0.74

0.91

1.11

1.09

113

1.18

1.23

1.29

1.38

1.50

1.68

1.83

1.19

1.23

1.28

1.33

1.39

1.49

1.61

1.83

1.97

80

80

80

80

80

80

110

110

110

1.37

1.41

1.46

1.51

1.57

1.67

1.85

2.07

2.21

1041

1226

1380

1569

1750

2163

2893

3900

4807

35kV 100% Insulation Level, 345 mils Insulation Thickness

manufacturing tolerances.Dimension and weights shown are nominal, unless otherwise indicated, and subject to

17

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-94735-05

Page 10: 5Power Cable Specs Set 2.cdr

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

ICEA-S-68-516

SPECIFICATIONS

three conductor cable, voltage size andlength.

Condumex Mining Cable EPR type SHD-GC

HOW TO ORDER

MINING CABLE EPR TYPE SHD-GC

THREE CONDUCTOR 5000 VOLTS

18.SHD-GC.01

with a nylon webbing, provides a tough, defense

round configuration.

and Health Administration Approval No. P-218-1-MSHA

by the Pennsylvania Department of Environmental

Resources. Meets MSHA flame test requirements.

6) Acceptance No. P-218-1-MSHA by Mines Safety

5) PLCV-Cured extra-heavy-duty CSPE, reinforced

4) Prevulcanized thermosetting non-wicking fillers

mechanical resistant jacket.

resistance, outstanding corona resistance,

high dielectric strength and chemical resistance.

designed for flexibility and resistance to

FEATURES

2) Ground check conductor facilitates fail-safe

3) EPR insulation offers excellent heat and moisture

are used if necessary to obtain a substantially

1) Special tinned copper stranded conductors

fatigue resulting from bending and flexing.

ground monitoring for maximum safety.

Dimension and weights shown are nominal, unless otherwise indicated, and subject to

6

4

2

1

1/0

2/0

3/0

4/0

300

350

7x30/29

7x47/29

7x74/29

7x37/25

7x47/25

7x60/25

7x75/25

19x35/25

19x49/25

19x58/25

0.20

0.25

0.31

0.35

0.39

0.45

0.50

0.59

0.69

0.76

110

110

110

110

110

110

110

110

120

120

10

8

6

5

4

3

2

1

1/0

2/0

8

8

8

8

8

8

8

8

8

8

1.56

1.68

1.87

1.95

2.08

2.20

2.36

2.50

2.81

2.95

1675

1888

2322

2653

3068

3504

4206

5023

6371

7654

SizeAWG/kcmil

Number ofStrands/AWG

ConductorDiameter

inch

InsulationThickness

mils

GroundSizeAWG

GroundCheck Size

AWG

OverallDiameter

inch

NetWeightlb/mft

manufacturing tolerances.

MAXIMUM CONDUCTOR TEMPERATURE

Normal continuous 90° C

130° COverload

250° CShort circuit

MAXIMUM OPERATING VOLTAGE

5,000 volts

Trailing cable on ac mining equipment

where service conditions are severe and

maximum safety is mandatory, such as

APPLICATION

power shovels and draglines in open-pit

mines, quarries, gantry cranes and slag

reclaiming. Also used for medium voltage

distribution in underground mines where

frequent relocation is necessary.

DESCRIPTION

1) Three flexible annealed tinned copperrope-lay stranded conductors.

2) Extruded semi-conducting conductor shieldand ethylene propylene rubber (EPR) insulation.

3) Color coded cotton/copper braid shieldapplied over semi-conducting tape.

4) Two annealed tinned copper rope-lay strandedgrounding conductors.

5) Annealed tinned copper rope-lay stranded

and covered with a yellow cotton braid.

chlorosulfonated polyethylene (CSPE) jacket.

6) Rubberized cotton binder tape.7) Nylon web reinforced extra-heavy-duty

ground check conductor, yellow EPR insulation

346 2 157

18

Page 11: 5Power Cable Specs Set 2.cdr

5) Overall flame retardant PVC jacket.

DESCRIPTION

XLPW insulation.

3) Fillers (if required)

4) Binder tape over core.

2) Cross-Linked polyethylene, thermosetting

1) Annealed bare stranded compressed

Class B copper conductors.

without grounding conductor.Volts number and size of conductors, with or

Condumex Type TC cable may be used for power,

messenger. Type TC cable may be used in wet

lighting, control, signal and communication circuits,in cable trays, raceways, direct burial, or on

HOW TO ORDER

Condumex Tray Cable Type TC/XHHW, 600

SPECIFICATIONS

UL 1277

APPLICATION

most chemicals in accordance with the

MAXIMUM OPERATING VOLTAGE

National Electrical Code.

or dry locations and in the presence of oil and

6) Acceptable for Class 1, Division 2, HazardousLocations applications.

5) PVC jacket is UL rated 90O

C and listed OilResistant I.

600 volts

MAXIMUM CONDUCTOR TEMPERATURE

90 CO

130 CO

FEATURES

OverloadNormal

1) UL listed for direct burial.2) Flame retardant, (passes UL 1277 70,000

National Electrical Code.

BTU flame test.)3) Sunlight resistant; can be installed outdoors.4) UL listed as Type TC for power and control

tray cable, use in accordance with the

3 145 2

POWER CABLE TYPE TC

XHHW 600 VOLTS

Size

AWG/kcmil

Numberof

Conductors

GroundConductor

AWG

InsulationThickness

mils

JacketThickness

mils

OverallDiameter

inch

NetWeightlb/Mft

Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.

8

6

4

2

1/0

2/0

3/0

4/0

250

350

500

8

6

4

2

1/0

350

500

3

3

3

3

3

3

3

3

3

3

3

4

4

4

4

4

4

4

10

8

8

6

6

4

4

4

4

3

2

10

8

8

6

6

3

2

45

45

45

45

55

55

55

55

65

65

65

45

45

45

45

55

65

65

60

60

80

80

80

80

80

80

110

110

110

60

80

80

80

80

110

110

0.66

0.74

0.88

1.03

1.21

1.31

1.42

1.54

1.75

1.96

2.25

0.73

0.87

0.97

1.12

1.34

2.17

2.49

336

474

691

1015

1501

1861

2255

2735

3298

4437

6120

418

630

867

1276

1900

5681

7870

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

19

Page 12: 5Power Cable Specs Set 2.cdr

DESCRIPTION

copper conductor.

2) Cross-linked polyethylene (XLPE)

insulation.

compressed (6 AWG-1000 MCM)

1) Annealed bare stranded class B

concentric round (14-8 AWG)

APPLICATION

Power or control circuits in recognized

switchboard wiring.

Dry locations 90° C

presence of oil. Also suitable as

designs.

temperatures.

4) Suitable for installation in sub-zero

pulling and greater conduit fill.

5) Optical "For CT use" marking, for use in

cable trays. Sunlight resistant in

FEATURES

2) Good moisture resistance.

raceways, in wet or dry location and in

75° CWet locationsOverload 130° CShort Circuit

MAXIMUM OPERATING VOLTAGE

3) Good resistance to most oils and

chemicals.

MAXIMUM CONDUCTOR TEMPERATURE

600 volts

accordance with NEC Article 318.6) Available in VW-1 and non VW-1

UL-44

SPECIFICATIONS

Chapter 9

250° C

1) Smaller overall diameter for easier

HOW TO ORDER

National Electrical Code References:

Article 310

VULCANEL®

XLPE cable, type XHHW-2,600 volts, size and length.

Ampacities

Switchboard wiring

Conduit fill tables

* Dupont trade mark

Article 384

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

VULCANEL

TYPE XHHW-2 600 VOLTS

®XLPE CABLE

2 1

Size

AWG/kcmil

Numberof

Strands

ConductorAreakcmil

ConductorDiameter

inch

InsulationsThickness

Mils

OverallDiameter

inch

NetWeightlb/Mft

manufacturing tolerances.

14

12

10

8

6

4

2

1/0

2/0

3/0

4/0

250

300

350

400

500

600

750

1000

7

7

7

7

7

7

7

19

19

19

19

37

37

37

37

37

61

61

61

4.1

6.5

10.3

16.5

26.2

41.7

66.3

106.0

133.0

168.0

211.0

0.07

0.09

0.11

0.15

0.18

0.23

0.29

0.37

0.41

0.47

0.52

0.57

0.62

0.67

0.72

0.80

0.88

0.98

1.14

30

30

30

45

45

45

45

55

55

55

55

65

65

65

65

65

80

80

80

0.13

0.15

0.17

0.24

0.27

0.32

0.38

0.48

0.52

0.58

0.63

0.70

0.75

0.80

0.85

0.93

1.04

1.15

1.30

19

48

42

71

98

153

241

378

446

556

697

851

997

1180

1306

1662

1974

2450

3240

Dimension and weights shown are nominal, unless otherwise indicated, and subject to

10

Page 13: 5Power Cable Specs Set 2.cdr

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

National Electrical Code References:

Product Article 310, Table 310-13

Ampacities Article 310-15

HOW TO ORDER

CONDUMEX type RHH-RHW-USE-2

XLPE 600 volts, size, length, quantity,

packaging.

DESCRIPTION

polyethylene (XLPE) insualtion.

1) Annealed bare stranded class B

conductor

2) Flame-retardant cross-linked

TYPE RHH-RHW-USE-2

COPPER XLPE 600 VOLTS

APPLICATION

May be installed in free air, all raceways or

underground service entrance cable.

Type RHH 90° C Dry and

temperatures.

6) Stable electrical propoerties.

UL-44 Standard for Rubber-Insulated

use in direct burial in industrial and

commercial application. May be used as

7) Extremely tough.

SPECIFICATIONS

4) Good resistance to most oils and

3) UL approved as VW-1 (RHH or RHW)

chemicals.

5) Suitable for installation in sub-zero

2) UL listed as types RHH or RHW or USE for

resistant insulation.

damp locations

ICEA S-66-524 Standard for Cross-Linked

Type RHW or 75° C Dry and

use in accordance with the National

Electrical Code.

MAXIMUM CONDUCTOR TEMPERATURE

600 volts

MAXIMUM OPERATING VOLTAGE

USE wet locatinons

1) Flame retardant, moisture and heat

FEATURES

Wires and Cables.

Polyethylene Insualted Wire and Cable.

Size

AWG/kcmil

Numberof

Strands

ConductorAreakcmil

ConductorDiameter

inch

InsulationsThickness

mils

OverallDiameter

inch

NetWeightlb/Mft

8

6

4

2

1/0

2/0

3/0

4/0

250

300

350

400

500

600

750

1000

7

7

7

7

19

19

19

19

37

37

37

37

37

61

61

61

16.5

26.2

41.7

66.3

106

133

168

211

0.15

0.18

0.22

0.28

0.36

0.41

0.46

0.51

0.56

0.61

0.66

0.71

0.79

0.87

0.97

1.12

60

60

60

60

80

80

80

80

95

95

95

95

95

110

110

110

0.27

0.31

0.35

0.41

0.53

0.58

0.63

0.69

0.76

0.82

0.87

0.92

0.99

1.11

1.20

1.36

73

108

161

245

392

485

600

746

887

1052

1216

1380

1708

2055

2542

3353

Dimension and weights shown are nominal, unless otherwise indicated, and subject tomanufacturing tolerances.

11 111

Page 14: 5Power Cable Specs Set 2.cdr

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-947307-04

CODE SIZE STRAND OVERALL DIAMETER NET WEIGHT RUPTURE STRENGTH

Turkey

Swan

Swallow

Sparrow

Robin

Raven

Quail

Pigeon

Penguin

Partridge

Linnet

Oriole

Ibis

Lark

Hawk

Hen

Heron

Dove

Eagle

Duck

Grosbeak

Starling

Crow

Drake

Condor

Canary

Rail

Bluejay

6

4

3

2

1

1/0

2/0

3/0

4/0

266.8

336.4

336.4

397.5

397.5

477.0

477.0

500.0

556.5

556.5

605.0

636.0

715.5

715.5

795.0

795.0

900.0

954.0

1113.0

6/1

6/1

6/1

6/1

6/1

6/1

6/1

6/1

6/1

26/7

26/7

30/7

26/7

30/7

26/7

30/7

30/7

26/7

30/7

54/7

26/7

26/7

54/7

26/7

54/7

54/7

45/7

45/7

0.198

0.250

0.281

0.316

0.355

0.398

0.447

0.502

0.563

0.642

0.721

0.741

0.783

0.806

0.858

0.883

0.904

0.927

0.953

0.953

0.990

1.051

1.035

1.108

1.093

1.162

1.165

1.259

5.03

6.35

7.14

8.03

9.02

10.11

11.35

12.75

14.30

16.31

18.31

18.82

19.89

20.47

21.79

22.43

22.96

23.55

24.21

24.21

25.15

26.70

26.29

28.14

27.76

29.51

29.59

31.98

36

58

73

91

115

145

183

231

291

366

162

525

545

619

654

743

781

765

869

779

872

986

918

1095

1021

1160

1076

1256

54

86

108

136

171

216

273

344

433

544

688

782

811

921

973

1106

1162

1138

1293

1159

1298

1467

1366

1629

1520

1726

1601

1869

1,190.3

1,860.8

2,304.0

2,857.5

3,555.0

4,387.5

5,310.0

6,682.5

8,430.8

11,317.5

14,107.5

17,325.0

16,312.5

20,317.5

19,507.5

23,850.0

24,750.0

22,725.0

27,900.0

23,400.0

25,200.0

28,350.0

26,100.0

31,500.0

28,125.0

32,337.0

25,875.0

30,987.0

WORD AWG or MCM AL/Steel Inch mm Lbs./mft kg/km lbs

manufacturing tolerances.Dimension and weights shown are nominal, unless otherwise indicated, and subject to

BARE ACSR CABLE

ALUMINUM CONDUCTOR STEEL REINFORCED

26.ACSR.01

DESCRIPTION

CONDUCTORS

Aluminum 1350 wire concentrically laid overa solid or stranded galvanized steel core.

Mechanical design requirements.

5) Good corrosion resistance.

3) High resistance to mechanical strength.

4) Wide variety of sizes available in long

lengths to suit both electrical and

fewer towers required.

strength to permit the longest possible

spans.

2) Minimum sag between supports with

1) Ideal combination of conductivity and

FEATURES

Code Word, quantity required in weight.

ACSR cable, size, Aluminum Association

HOW TO ORDER

Overhead transmission, subtransmission

overhead electrical cables. Messenger and

overhead lines. Messenger cables to support

APPLICATION

and distribution systems. Static wires to protect

power support conductor in catenary systems

for railroad electrification.

SPECIFICATIONS

ASTM B498 Galvanized steel class A

ASTM B232 Conductor overall

SPECIFICATIONS

ASTM B230 Aluminum wires

MAXIMUM CONDUCTOR TEMPERATURE

Normal Operation 75 °C

112

Page 15: 5Power Cable Specs Set 2.cdr

NOTES:

Condumex Wire and Cable 2590 114th Street, #200 - Grand Prairie, TX 75050 (800) 925-94735-05

Page 16: 5Power Cable Specs Set 2.cdr

Grand Prairie, Texas

800-925-9473