    easYgen-3200 TrainingSection 10 - Application

    marked

    CERTIFICATE ofDesign Assessment

    byABSAmerican Bureau of Shipping & Affiliated Companies

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    2/19

    Proprietary Information

    Proprietary Information

    ContentsIntroduction

    Start / Stop in Auto

    Logical Outputs

    Start / StopAlarm Classes

    Protection

    Slide 3

    4

    6

    1013

    14

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    3/19

    3

    Proprietary Information

    Introduction

    This section is a summary

    and repeating of things

    mentioned before.

    It is designed to memorize

    important settings and how

    to handle different

    applications.

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    4/19

    4

    Proprietary Information

    Generator:

    Start conditions

    LM: Start in auto is true

    may be used with load dependent start/stop function

    LM: Start w/o load is true

    LM: Critical mode is true

    Loss of mains {GCB/MCB} (Emergency mode)

    Mains voltage/frequency out of operating range

    Mains rotation field wrong

    Fail to close MCB (if parameter is enabled)

    Stop conditions

    LM: Start conditions are false

    Alarm class C-F detected

    LM: Stop in auto

    LM: Inhibit emergency mode

    Mains:

    Close MCB: Open MCB:

    Mains are within accepted limits Dependent upon breaker logic

    DI8 is de-energized (MCB is open) For mains decoupling

    DI6 is energized (Release MCB) (if parameter is set)

    Conditions for synchronization or

    dead bus closing are met

    Start / Stop in Auto

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    5/19

    5

    Proprietary Information

    Start / Stop in Auto

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    6/19

    6

    Proprietary Information

    Priority Hierarchy of the Logical Outputs:

    Start

    Start, breaker dependingon parameter

    No start

    Open breaker

    Close breakerClose breaker with pause

    No start

    Open breaker

    Logical Outputs

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    7/19

    7

    Proprietary Information

    Logical OutputsLogical Functions

    - Start request in AUTO

    - Stop request in AUTO

    - Load dependent (LD) start stop- Start w/o load

    - Critical mode

    - Inhibit emergency

    - External acknowledge

    - Undelayed close GCB- External mains decoupling

    requested

    - Enable MCB

    - Firing speed reached

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    8/19

    8

    Proprietary Information

    Logical OutputsLogical Functions

    -Setpoint 2 power

    -Setpoint 2 power factor

    -Setpoint 2 frequency

    -Setpoint 2 voltage

    -Frequency droop active

    -Voltage droop active

    -Discrete f/P + (raise)

    -Discrete f/P(lower)-Discrete V/PF + (raise)

    -Discrete V/PF(lower)

    -RUN Synchronization mode

    -CHECK Synchronization mode

    -PERMISSIVE Synchronization mode

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    9/19

    9

    Proprietary Information

    Logical OutputsLogical Functions

    - Constant idle run

    - Auto idle mode

    - AUTO operation mode

    - MANUAL operation mode

    - STOP operation mode

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    10/19

    10

    Proprietary Information

    Diesel engine

    - Pre-glow function

    - Fuel or Stop solenoid activation

    - Crank/start circuit control

    Gas engine

    - Ignition

    - Gas valve

    - Crank/start circuit control

    External logic

    - Fuel solenoid as a start request to external controllers

    - External control must take care of start sequenceno start failure

    Start / Stop Logic

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    11/19

    11

    Proprietary Information

    Start / Stop SequenceDiesel engine

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    12/19

    12

    Proprietary Information

    Start / Stop SequenceGas engine

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    13/19

    13

    Proprietary Information

    Alarm classes

    Warning

    Shut down

    Shut down

    Shut down

    Shut down

    Action

    Display

    Display and Horn

    Display and Horn

    Display and Horn

    Display and Horn

    Display and Horn

    Unlaod Gen. And open GCB

    Open GCB immediate

    Unlaod Gen. And open GCB

    Open GCB immediate

    Cool down

    Cool down

    Immediate Stop

    Immediate Stop

    For control purposes via LogicsManager to

    change/modify sequencing or discrete outputs

    Warning

    Class Result

    internal

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    14/19

    14

    Proprietary Information

    # of Trip Levels ANSI Code

    Over-/undervoltage 2/2 [59/27]

    Voltage asymmetry 1 [47]

    Over-/underfrequency 2/2 [81O/U]

    Overload (IOP/MOP) 2 [32]

    Reverse/reduced power 2 [32R/F]

    Unbalanced load 2 [46 measured]

    Definite time-overcurrent 3 [50/51]

    Inverse time-overcurrent 1 [IEC 255]

    Overspeed (MPU) 2 [12]

    Measured ground current 2 [50G] Calculated ground current 2

    Generator Protection

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    15/19

    15

    Proprietary Information

    # of Trip Levels ANSI Code

    Power factor (PF) lagging 2

    PF leadingloss of excitation 2 [40Q]

    Phase rotation field CW/CCW 1

    PsetpointPactualmismatch 1 Controller* Unload mismatch (time out monitoring) 1 Controller*

    Operating range failed 1 Controller*

    * plausibility monitoring features

    Generator Protection

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    16/19

    16

    Proprietary Information

    Engine Protection Maintenance days exceeded

    Maintenance hours exceeded

    Over-/Underspeed (MPU)

    Unintended Stop

    Engine Stop malfunction

    Speed/frequency mismatch

    Start failure

    Charge alternator low voltage

    Red stop lamp (J1939)

    Amber warning lamp (J1939)

    Battery over-/undervoltage

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    17/19

    17

    Proprietary Information

    Mains Monitoring and decoupling# of Trip Levels ANSI Code Over-/undervoltage 2/2 [59/27 ]

    Over-/underfrequency 2/2 [81O/U]

    Import/Export power 2 [32]

    Power factor leading 2

    Power factor lagging 2 Phase shift 1ph/3ph [78 ]

    Field rotation

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    18/19

    18

    Proprietary Information

    GCB / MCB fail to close

    GCB / MCB fail to open

    Synch. Time Out GCB / MCB

    Phase rotation mismatch generator / busbar / mains Mains decoupling

    CAN bus communications monitoring (J1939, CANopen)

    Parameter alignment (multiple units)

    Missing members (multiple units)

    EEPROM failure (internal CPU)

    Wire break analog inputs

    Discrete inputs

    FlexLimitsTM for analog values

    Miscellaneous Monitoring

    Start / Stop Auto

    Start / Stop

    Logical Outputs

    Alarm Classes

    Protection

    Introduction

  • 8/13/2019 37397 a EG3200 Section 10 Application (NXPowerLite)

    19/19

    19

    Proprietary Information

    Note:

    Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to

    update or otherwise revise any portion of this publication at any time. Technical data and detailed information is available in Woodward

    product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or

    information otherwise expressly represented in writing by Woodward as correct and accurate for the specific facts, circumstances andapplications.

    Other sections are :

    1 Overview

    2 Hardware and I/O

    3 Operational Modes

    4 Configuration and ToolKit

    5 Communication

    6 LogicsManager

    7 Analog Manager

    8 Controller

    9 Synchronization and breaker

    10 Application