36 kV Medium Voltage Vacuum circuit...

44
Fixed, middle rolling and floor rolling ranges of circuit breaker and disconnector Make the most of your energy SM 36 kV Medium Voltage Vacuum circuit breaker HVX Series Catalogue | 2015 Medium Voltage Distribution

Transcript of 36 kV Medium Voltage Vacuum circuit...

Page 1: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

Fixed, middle rolling and floor rolling ranges of circuit breaker and disconnector

Make the most of your energySM

36 kV Medium Voltage Vacuum circuit breaker

HVX SeriesCatalogue | 2015Medium Voltage Distribution

Page 2: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

HVX series

Page 3: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 1

Contents

General overview 5

HVX Range 13

Complementary devices 33

Order form 39

HVX series

Page 4: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN2

Your requirements

Ease of use

Reliability

Safety

Page 5: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 3

Our solution Ease of use

• Modular design can adapt to requirements• Compact, simple installation facilitates

integration• Straightforward operation • Environmentally friendly with no harmful gas

or oil released into the environment

Reliability• Robust and field proven technology• Limited maintenance• Extremely resistant to severe environments

due to its embedded pole construction• Excellent mechanical performance

Safety• Conformity with main standards• Fully tested equipment• Highly visible mechanical indicators• No hazardous tripping• Comprehensive Interlocks

Page 6: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

General oveview

Page 7: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 5

General overviewHVX series

Application 6

Standards and certifications 7

Operating conditions 7

Presentation 8

Page 8: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN6

PE

6050

2

HVX series

The result of a sustained development effort for application in air-insulated switchgear unitsThe HVX series vacuum circuit breaker is the technical result of SchneiderElectric’s one hundred years, experience in the medium-voltage field.The HVX series offers a proven state-of-the-art design to meet your specifications for power switching devices in air-insulated switchgear.

b a fixed, frontal version b a withdrawable, frontal version with a circuit breaker and its cradle or its cassette b a fixed version equipped with an integrated protection system b accessories supplied separately.

The HVX series circuit breaker is operated via a spring mechanism that provides an operating speed independent of the operator and that does not require an auxiliary power supply.When the operating mechanism is motorised the circuit breaker can include telecontrol functions and carry out rapid reclosing cycles.The circuit breaker versions are easy to integrate in a cubicle environment.An Installation Guide details the required procedure.

ApplicationsThe HVX series is our latest range of vacuum circuit breakers, which are mainly integrated in MV switchgear. The HVX series comprises core components of MV switchgear for panel builders, which are used to protect overhead cables, cables, motors, transformers or generators. The HVX series is suitable for mainstream air-insulated switching devices and is widely used in the Oil & Gas, Power distribution system, Transportation, Industry and Mining & Metal segaments.

Application

IndustryPower distribution

Mining & Metal

Oil & Gas

PE

5657

9

PE

5825

2

PE

5825

3

Page 9: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 7

Certified quality in accordance withISO 9001 and ISO 9002

Operating conditionsThe normal range of operating conditions for HVX circuit breakers is in line withIEC62271-100, IEC62271-1. Please consult the manufacturer for any requirement beyond the normal range of operating conditions.

Operating conditionsTemperature grade Optional:

-5°C indoor -25°C indoor

Minimum/maximum ambient temperature -5°/40°C

Average value over 24 hours (max) 35°C

Altitude above sea level 1000 m

(For installation at higher altitudes, please consult us.)

HVX series Standards and certifications& Operating conditions

StandardsHVX series vacuum circuit breakers conform to the following standards:IEC 62271-100, IEC 62271-1.

Quality & EnvironmentQuality production management The vacuum interrupter manufacturing units are certified ISO 9001, and employ a mature and robust Quality Management System (QMS).

Protection of the environmentSchneider Electric is committed to a long-term environmental approach. All necessary measures have been taken in connection with our services, suppliers and subcontractors to ensure that the materials used in the composition of the equipment do not contain any substances prohibited by regulations and directives.In order to help you protect the environment and relieve you of any concerns in terms of storage or dismantling, Schneider Electric Services offers to take back your equipment at the end of its life.

Page 10: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN8

Tensioning the spring

Spring drum

Main shaft

Drive casing

Vacuum interrupter chamber

Vacuum interrupter chamber

Drive casing

Opening Closing

PM

1042

00HVX series Presentation

Operating mechanismThe operating mechanisms have been simplified to increase reliability and give extended life with very low maintenance.Instead of the traditional spring operating mechanism, the HVX series incorporates a single-shaft system and only one torsion spring, reducing the number of parts and increasing reliability.The cam output from three independent phases is ideal for the vacuum switch.The transmission mechanism's one-step output and the special axletree design provides optimum transmission efficiency to ensure energy saving and a stable, reliable mechanism.

Operating principleEnergy is stored in the spiral spring by means of the electric motor or manual crank. Opening and closing of the vacuum interrupter is controlled by the cam; upon closing, the spring automatically restores the energy for an integrated automatic on/off operating cycle.An on/off storage mechanism, with its special mechanism, can absorb the excess energy of the drive mechanism through a quick on/off operation.The operating mechanism has electric and manual charging devices. The relevant interlock prevents manipulation errors after energy storage.

Drive spring-charging mechanism using a crank

The HVX series is designed as a modular system, allowing it to be interchanged with similar products. The HVX series is available in a range of standard, fixed or withdrawable configurations, with plug-in or bolted connections.

The values below are given for normal operating conditions according to IEC62271-100, IEC62271-1.

Technical characteristicsRated voltage Ur (kV) 36

Rated lightning impulse withstand voltage Up (kV peak) 170

Rated short-time power-frequency voltage (kV) 70

Rated short-circuit making current (kA) 6380

Rated short-circuit breaking current (kA) 2531.5

Rated current(1) (A) 1,250-3,150

(1) When the rated current is 3150 A, force cooling is required.

DM

1033

91

DM

1033

92

Page 11: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 9

OFF button (rocker “O”) or push button “O” to switch circuit breaker OFF (open)

ON button (rocker “I”) or push button “I” to switch circuit breaker ON (close)

Rating plate

Operation counter

Circuit breaker position indicator

Closing spring position indicator

Insertion opening for charging the closing spring

HVX series Presentation

Vacuum interrupterThe Schneider Electric VG vacuum interrupter series achieves a truly optimal design, thanks to the latest computer modeling tools. With the most advanced one-stop sealing technology, the VG series minimizes artificial pollution during production.Based on our patent design and comprehensive knowledge of vacuum interrupter technology, Schneider Electric's vacuum interrupter is a standout in the medium-voltage field with its high reliability, small size and long service life.

Embedded-pole constructionThe embedded pole is another of Schneider Electric's contributions to medium voltage products, with its 10 years-plus experience in design and manufacture, and it has been tried and tested in the field for many years. Employing the embedding technology, it completely integrates the vacuum interrupter, the main circuit and the insulated shaft in an epoxy pole to totally isolate the main circuit from the outside. This gives the pole optimum environmental adaptability, since the circuit breaker can function normally under harsh conditions.

InterfaceFront face Compact and user-friendly design of the front face, integrating all important indications and statuses for clear understanding.

PM

1042

04

DM

1033

93

Page 12: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN10

HVX series Presentation

TestIn compliance with the present standards of vacuum circuit breaker performance, HVX has been demonstrated through a series of R&D timing and type tests. These tests have been performed in the manufacturer’s own laboratory and authoritative institutions such as KEMA. The test content not only includes the general type test items but also covers different special requirements, for example, generator protection, capacitor bank switching, breaking of hyper-standards and short-circuit making current, very long electrical and mechanical endurance, etc.

Floor rolling designIn addition to the middle rolling, the floor rolling design is also available if preferred. It provides the necessary robust interlock suitable for your operational requirements, and can surely fulfil all your possible needs and ensure a high level of quality.

CradleWe can provide cradles for various kinds of cabinets, and can prepare bus grounding switches according to your specific requirements, which are suitable for various electrical performance and installation requirements.

Middle rolling designThe robust design of the middle rolling truck provides you with a reliable interlock with panels, and flexible racking-in and racking-out operations. The mechanical and electrical design effectively avoids handling errors.

DM

1033

95D

M10

3396

DM

1033

94

Page 13: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 11

UTX Disconnector truckThis device can be used to disconnect the upstream and downstream circuits in the cubicle. It is installed in the same location as the withdrawable circuit breaker in the cradle.It includes a device for locking it in the in-service position.

HVX series Presentation

Relationship between the permitted operating times of vacuum interrupter and breaking current applicationsThe following graph explains the relationship between the permitted VG operating times and breaking current.

Applications

b Rated short-circuit breaking current and non-full loaded current b Breaking of asymmetrical current b Automatic re-closing b Connection to no-load cables and overhead lines b Out-of-phase breaking b Connection to no-load transformer b Double earthing fault current breaking b Breaker transient recovery voltage gradient triggering significant

short-circuit current b Switching motors and inductance in a vacuum

MTX Voltage transformer truckMTX trolleys suitable for various kinds of voltage transformers, enabling you to configure the middle rolling chassis or floor rolling chassis according to the installation requirements.

DM

1033

98

DM

1033

99D

M10

3400

Page 14: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

HVX Range

Page 15: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 13

HVX RangeHVX series

Overview 14

HVX series Vacuum circuit breaker Selection guide 16Dimensions HVX 36 kV series fixed type 17HVX 36 kV series middle rolling type 18HVX 36 kV series Floor rolling type 19Cradle - For HVX 36 kV series middle rolling type 20Electrical circuit diagram HVX 36 kV vacuum circuit breaker, fixed type with anti-pumping relay 21HVX 36 kV vacuum circuit breaker, withdrawable type with anti-pumping relay 22

UTX Disconnector truck Selection guide 23Dimensions UTX 36 kV middle rolling type 24UTX 36 kV floor rolling type 25Cradle - For UTX 36 kV series middle rolling type 26

MTX Voltage transformer truck Selection guide 27Dimensions MTX 36 kV middle rolling type 28MTX 36 kV floor rolling type 29Cradle - For MTX 36 kV series middle rolling type 30

Page 16: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN14

OverviewHVX series

HVX series design type Fixed Middle rolling Floor rolling

Type Fixed type Middle rolling type Floor rolling typeRated voltage 36 kV 36 kV 36 kV

Rated short-circuit current Up to 31.5 kA Up to 31.5 kA Up to 31.5 kA

Rated current(1) Up to 3150 A Up to 3150 A Up to 3150 A

Benefits

Fixed Vacuum Circuit Breaker.Embedded pole for better dielectric and environmental pollution withstand.

Middle rolling Vacuum Circuit Breaker.Embedded pole for better dielectric and environmental pollution withstand.

Floor rolling Vacuum Circuit Breaker.Embedded pole for better dielectric and environmental pollution withstand.

(1) When the rated current is 3150 A, force cooling is required.

UTX design type Middle rolling Floor rolling

Type Middle rolling type Floor rolling typeRated voltage 36 kV 36 kV

Rated short-circuit current Up to 31.5 kA Up to 31.5 kA

Rated current(1) Up to 3150 A Up to 3150 A

Benefits

Middle rolling Disconnector Truck.Embedded pole for better dielectric and environmental pollution withstand.

Floor rolling Disconnector Truck.Embedded pole for better dielectric and environmental pollution withstand.

(1) When the rated current is 3150 A, force cooling is required.

DM

1033

94

DM

1033

95

DM

1034

01D

M10

3399

DM

1034

02

Page 17: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 15

OverviewHVX series

MTX Design type Middle rolling Floor rolling

Type Middle rolling type Floor rolling typeRated voltage 36 kV 36 kV

Power frequency withstand voltage Up to 70 kV Up to 70 kV

Lightning impulse withstand voltage Up to 170 kV Up to 170 kV

BenefitsMiddle rolling voltage transformer truck, suitable for various installation requirements.

Floor rolling voltage transformer truck, suitable for various installation requirements.

DM

1034

00

DM

1034

03

Page 18: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN16

Selection guideHVX series Vacuum circuit breaker

Type

HVX

36-

25-1

2

HVX

36-

25-1

6

HVX

36-

25-2

0

HVX

36-

25-2

5

HVX

36-

25-3

1(1)

HVX

36-

31-1

2

HVX

36-

31-1

6

HVX

36-

31-2

0

HVX

36-

31-2

5

HVX

36-

31-3

1(1)

Phase distance mm 275/300

Rated voltage kV 36

Rated insulation level

Power frequency withstand voltage kV 70

Lightning impulse withstand voltage kV 170

Rated frequency Hz 50/60

Rated current A 1250 1600 2000 2500 3150(1) 1250 1600 2000 2500 3150(1)

Rated peak current withstand current (50/60 Hz) kA 63 80

Rated short time withstand current (4 s) kA 25 31.5

Rated short-circuit breaking current

Rated short-circuit breaking current kA 25 31.5

Direct current component percentage % 36

No-load cable breaking current A 50

Rated operation sequence

0-0.3 s-CO-180 s-CO b

0-180 s-CO-180 s-CO b

Switch operating cycles (electrical/mechanical)

Drive mechanism operations Per numbers 10,000

Vacuum interrupter operations Per numbers 30,000

Rated current operations Per numbers 10,000

Minimum/Maximum closing time ms 40/63

Minimum/Maximum opening time ms 35/53

Contact eroding bedding mm 3.5

Charging time s 4~12

Arc time ms 2~15

Weight(2)

Fixed kg 280

Middle rolling kg 375

Floor rolling kg 415

(1) When the rated current is 3150 A, forced cooling is required.(2) The net weight of the product is for reference only.For special requirements, please consult us.

HVX 36 kV vacuum circuit breaker

HVX 36 - 31 - 12 - E

HVX type F: Fixed typeE: Middle rolling typeG: Floor rolling type

Rated voltage kV

Rated short-circuit breaking current kA

Rated current (x100 A)

DM

1033

94

Page 19: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 17

Dimensions HVX 36 kV series fixed type

HVX series Vacuum circuit breaker

36 kV, ...2500/3150(1), ...31.5 kA

P (mm) D (mm) E (mm) H (mm)

275 800 850 400

275 800 850 400

300 850 900 325

300 850 900 400

(1) When the rated current is 3150 A, forced cooling is required.

DM

1034

04

Page 20: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN18

1

2

Rated current (A) 1250 1600 2000 2500 3150(1)

ØM mm 88 118 118 148 148

ØW mm 49 79 79 109 109

(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.

Dimensions HVX 36 kV series middle rolling type

HVX series Vacuum circuit breaker

1 This connecting arm is used for 2500 A.2 This connecting arm is used for <2000 A.

DM

1034

05

Page 21: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 19

1

2

Dimensions HVX 36 kV series floor rolling type

HVX series Vacuum circuit breaker

Rated current (A) 1250 1600 2000 2500 3150(1)

ØM mm 88 118 118 148 148

ØW mm 49 79 79 109 109

(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.

1 This connecting arm is used for 2500 A.2 This connecting arm is used for <1250 A.

DM

1034

06

Page 22: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN20

1200

L

1333

367.

536

7.5

1097

1137

1765

647

491

460

275 275

1325

120

325

10

1

Dimensions Cradle - For HVX 36 kV series middle rolling type

HVX series Vacuum circuit breaker

Rated working current (A)

Rated short-circuit breaking current (kA)

Dimensions(mm)L Contacts

1250 25...31.5 2400 Ø49 x 120

2000 31.5 2490 Ø79 x 102

2500 31.5 2490 Ø109 x 102

1 The earthing switch is optional.

DM

1034

07

Page 23: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 21

-Q0

-Q0

OI

9 10

-S12

1 2

3 4 16

21

22

611

38

28

12

11

24

13

14

34

1 2 U1

U2

-M1

M

4 3 35

25

36

26

-S2

65

D1

D2

-F4

U< 4

4

43

C1

C2

-F3

I>

42

32

9 10

-S2

C1

C2

-F2

14

4 21

22

31

32

13

14

-S12

87 A2-K

01

A1

truck

3 4

-S11

C1

C2

-F12

2313

1 2

-S11

C1

C2

-F11

30

31

41

13

14

-S11

5 6

15

16

7 8 17

19

15

-X01

18

9-X

01

87

51

40

12

15

16

-S2

9 10

-S11

E1

E2

-Y1

20

13

14

-S12

11

12

-S11

5 6

39

16

15

29

10

-S61

41 1 2

-S6 -+

04

1

1

Electrical circuit diagramHVX 36 kV vacuum circuit breaker, fixed type with anti-pumping relay

HVX series Vacuum circuit breaker

1. T

his

circ

uit d

iagr

am s

how

s th

e m

axim

um s

witc

hgea

r equ

ipm

ent.

The

stan

dard

eq

uipm

ent d

oesn

't in

clud

e op

tiona

l ite

ms.

If th

e cu

stom

er re

quire

s op

tiona

l ite

ms,

pl

ease

sta

te th

is w

hen

plac

ing

the

orde

r.2.

Circ

uit b

reak

er is

dis

char

ged

and

in o

pen

posi

tion,

trol

ley

is in

ser

vice

pos

ition

.

3. If

Circ

uit b

reak

er w

ithou

t blo

ckin

g m

agne

t for

clo

sing

Y1,

circ

uit d

iagr

am

acco

rdin

g to

das

h s

how

n.

-Q0

Uni

ts in

corp

orat

ed in

the

circ

uit b

reak

er in

com

plia

nce

with

ord

er

-M1

Mot

or fo

r ene

rgy

stor

ing

devi

ce-S

11/1

2

Aux

iliar

y sw

itch

posi

tion

indi

cato

r

-S2

Mic

ro-s

witc

h fo

r mot

or c

ontro

l -S

6 M

icro

-sw

itch

for b

lock

ing

mag

net

-Y1

Blo

ckin

g m

agne

t for

clo

sing

(opt

iona

l)-F

11

1. A

uxili

ary

open

ing

rele

ase

-F12

2.

Aux

iliar

y op

enin

g re

leas

e (o

ptio

nal)

-F2

Aux

iliar

y cl

osin

g re

leas

e

-F3

Indi

rect

ove

r-cu

rren

t rel

ease

(opt

iona

l) -F

4 U

nder

-vol

tage

rele

ase

(opt

iona

l) -K

01

Ant

i-pum

ping

-rel

ay-S

61

Mic

ro-s

witc

h ac

tuat

ed b

y op

erat

ion

DM

1034

08

Page 24: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN22

-S11

10

9-Q

0

-Q0

9 10

-S12

1 2

11 12

D4

B4

B3

D3

B2

A8

A7

13

14

-S2

65

B16

B15

B8

3 4B7

D6

5 6D5

D16

D15

1 2 U1

U2

-M1

M

4 3 A2

A1

11 12

9 10

-S2

C1

C2

-F2

A6

A5

21

22

-S61

41

13

14

-S12

87 A2-K

01

A1

truck

13

14

-S11

5 6

15

16

7 8 B1

A16

A14

-X01

A13

A15

-X01

A12

1 2

-S11

C1

C2

-F11

A4

A3

D11

11 12

A9

D1

B9

15

16

B10

13

14

S8

13

14

13

14

23

24

33

34

C6

X01

C3

D14

C10

6

14

13

S9

16

24

23

15

53

-Q1

14

2

D13

53

54

43

44

C13

C14

12

13

34

33

14

44

43

11

8

-Y0

17

54

53

18

97

B5

B6

B13

B14

C8

C5

X01

B12

C12

C11

A11

E1

E2

-Y1

13

14

-S12

C9

B11

31

32

C2

C1

C2

-F12

3 4

-S11

D10

C1

1 2

-S6

OI

C15

C16

C4

C7

3 4

-S42

1 2

-S41

C1

C2

-F3

I>

C1

C2

-F4 U

<

D2

D7

D8

D9

15

16

-S2

1 2

-S43 -+

test

po

sitio

n

se

rvic

e

po

sitio

n

02

Electrical circuit diagramHVX 36 kV vacuum circuit breaker, withdrawable type with anti-pumping relay

HVX series Vacuum circuit breaker

1. T

his

circ

uit d

iagr

am s

how

s th

e m

axim

um s

witc

hgea

r equ

ipm

ent.

The

stan

dard

eq

uipm

ent d

oesn

't in

clud

e op

tiona

l ite

ms.

If th

e cu

stom

er re

quire

s op

tiona

l ite

ms,

pl

ease

sta

te th

is w

hen

plac

ing

the

orde

r.2.

Circ

uit b

reak

er is

dis

char

ged

and

in o

pen

posi

tion,

trol

ley

is in

ser

vice

pos

ition

, bl

ocki

ng m

agne

t for

clo

sing

is d

e-en

ergi

sed.

-Q0

Uni

ts in

corp

orat

ed in

the

circ

uit b

reak

er in

com

plia

nce

with

ord

er-M

1 M

otor

for e

nerg

y st

orin

g de

vice

-S

11/1

2 A

uxili

ary

switc

h po

sitio

n in

dica

tor

-S2

Mic

ro-s

witc

h fo

r mot

or c

ontro

l-S

41/4

2 M

icro

-sw

itch

actu

ated

by

push

but

ton

On/

off (

optio

nal)

-S43

M

icro

-sw

itch

actu

ated

by

brea

k bu

tton

(opt

iona

l)-S

6 M

icro

-sw

itch

for b

lock

ing

mag

net

-Y1

Blo

ckin

g m

agne

t for

clo

sing

(opt

iona

l)-F

11

1. A

uxili

ary

open

ing

rele

ase

-F12

2.

Aux

iliar

y op

enin

g re

leas

e (o

ptio

nal)

-F3

Indi

rect

ove

r-cu

rren

t rel

ease

(opt

iona

l)-F

4 U

nder

-vol

tage

rele

ase

(opt

iona

l) -S

61

Mic

ro-s

witc

h ac

tuat

ed b

y tru

ck o

pera

tion

or tr

uck

not i

n en

d po

sitio

n-F

2

Aux

iliar

y cl

osin

g re

leas

e-K

01

Ant

i-pum

ping

-rel

ay-Q

1 U

nits

inco

rpor

ated

in th

e sw

itchg

ear t

ruck

in

com

plia

nce

with

ord

er-S

8 Te

st p

ositi

on s

witc

h -S

9 S

ervi

ce p

ositi

on s

witc

h-Y

0 B

lock

ing

mag

net b

lock

ing

for t

rolle

y (o

ptio

nal)

DM

1034

09

Page 25: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 23

Selection guideUTX Disconnector truck

Type

UTX

36-

25-1

2

UTX

36-

25-1

6

UTX

36-

25-2

0

UTX

36-

25-2

5

UTX

36-

25-3

1(1)

UTX

36-

31-1

2

UTX

36-

31-1

6

UTX

36-

31-2

0

UTX

36-

31-2

5

HVX

36-

31-3

1(1)

Phase distance mm 275

Rated voltage kV 36

Rated insulation level

Power frequency withstand voltage kV 70

Lightning impulse withstand voltage kV 170

Rated frequency Hz 50/60

Rated curent A 1250 1600 2000 2500 3150(1) 1250 1600 2000 2500 3150(1)

Rated short-circuit breaking current kA 25 31.5

Weight(2)

Middle rolling kg 255 260 280 290 310 255 260 280 290 310

Floor rolling kg 320 325 345 355 385 320 325 345 355 385

(1) When the rated current is 3150 A, forced cooling is required.(2) The net weight of the product is for reference only.For special requirements, please consult us.

UTX 36 kV disconnector truck

UTX 36 - 31 - 12 - E

UTX type E: Middle rolling typeG: Floor rolling typeRated voltage (kV)

Rated short-circuit breaking current

Rated current (x100 A)

DM

1033

99

Page 26: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN24

1044

106013.5 13.5

1051

952.

5

410555

440

275 275

1025

.5

780

325

520

ØM

410 356Ø

W

1

2

Dimensions UTX 36 kV middle rolling type

UTX Disconnector truck

Rated current (A) 1250 1600 2000 2500 3150(1)

ØM mm 88 118 118 148 148

ØW mm 49 79 79 109 109

(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.

1 This connecting arm is used for 2500 A.2 This connecting arm is used for <1250 A.

DM

1034

10

Page 27: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 25

750

1051275 275

966

1060

1044

13.5 13.5

507410 356.5

440

1571

620

410

780

325

520

760.5

ØM

ØW

1

2

Dimensions UTX 36 kV floor rolling type

UTX Disconnector truck

Rated current (A) 1250 1600 2000 2500 3150(1)

ØM mm 88 118 118 148 148

ØW mm 49 79 79 109 109

(1) When the rated current is 3150 A, forced cooling is required.For special requirements, please consult us.

1 This connecting arm is used for 2500 A.2 This connecting arm is used for <1250 A.

DM

1034

11

Page 28: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN26

1200

L

1333

367.

536

7.5

1097

1137

1765

647

491

460

Ø13

275 275

1325

L44X120

M12,1250AM21,2000A

120

325

10

1

Dimensions Cradle - For UTX 36 kV series middle rolling type

UTX Disconnector truck

Rated working current(A)

Rated short-circuit breaking current (kA)

Dimensions(mm)L Contacts

1250 25...31.5 2400 Ø49 x 120

2000 31.5 2490 Ø79 x 102

2500 31.5 2490 Ø109 x 102

1 The earthing switch is optional.

DM

1034

14

Page 29: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 27

Selection guideMTX Voltage transformer truck

Type Truck Phase distance(mm)

Rated voltage(kV)

Rated insulation level Rated frequency(Hz)

Weight(1)

(kg)Power frequency withstand voltage(kV)

Lightning impulse withstand voltage(kV)

MTX36-E275 Middle rollingtruck

275 36 95 185 50/60 390

MTX36-G275 Floor rollingtruck

275 36 95 185 50/60 455

(1) The net weight for product is for reference only.For special requests, please consult us.

MTX 36 kV Voltage transformer truck

MTX 36 - E - 275

Phase distance (mm)MTX type

Rated voltage (kV) E: Middle rolling typeG: Floor rolling type

DM

1034

00

Page 30: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN28

1052275275

1060

1044

13.5 13.5

462

845

242

760.6

1025

.5

555

410

286.5 440

DimensionsMTX 36 kV middle rolling type

MTX Voltage transformer truck

DM

1034

15

Page 31: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 29

845

1052

940750

275275

966

1044

106013.5 13.5

802

1572

.5

555410

242760.5

440

DimensionsMTX 36 kV floor rolling type

MTX Voltage transformer truck

DM

1034

16

Page 32: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN30

1200

2400

1333

367.

5

1097

1137

1765

647

491

460

Ø13

275 275

1325

L44X120

M12

122

162.

5

10

1

DimensionsCradle - For MTX 36 kV series middle rolling type

MTX Voltage transformer truck

1 The earthing switch is optional.

DM

1034

17

Page 33: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 31

Page 34: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN32

Complementary devices

Page 35: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 33

Complementary devicesHVX seriesComplementary devices

HVX series Complementary devices 33

Page 36: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN34

Complementary devicesHVX series

ReleaseAuxiliary release F2, F11/F12The auxiliary release coil is actuated by the auxiliary power supply. The coil is designed for short-term operation only; its main circuit is therefore routed via an auxiliary switch contact controlled by the circuit breaker shaft, and upon release it interrupts the current circuit.

Over-current release F3(Transformer-type over-current release) Over-current releases are used for automatic release of switching devices in the event of short-circuits and over-currents. Once the protection device reacts, the release is actuated by the transformer current, thus causing the switch to be tripped. These releases are supplied for transformer secondary currents of 0.5 A, 1 A and 5 A.

Under-voltage release F4Under-voltage releases are used for the auxiliary boost voltage return circuit.Whenever the auxiliary current is interrupted or its voltage drops significantly, the switching device is immediately tripped.

Auxiliary switchAuxiliary switch in switching position S11/S12Auxiliary switches are always actuated directly by the switch shaft via an intermediate linkage, the position of which always corresponds to the position of the main contacts, indicating the breaker's on and off position status; during wiring, the interlock assists the release to prevent handling errors. Generally speaking, the circuit breaker is equipped with two auxiliary switches with a total of eight contact elements.

Auxiliary switch in charging position S2The auxiliary switch is mainly used to check and indicate the charging status. It is connected by the charging mechanism to ensure that, during the closing operation, the driving mechanism can automatically store energy. When charging is complete, it breaks the electrical charging circuit. Generally speaking, the circuit breaker is equipped with an auxiliary switch with eight contact elements.

DM

1034

18

DM

1034

19D

M10

3420

DM

1034

21D

M10

3422

DM

1034

23

Page 37: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 35

Anti-pumping relay K01If both ON and OFF commands are permanently present on the circuit breaker at the same time, the latter returns to open position after closing; it remains in this open position until the ON command is issued again. This prevents continuous closing and opening (i.e. “anti-pumping”).

HVX series Complementary devices

Operation counterThe operation counter installed on the operating interface records the circuit breaker operating frequency.

Charging motor M1This electrically stores energy for the circuit breaker operating mechanism, preparing energy for the next closing operation.

Blocking magnetBlocking magnet for closing Y1If the secondary controlling power supply is lost, the circuit breaker cannot perform the normal closing operation (including manual closing).

Blocking magnet for trolley Y0If the secondary controlling power supply is lost, the trolley cannot perform the normal manual operation.

DM

1034

24D

M10

3425

DM

1034

26D

M10

3427

DM

1034

28

Page 38: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN36

Devices Designation No. in configuration

Rated operating voltage Ua (V) Working voltage Ua (V)

Rated power(W)

Charging motor M1 1 DC 2448110220

85~110% Ua Approx. 100

AC 110220

Closing coil F2 DC 2448110220

85~110% Ua 180

AC 110220

85~110% Ua

Opening coil F11F12

DC 2448110220

70~110% Ua 180

AC 110220

85~110% Ua

Under-voltage release F4 1 DC 2448110220

35~0% Ua Approx. 12

AC 110220

Devices Designation No. in configuration Working voltage Ua (V) Rated powerOver-current release F3 2 0.5

15

90~110% Ua

Auxiliary switch technical parametersRated voltage ofauxiliary switch

Unit DC ACV ≤ 48 125 220 120 230

Breaking capacity A 10 3.8 2 10

Time constant T=L/R 10

Rated short-circuit withstand current 250 A/3 s

Rated current 15

Operating time of coil and motorDuration of the minimum opening command 20 ms

Duration of the minimum closing command 20 ms

Motor charging time 4~12 s

HVX series Complementary devicesD

M10

3426

DM

1034

19D

M10

3419

DM

1034

21D

M10

3420

Page 39: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 37

Page 40: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN38

Order form

Page 41: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 39

Order formHVX 36 kV vacuum circuit breaker

HVX36Ordering unit: Project name: Customer's order number:

Basic configuration:

Product model Quantity

Installation method □ Fixed type (F type) □ Middle rolling type (E type) □ Floor rolling type (G type)

Rated voltage □ 36 kV

Rated current □ 1250 A □ 1600 A □ 2000 A □ 2500 A □ 3150 A

Rated short-circuit breaking current □ 25 kA □ 31.5 kA

Phase distance (P) □ 275 mm □ 300 mm

Charging motor (M1) □ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 110 VAC □ 220-230 VAC

Opening release (F11) □ 24 VDC □ 48-60 VDC □ 110-125 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC

Closing release (F2) □ 24 VDC □ 48-60 VDC □ 110-125 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC

Anti-pumping relay (K01) □ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC

Auxiliary contact □ 8 NO+8 NC □ 12 NO+12 NC

Secondary wiring mode □ Installation of 58-pin low voltage plug, with slots

□ Installation of 64-pin low voltage plug, with slots

□ Other

Withdrawable type (E type, G type)

Trolley and earthing method

□ Middle rolling trolley with copper earthing bar (E type)

□ Floor rolling trolley with copper earthing bar (G type)

Optional configuration:

Secondary opening release (F12) □ 24 VDC □ 48-60 VDC □ 110-125 VDC □ 220 VDC □ 110-120 VAC □ 220-230 VAC □ Other

Over-current release (F3) □ 0.5 A □ 1 A □ 5 A

Secondary over-current release (F32)

□ 5 A

Under-voltage release (F4) □ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC

□ 100-110 VAC □ 230 VAC □ Other

Blocking magnet for closing circuit (Y1)

□ 24 VDC □ 30 VDC □ 48 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC □ Other

□ 24 VAC □ 30 VAC □ 48 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC □ Other

Manual C/O button micro-switch (S41-S43)

□ One control output and one signal output □ One control output and two signal outputs □ None

Withdrawable type (E type, G type)

Blocking magnet for trolley (Y0)

□ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC

□ 24 VAC □ 48 VAC □ 60 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC

Other special requirements 1

2

3

4

5

(If there are any other special requirements, please list them in the column and attach the corresponding drawing or attachment.)

Complete (signature/seal):

Notes: 1. This form is completed by the ordering unit. Please enter a “ √ ” in the selected item “□”. 2. Attachment configuration: Each circuit breaker is equipped with a secondary slot and a compatible secondary contact pin; the trolley crank

configuration is based on the project; that is, five circuit breakers in one project are equipped with a set of trolley cranks (fewer than five circuit breakers are equipped in the same way as projects with five circuit breakers). If additional requirements are expressed, the corresponding fees will be charged according to the price stated in the attachment.

3. The above "standards" refer to the standard plans in the samples; with regard to non-standard plans or specific concerns, please contact the Customer Care Centre hotline.

4. If the customer does not choose the optional configuration program, the circuit breaker configuration will not incorporate this component. However, if the customer chooses an optional configuration or other non-standard program, certain fees will be charged and the date of delivery will be extended appropriately. For the specific costs, please refer to our company's price list or consult our salesperson.

Page 42: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN40

Order formUTX 36 kV disconnector truck

UTX36Ordering unit: Project name: Customer's order number:

Basic configuration:

Product model Quantity

Installation method □ Middle rolling type (E type) □ Floor rolling type (G type)

Rated voltage □ 36 kV

Rated current □ 1250 A □ 2500 A

Rated short time withstand current □ 25 kA □ 31.5 kA

Phase distance (P) □ 275 mm □ 300 mm

Secondary wiring mode □ Installation of 64-pin low voltage plug, with slots □ Other

Withdrawable type (E type, G type)

Trolley and earthing method

□ Middle rolling trolley with copper earthing bar (E type) □ Floor rolling trolley with copper earthing bar (G type)

Optional configuration:

Withdrawable type (E type, G type)

Blocking magnet for trolley

□ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC □ 24 VAC

□ 48 VAC □ 60 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC □ 230 VAC

Other special requirements 1

2

3

4

5

(If there are any other special requirements, please list them in the column and attach the corresponding drawing or attachment.)

Complete (signature/seal):

Notes: 1. This form is completed by the ordering unit. Please enter a “ √ ” in the selected item “□”. 2. The above "standards" refer to the standard plans in the samples; with regard to non-standard plans or specific concerns, please contact the

Customer Care Centre hotline. 3. If the customer does not choose the optional configuration program, the circuit breaker configuration will not incorporate this component. However, if

the customer chooses an optional configuration or other non-standard program, certain fees will be charged and the date of delivery will be extended appropriately. For the specific costs, please refer to our company's price list or consult our salesperson.

Page 43: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

NRJED314609EN 41

Order formMTX 36 kV disconnector truck

Complete (signature/seal):

Notes: 1. This form is completed by the ordering unit. Please enter a “ √ ” in the selected item “□”. 2. The above "standards" refer to the standard plans in the samples; with regard to non-standard plans or specific concerns, please contact the

Customer Care Centre hotline. 3. If the customer does not choose the optional configuration program, the circuit breaker configuration will not incorporate this component. However, if

the customer chooses an optional configuration or other non-standard program, certain fees will be charged and the date of delivery will be extended appropriately. For the specific costs, please refer to our company's price list or consult our salesperson.

MTX36Ordering unit: Project name: Customer's order number:

Basic configuration:

Product model Quantity:

Installation method □ Middle rolling type (E type) □ Floor rolling type (G type)

Rated voltage □ 36 kV

Phase distance (P) □ 275 mm

Secondary wiring mode □ Installation of 64-pin low voltage plug, with slots □ Other

Withdrawable type (E type, G type)

Trolley and earthing method

□ Middle rolling trolley with contacts on both sides and VT earthing (E type)

□ Floor rolling trolley with contacts on both sides and VT earthing (G type)

Optional configuration:

Withdrawable type (E type, G type)

Blocking magnet for trolley

□ 24 VDC □ 48 VDC □ 60 VDC □ 110 VDC □ 125 VDC □ 220 VDC □ 230 VDC □ 24 VAC

□ 48 VAC □ 60 VAC □ 110 VAC □ 125 VAC □ 220 VAC □ 230 VAC □ 230 VAC

Other special requirements 1

2

3

4

5

(If there are any other special requirments, please list them in the column and attch the corresponding drawing or attachment.)

Page 44: 36 kV Medium Voltage Vacuum circuit breakerms.schneider-electric.be/Main/HVX/Catalogue/NRJED314609EN.pdf36 kV Medium Voltage Vacuum circuit breaker ... breaker, fixed type with anti-pumping

Make the most of your energy™

www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

This document has been printed on ecological paper.

© S

chne

ider

Ele

ctric

Indu

strie

s S

AS

- A

ll rig

hts

rese

rved

.

Schneider Electric Industries SAS

35, rue Joseph MonierCS 30323F - 92505 Rueil-Malmaison cedex (France)RCS Nanterre 954 503 439Share capital: €896,313,776 www.schneider-electric.com

Publication: Schneider Electric Industries SASPrinting:

01-2015NRJED314609EN