This document is issued by means of
a computerized system.
The digitally stored original is ele
ctronically approved. The
approved document has a date entered
in the `Approved'-field.
A manual signature is not required.
The information contained in this document has to kept strictly
confidential. Any unautorized use, reproduction, distribution
or disclosure to third parties are strictly forbidden.
ABB reservs all rights regarding Intellectual Property Rights.
© Copyright 2010 ABB. All rights reserved.
A
B
C
2 3 4 5 6
D
C
B
A
654321
D1
25
( 20)
25
225
86
16
65
86
R6
70
480
240 60
230
22
88
590
170 L
D
15
46
R8
185
998
115
555 (Draw lead length)
M8
20
35
M8
Bushing Data:Rated Voltage 52 kV
Phase to Ground Voltage 52 kV
Dry Lightning Impulse 1,2/50µs 250 kV
Wet power frequency AC 105 kV
Routine test 1min dry 50Hz 120 kV
Rated Current 800 A
Creepage Distance 1690±50 mm
Creepage Distance Protected 650 mm
Mass 23 kg
Ordering Data:BUSHING COLOUR AIR INSULATOR
LF123013-K BROWN
-L LIGHT GREY
OUTER TERMINAL
LF 170 002-A Cu alloy, 30,125
LF 170 001-A Al, 30,125
OTHER TYPES ON REQUEST
INNER TERMINAL FOR STRANDED CABLE
For brazing Conductor area D1
LF 170 011-S up to 150mm² 18
LF 170 011-U Undrilled with pilot hole 5
For crimping or brazing Conductor area D1
LF 170 010-M 50mm² 11
LF 170 010-N 70mm² 13
LF 170 010-L 95mm² 15
SOLID ROD CONNECTOR
LF 170 019-A for Alt.1
Earthedlayer
OUTER TERMINAL
END SHIELD SOLID ROD CONNECTOR
INNER TERMINALFOR STRANDED CABLE
The solid rod can be divided either:Alt.1: 20mm below the bushing flange orAlt.2: 20mm below the upper end of the bottom porcelain
Test tap
M12
6 mountingholes 16
1:5
1:5
Alt.1 orAlt.2
Material D L
Material
Cu
N/A for Alt.2
(1)2751369-109No. Shts.Document no.
1Changed at specified placesA
Sheet no.OrderRevision
82WITHOUT OIL LEVEL GAUGE STD END SHIELD2011-12-06Urban Schander
LanguageUsed in productApproved by
GOB 250-800-02011-11-26Sri Ambicai
Take over departmentModified by
PPCO/BK2011-08-29Sri Ambicai
TitleResponsible departmentPrepared
(For Earthing)(For Earthing)