2012 Seminar Jalayerian

download 2012 Seminar Jalayerian

of 34

description

2012 Seminar Jalayerian

Transcript of 2012 Seminar Jalayerian

  • 2012-ESD, Inc.

    By: Mehdi Jalayerian, PE, LEED AP BD+C

    Executive Vice President Environmental Systems Design, Inc.

    2012 Spring Seminar, June 14, 2012

    High Rise Building Air Pressure, Infiltration & Stack Effect

    Theory and Impact on Indoor Environment

  • 2012-ESD, Inc.

    Learning Objectives

    Basic Theory of Air Flow Around and In High Rise Building Wind Stack-Effect

    Vertical Compartmentation Elevators Stairs Impact on Energy Impact on Pressure

    Smoke Management Pressurization (Stairs/Space) Smoke Control Considerations

    Example Building Air Movement/Pressure Analysis 16 Story Hotel Mixed-use Tall Building

    Summary Guidelines

  • 2012-ESD, Inc.

    Air Flow in High Rise Buildings

    Forced ventilation Building supply/exhaust air systems Fully controlled and distributed

    Natural ventilation Pressure from wind and/or stack effect Strategically placed intentional openings

    Infiltration Uncontrolled air leakage Unintentional openings in building envelope Air leakage through floor/wall openings Driven by wind force, temperature difference (buoyancy), and/or

    system/appliance induced Space Pressurization

    Normal mode pressurization Fire mode pressurization (fire floor and stairs) for smoke

    management

  • 2012-ESD, Inc.

    Air movement into/out of a building is caused by wind pressure and stack effect pressure

    Wind pressure causes air to infiltrates into the building, or ex-filtrate out of the building

    Stack effect (air buoyancy) pressure causes air to rise or drop

    Cold Weather Air infiltrates into the lower half of the

    building, rises to upper floors due to stack effect and exfiltrates in the upper half of the building.

    Hot Weather Air infiltrates into the upper half of the

    building, drops to lower floors due to stack effect and exfiltrates in the lower half of the building.

    Basic Theory WIND VELOCITY PROFILE

    EXFILTRATION

    INFILTRATION

    STAC

    K E

    FFEC

    T

    NUTRAL PLANE

    AVERAGE SURROUNDING ROOF HEIGHT OR 10M ABOVE GRADE

  • 2012-ESD, Inc.

    Basic Theory Air Flow Around Building

  • 2012-ESD, Inc.

    Basic Theory - Wind Pressure

    Wind creates a distribution of static pressure on the building envelope, which is dependent on wind direction and location on building envelope. Pw = C Cp v2/2

    Pw = wind pressure difference, inches of water C = unit conversion, 0.0129 Cp = surface pressure coefficient, dimensionless = air density, lbm/ft3 (about 0.075) v = wind speed, mph Note: Wind Pressure at top of 60 Story: Upwind = +1.32 in. of Water Sides = +0.61 in. of Water Downwind = -0.61 in. of Water

    2X

    X

    Wind 15 mph

    +0.33 in WG

  • 2012-ESD, Inc.

    Basic Theory - Stack Effect Pressure

    Air density varies with temperature. In cold weather, low density air infiltrated into a building rises and creates stack effect pressure. Ps = C2 i g (h-hNPL)(Ti -To)/To

    Ps = pressure difference, inches of water C2 i g = density and gravity constant, 0.01444 h = height of observation, ft NPL = building neutral pressure level T = absolute temperature, oR i & o = inside & outside Note: Stack Pressure is approximately 1 in. of water for a 60-story building and -10oF outside T

    +0.95 in WG

  • 2012-ESD, Inc.

    Basic Theory Overall Pressure

    Natural air movement in a building is due to pressure difference caused by wind and temperature difference between indoor and outdoor air (stack effect). P = (Po - Pi )+ Pw + Ps

    P = pressure difference Po = outside static pressure Pi = interior static pressure Pw= pressure difference due to wind (depends on orientation) Ps = pressure difference due to stack effect

    Wind

    Stack Effect

    Overall

    Adjusted Neutral

  • 2012-ESD, Inc.

    Basic Theory Air Flow Through Opening

    Dynamic air flow through an opening is proportional to square root of the pressure difference across the flow path.

    Q = C x Cf x A x (2P/)

    Q = Air flow, CFM C = Unit Conversion, 776 Cf = Flow Coefficient, typically = 0.6-0.7 A = Opening Area, ft2 P = pressure difference, inches of water = air density, lbm/ft3 (about 0.075 at standard conditions)

    Operation of building appliances and mechanical ventilation systems impact natural air movement. The impact is included with outside/inside pressure difference

  • 2012-ESD, Inc.

    Basic Theory - Air Flow Network

    AMBIENT NODES

    SPACE NODES

    STAIR NODES

    ELEVATOR NODES

    Flow equations are developed between nodes (pressure & mass balance) Q = C x A x (2P)/ System of equations are solved for each calculation time period Software: NIST CONTAM LBNL COMIS e-Quest

    STAIR/ELEVATOR INTERCONNECTION

    SPACE NODES INTERCONNECTION

  • 2012-ESD, Inc.

    Example High Rise Building Air Infiltration

    Assumptions 60-Story Office 200 feet x 100 feet floor plate Average leakage curtain wall Weather-stripped exterior exist

    doors Revolving doors + swing exit

    doors at main lobby Standard door on typical floor stair Average leakage elevator doors Exterior condition at -10oF Interior condition at 73oF Wind direction from south (longer

    wall) Wind speed 15 mph (33 feet

    above grade)

    GROUND FLOOR

    LOBBY

    TENANT TENANT

    N

    TYPICAL FLOOR

    TENANT

  • 2012-ESD, Inc.

    Building Air Infiltration Effect of Elevators

    Single Zone Elevators

    Two Zones Elevators

    Three Zones Elevators

    Total Infiltration Heat Load 6,357 KW 2,903 KW 1,652 KW 100% 45.7% 25.9%

    60-Story Office BuildingEffect of Elevator Zones

    -15000 -10000 -5000 0 5000 10000 15000

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    41

    43

    45

    47

    49

    51

    53

    55

    57

    59

    Floo

    r

    Infiltration, scfm

    Single Zone Two Zones Three Zones

    ~74% reduction

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    #1 #2ELEVATORS STAIRS

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR HR #1 #2ELEVATORS STAIRS

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

  • 2012-ESD, Inc.

    Elevator Shaft Air Flow

    60 Story Office BuildingElevator Shaft Air Flow (Winter)

    -15000 -10000 -5000 0 5000 10000 15000

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    41

    43

    45

    47

    49

    51

    53

    55

    57

    59

    Floo

    r

    Air Flow, CFM

    Single Zone Two Zones Three Zones

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    #1 #2ELEVATORS STAIRS

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR HR #1 #2ELEVATORS STAIRS

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

    Single Zone Elevators

    Two Zones Elevators

    Three Zones Elevators

  • 2012-ESD, Inc.

    Building Air Infiltration Effect of Stairs

    Single Zones Stairs

    Three Zones Stairs

    Total Infiltration Heat Load 1,652 KW 909 KW

    100% 55%

    60-Story Office BuildingEffect of Stair Zones (Three Elevator Zones)

    -6000 -4000 -2000 0 2000 4000 6000 8000 10000 12000 14000

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    41

    43

    45

    47

    49

    51

    53

    55

    57

    59

    Floo

    r

    Infiltration, scfm

    Three Zones Elevators/Single Zone Stairs Three Zones Elevators/Three Zones Stairs

    ~45% reduction

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

  • 2012-ESD, Inc.

    60 Story Building Space Pressure

  • 2012-ESD, Inc.

    Typical Stair Air Separation/Lock

    Up

    Up

    Down

    AIR LOCK

    2'-6"

    2'-6"

    2'-6"

    Down

    2'-6"

    TYPICAL FLOOR

    TENANT

    Alternate B

    Alternate A

    Up

    UpDown

    Down

    Air S

    epar

    atio

    n

    2'-6

    "

    2'-6

    "

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

  • 2012-ESD, Inc.

    60 Story Building Infiltration Load (Energy)

  • 2012-ESD, Inc.

    High Rise Building - Smoke Management

    System Objectives Reduce occupant death and

    injuries Delay smoke accumulation Reduce smoke migration Provide safe escape route Provide safe refuge area

    Reduce property loss Purge smoke Manage fire impact

    System Approach Design/operate system to

    prevent smoke entering the unaffected areas

    Integrate Smoke Control with Fire Protection System

    Allow for operational flexibility Use HVAC system for smoke

    control to improve system reliability

    Utilize compartmentation Pressurization

    Horizontal Vertical Stairs Lobbies

  • 2012-ESD, Inc.

    Pressurization Normal Mode of Operation

    Floor Pressurization Main building lobby is pressurized Each floor is provided with required

    supply and exhaust Each zone of building is pressurized

    by maintaining differential air flow between supply/exhaust to minimize infiltration

    Stair pressurization systems are off GROUND FLOOR

    TYPICAL FLOOR

    LOBBY

    TENANT TENANT

    100% SUPPLY and 80-90% EXHAUST

  • 2012-ESD, Inc.

    Pressurization Normal Mode of Operation

    Three Zones Central AHU

    Three Zones Elevator Single Zone Stairs

    60-Story Office Building InfiltrationEffect of AHU Pressurization (Normal Mode)

    -10000 -5000 0 5000 10000 15000

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    41

    43

    45

    47

    49

    51

    53

    55

    57

    59

    Floo

    r

    Infiltration, scfm

    AHU - OFF AHU - ON

    Building Infiltration Load Reduces by 70% (1652 kW reduced to 506 kW)

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

  • 2012-ESD, Inc.

    Pressurization Fire Mode of Operation

    Floor Pressurization Main building lobby is pressurized Fire Floor is provided with full

    exhaust Floors above and below fire floor is

    provided with full supply air All other floors operate normal mode Stairs not pressurized

    GROUND FLOOR

    FIRE FLOOR

    LOBBY

    TENANT TENANT

    NO SUPPLY and 100% EXHAUST

    ABOVE OR BELOW FIRE FLOOR

    100% SUPPLY and NO EXHAUST

  • 2012-ESD, Inc.

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    Pressurization Fire Mode of Operation

    Exhaust on Fire Floor & Supply Above/Below

    Single Zone Stairs Non-pressurized

    60-Story Office Building InfiltrationSmoke Condition (Level 28) - Fire Mode Pressurization

    -20000 -15000 -10000 -5000 0 5000 10000 15000

    1

    3

    5

    7

    9

    11

    13

    15

    17

    19

    21

    23

    25

    27

    29

    31

    33

    35

    37

    39

    41

    43

    45

    47

    49

    51

    53

    55

    57

    59

    Floo

    r

    Infiltration, scfm

    AHU - ON AHU - ON - Smoke Mode

    Negative Press. (Exhaust) Positive Press. (Supply)

    No Stair Pressurization Provided

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

  • 2012-ESD, Inc.

    Pressurization Fire Mode/Stair Impact

    Floor and Stair Pressurization Main building lobby is pressurized Fire Floor is provided with full

    exhaust Floors above and below fire floor is

    provided with full supply air All other floors operate normal mode Stairs are pressurized

    GROUND FLOOR

    FIRE FLOOR

    LOBBY

    TENANT TENANT

    ABOVE OR BELOW FIRE FLOOR

    NO SUPPLY and 100% EXHAUST STAIRS PRESSURIZED

    100% SUPPLY and NO EXHAUST STAIRS PRESSURIZED

    STAIRS PRESSURIZED

  • 2012-ESD, Inc.

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    Pressurization Fire Mode/Stair Impact

    Exhaust on Fire Floor & Supply Above/Below

    Single Zone Stairs Pressurized doors open

    Open Exit Door

    Open Exit Doors

    Stairs Are Pressurized

    605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110987654321

    LR MR HR #1 #2ELEVATORS STAIRS

  • 2012-ESD, Inc.

    Elevator Shaft Air Flow Fire Mode

    Open Exit Door

    Open Exit Doors

    Exhaust on Fire Floor & Supply Above/Below Doors open on fire, above/below and ground floors

    60 Story Office Building - Elevator Shaft Air Flow (Winter)Smoke Condition on Level 28 (Building and Stairs Pressurized)

    -4000 -2000 0 2000 4000 6000 8000 10000 12000 14000 16000

    13579

    11131517192123252729313335373941434547495153555759

    Floo

    r

    Air Flow, CFM

    Three Zones Three Zones - FireMode/Pressurized

  • 2012-ESD, Inc.

    Stair Air Flow Fire Mode

    Open Exit Door

    Open Exit Doors

    60 Story Ofice BuildingEffect of Stair Compartment on Pressurized Stair Air Flow - Smoke Condition (Level 28)

    -15000 -12500 -10000 -7500 -5000 -2500 0 2500 5000 7500

    13579

    11131517192123252729313335373941434547495153555759

    Floo

    r

    Air Flow, CFM

    Single Compartment Stair Three Compartment Stair

    Exhaust on Fire Floor & Supply Above/Below Doors open on fire, above/below and ground floors

  • 2012-ESD, Inc.

    Stair Pressure Fire Mode

    Open Exit Door

    Open Exit Doors

    60 Story Ofice BuildingEffect of Stair Compartment on Stair Pressure - Smoke Condition (Level 28)

    -0.10 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80

    13579

    11131517192123252729313335373941434547495153555759

    Floo

    r

    Pressure, in WG

    Single Compartment Stair Three Compartment Stair

    MA

    XIM

    UM

    STA

    IR P

    RES

    SUR

    E TO

    MA

    INTA

    IN D

    OO

    R F

    OR

    CE

    Exhaust on Fire Floor Supply Above/Below

    Doors open on fire floor, floors above/below fire floor and

    ground floors

  • 2012-ESD, Inc.

    Smoke Control Considerations

    Building envelope design Compartmentation

    Building occupancy types Zones

    Elevator shafts design/construction

    Stair shafts design/construction

    Air leakage paths (smoke movement)

    Local design temperatures Local wind velocities:

    Site Envelope (wind tunnel test)

    HVAC system: System zoning Components design System Activation/Controls

    Fire protection, detection and alarm system Integration/coordination

    Firefighters Access: To site To manual/remote control of

    system Exiting plan

    Refuge areas Exit duration

    Security and access control (door status/control)

  • 2012-ESD, Inc.

    16 Story Hotel Example Space Pressure

  • 2012-ESD, Inc.

    Tall Building Example Infiltration Air Flow

  • 2012-ESD, Inc.

    Tall Building Example Space Pressure Hotel Shut

    tle

    Pub

    lic P

    arki

    ng S

    huttl

    e

    Res

    iden

    tial P

    arki

    ng S

    huttl

    e

    Res

    iden

    tial L

    ow Z

    one

    Res

    iden

    tial -

    Hig

    h Zo

    ne

    Res

    iden

    tial F

    riegh

    t

    Bui

    ldin

    Frie

    ght

    Hot

    el F

    riegh

    t

    Am

    eniti

    es F

    riegh

    t

    Hot

    el

    Am

    eniti

    es -

    1

    Am

    eniti

    es -

    2

    9291908988878685848382818079787776757473727170696867666564636261605958575655545352515049484746454443424140393837363534333231302928272625242322212019181716151413121110

    98765432

    LobbyLL-1LL-2LL-3LL-4LL-5

  • 2012-ESD, Inc.

    Tall Building Example Space Pressure

  • 2012-ESD, Inc.

    Summary

    High rise building infiltration can be significantly reduced by vertical compartmentation of building shafts (elevators, stairs, HVAC risers)

    Vertical compartmentation of building shafts creates more uniform pressure and air flow characteristics

    High rise buildings HVAC system will perform more effectively and more efficiently through a managed plan for stack effect

    Smoke control system configuration and performance must be carefully analyzed for various fire conditions and plan designs

    Integrated design process between architecture, structure and MEP assures an optimized building natural air flow

    High rise buildings natural air flow, air pressures characteristics and stack effect must be reviewed early in the design stage

    Minimum of two air barriers (walls, doors & vestibules) shall separate the internal building shafts (elevator, stairs) from the outside environment on each floor main lobby, sky lobbies and loading dock levels may require additional layer of separation)

  • 2012-ESD, Inc.

    Thank you!

    High Rise Building Air Pressure, Infiltration & Stack EffectTheory and Impact on Indoor EnvironmentLearning ObjectivesAir Flow in High Rise BuildingsBasic TheoryBasic Theory Air Flow Around BuildingBasic Theory - Wind PressureBasic Theory - Stack Effect PressureBasic Theory Overall PressureBasic Theory Air Flow Through OpeningBasic Theory - Air Flow NetworkExample High Rise Building Air InfiltrationBuilding Air Infiltration Effect of ElevatorsElevator Shaft Air Flow Building Air Infiltration Effect of Stairs60 Story Building Space PressureTypical Stair Air Separation/Lock60 Story Building Infiltration Load (Energy)High Rise Building - Smoke ManagementPressurization Normal Mode of OperationPressurization Normal Mode of OperationPressurization Fire Mode of OperationPressurization Fire Mode of OperationPressurization Fire Mode/Stair ImpactPressurization Fire Mode/Stair ImpactElevator Shaft Air Flow Fire ModeStair Air Flow Fire ModeStair Pressure Fire ModeSmoke Control Considerations16 Story Hotel Example Space PressureTall Building Example Infiltration Air FlowTall Building Example Space PressureTall Building Example Space PressureSummaryThank you!