CB7 Systems LLC 200016 CBF Load System Specifications

200016 CBF

Water Cooled AC Load System

Specifications

CB7 Systems LLC

Version 0.01 Page:1 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

© 2014 CB7 Systems LLC — All Rights Reserved.The copyright laws of the United States and other countries protect this material. It may not be reproduced, distributed, or altered in any fashion without the expressed written consent of CB7 Systems LLC.

DisclaimerThe contents of this document, including all specifications, are subject to change without notice.

Version 0.01 Page:2 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

Version 0.01 Page:3 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

200016 Technical DataSize:

72 in x 40 in x 24 in

Weight:

850 lbs.

Voltage:

480 VAC 3Ph Delta 50/60Hz

Current:

303 A/Ph

Power:

252 KW

Maximum Flow Rate:

60 GPM

Maximum Fluid Pressure:

150 PSI

Maximum Outlet Temperature:

Adjustable to 95 degC

Load Connections:

Cam Lok

Fluid Connections:

2 inch type F

Coolant:

water or water/glycol

Version 0.01 Page:4 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

200016 Technical Data (cont)Operation Modes:

Loadbank (fixed power load)Delta T (fixed power)Delta T (fixed flow rate)Fixed T (fixed power)Fixed T (fixed flow rate)

Measurement Capability:

Input Load VoltageLoad CurrentLoad PowerInlet TemperatureExhaust TemperatureFluid Flow RateBTUs expended

Safety Features:

Over Temperature (sensor / thermal switch / relief valve)Adjustable Limit On Exhaust Temperature Over Pressure Over PowerOver VoltageTrapped AirPhase Imbalance

Display:

7 inch Color Touch Screen

Version 0.01 Page:5 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

200016 Technical Data (cont)

Communication:

EthernetCAN busRS232USB

Protocols:

HTTP (web)TCP SocketsModbus TCPSNMP v2cTelnetJ1939 (CanBus)

External Control Power:

120VAC Single Ph (150 watt)8 channels

Extended Configuration:

Series connection higher power with extended Delta TParallel connection higher power with increased flow rate

Other:

Real Time Clock Calendar1MB non volatile memory

Version 0.01 Page:6 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Windows Control

Version 0.01 Page:7 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Integrated Web Page

Version 0.01 Page:8 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Android Control

Version 0.01 Page:9 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Touch Screen Interface

Version 0.01 Page:10 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF ASCII Commands

SETP sets load bank fixed power levelDTF sets load bank delta t / fixed flow modeDTP sets load bank delta t / fixed power modeFTF sets load bank fixed t / fixed flow modeFTP sets load bank fixed t / fixed power mode

VAB? returns measured AB phase voltageVBC? returns measured BC phase voltageVAC? returns measured AC phase voltageIA? returns measured A phase currentIB? returns measured B phase currentIC? returns measured C phase currentV? returns composite measured phase voltageI? returns composite measured phase currentP? returns load bank measured powerTIN? returns measured input temperatureTOUT? returns measured exhaust temperaturesFLOW? returns measured flow rate

ALARM? returns load bank alarm valueSTATUS? returns load bank status value

BTU initializes BTU counterBTU? returns BTUs expended

FAREN changes to fahrenheit units modeCELSI changes to celsius units modeCLRALRM clears the load bank latched alarmsCLRSTAT clears the load bank latched status

SETP? returns load bank programmed powerMODE? returns load bank programmed operation modeDT? returns load bank programmed delta tF? returns load bank programmed flow rateMODEL? returns load bank model information

MAXP? returns load bank telemetry - maximum applied powerMAXV? returns load bank telemetry - maximum applied voltageMAXI? returns load bank telemetry - maximum applied currentMINV? returns load bank telemetry - minimum applied voltage (under load)MAXF? returns load bank telemetry – maximum flow rateMINF? returns load bank telemetry – minimum flow rate

Version 0.01 Page:11 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF ASCII Commands (cont)

IP? returns Ethernet IP addressIP sets Ethernet IP addressNM? returns Ethernet Net MaskNM sets Ethernet Net MaskGWY? returns Ethernet Gateway addressGWY sets Ethernet Gateway addressPORT? returns Ethernet TCP port valuePORT sets Ethernet TCP port valueMAC? returns Ethernet MAC address

SNMPNME? returns SNMP name informationSNMPNME sets SNMP name informationSNMPCON? returns SNMP contact informationSNMPCON sets SNMP contact informationSNMPLOC? returns SNMP location informationSNMPLOC sets SNMP location informationTRAPADR? returns SNMP trap addressesTRAPADR sets SNMP trap addressesTRAPEN? returns SNMP enabled trap addressesTRAPEN sets SNMP enabled trap addressesTRAPCOM? returns SNMP trap community informationTRAPCOM sets SNMP trap community informationTRAPTEST sends a test trap to all enabled trap addresses

COMMCFG? returns active communication channelsCOMMCFG sets active communication channelsTEMP? returns load bank internal processor temperature

Version 0.01 Page:12 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Modbus Register Map

Discrete Register 0x08 Voltage Phase Imbalance AlarmDiscrete Register 0x09 Current Phase Imbalance AlarmDiscrete Register 0x0A Trapped Air AlarmDiscrete Register 0x0B Over Temp Alarm

Input Register 0x01 AB VoltageInput Register 0x02 BC VoltageInput Register 0x03 AC VoltageInput Register 0x04 A CurrentInput Register 0x05 B CurrentInput Register 0x06 C CurrentInput Register 0x07 Measured PowerInput Register 0x08 Measured VoltageInput Register 0x09 Measured CurrentInput Register 0x1E Card TemperatureInput Register 0x22 AB BC Voltage ImbalanceInput Register 0x23 AB AC Voltage ImbalanceInput Register 0x24 BC AC Voltage ImbalanceInput Register 0x25 AB Current ImbalanceInput Register 0x26 AC Current ImbalanceInput Register 0x27 BC Current ImbalanceInput Register 0x28 Max Measured PowerInput Register 0x29 Max Measured VoltageInput Register 0x2A Max Measured CurrentInput Register 0x2B Min Measured Voltage Under LoadInput Register 0x2A 1000*VAB Gain CalInput Register 0x2B 1000*VBC Gain CalInput Register 0x2C 1000*VAC Gain CalInput Register 0x2D 1000*IA Gain CalInput Register 0x2E 1000*IB Gain CalInput Register 0x2F 1000*IC Gain CalInput Register 0x31 System VoltageInput Register 0x32 System CurrentInput Register 0x33 System PowerInput Register 0x34 SystemTypeInput Register 0x35 INTEGER FIRMWARE VERSIONInput Register 0x36 INTEGER PART NUMBERInput Register 0x37 IP 0Input Register 0x38 IP 1Input Register 0x39 IP 2Input Register 0x3A IP 3Input Register 0x3B NM 0Input Register 0x3C NM 1Input Register 0x3D NM 2Input Register 0x3E NM 3Input Register 0x40 GWY 0Input Register 0x41 GWY 1Input Register 0x42 GWY 2Input Register 0x43 GWY 3Input Register 0x44 MAC 0

Version 0.01 Page:13 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Modbus Register Map (cont)

Input Register 0x45 MAC 1Input Register 0x46 MAC 2Input Register 0x47 MAC 3Input Register 0x48 MAC 4Input Register 0x49 MAC 5Input Register 0x4A DNS1 0Input Register 0x4B DNS1 1Input Register 0x4C DNS1 2Input Register 0x4D DNS1 3Input Register 0x4E DNS2 0Input Register 0x4F DNS2 1Input Register 0x50 DNS2 2Input Register 0x51 DNS2 3Input Register 0x52 DHCP 0Input Register 0x53 DHCP 1Input Register 0x54 DHCP 2Input Register 0x55 DHCP 3Input Register 0x56 SMTP 0Input Register 0x57 SMTP 1Input Register 0x58 SMTP 2Input Register 0x59 SMTP 3Input Register 0x5A SNMP Trap Address 00Input Register 0x5B SNMP Trap Address 01Input Register 0x5C SNMP Trap Address 02Input Register 0x5D SNMP Trap Address 03Input Register 0x5E SNMP Trap Address 10Input Register 0x5F SNMP Trap Address 11Input Register 0x60 SNMP Trap Address 12Input Register 0x61 SNMP Trap Address 13Input Register 0x62 SNMP Trap Address 20Input Register 0x63 SNMP Trap Address 21Input Register 0x64 SNMP Trap Address 22Input Register 0x65 SNMP Trap Address 23Input Register 0x66 SNMP Trap Address 30Input Register 0x67 SNMP Trap Address 31Input Register 0x68 SNMP Trap Address 32Input Register 0x69 SNMP Trap Address 33Input Register 0x6A TCP PortInput Register 0x6B Communication CfgInput Register 0x6C CBF current modeInput Register 0x6D CBF current statusInput Register 0x6E CBF current alarmInput Register 0x6F CBF msrd power in KWInput Register 0x70 CBF msrd inlet tempInput Register 0x71 CBF msrd exhaust tempInput Register 0x72 CBF msrd flow rateInput Register 0x73 CBF msrd delta tInput Register 0x74 CBF fahrenheit / celsiusInput Register 0x75 CBF set powerInput Register 0x76 CBF set delta tInput Register 0x77 CBF set t exhaust

Version 0.01 Page:14 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Modbus Register Map (cont)

Input Register 0x78 CBF set flow rateInput Register 0x79 CBF pcr drive voltageInput Register 0x7A CBF servo drive voltageInput Register 0x7B CBF flow switchInput Register 0x7C CBF max measured flow rateInput Register 0x7D CBF min measured flow rateInput Register 0x7E CBF max measured temp

Holding Register 0x01 Reset SystemHolding Register 0x02 Restart SystemHolding Register 0x1E Card TemperatureHolding Register 0x22 AB BC Voltage ImbalanceHolding Register 0x23 AB AC_Voltage ImbalanceHolding Register 0x24 BC AC_Voltage ImbalanceHolding Register 0x25 AB Current ImbalanceHolding Register 0x26 AC Current ImbalanceHolding Register 0x27 BC Current ImbalanceHolding Register 0x28 Max Measured PowerHolding Register 0x29 Max Measured VoltageHolding Register 0x2A Max Measured CurrentHolding Register 0x2B Min Measured Voltage Under LoadHolding Register 0x2A 1000*VAB Gain CalHolding Register 0x2B 1000*VBC Gain CalHolding Register 0x2C 1000*VAC Gain CalHolding Register 0x2D 1000*IA Gain CalHolding Register 0x2E 1000*IB Gain CalHolding Register 0x2F 1000*IC Gain CalHolding Register 0x31 System VoltageHolding Register 0x32 System CurrentHolding Register 0x33 System PowerHolding Register 0x34 System TypeHolding Register 0x35 INTEGER FIRMWARE VERSIONHolding Register 0x36 INTEGER PART NUMBERHolding Register 0x37 IP0Holding Register 0x38 IP1Holding Register 0x39 IP2Holding Register 0x3A IP3Holding Register 0x3B NM0Holding Register 0x3C NM1Holding Register 0x3D NM2Holding Register 0x3F NM3Holding Register 0x40 GWY0Holding Register 0x41 GWY1Holding Register 0x42 GWY2Holding Register 0x43 GWY3Holding Register 0x44 MAC0Holding Register 0x45 MAC1Holding Register 0x46 MAC2Holding Register 0x47 MAC3Holding Register 0x48 MAC4Holding Register 0x49 MAC5

Version 0.01 Page:15 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Modbus Register Map (cont)

Holding Register 0x4A DNS1 0Holding Register 0x4B DNS1 1Holding Register 0x4C DNS1 2Holding Register 0x4D DNS1 3Holding Register 0x4E DNS2 0Holding Register 0x4F DNS2 1Holding Register 0x50 DNS2 2Holding Register 0x51 DNS2 3Holding Register 0x52 DHCP0Holding Register 0x53 DHCP1Holding Register 0x54 DHCP2Holding Register 0x55 DHCP3Holding Register 0x56 SMTP0Holding Register 0x57 SMTP1Holding Register 0x58 SMTP2Holding Register 0x59 SMTP3Holding Register 0x5A SNMP Trap Address0 0Holding Register 0x5B SNMP Trap Address0 1Holding Register 0x5C SNMP Trap Address0 2Holding Register 0x5D SNMP Trap Address0 3Holding Register 0x5E SNMP Trap Address1 0Holding Register 0x5F SNMP Trap Address1 1Holding Register 0x60 SNMP Trap Address1 2Holding Register 0x61 SNMP Trap Address1 3Holding Register 0x62 SNMP Trap Address2 0Holding Register 0x63 SNMP Trap Address2 1Holding Register 0x64 SNMP Trap Address2 2Holding Register 0x65 SNMP Trap Address2 3Holding Register 0x66 SNMP Trap Address3 0Holding Register 0x67 SNMP Trap Address3 1Holding Register 0x68 SNMP Trap Address3 2Holding Register 0x69 SNMP Trap Address3 3Holding Register 0x6A TCP PortHolding Register 0x6B Communication CfgHolding Register 0x6C CBF current modeHolding Register 0x6D CBF current statusHolding Register 0x6E CBF current alarmHolding Register 0x6F CBF msrd power in KWHolding Register 0x70 CBF msrd inlet tempHolding Register 0x71 CBF msrd exhaust tempHolding Register 0x72 CBF msrd flow rateHolding Register 0x73 CBF msrd delta tHolding Register 0x74 CBF fahrenheit / celsiusHolding Register 0x75 CBF set powerHolding Register 0x76 CBF set delta tHolding Register 0x77 CBF set t exhaustHolding Register 0x78 CBF set flow rateHolding Register 0x79 CBF pcr drive voltageHolding Register 0x7A CBF servo drive voltageHolding Register 0x7B CBF flow switchHolding Register 0x7C CBF max measured flow rate

Version 0.01 Page:16 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF Modbus Register Map (cont)

Holding Register 0x7D CBF min measured flow rateHolding Register 0x7E CBF max measured temp

Version 0.01 Page:17 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB

-- CBF control MIB.-- -- Author Date Comment-- ==================================================================-- Lance Palatini 2/1/14 Initial--

CB7SYSTEMS DEFINITIONS ::= BEGIN

IMPORTSenterprises, IpAddress

FROM RFC1155-SMIOBJECT-TYPE

FROM RFC-1212TRAP-TYPE

FROM RFC-1215DisplayString

FROM RFC1213-MIB;

on-off ::= INTEGER {off (0),on (1)

}

cb7systems OBJECT IDENTIFIER ::= { enterprises 43048 }product OBJECT IDENTIFIER ::= { cb7systems 1 }setup OBJECT IDENTIFIER ::= { cb7systems 2 }control OBJECT IDENTIFIER ::= { cb7systems 3 }

productname OBJECT-TYPESYNTAX DisplayStringACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { product 1 }

productversion OBJECT-TYPESYNTAX DisplayStringACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { product 2 }

Version 0.01 Page:18 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB (cont)versiondate OBJECT-TYPE

SYNTAX DisplayStringACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { product 3 }

trapsTable OBJECT-TYPESYNTAX SEQUENCE OF TrapsEntryACCESS not-accessibleSTATUS mandatoryDESCRIPTION

"Trap table"::= { setup 1 }

trapsEntry OBJECT-TYPESYNTAX TrapsEntryACCESS not-accessibleSTATUS mandatoryDESCRIPTION

"Single trap entry containing trap receiver info."INDEX { trapReceiverNumber }::= { trapsTable 1 }

TrapsEntry ::= SEQUENCE {trapReceiverNumber

INTEGER,trapEnabled

INTEGER,trapReceiverIPAddress

IpAddress,trapCommunity

DisplayString}

--

trapReceiverNumber OBJECT-TYPESYNTAX INTEGER (0..4)ACCESS read-onlySTATUS mandatoryDESCRIPTION

"Index of trap receiver"::= { trapsEntry 1 }

Version 0.01 Page:19 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB (cont)trapEnabled OBJECT-TYPE

SYNTAX INTEGER {no (0),yes (1)

}ACCESS read-writeSTATUS mandatoryDESCRIPTION

"Indicates if this trap entry is enabled or not."::= { trapsEntry 2 }

trapReceiverIPAddress OBJECT-TYPESYNTAX IpAddressACCESS read-writeSTATUS mandatoryDESCRIPTION

"Trap receiver IP address"::= { trapsEntry 3 }

trapCommunity OBJECT-TYPESYNTAX DisplayString (SIZE(0..7))ACCESS read-writeSTATUS mandatoryDESCRIPTION

"Trap community to be used by agent to send trap"::= { trapsEntry 4 }

systemname OBJECT-TYPESYNTAX DisplayStringACCESS read-writeSTATUS mandatoryDESCRIPTION

""::= { control 1 }

systemcontact OBJECT-TYPESYNTAX DisplayStringACCESS read-writeSTATUS mandatoryDESCRIPTION

""::= { control 2 }

systemlocation OBJECT-TYPESYNTAX DisplayStringACCESS read-writeSTATUS mandatoryDESCRIPTION

""::= { control 3 }

Version 0.01 Page:20 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB (cont)systemtesttrap OBJECT-TYPE

SYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 4 }

systemruntime OBJECT-TYPESYNTAX DisplayStringACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 5 }

systemtemperature OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 6 }

cbftrappedairfail OBJECT-TYPESYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 7 }

cbfovertempfail OBJECT-TYPESYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 8 }

cbfvoltageimbalance OBJECT-TYPESYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 9 }

Version 0.01 Page:21 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB (cont)cbfcurrentimbalance OBJECT-TYPE

SYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 10 }

cbfoperationmode OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 11 }

cbfstatus OBJECT-TYPESYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 12 }

cbfalarm OBJECT-TYPESYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 13 }

cbfmeasuredtin OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 14 }

cbfmeasuredtout OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 15 }

Version 0.01 Page:22 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB (cont)cbfmeasuredflow OBJECT-TYPE

SYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 16 }

cbfmeasureddeltat OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 17 }

cbfahrenheit OBJECT-TYPESYNTAX INTEGERACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 18 }

cbfmeasuredvoltage OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 19 }

cbfmeasuredcurrent OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 20 }

cbfmeasuredpower OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 21 }

Version 0.01 Page:23 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB (cont) cbfsetpower OBJECT-TYPE

SYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 22 }

cbfsetflow OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 23 }

cbfsetdeltat OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 24 }

cbfsettout OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 25 }

cbfsetmode OBJECT-TYPESYNTAX DisplayString (SIZE(0..15))ACCESS read-onlySTATUS mandatoryDESCRIPTION

""::= { control 26 }

trapcbfairfail TRAP-TYPEENTERPRISE enterprisesVARIABLES { cbftrappedairfail }DESCRIPTION

""::= 1

Version 0.01 Page:24 of 25

CB7 Systems LLC 200016 CBF Load System Specifications

CBF SNMP MIB (cont)trapcbfovertemp TRAP-TYPE

ENTERPRISE enterprisesVARIABLES { cbfovertempfail }DESCRIPTION

""::= 2

cbftrapphaseimbalance TRAP-TYPEENTERPRISE enterprisesVARIABLES { cbfphaseimbalance }DESCRIPTION

""::= 3

traptest TRAP-TYPEENTERPRISE enterprisesVARIABLES { systemtesttrap }DESCRIPTION

""::= 4

END