17. Steam Trap & Steam Specialty Sizing - 3rd Edition
description
Transcript of 17. Steam Trap & Steam Specialty Sizing - 3rd Edition
TRA
PS
&
SPEC
IALT
IES
- 313 -
SECTION VITRAPS &
SPECIALTIES
30
Applications● Steam Lines ● Unit Heaters
● Process Equipment ● Oil Preheaters
● Steam Cookers ● Converters
● Steam Heated Vats ● Coils
● Pressing Machinery ● Rotating Drum
Proven Caged Stainless Steel Balanced Pressure Thermostatic Air Vent
automatically discharges air and non-condensables
Stainless Steel Strainer with large screen area prevents dirt problems
ConnectionsSizes 1/2” – 2” screwed
NPT (BSPT optional) Sizes 11/2” & 2” flanged
ANSI 250
Weighted Stainless Steel Free Float Ball
multi-contact surface area modulates orifice discharge to
provide smooth, continuous discharge and immediate
response to load variations
Stainless Steel Sleeve eliminates body erosion
Stainless Steel Seatfull bore prevents choking
and permits ample capacities
Liquid Levelmaintains seal over orifice to prevent live steam loss
Bottom & Side Blowdown Connections
for preventative maintenance
GuaranteeTraps are guaranteed against defects
in materials or workmanship for 3 years.
NOVA NFT250 Series Variable Orifice
Steam TrapsPressures To 250 PSIGTemperatures to 450°F
31
Applications● Steam Lines ● Unit Heaters
● Process Equipment ● Oil Preheaters
● Steam Cookers ● Converters
● Steam Heated Vats ● Coils
● Pressing Machinery ● Rotating Drum
DURA-FLOInverted Bucket
Steam TrapPressures To 250 PSIGTemperatures to 450°F
Withstands Severe ConditionsHeavy wall cast iron cover and
body provide many years of trouble free service.
Smooth Action and Tight Shutoff
Stainless steel linkage, valve and seats are precisionmanufactured to insure
optimal performance.
Ideal for “Dirty” Systems
Valve and seat located at top of trap and stainless
steel strainers available on most horizontal models
ensure long service.
Maximum Compatibility with Existing Installations
Pressure change assemblies are interchangeable with
Armstrong which guaranteesmaximum flexibility when
stocking repair parts.
Easy to MaintainWorking parts lift out with top for quick inspection and maintenance.
Resists CorrosionStainless steel bucket provides maximum service life with minimum deterioration.
Minimizes Effects of Water HammerOpen bucket design avoids collapse typical of sealed floats.
Suitable for Wide Variety of Loads/ApplicationsHorizontal and vertical models in thirteen body sizes are one of themost comprehensive invertedbucket trap lines available.
32
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
On startup, the thermostatic air vent (caged stainlesswelded bellows) is open, allowing air to flow freelythrough the vent valve orifice. When condensate flowsinto the trap, the float rises, allowing condensate tobe discharged. Once air and non-condensibles havebeen evacuated, hot condensate will cause the therm-ostatic vent to close. Condensate will continue to bedischarged as long as condensation occurs.
During normal operation, an increase in the loadcauses the liquid level in the trap to rise. The float thenrises and rolls off the seat ring, allowing morecondensate to flow out. The float sinks as thecondensate load decreases, moving nearer to theseat ring, decreasing the effective size of the orificeand allowing less condensate to discharge. Thisprovides smooth, continuous operation that reactsinstantly to load variation while maintaining a waterseal over the seat ring to prevent live steam loss.
NOVA NFT250 SERIESVARIABLE ORIFICE
STEAM TRAPSPressures To 250 PSIG (17.2 barg)
Temperatures to 450°F (232°C)
All Stainless Steel Internal Components — Hardenedvalves and seats. Extra long life and dependable service.Resists water hammer. Protects against erosion andcorrosion.Erosion Proof — Discharge passage is protected with astainless steel liner.Integral Strainer — Stainless Steel screen prevents dirtproblems. Blow-down connection provided.Thermostatic Air Vent — Full balanced pressureelement for immediate and complete air venting.Variable Orifice — Condensate is discharged continu-ously through the seat ring which is modulated by thefloat. This provides a smooth, even flow without highvelocity or steam entrainment.SLR Orifice — Optional continuous bleed prevents flashsteam lockup when it is impossible to install trap at lowpoint in system.Guarantee — Traps are guaranteed against defects inmaterials or workmanship for 3 years.
MODELS
● NFT250–Low capacity● NFT251–Medium capacity● NFT252–High capacity● NFT253–Super high capacity
APPLICATIONS
● Steam Lines● Process Equipment● Steam Cookers● Steam Heated Vats● Pressing Machinery● Unit Heaters● Oil Preheaters● Converters● Coils● Rotating Drum
OPTIONS
● SLR - SLR Orifice● B - Blowdown Valve (contact factory)● Orifice Continuous Bleed Air Vent● 250# - 250# Flanged Connection* (Flat Faced)*Available on NFT 253 only.
Canadian Registration # OE0591.9C
OPERATION
Installation Tip: Add Uniflex Pipe Coupling for ease of maintenanceSEE PAGE 102
Installation Tip: Always install STV Test & Block Valve as part of trap stationSEE PAGE 118
See Page 9
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
33
A
B
D
Clearance for Maintenance
C
Connections: 1⁄2"-2" NPT or 11⁄2"-2" Flanged
Steam trap shall be of float and thermostatic design. Float shallbe free of levers, linkages, or other mechanical connections. Floatshall be weighted to maintain orientation and shall act as thevalve being free to modulate condensate through the seat ring.Air vent shall be of balanced pressure design with stainless steelwelded encapsulated bellows capable of discharging air andnoncondensable gases continuously within 15°F of saturatedtemperature. Trap shall contain integral strainer and stainlesssteel exhaust port sleeve. Trap shall be cast iron bodied suitablefor pressures to 250 psi and available in 1/2" through 2" NPT orflanged.
NOVA NFT250 SERIESVARIABLE ORIFICE
STEAM TRAPSSPECIFICATION
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating PressureORIFICE PMO
20 20 psig (1.4 barg)50 50 psig (3.5 barg)100 100 psig (6.9 barg)150 150 psig (10.3 barg)250 250 psig (17.2 barg)
PMA: Max. Allowable Pressure: 250 psig (17.2 barg)
TMA: Max. Allowable Temperature: 450°F (232°C)
DimensionsInches (mm) Weight
Model Size Connection Lbs.A B C D (kg)
NFT250 1/2 & 3/4 NPT 41/4 23/4 35/8 51/2 6
(108) (69) (92) (140) (2.7)
NFT251 3/4 & 1 NPT 51/2 215/16 49/16 63/4 13
(140) (74) (116) (171) (5.9)
NFT252† 1 & 11/2 NPT 11 215/16 73/4 10 41
(279) (74) (197) (254) (18.6)
NPT 133/4 215/16 115/8 153/8 120
NFT253 11/2 & 2(349) (74) (295) (391) (54.5)
250# Flg. 153/4 215/16 115/8 153/8 130
(400) (74) (295) (391) (59.1)
A
B
CD
Clearance for Maintenance
Maximum Capacity–lbs/hr (10°F Below Saturation)Orifice Differential – PSIG (barg)
Trap Size Max. 1 5 10 15 20 30 50 75 100 125 150 175 200 225 250∆P (.07) (.34) (.69) (1.03) (1.38) (2.07) (3.45) (5.17) (6.90) (8.62) (10.3) (12.1) (13.8) (15.5) (17.2)
0.193 20 264 810 1050 1100 12000.141 50 190 430 610 750 870 1070 1400
NFT250 0.102 100 88 160 250 300 350 425 530 670 7100.091 150 70 140 219 260 295 345 410 470 520 555 5900.067 250 37 90 140 170 200 240 300 340 390 405 415 440 460 480 5000.277 20 590 1600 2100 2400 24500.209 50 340 760 1080 1330 1540 1900 2460
NFT251 0.157 100 200 500 650 740 830 950 1100 1300 14000.141 150 170 385 527 627 705 825 990 1130 1240 1330 14150.120 250 110 255 360 425 500 575 700 800 900 940 1000 1050 1100 1150 12000.593 20 2720 6280 8600 10500 117000.469 50 1750 3920 5560 6830 7900 9700 12600
NFT252 0.339 100 930 2170 3130 3840 4460 4990 6020 7030 79600.316 150 850 1935 2650 3150 3540 4140 4970 5685 6230 6690 71000.261 250 670 1400 1900 2400 2540 3000 3500 4100 4200 4900 5100 5300 5500 5750 60001.102 20 8000 15000 18000 19900 228000.875 50 5460 12600 15600 16900 18400 21000 25400
NFT253 0.593 100 2800 6350 8700 10900 12800 13700 16600 18700 210000.578 150 2690 6120 8385 9970 11200 13100 15700 17980 19700 21150 224500.484 250 1600 3770 5300 6470 7560 8610 10400 12100 13600 14600 15500 16300 17100 17800 18400
For Kg/Hr Multiply by .454
MATERIALS OF CONSTRUCTION
Body and Cover . . . . . . . .Cast Iron ASTM A126BAll Internal Parts . . . . . . . . . . . . . . .Stainless SteelAir Vent . . . . . .Balanced Pressure, Stainless SteelCover Gasket . . . . . . . . . . . . . . . . .Graphite Fiber
34
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
On startup, the thermostatic air vent (cagedstainless welded bellows) is open, allowing air toflow freely through the vent valve orifice. Whencondensate flows into the trap, the float rises,allowing condensate to be discharged. Once air andnon-condensibles have been evacuated, hotcondensate will cause the thermostatic vent toclose. Condensate will continue to be discharged aslong as condensation occurs.
During normal operation, an increase in the loadcauses the liquid level in the trap to rise. The floatthen rises and rolls off the seat ring, allowing morecondensate to flow out. The float sinks as thecondensate load decreases, moving nearer to theseat ring, decreasing the effective size of the orificeand allowing less condensate to discharge. Thisprovides smooth, continuous operation that reactsinstantly to load variation while maintaining a waterseal over the seat ring to prevent live steam loss.
NOVA NFT650 SERIESVARIABLE ORIFICE
STEAM TRAPSPressures To 650 PSIG (44.8 barg)
Temperatures to 750°F (400°C)
All Stainless Steel Internal Components — Hardenedvalves and seats. Extra long life and dependable service.Resists water hammer. Protects against erosion andcorrosion.Erosion Proof — Discharge passage is protected with astainless steel liner.Integral Strainer — Stainless Steel screen prevents dirtproblems. Blow-down connection provided.Thermostatic Air Vent —Provided with balancedpressure element for immediate and complete air venting.Variable Orifice — Condensate is dischargedcontinuously through the seat ring which is modulated bythe float. This provides a smooth, even flow without highvelocity or steam entrainment.SLR Orifice — Optional continuous bleed prevents flashsteam lockup when it is impossible to install trap at lowpoint in system.Guarantee — Traps are guaranteed against defects inmaterials or workmanship for 3 years.
MODELS
● NFT651–Low capacity● NFT652–Medium capacity● NFT653–High capacity
APPLICATIONS
● Steam Lines● Process Equipment● Steam Cookers● Steam Heated Vats● Pressing Machinery● Unit Heaters● Oil Preheaters● Converters● Coils● Rotating Drum
OPTIONS
● SLR - SLR Orifice● B - Blowdown Valve (contact factory)● Continuous Bleed Air Vent● 300# or 600# Flanged Connection* (Raised
Face)*Available on NFT652 and NFT653 only.
Canadian Registration # OE0591.9C
OPERATION
Installation Tip: Add Uniflex Pipe Coupling for ease of maintenanceSEE PAGE 102
Installation Tip: Always install STV Test & Block Valve as part of trap stationSEE PAGE 118
See page 9
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
35
Steam trap shall be of float and thermostatic design. Float shall befree of levers, linkages, or other mechanical connections. Floatshall be weighted to maintain orientation and shall act as thevalve being free to modulate condensate through the seat ring.Air vent shall be of balanced pressure design with stainless steelwelded encapsulated bellows capable of discharging air andnoncondensable gases continuously within 15°F of saturatedtemperature. Trap shall contain integral strainer and stainlesssteel exhaust port sleeve. Trap shall be cast steel bodied suitablefor pressures to 650 psi and available in 1/2" through 2" NPT,Socket Weld, or flanged.
NOVA NFT650 SERIESVARIABLE ORIFICE
STEAM TRAPSSPECIFICATION
A
B
CD
Clearance for Maintenance
A
B
C
Clearance for Maintenance
D
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating PressureORIFICE PMO
20 20 psig (1.4 barg)50 50 psig (3.5 barg)100 100 psig (6.9 barg)175 175 psig (12.1 barg)300 300 psig (20.7 barg)400 400 psig (27.6 barg)600 600 psig (41.4 barg)
PMA: Max. Allowable Pressure: 650 psig (44.8 barg)
TMA: Max. Allowable Temperature: 750°F (400°C)
DimensionsInches (mm) Weight
Model Size A B C D Lbs.NPT 300# 600# (kg)
NFT651 1/2, 3/4 & 1 51/2 — — 31/16 57/16 71/4 21
(140) (78) (138) (184) (9.5)
1 11 133/4 133/4 215/16 83/4 113/8 84
NFT652(279) (349) (349) (75) (222) (290) (38.2)
11/2 & 2 11 133/4 149/16 215/16 83/4 113/8 87
(279) (349) (370) (75) (222) (290) (39.5)
11/2 133/4 163/4 173/8 35/16 117/8 16 192
NFT653(349) (426) (411) (84) (392) (406) (87.3)
2 133/4 1611/16 177/16 35/16 117/8 16 195
(349) (424) (443) (84) (302) (406) (88.6)
For Kg/Hr Multiply by .454
MATERIALS OF CONSTRUCTION
Body & Cover . . . . . .ASTM A216 Grade WCBCover Gasket . . . . .Spiral Wound 304 Stainless
w/graphite fillerAll Internal . . . . . . . . . . . . . . . . .Stainless SteelAir Vent . . .Balanced Pressure, Stainless Steel
Connections: 1⁄2-2" NPT or 11⁄2-2" Flanged
Maximum Capacity - lbs/hr (10 degrees Below Saturation)Trap Orifice MAX Differential - PSIG (barg)
Size ∆P 1 5 10 20 50 75 100 150 175 200 250 300 400 500 600(.07) (.34) (.69) (1.38) (3.45) (5.17) (6.90) (10.3) (12.1) (13.8) (17.2) (20.7) (27.6) (34.5) (41.4)
0.277 20 590 1600 2100 24500.209 50 340 760 1080 1540 24600.157 100 200 500 650 830 1100 1300 14000.141 150 170 385 527 705 990 1130 1240 1415
NFT651 0.130 175 180 350 500 675 900 1000 1100 1300 14000.120 250 110 255 360 500 700 800 900 1000 1050 1100 12000.106 300 105 240 330 435 575 675 750 875 955 1020 1140 12550.096 400 100 220 300 390 510 585 640 740 795 835 920 1000 11400.081 600 75 145 180 225 300 340 375 435 465 490 540 585 665 740 8000.593 20 2720 6280 8600 117000.469 50 1750 3920 5560 7900 126000.339 100 930 2170 3130 4460 6020 7030 79600.316 150 850 1935 2650 3540 4970 5685 6230 7100
NFT652 0.297 175 800 1700 2300 3200 4400 5000 5500 6400 69000.261 250 670 1400 1900 2540 3500 4100 4200 5100 5300 5500 60000.238 300 645 1240 1565 1955 2575 2940 3220 3740 4000 4220 4640 50600.213 400 515 995 1250 1565 2060 2355 2575 2995 3200 3380 3720 4050 46000.180 600 370 710 895 1120 1470 1680 1840 2140 2290 2410 2655 2890 3300 3655 39551.102 20 8000 15000 18000 228000.875 50 5460 12600 15600 18400 254000.593 100 2800 6350 8700 12800 16600 18700 210000.578 150 2690 6120 8385 11200 15700 17980 19700 22450
NFT653 0.547 175 2400 5500 7600 10300 14400 16500 18200 20750 219000.484 250 1600 3770 5300 7560 10400 12100 13600 15500 16300 17100 184000.453 300 1500 3500 5200 7075 9325 10655 11655 13545 14485 15275 16815 183150.404 400 1400 2800 4200 5630 7420 8480 9270 10770 11520 12150 13380 14570 165550.339 600 800 1800 2800 3900 5220 5970 6530 7585 8110 8555 9420 10260 11655 12960 13990
36
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
Air entering trap is immediately dischargedthrough the high capacity integral air vent. Thethermostatic vent will close just prior to saturationtemperature. The balanced design will allow ventingof non-condensibles that collect in the floatchamber when operating at design pressure. Whensteam enters the trap, the thermostatic air vent
closes to prevent steam loss. When steam gives up it’slatent heat, it becomes condensate. This “condensate”enters the trap and causes the stainless steel ball floatto rise. Raising of the float opens the discharge valve,allowing condensate to be continuously discharged asit enters the trap. The condensate level in the trap bodyis maintained above the discharge seat, providing apositive seal against the loss of steam.
FTN SERIESFLOAT & THERMOSTATIC
STEAM TRAPSPressures To 125 PSIG (8.6 barg)Temperatures to 450°F (232°C)
Universal Four-port Design — Four possible hookupcombinations of the “H” pattern body and pipingdimensions similar to other major manufacturers allowmaximum installation flexibility for easy replacement ofother traps. Inlet and outlet taps on larger sized trapslocated in the cover to permit larger capacities.All Stainless Steel Internal Components — Hardenedvalves and seats. Extra long life and dependableservice. Resists water hammer. Protects againsterosion and corrosion.Balanced Pressure Thermostatic Element — allowsventing of non-condensibles while operating at designpressure.Rugged Welded Stainless Steel Element —Increases service life.Wide Selection of Differential Pressures — Sizes3/4" to 2" available with 15, 30, 75 and 125 psigdifferential pressures.Air Line Water Removal — Special configurationFTNA optimized for compressed air service.Repairable In-line — Can be serviced withoutdisturbing system piping.
MODELS
● FTN-15–Steam pressures to 15 PSIG● FTN-30–Steam pressures to 30 PSIG● FTN-75–Steam pressures to 75 PSIG● FTN-125–Steam pressures to 125 PSIG● FTNA-75–Air pressures to 75 PSIG● FTNA-125–Air pressures to 125 PSIG
APPLICATIONS
● Unit Heaters & other Space HeatingEquipment
● Heat Exchangers/Reboilers● Steam Heating Coils● Steam Main Drips● Air Compressor Receivers● Air Line Drips● Air Powered Process Equipment
OPTIONS
● Repair Kits
OPERATION
Installation Tip: Add Uniflex Pipe Coupling for ease of maintenanceSEE PAGE 102
Installation Tip: Always install STV Test & Block Valve as part of trap stationSEE PAGE 118
See page 9
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
37
Connections: 3/4"-2" NPT
Maximum Capacity—lbs/hr (10°F Below Saturation)Size Differential–PSIG (barg)
Trap NPT Orifice 1/4 1/2 1 2 5 10 15 20 25 30 40 50 75 100 125(in.) (.017) (.034) (.069) (.138) (.345) (.690) (1.03) (1.38) (1.72) (2.07) (2.76) (3.45) (5.17) (6.90) (8.62)
FTN-15 3/4" .218 279 369 489 650 785 1000 1075FTN-15 1" .218 279 369 489 650 785 1000 1075FTN-15 1 1/4" .312 600 770 980 1240 1640 2000 2340FTN-15 1 1/2" .500 1100 1700 2400 3300 5000 6600 7600FTN-15 2" .625 2300 2800 3600 4650 6900 9000 10900FTN-30 3/4" .218 279 369 489 650 785 1000 1075 1210 1300 1370FTN-30 1" .218 279 369 489 650 785 1000 1075 1210 1300 1370FTN-30 1 1/4" .228 375 500 690 910 1200 1500 1680 1800 1900 2000FTN-30 1 1/2" .390 1000 1300 1700 2300 3400 4600 5500 6000 6600 7000FTN-30 2" .500 1300 1800 2500 3400 5200 6800 7800 8600 9300 10000FTN-75† 3/4" .166 160 213 280 365 520 700 795 875 930 970 1120 1230 1450FTN-75† 1" .166 160 213 280 365 520 700 795 875 930 970 1120 1230 1450FTN-75† 1 1/4" .312 550 725 960 1300 1900 2650 3050 3400 3700 4000 4400 4750 5400FTN-75† 1 1/2" .312 550 725 960 1300 1900 2650 3050 3400 3700 4000 4400 4750 5400FTN-75† 2” .421 850 1100 1500 2000 3100 4150 4750 5200 5500 5800 6400 6800 7700FTN-125† 3/4" .125 100 135 175 230 330 415 500 585 620 685 750 830 970 1110 1190FTN-125† 1" .125 100 135 175 230 330 415 500 585 620 685 750 830 970 1110 1190FTN-125† 1 1/4" .246 400 520 680 890 1300 1700 2050 2300 2500 2700 3000 3200 3800 4200 4500FTN-125† 1 1/2" .246 400 520 680 890 1300 1700 2050 2300 2500 2700 3000 3200 3800 4200 4500FTN-125† 2" .332 550 675 880 1225 1950 2600 3000 3250 3500 3800 4200 4600 5500 6100 6600
Steam trap shall be of float and thermostatic design. Float shallactuate the valve via a hinged lever and linkage. Air vent shall beof balanced pressure design with stainless steel weldedencapsulated bellows capable of discharging air andnoncondensable gases continuously within 15°F of saturatedtemperature. Traps through 1-1/4" shall employ “H” patternconnections to accommodate multiple piping configurations.Trap shall be cast iron bodied suitable for pressures to 125 psiand available in 3/4" through 2" NPT.
FTN SERIESFLOAT & THERMOSTATIC
STEAM TRAPSSPECIFICATION
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating PressureORIFICE PMO
15 15 psig (1.03 barg)30 30 psig (2.07 barg)75 75 psig (5.17 barg)125 125 psig (8.62 barg)
PMA: Max. Allowable Pressure250 psig (17.2 barg)
TMA: Max. Allowable Temperature450°F (232°C)
3/4", 1" - All 11/4" - FTN-15,
FTN-30
11/2", 2" - All *11/4" - FTN-75,
FTN-125,FTNA-75*,FTNA-125*
MATERIALS OF CONSTRUCTION
Body & Cover . .Cast Iron ASTMA126BAll Internal . . . . . . . . . .Stainless SteelAir Vent (FTN only) . . . .Balanced Pressure,
Welded Stainless Steel
DimensionsInches (mm) Weight
Model No. Size A B C D E E1 lbs (kg)3/4 6.25 5.50 3.31 3.00 5.75 — 9
(159) (140) (84) (76) (146) (4.1)1 6.25 5.50 3.31 3.00 5.75 — 9
(159) (140) (84) (76) (146) (4.1)FTN-15, FTN-30 11/4 6.25 5.75 3.00 3.81 5.75 — 91/2
(159) (146) (76) (97) (146) (4.3)11/2 8.50 4.25 3.00 0.70 — 8.40 18
(216) (108) (76) (18) (213) (8.2)2 9.81 4.94 4.94 0.12 9.12 — 26
(249) (123) (123) (3) (232) (11.8)3/4 6.25 5.50 3.31 3.00 5.75 9
(159) (140) (84) (76) (146) (4.1)1 6.25 5.50 3.31 3.00 5.75 — 9
(159) (140) (84) (76) (146) (4.1)FTN-75, FTN-125 11/4 8.50 4.25 3.00 0.70 — 8.40 18FTNA-75,FTNA-125 (216) (108) (76) (18) (213) (8.2)
11/2 8.50 4.25 3.00 0.70 — 8.40 18(216) (108) (76) (18) (213) (8.2)
2 9.81 4.94 4.94 0.12 9.12 — 26(249) (123) (123) (3) (232) (11.8)
For Kg/Hr Multiply by .454 †For FTNA capacities, multiply by 1.33.
*1/8" NPT tap at top boss for balancing line.
38
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
MAX-FLOSUPER HIGH CAPACITY FLOAT
& THERMOSTATIC STEAM TRAPSPressures to 175 PSIG (12.1 barg)
Temperatures to 377ºF (192ºC)
● High Capacities
● Rugged cast iron body and cover
● Stainless steel thermostatic elementeliminates air binding
● Stainless steel float and lever mechanism
● Below condensate level seat designprevents steam leakage
● Resistant to water hammer and corrosion
● In-Line repairable
MODELS
HC-15 - Steam pressures to 15 PSIGHC-30 - Steam pressures to 30 PSIGHC-75 - Steam pressures to 75 PSIGHC-125 - Steam pressures to 125 PSIGHC-175 - Steam pressures to 175 PSIG
During startup, air and non-condensible gasesenter the trap and are automatically vented throughan accurate balanced pressure internal thermostat-ic air vent. As condensate enters the trap, the floatand lever mechanism is raised, lifting the valve off
the seat, discharging the condensate. Condensatewill continue to be discharged at the same rate atwhich it is entering. Any air or non-condensible gasthat may accumulate will be continually and efficientlypassed by the thermostatic air vent.
OPERATION
APPLICATIONS
● Very High Condensate Loads ● Continuous Drainage With High Air Venting
Capacity Requirements● Industrial And Commercial Applications ● Absorption Systems● Air Handling Coils● Heat Exchangers● Dryers Evaporators● Hot water Generators● Rendering Machines● Steam Process Equipment● Air Make-up Coils● Unit Heaters And Cooking Kettles
Installation Tip: Add Uniflex Pipe Coupling for ease of maintenanceSEE PAGE 102
Installation Tip: Always install STV Test & Block Valve as part of trap stationSEE PAGE 118
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
39
MAXIMUM OPERATING CONDITIONSPMO: Max. Operating Pressure see orifice selectionTMO: Max. Operating Temperature saturated at pressurePMA: Max. Allowable Pressure 175 PSIG (12.1 barg)PMA: Max. Allowable Pressure 377ºF (192ºC)
MATERIALS OF CONSTRUCTIONBody & Cover . . . . . . . . .Cast Iron 30,000 psi tensileValve Pin and Seat . . . . . .Stainless Steel (Hardened)Float . . . . . . . . . . . . . . . . . . . . . . . . .Stainless SteelLever Assembly . . . . . . . . . . . . . . . . .Stainless SteelThermostatic Air Vent . . . . . . . . .Stainless Steel Cage
& Thermal ElementCover Bolts . . . . . . . . . . . . . . . . . . . . . . . . .Grade 5Baffle . . . . . .Stainless Steel (2-1/2 (65mm) units only)
Dimensions
NPT Size Weight MODEL in. (mm) A B C D E F G H J K L lbs (kg)
HC-175 11⁄4 & 11⁄2 41⁄2 85⁄16 89⁄16 3 33⁄8 2 45⁄64 13⁄8 18 (32 & 40) (108) (211) (217) (76) (86) (51)
—(17.8) (35)
— —(8)
ALL 2 10 15 151⁄2 65⁄8 43⁄4 31⁄2 108 (50) (254) (381) (394) (168) (121) (89)
— — — — —(49)
ALL 21⁄2 141⁄2 201⁄4 173⁄8 91⁄2 1415⁄16 61⁄4 5 12 15⁄8 41⁄2 7 175 (65) (368) (514) (441) (241) (379) (159) (127) (305) (41) (114) (178) (79)
Maximum Capacity-lbs/hrDifferential - PSIG (barg)
Trap Orifice 1/4 1/2 1 2 5 10 15 20 25 30 40 50 60 75 100 125 150 175Max ∆P (0.017) (0.035) (0.07) (0.14) (0.35) (0.69) (1.0) (1.4) (1.69) (2.1) (2.8) (3.5) (4.2) (5.2) (6.9) (8.6) (10.4) (12.1)
HC-15, 2" .970 6500 8000 9500 10800 15500 20900 24000
HC-15, 21⁄2" 1.875 17000 20000 27000 36000 46000 55000 60000
HC-30, 2" .876 3400 4600 6400 8400 12500 16900 19000 21500 23590 24000
HC-30, 21⁄2" 1.624 14000 17000 20900 25500 33200 40500 45500 49400 52700 55600
HC-75, 2" .858 2550 3150 4300 5450 7600 10400 11400 12500 13500 14250 15600 17150 18600 20500
HC-75, 21⁄2" 1.031 5900 7700 10000 13000 18600 24200 28300 31600 34400 36800 41100 44800 48040 52300
HC-125, 2" .448 2300 2800 3450 4200 5450 6600 7450 8050 8600 8950 10350 11950 13400 15600 18850 21800
HC-125, 21⁄2" .797 4000 5300 6900 9100 13000 17100 20000 22400 24500 26300 29400 32100 34650 37600 42100 46000
HC-175, 11⁄4" .210 260 350 480 640 940 1190 1450 1560 1670 1750 1910 2040 2100 2300 2500 2900 3140 3240
HC-175, 11⁄2" .210 260 350 480 640 940 119 1450 1560 1670 1750 1910 2040 2100 2300 2500 2900 3140 3240
HC-175, 2" .375 2100 2600 3000 3500 4400 4900 5350 5800 6250 6700 7600 8600 9550 11000 13000 14750 16500 18000
HC-175, 21⁄2" .688 2460 3350 4600 6200 9400 12800 15400 17500 19300 21000 23800 26300 28060 31600 35900 39700 43100 46200
DB
A
E
F
C
B
E
D
F
JH
A
Drain
CMAX-FLOSUPER HIGH CAPACITY FLOAT
& THERMOSTATIC STEAMTRAPS
SPECIFICATIONSteam trap shall be of float and thermostatic design.Float shall actuate the valve via a hinged lever andlinkage. Air vent shall be of balanced pressure designwith stainless steel welded encapsulated bellowscapable of discharging air and noncondensable gasescontinuously. Trap shall be cast iron bodied suitable forpressures to 175 PSI and shall be a _______ NPTconnection.
For Kg/Hr Multiply by .454
A
D
F
G GH
B
KL
J
CE
Inlet
Discharge
4-Holes, 17/32" Dia.
Thermostatic Vent
2"
11⁄4"&
11⁄2"
21⁄2"
1/4" Thermostatic Vent - Tobe piped to gravity return line.
40
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
FTE SERIESFLOAT & THERMOSTATIC
STEAM TRAPSPressures to 464 PSIG (32 barg)Temperatures to 850ºF (454ºC)
● High Capacities
● Rugged cast iron, ductile iron or cast steel bodyand cover
● Stainless steel thermostatic element eliminatesair binding
● Stainless steel float and lever mechanism
● Below condensate level seat design preventssteam leakage
● Resistant to water hammer and corrosion
● In-Line repairable
MODELS
CAST IRON BODY
● FTE-10 – To 200 PSIG Threaded Connections● FTE-43 – To 200 PSIG Flanged Connections
DUCTILE IRON BODY
● FTE-14 – To 200 PSIG Threaded Connections
CAST STEEL BODY
● FTE-44 – To 465 PSIG Threaded/Socket Weld Connections● FTE-44F – To 465 PSIG Flanged Connections
During startup, air and non-condensible gasesenter the trap and are automatically ventedthrough an accurate balanced pressure internalthermostatic air vent. As condensate enters thetrap, the float and lever mechanism is raised,
lifting the valve off the seat, discharging the condensate.Condensate will continue to be discharged at the samerate at which it is entering. Any air or non-condensible gasthat may accumulate will be continually and efficientlypassed by the thermostatic air vent.
OPERATION
APPLICATIONS
● Very High Condensate Loads ● Continuous Drainage With High Air Venting
Capacity Requirements● Industrial And Commercial Applications ● Absorption Systems● Air Handling Coils● Heat Exchangers● Dryers Evaporators● Hot water Generators● Rendering Machines● Steam Process Equipment● Air Make-up Coils● Unit Heaters And Cooking Kettles
OPTIONS
● BSPT Threaded connection● S-SLR Orifice on FTE-10● Socket Weld connection on FTE-44● Flanged connections
• ANSI 125/150, 300, 600• DIN 10, 16, 25 or 40• BS10 - F, H, J, K or R
FTE 10 FTE 14
FTE 43 FTE 44
FTE 44F
Installation Tip: Always install STV Test & Block Valve as part of trap stationSEE PAGE 118
Installation Tip:Add Uniflex Pipe Coupling for ease of maintenance on NPT Traps
SEE PAGE 102
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
41
SPECIFICATIONSteam trap shall be of float and thermostatic design. Float shallactuate the valve via a hinged lever and linkage. Air vent shall beof balanced pressure design with stainless steel welded encap-sulated bellows capable of discharging air and noncondensablegases continuously. Trap shall be _______ bodied suitable forpressures to _____ PSI and shall be a _______ connection.
MAXIMUM OPERATING CONDITIONS
CAST IRON/DUCTILE IRONPMO: Max. Operating Pressure see orifice selectionTMO: Max. Operating Temperature saturated at pressure
PMA: Max. Allowable Pressure 232 psig (16 barg)PMA: Max. Allowable Pressure 450ºF (232ºC)
CAST STEELPMO: Max. Operating Pressure see orifice selectionTMO: Max. Operating Temperature saturated at pressure
PMA: Max. Allowable Pressure 465 psig (32 barg)TMA: Max. Allowable Pressure 850ºF (454ºC)
MATERIALS OF CONSTRUCTION
Body & Cover ………………Cast Iron (ASTM A48 CI. 30)…………………………Ductile Iron (DIN 1693 GGG 40)
…………………………Cast Steel (ASTM A216 Gr. WCB)Valve ………………………Stainless Steel 304 (up to 1")
………………………………Stainless Steel 410 (11⁄2", 2") Valve Seat ……………………………Stainless Steel 410Housing & Housing Cover for Float Mechanism ……………………………ASTM A743 Gr. CA 40 (Investment Cast)Float ……………………………………Stainless Steel 304Lever Assembly ………………………Stainless Steel 304Thermostatic Airvent …………………Stainless Steel 304Cover Bolts ………………………………………SAE Gr. 8
Maximum Capacity—lbs/hr (10ºF Below Saturation)
FTE SERIESFLOAT & THERMOSTATIC STEAM TRAPS
Connections: 1/2" – 2" NPT, Flanged or Socket Weld
Max ∆P Differential Pressure-PSIG (barg)
Trap Size OrificeBAR PSI
5 10 20 40 50 65 80 100 125 145 180 200 300 400 465inlet (in.) (.345) (.690) (1.38) (2.76) (3.45) (4.50) (5.52) (6.90) (8.62) (10.0) (12.4) (13.8) 20.7 27.6 32.11/2 0.142 4.5 65 400 520 700 950 1000 1150
FTE-10, 14, & 43 & 0.095 10.0 145 275 380 530 720 800 900 1000 1080 1250 13803/4 0.079 14.0 200 200 290 400 570 640 700 800 900 1020 1100 1240 1300
0.256 4.5 65 1650 2200 3050 4200 5000 5200FTE-10, 14, & 43 1 0.17 10.0 145 870 1250 1650 2350 2600 3000 3200 3500 3900 4100
0.142 14.0 200 640 800 1250 1600 1800 2000 2200 2550 2780 2900 3020 31000.689 4.5 65 4200 6000 8800 12500 13500 15000
FTE-10 & 43 11⁄2 0.571 10.0 145 2800 3900 5600 8000 9000 10000 11500 13000 14200 150000.531 14.0 200 1800 2600 3600 5000 5450 6000 6900 7800 8600 9000 9650 100001.063 4.5 65 13500 19800 28000 40000 45000 50500
FTE-10 & 43 2 0.811 10.0 145 7300 10000 14500 20000 22500 26000 29000 32000 35000 400000.657 14.0 200 3500 5000 6800 9600 10500 12000 13500 15000 16500 17500 19000 20000
0.142 4.5 65 400 520 700 950 1000 11501/2 0.095 10.0 145 275 380 530 720 800 900 1000 1080 1250 1380
FTE-44 & 44F & 0.079 14.0 200 200 290 400 570 640 700 800 900 1020 1100 1240 13003/4 0.07 21.0 300 110 145 200 280 315 350 400 430 480 520 580 610 700
0.063 32.0 465 65 90 120 155 170 200 215 250 280 300 325 345 400 425 4400.256 4.5 65 1650 2200 3050 4200 5000 52000.17 10.0 145 870 1250 1650 2350 2600 3000 3200 3500 3900 4100
FTE-44 & 44F 1 0.142 14.0 200 640 800 1250 1600 1800 2000 2200 2550 2780 2900 3020 31000.114 21.0 300 400 520 700 950 1000 1150 1600 1850 2020 2150 2350 2500 28000.095 32.0 465 275 380 530 720 800 900 1000 1080 1250 1380 1440 1500 1800 2000 20500.689 4.5 65 4200 6000 8800 12500 13500 150000.571 10.0 145 2800 3900 5600 8000 9000 10000 11500 13000 14200 15000
FTE-44 & 44F 11⁄2 0.531 14.0 200 1800 2600 3600 5000 5450 6000 6900 7800 8600 9000 9650 100000.531 21.0 300 1800 2600 3600 5000 5450 6000 6900 7800 8600 9000 9650 10000 130000.531 32.0 465 1800 2600 3600 5000 5450 6000 6900 7800 8600 9000 9650 10000 13000 14300 150001.063 4.5 65 13500 19800 28000 40000 45000 505000.811 10.0 145 7300 10000 14500 20000 22500 26000 29000 32000 35000 40000
FTE-44 & 44F 2 0.657 14.0 200 3500 5000 6800 9600 10500 12000 13500 15000 16500 17500 19000 200000.657 21.0 300 3500 5000 6800 9600 10500 12000 13500 15000 16500 17500 19000 20000 270000.657 32.0 465 3500 5000 6800 9600 10500 12000 13500 15000 16500 17500 19000 20000 27000 29800 31000
For Kg/Hr Multiply by .454
42
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
FTE-10 CAST IRON & FTE-44 CAST STEEL 1"
FTE-10 CAST IRON & FTE-44 CAST STEEL 1/2" & 3/4"
FTE-10 CAST IRON & FTE-44 CAST STEEL 11⁄2" & 2"
FTE-14-DUCTILE IRON 1/2", 3/4" & 1"
SERIES FTE DIMENSIONS
Inches (mm) WeightSizeA B C D lbs. (kg)
1/243⁄4 41⁄4 25⁄8 513⁄16 7.9
(121) (108) (67) (148) (3.6)
3/443⁄4 41⁄4 25⁄8 513⁄16 7.9
(121) (108) (67) (148) (3.6)
1511⁄16 41⁄4 3 69⁄16 10.1(145) (108) (76) (167) (4.6)
SERIES FTE-14
DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
A
B
C
D
E F
A
B
C
D
E F
A
B
C
DE
F
A
B
CD
SERIES FTE-10 & FTE 44DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
Inches (mm) Weight Lbs(kg)Size
A B C D E F FTE-10 FTE-44
1/251⁄16 21⁄8 21⁄8 511⁄16 45⁄16 611⁄16 10.5 11.4(128) (54) (54) (145) (110) (170) (4.8) (5.2)
3/451⁄16 21⁄8 21⁄8 511⁄16 45⁄16 611⁄16 10.5 11(128) (54) (54) (145) (110) (170) (4.8) (5.0)
151⁄16 45⁄16 215⁄16 71⁄2 65⁄16 81⁄2 18.7 17.6(128) (110) (75) (190) (160) (216) (8.5) (8.0)
11⁄2111⁄8 5 45⁄16 10 77⁄8 113⁄8 49.5 48.4(282) (127) (110) (254) (200) (289) (22.5) (22.0)
2121⁄8 51⁄2 5 101⁄4 77⁄8 1113⁄16 61.6 59.4(308) (140) (127) (260) (200) (300) (28.0) (27.0)
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
43
SERIES FTE DIMENSIONS
FTE-43 CAST IRON 1"
FTE-43 CAST IRON 1/2" & 3/4"
FTE-43 CAST IRON 11⁄2" & 2"
FTE-44F CAST STEEL 1"
FTE-44F CAST STEEL 1/2" & 3/4"
FTE-44F CAST STEEL 11⁄2" & 2"
A
B
C
DE
A
B
C
DE
A
B
C
DE
Inches (mm) WeightSize
A B C D E Lbs. (kg)
1/257⁄8 21⁄8 21⁄8 71⁄2 45⁄16 15.4
(150) (54) (54) (190) (110) (7.0)
3/457⁄8 21⁄8 21⁄8 79⁄16 45⁄16 16.5
(150) (54) (54) (192) (110) (7.5)
165⁄16 45⁄16 215⁄16 910⁄16 65⁄16 25.3(160) (110) (75) (245) (160) (11.5)
11⁄291⁄16 5 45⁄16 131⁄8 77⁄8 61.6(230) (127) (110) (333) (200) (28.0)
291⁄16 51⁄2 5 131⁄2 77⁄8 74.8(230) (140) (127) (343) (200) (34.0)
Inches (mm) WeightSize
A B C D E Lbs. (kg)
1/281⁄4 21⁄8 21⁄8 59⁄16 45⁄16 16.5
(210) (54) (54) (141) (110) (7.5)
3/481⁄4 21⁄8 21⁄8 59⁄16 45⁄16 17.6
(210) (54) (54) (141) (110) (8.0)
181⁄4 45⁄16 215⁄16 71⁄2 65⁄16 25.3
(210) (110) (75) (190) (160) (11.5)
11⁄21213⁄16 5 45⁄16 95⁄8 77⁄8 60.5(325) (127) (110) (245) (200) (27.5)
21213⁄16 51⁄2 5 97⁄8 77⁄8 74.8(325) (140) (127) (251) (200) (34.0)
SERIES FTE-43
DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
SERIES FTE-44F
DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
D
D
D
A
A
A
B
B
B
C
C
C
E
E
E
44
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
DURA-FLOINVERTED BUCKET
STEAM TRAPSPressures To 250 PSIG (17.2 barg)
Temperatures to 450°F (232°C)Hardened Stainless Steel Valve and Seat — Long lifeand maximum corrosion resistance.Stainless Steel Bucket — Long lasting, rugged andnaturally resistant to water hammer.Inexpensive — Low maintenance and initial cost.Repairable in-line — All working parts lift out of top oftrap.Cast Iron Body — Durable heavy wall constructionprovides years of reliable service.Suitable for Wide Variety of Loads/Applications —Horizontal and vertical models in thirteen body sizes.Resists Dirt and Scale — Valve and seats positioned attop of traps and internal stainless strainer available onmost horizontal models ensure long service.
MODELS
● 80S–Low capacity horizontal w/integral strainer● 81S–Medium low capacity horizontal w/integral strainer● 82S–Medium capacity horizontal w/integral strainer● 83S–Medium high capacity horizontal w/integral strainer● 84–High capacity horizontal● 85–Super high capacity horizontal● 86–Ultra high capacity horizontal● 21–Medium low capacity vertical● 22–Medium capacity vertical● 23–Medium high capacity vertical● 24–High capacity vertical● 25–Super high capacity vertical● 26–Ultra high capacity vertical
Trap Closed – After trap is installedand primed, steam entering thetrap collects in the top of thebucket, floating the bucket andforcing the valve into its seat.
Trap Begins to Open – Ascondensate begins to flow into thetrap, steam and air are forced fromthe bucket. This causes the bucketto begin losing buoyancy, tendingto pull the valve from its seat.
Trap Discharges – When enoughcondensate has entered the trap,displacing the steam and air, thebucket drops, pulling the valvefrom the seat and allowingcondensate and air to discharge.
Trap Closes – As the flow ofcondensate stops, steam entersthe trap and refloats the bucket,forcing the valve into its seat.The cycle then repeats as morecondensate reaches the trap.
OPERATION
APPLICATIONS
● Steam Lines● Process Equipment● Steam Cookers● Steam Heated Vats● Pressing Machinery● Unit Heaters● Oil Preheaters● Converters● Coils● Rotating Drum
OPTIONS
● Repair KitsCanadian Registration # OE 0591.1C
Installation Tip: Add Uniflex Pipe Coupling for ease ofmaintenance SEE PAGE 102
Installation Tip: Always install STV Test & Block Valve as partof trap station SEE PAGE 118
See page 9
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
45
Connections: 1⁄2" – 21⁄2" NPT
DURA-FLOINVERTED BUCKET
STEAM TRAPSSPECIFICATION
Furnish and install as shown on the plans, inverted buckettraps capable of discharging condensate, air and other non-condensible gases without loss of steam. These traps shall havea heavy cast iron body, hardened stainless steel valve and seat,all stainless steel linkage and bucket, and an asbestos free fibercover gasket.
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating Pressure see orifice selectionTMO: Max. Operating Temperature saturated at pressurePMA: Max. Allowable Pressure 250 psig (17.2 barg)TMA: Max. Allowable Temperature 450°F (232°C)
MATERIALS OF CONSTRUCTION
Body & Cover ……………………Cast Iron ASTM-A-126/A48Bucket & Linkage ………………………………Stainless SteelValve & Seat …………………………Hardened Chrome SteelStandpipe ……………………………………………Steel PipeCover Gasket ……………………………Asbestos Free Fiber
A
DURA-FLO Dimension TableTrap End Inches (mm) Weight
Connections A B C Lbs (kg)80S 1⁄2, 3⁄4 51⁄16 211⁄16 31⁄2 7
(129) (69) (89) (3.2)81S 1⁄2, 3⁄4, 1 51⁄16 211⁄16 47⁄16 8
(129) (69) (113) (3.6)82S 1⁄2, 3⁄4 7 37⁄8 57⁄16 22
(178) (98) (138) (10.0)83S 3⁄4, 1 81⁄8 5 75⁄8 32
(206) (127) (194) (14.5)84 1, 11⁄4 9 53⁄4 713⁄16 47
(229) (146) (199) (21.3)85 11⁄2, 2 101⁄4 8 83⁄8 74
(260) (203) (213) (33.6)86 2, 21⁄2 13 93⁄4 11 140
(330) (248) (279) (63.5)21 1⁄2 63⁄8 41⁄4 — 6.5
(162) (108) (2.9)22 1⁄2, 3⁄4 8 55⁄8 — 16
(203) (143) (7.3)23 3⁄4, 1 101⁄2 67⁄8 — 28
(267) (175) (12.7)24 1, 11⁄4 121⁄2 71⁄2 — 35
(318) (190) (15.9)25 1, 11⁄2 143⁄8 91⁄16 — 60
(365) (230) (27.2)26 11⁄2, 2 1611⁄16 101⁄4 — 90
(424) (260) (40.8)
80 SERIES,HORIZONTAL
20 SERIES,VERTICAL
A
A B
B
C
46
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
DURA-FLO CAPACITY TABLES
Trap Orifice 0.50 1 5 10 15 20 25 30 40 60 70 80 100 125 130 150 180 200 225 250
Size Max ∆P (.034) (.069) (.345) (.690) (1.03) (1.38) (1.72) (2.07) (2.76) (4.14) (4.83) (5.52) (6.90) (8.62) (8.97) (10.3) (12.4) (13.8) (15.5) (17.2)
3/16 20 200 270 450 560 640 690
80S1/8 80 80 110 200 300 360 420 460 500 540 620 660 690
7/64 125 - 55 90 145 195 260 305 345 400 485 525 565 640 680
3/32 150 - - 70 110 150 200 240 270 310 380 410 440 480 540 545 570
1/4 15 300 450 830 950 1060
81S3/16 30 190 300 540 670 770 880 950 1000
&5/32 70 100 165 180 430 495 585 655 710 770 900 950
21 1/8 125 70 130 220 340 390 460 515 560 610 710 760 800 860 950
7/64 200 - 65 150 230 275 335 375 405 455 545 580 610 665 735 780 810 850 860
3/32 250 - - 100 150 190 240 270 290 340 420 450 470 520 575 585 620 670 700 730 760
5/16 15 570 850 1600 1900 2100
82S1/4 30 350 500 950 1380 1630 1800 1900 2050
&3/16 70 250 420 785 950 1120 1260 1395 1500 1700 2000 2200
22 5/32 125 180 300 560 680 800 900 995 1070 1220 1440 1550 1650 1800 2000
1/8 200 100 180 325 465 505 575 650 710 805 980 1050 1105 1225 1375 1410 1500 1560 1600
7/64 250 75 130 240 340 370 420 480 520 590 720 770 810 900 1010 1020 1100 1170 1230 1280 1300
1/2 15 1410 1880 2900 3500 3900
3/8 30 990 1400 2300 2700 3300 3500 3800 4000
83S5/16 60 600 940 1730 2045 2510 2825 2995 3135 3800 4400
& 9/32 80 510 735 1350 1595 1960 2205 2340 2450 2880 3490 3800 400023
1/4 125 385 600 1100 1300 1600 1800 1910 2000 2350 2850 3100 3300 3600 3900
7/32 180 300 490 860 1165 1350 1595 1865 2085 2205 2510 2695 2820 3065 3185 3300 3500 3700
3/16 250 255 400 700 950 1100 1300 1520 1700 1800 2050 2200 2300 2500 2600 2700 2800 3020 3200 3400 3500
5/8 15 2160 2900 4800 5800 6500
1/2 30 1450 2250 3700 4750 5200 6000 6500 6800
843/8 60 1050 1750 2950 3550 4000 4700 5000 5400 5800 6800
& 11/32 80 800 1560 2500 2900 3200 3500 4000 4400 4850 5750 6000 640024
5/16 125 660 1200 1950 2450 2750 3100 3250 3500 4000 4800 5250 5600 6200 6700
9/32 180 550 950 1500 1900 2200 2350 2700 2900 3250 3800 4250 4500 4800 5500 5600 5700 6000
1/4 250 350 580 1000 1250 1450 1800 2000 2200 2600 3150 3350 3500 3800 4300 4450 4700 5000 5300 5500 5700
3/4 15 3100 4160 7600 9000 10000
9/16 30 1800 2900 5200 6400 7700 8500 9200 9800
857/16 60 1400 2200 3800 5000 6000 6600 7100 7600 8300 9500
& 3/8 100 1100 1700 3000 3600 4500 5200 5800 6100 7000 8500 9200 9700 10400
25 11/32 130 900 1500 2600 3200 3900 4500 5000 5400 6200 7500 8050 8500 9600 10900 11000
5/16 180 750 1200 2100 2600 3200 3700 4100 4500 5400 6600 7000 7257 8118 8979 9040.5 9500 10000
9/32 225 600 970 1700 2100 2600 2950 3300 3600 4500 5400 5700 5900 6600 7300 7350 7850 8400 9200 9800
1/4 250 400 700 1200 1500 1900 2100 2400 2600 3200 3800 4000 4150 4600 5100 5150 5500 5950 6350 6650 7000
1-1/16 15 6240 8400 14500 17300 19200
7/8 25 4100 5490 10000 12930 15620 18500 20000
863/4 40 2900 4500 8200 10600 12800 15000 16700 18000 20000
&5/8 60 2100 3500 6900 8700 10600 12100 13300 14250 16300 19800
26 9/16 80 1900 3095 6000 7600 9300 10600 11700 12500 14300 17300 18300 19000
1/2 125 1600 2600 5000 6400 7800 8900 9800 10500 12000 14500 15400 16300 18000 20000
7/16 180 1400 2210 4180 5530 6640 7500 8490 9230 10450 12420 13300 14150 15750 17400 17900 18500 20000
3/8 250 1000 1800 3400 4500 5400 6100 6900 7500 8500 10100 10800 11500 12800 14200 14300 15600 16900 17500 18500 19000
For Kg/Hr Multiply by .454
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
47
DURA-FLO INVERTED BUCKET
STEAM TRAPSPCA REPAIR KITS
FTN SERIES FLOAT & THERMOSTATIC
STEAM TRAPSREPAIR KITS
Quick, easy and economicalSimplifies and standardizes inventoryAll stainless steel corrosion resistant internal partsHardened stainless steel condensate valves and seatsfor extra long life
MODELS
● 80S–Orifice ratings 20, 80, 125, 150● 81S & 21–Orifice ratings 15, 30, 70, 125, 200, 250● 82S & 22–Orifice ratings 15, 30, 70, 125, 200, 250● 83S & 23–Orifice ratings 15, 30, 60, 80, 125, 180, 250● 84 & 24–Orifice ratings 15, 30, 60, 80, 125, 180, 250● 85 & 25–Orifice ratings 15, 30, 60, 100, 130, 180, 225, 250● 86 & 26–Orifice ratings 15, 25, 40, 60, 80, 125, 180, 250
High quality replacement kitsRebuild existing F & T Traps far more economically thanreplacementQuick, easy and economicalSimplifies and standardizes inventoryAll stainless steel corrosion resistant internal partsHardened stainless steel condensate valves and seatsfor extra long lifeRepairs other leading manufacturers’ F & T Traps
MODELS
● FTN-15 available in 3⁄4", 1", 11⁄4", 11⁄2" and 2"● FTN-30 available in 3⁄4", 1", 11⁄4", 11⁄2" and 2"● FTN-75 available in 3⁄4", 1", 11⁄4", 11⁄2" and 2"● FTN-125 available in 3⁄4", 1", 11⁄4", 11⁄2" and 2"
All 3⁄4" and 1" kits as well as 11⁄4" FTN-15 and FTN-30 kitssupplied with cover assembly.
All 11⁄4" FTN-75 and FTN-125 kits as well as all 11⁄2" and 2"kits supplied as mechanism complete.
SEAT RING
VALVE LINKAGE ASS’Y
PIVOT BRACKET
Supplied in a labeled, clear plastic bag.
Consult factory for latest crossover fitments.
CAP SCREWS(2 req’d)
NAMEPLATES(2 req’d)
See Capacity Charts on page 37
48
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
SEALED STAINLESS STEEL
DURA-FLOINVERTED BUCKET STEAM TRAPS
Pressures to 650 PSIG (45 barg)Temperatures to 497ºF (258ºC)
Easy Trap Replacement — Universal two bolt swivelmounting option simplifies removal from system.
Simple Installation — Stainless mounting Block mountspermanently into system. Trap installs via two boltuniversal mount connection.
Hardened Chrome Steel Valve and Seat — Long lifeand maximum corrosion resistance.
Stainless Steel Bucket — Long lasting, rugged andnaturally resistant to water hammer.
Inexpensive — Low maintenance and initial cost.
Stainless Steel Body — Durable heavy wall constructionprovides years of reliable service and resists corrosionand freezing.
Suitable for Wide Variety of Loads/Applications —Horizontal models in three body sizes.
Resists Dirt and Scale — Valve and seats positioned attop of traps ensure long service.
Maintenance Free (TSBT-_S and USBT-_S) — Sealeddesign prevents unnecessary tampering. Trap can beinspected and replaced without breaking pipe.
Freeze Resistant — Extruded SS Body helps preventproblems associated with freezing conditions.
MODELS
NPT CONNECTION
● TSBT-LS – Low Capacity, 200 PSIG● TSBT-MS – Medium Capacity, 340 PSIG● TSBT-HS – High Capacity, 650 PSIG
UMT CONNECTION
● USBT-LS – Low Capacity, 200 PSIG● USBT-MS – Medium Capacity, 340 PSIG● USBT-HS – High Capacity, 650 PSIG
UMT CONNECTOR BLOCKS● UMTC–Standard connector (1/2" & 3/4" only)● UMTCY-RH–Right Hand Connector with Y Strainer● UMTCY-LH–Left Hand connector with Y Strainer● UMTVS-BB–Connector with Isolation Valves, Strainer,
Blowdown Valve and Test Port
APPLICATIONS
● Steam Lines● Process Equipment● Steam Cookers● Steam Heated Vats● Pressing Machinery● Unit Heaters● Oil Preheaters● Converters● Coils● Rotating Drum
Canadian Registration #: OE10389.52
After trap is installed and primed, steam enter-ing the trap collects in the top of the bucket,floating the bucket and forcing the valve into itsseat. As condensate begins to flow into the trap,steam and air are forced from the bucket. Thiscauses the bucket to begin losing buoyancy,tending to pull the valve from its seat. When
OPERATION
enough condensate has entered the trap, displacing thesteam and air, the bucket drops, pulling the valve fromthe seat and allowing condensate and air to discharge.As the flow of condensate stops, steam enters the trapand re-floats the bucket, forcing the valve into its seat.The cycle then repeats as more condensate reaches thetrap.
For information on Big Block UMTVS-BB ConnectorSEE PAGE 116
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
49
Connections: 3/8" – 1" NPT
A
B
C
D
TSBT SEALED SERIES
Differential Pressure
TrapOrifice
5 10 15 30 40 70 80 125 200 250 300 400 650Size MOP (0.34) (0.69) (1.03) (2.07) (2.76) (4.83) (5.52) (8.62) (13.79) (17.24) (20.69) (27.59) (44.83)
SBT-LS & TSBT-LS 3/32 200 85 120 145 200 230 300 325 400 5001/4 15 800 920 10403/16 30 540 690 800 1000
USBT-MS 5/32 70 390 490 560 700 790 940& 1/8 125 260 325 400 530 600 750 800 970
TSBT-MS 7/64 200 200 265 315 410 470 580 610 720 9003/32 250 155 200 240 315 360 440 480 560 690 7505/64 400 100 130 155 210 235 280 310 360 440 460 510 580*1/4 40 1040 1350 1580 2000 2350
USBT-HS 3/16 80 680 930 1120 1550 1775 2400 2300& 1/8 250 320 42 510 700 790 1020 1090 1300 1650 1800
TSBT-HS 7/64 300 220 280 325 430 500 630 685 800 1000 1100 12003/32 650 175 225 270 370 400 510 540 650 800 870 930 1050 1300
For Kg/Hr Multiply by .454
Maximum Capacity—(lbs/hr)
Inches (mm) WeightModelA B C D lbs(kg)
TSBT-LS23⁄4 59⁄16 45⁄16 49⁄16 2.25(70) (142) (110) (116) (1)
TSBT-MS23⁄4 69⁄16 45⁄16 59⁄16 2.5(70) (167) (110) (141) (1.1)
TSBT-HS37⁄8 89⁄16 5 73⁄8 7(99) (218) (127) (187) (3.2)
DIMENSIONS inches (mm)AND WEIGHTS pounds (kg)
SEALEDSTAINLESS STEEL
DURA-FLOINVERTED BUCKET STEAM TRAPS
SPECIFICATIONFurnish and install as shown on the plans, inverted bucket trapscapable of discharging condensate, air and other non-condensablegases without loss of steam. These traps shall have a stainlesssteel sealed body, hardened chrome steel valve and seat and an allstainless steel linkage and bucket. It shall have a universal mountconnector option.
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating Pressure See Orifice SelectionTMO: Max. Operating Temperature Saturated at PMO
PMA: Max. Allowable Pressure -LS 200 psig (13.8 barg) at 450ºF (232ºC) MS 307 psig (21.2 barg) at 450ºF (232ºC)HS 650 psig (44.8 barg) at 497ºF (258ºC)
TMA: Max. Allowable Temperature - MS, LS & HS - 800ºF (425ºC)
MATERIALS OF CONSTRUCTION
Body ……………………………………………AISI 304 SSBucket …………………………………………AISI 304 SSBucket Clip………………………………………AISI 304 SSLever ……………………………………………AISI 304 SSInlet Tube ………………………………………AISI 304 SSValve………………………Hardened Chrome Steel AISI D3Valve Seat ………………Hardened Chrome Steel AISI D3Connector ………………………………………AISI 304 SS
B
D
A
E
C
B
C
D
E
USBT SEALED SERIESA
Connections: Universal Mount Two Bolt Swivel Connection
Inches (mm) WeightModel
A B C D E lbs(kg)
USBT- 23⁄4 6 23⁄4 45⁄8 4 4.25LS (70) (152) (70) (117) (101.6) (2)
USBT- 23⁄4 73⁄16 23⁄4 513⁄16 4 4.75MS (70) (183) (70) (148) (101.6) (2.2)
USBT- 37⁄8 83⁄4 23⁄4 73⁄8 5 7HS (99) (222) (70) (187) (127) (3.2)
DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
* CRN not available
50
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
REPAIRABLESTAINLESS STEEL
DURA-FLOINVERTED BUCKET STEAM TRAPS
Pressures to 650 PSIG (45 barg)Temperatures to 497ºF (258ºC)
Easy Trap Replacement — Universal two bolt swivelmounting option simplifies removal from system.
Simple Installation — Stainless mounting Block mountspermanently into system. Trap installs via two bolt universalmount connection.
Hardened Chrome Steel Valve and Seat — Long life andmaximum corrosion resistance.
Stainless Steel Bucket — Long lasting, rugged and naturallyresistant to water hammer.
Inexpensive — Low maintenance and initial cost.
Stainless Steel Body — Durable heavy wall constructionprovides years of reliable service and resists corrosion andfreezing.
Suitable for Wide Variety of Loads/Applications —Horizontal models in three body sizes.
Resists Dirt and Scale — Valve and seats positioned at topof traps ensure long service.
Repairable Model (TSBT-_R & USBT-_R) — Removablecover allows pressure change or repair with existing Dura-FloPCA kits.
MODELS
NPT CONNECTION, REPAIRABLE● TSBT-LR – Low Capacity, 200 PSIG● TSBT-MR – Medium Capacity, 400 PSIG● TSBT-HR – High Capacity, 650 PSIG
UMT CONNECTION, REPAIRABLE
● USBT-LR – Low Capacity, 200 PSIG● USBT-MR – Medium Capacity, 400 PSIG● USBT-HR – High Capacity, 650 PSIG
UMT CONNECTOR BLOCKS
● UMTC–Standard connector (1/2" & 3/4" only)● UMTCY-RH–Right Hand Connector w/Y strainer*● UMTCY-LH–Left Hand Connector w/Y strainer*● UMTVS-BB–Connector with Isolation Valves, Strainer,
Blowdown Valve and Test Port
APPLICATIONS
● Steam Lines● Process Equipment● Steam Cookers● Steam Heated Vats● Pressing Machinery● Unit Heaters● Oil Preheaters● Converters● Coils● Rotating Drum
Canadian Registration # OE10389.52
After trap is installed and primed, steam entering thetrap collects in the top of the bucket, floating thebucket and forcing the valve into its seat. Ascondensate begins to flow into the trap, steam andair are forced from the bucket. This causes thebucket to begin losing buoyancy, tending to pull thevalve from its seat. When enough condensate has
OPERATION
entered the trap, displacing the steam and air, the bucketdrops, pulling the valve from the seat and allowingcondensate and air to discharge. As the flow ofcondensate stops, steam enters the trap and re-floatsthe bucket, forcing the valve into its seat. The cycle thenrepeats as more condensate reaches the trap.
For information on Big Block UMTVS-BB ConnectorSEE PAGE 116
845.778.5566 ● Fax: 845.778.7123 ● www.nicholsonsteamtrap.com
51
REPAIRABLESTAINLESS STEEL
DURA-FLOINVERTED BUCKET STEAM TRAPS
SPECIFICATIONFurnish and install as shown on the plans, inverted bucket trapscapable of discharging condensate, air and other non-conden-sable gases without loss of steam. These traps shall have a stain-less steel sealed body, hardened chrome steel valve and seat andan all stainless steel linkage and bucket. It shall also have a univer-sal mount connection option. The repairable traps shall have aremovable cover to allow repair or orifice change.
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating Pressure See Orifice SelectionTMO: Max. Operating Temperature Saturated at PMO
PMA: Max. Allowable Pressure -LR 200 psig (13.8 barg) at 450ºF (232ºC) MR 420 psig (29.0 barg) at 450ºF (232ºC)HR 650 psig (44.8 barg) at 497ºF (258ºC)
TMA: Max. Allowable Temperature 800ºF (425ºC)
MATERIALS OF CONSTRUCTION
Body ………………………………………ASTM A351 CF8Cover ………………………………………ASTM A351 CF8Bucket……………………………………………AISI 304 SSBucket Clip………………………………………AISI 304 SSLever ……………………………………………AISI 304 SSInlet Tube ………………………………………AISI 304 SSValve ……………………Hardened Chrome Steel AISI D3Valve Seat ………………Hardened Chrome Steel AISI D3Swivel Connector ………………………………AISI 304 SSCover Gasket ………………Spiral Wound 304 SS wIth Grafoil
For Kg/Hr Multiply by .454
A
B
C
D
E
Differential Pressure
TrapOrifice
5 10 15 30 40 70 80 125 200 250 300 400 650
Size MOP (0.34) (0.69) (1.03) (2.07) (2.76) (4.83) (5.52) (8.62) (13.79) (17.24) (20.69) (27.59) (44.83)
TSBT-LR, USBT-LR 3/32 200 85 120 145 200 230 300 325 400 500
1/4 15 800 920 1040
3/16 30 540 690 800 1000
TSBT-MR, 5/32 70 390 490 560 700 790 940USBT-MR 1/8 125 260 325 400 530 600 750 800 970
7/64 200 200 265 315 410 470 580 610 720 900
3/32 250 155 200 240 315 360 440 480 560 690 750
5/64 400 100 130 155 210 235 280 310 360 440 460 510 580
1/4 40 1040 1350 1580 2000 2350
3/16 80 680 930 1120 1550 1775 2400 2300TSBT - HR
1/8 250 320 42 510 700 790 1020 1090 1300 1650 1800USBT-HR7/64 300 220 280 325 430 500 630 685 800 1000 1100 1200
3/32 650 175 225 270 370 400 510 540 650 800 870 930 1050 1300
Maximum Capacity—(lbs/hr)
USBT REPAIRABLE SERIES
Inches (mm) WeightModelA B C D E lbs(kg)
USBT- 27⁄8 63⁄8 23⁄4 55⁄8 41⁄4 7.25LR (73) (161) (70) (143) (108) (3.3)
USBT- 27⁄8 73⁄8 23⁄4 65⁄8 41⁄4 8MR (73) (186) (70) (168) (108) (3.6)
USBT- 41⁄8 93⁄4 23⁄4 83⁄4 61⁄4 25HR (104.8) (247.7) (70) (222.3) (158.8) (11.33)
DIMENSIONS inches (mm) AND WEIGHTS pounds (kg)
Inches (mm) WeightModelA B C D lbs(kg)
TSBT-LR27⁄8 61⁄4 45⁄16 59⁄16 6.6(73) (159) (110) (141) (3.0)
TSBT-MR27⁄8 71⁄4 45⁄16 69⁄16 7.2(73) (184) (110) (166) (3.2)
TSBT-HR41⁄8 91⁄2 5 81⁄2 22
(104.8) (241.3) (127) (215.9) (10)
DIMENSIONS inches (mm)AND WEIGHTS pounds (kg)
A
B
C
D
TSBT REPAIRABLE SERIES
Connections: 3/8" – 1" NPT
Connections: Universal Mount Two Bolt Swivel Connection
NTD
600
SER
IES
THER
MO
-AC
TIVE
TR
AP
- 334 -
Installation Tip: Always install STV Test & Block Valve as part of trap stationSEE PAGE 354
Installation Tip: Add Uniflex Pipe Coupling for ease of maintenanceSEE PAGE 374
Incoming air and condensate flow through thetrap body and into the control chamber. Linepressure raises the disc off the seat allowingcomplete discharge. When flashing condensateenters the cartridge, flow velocity increases,creating low pressure underneath the disc.Flashing condensate at high velocity strikes theinside wall of the disc chamber and is deflected
to the top of the disc causing a pressure buildup. The discis forced down onto the seat by this pressure imbalance.The trap remains closed as flashed vapor in the controlchamber keeps the disc seated. Pressure inside the cap isnot lowered until the trapped flash vapor condenses due tobody radiation. Condensing steam lowers the pressureabove the disc. Disc is then lifted and the cycle repeated.
NTD600 SERIESTHERMODYNAMIC
STEAM TRAPSPressures To 600 PSIG (41.3 barg)
Temperatures to 800°F (426°C)Compact Design — Hardened stainless steel disc is theonly moving part.
Inexpensive — Low initial cost is less expensive thanrepairable technologies.
Simplifies Installation — Works in any position.
Rugged — Handles water hammer and superheat.
Reliable, Efficient Operation — Blast discharge helps toeliminate dirt buildup and provides tight shutoff
Freeze resistant — Self draining design prevents freezing.
All Stainless Steel Construction — Resists both internaland external corrosion.
Easy to Monitor — Audible discharge cycle makeschecking operation simple.
MODELS
● NTD600–Thermodynamic Disc Trap● NTD600S–NTD600 with integral strainer● NTD600B–NTD600S with blowdown valve
APPLICATIONS
● Steam Tracing● Drips● Heating
NTD600 Model Only:Canadian Registration # OE0591.9C
OPERATION
Connections: 3⁄8" – 1" NPT
Steam trap shall be of thermodynamic design. Body shall be of allstainless construction and hardened throughout. Seat shall beintegral to body. Cover shall seal to body without gaskets or seals.Trap shall be suitable for pressures through 600 psi and available in3/8" through 1".
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating Pressure 600 psig (41.3 barg)TMO: Max. Operating Temperature 800°F (426°C)PMA: Max. Allowable Pressure 600 psig (41.3 barg)TMA: Max. Allowable Temperature 800°F (426°F)
MATERIALS OF CONSTRUCTION
Body ……………………………420F SS ASTM A743 CA40FCap & Disc ………………………………416 SS ASTM A582Blow Down Valve …………………………………304/316SSScreen …………………………………………Stainless Steel
NTD600 SERIESTHERMODYNAMIC
STEAM TRAPSSPECIFICATION
C
B
A
Maximum Capacity—lbs/hr 10°F Below Saturation Differential PSIG (barg)
NPT 3.5 5 10 20 30 50 75 100 150 200 300 400 500 600Connection (0.24) (0.34) (0.7) (1.4) (2.1) (3.4) (5.2) (6.9) (10.3) (13.8) (20.7) (27.6) (34.5) (41.3)
3/8" 180 185 190 200 215 245 305 370 500 610 790 960 1100 1250
1/2" 300 310 345 410 465 575 700 810 1000 1140 1410 1630 1830 2000
3/4" 405 420 470 560 640 810 1000 1160 1450 1670 2100 2430 2750 3050
1" 640 670 725 865 980 1200 1470 1750 2200 2600 3250 3780 4250 4700
Dimensions in inches (mm) Weightin Lbs.
(kg)Size A B C3/8" 2 13/4 13/4 .8
(51) (44) (44) (.36)1/2" 211/16 13/4 2 1.2
(68) (44) (51) (.55)3/4" 213/16 25/16 27/16 1.85
(71) (59) (62) (.86)
1" 35/16 21/2 27/8 3.1
(84) (64) (73) (1.8)
For Kg/Hr Multiply by .454
- 335 -
NTD
600
SER
IES
THER
MO
-AC
TIVE
TR
AP
NOTE: The NTD600 Series works efficiently at all line pressures between 5+600 psi and back pressures up to 80% of line pressures.
- 336 -
LIQ
UID
ATO
R 4
50TH
ERM
OST
ATIC
TR
AP
Thermal actuator is filled at its free length witha liquid having a lower boiling point than water.On start-up, valve is normally open. Whensteam enters trap, thermal actuator fillvaporizes to a pressure higher than linepressure. This forces valve into seat orifice toprevent any further flow. As condensatecollects, it takes heat from thermal actuator,
lowering internal pressure. Line pressure will then compressthermal actuator to open valve and discharge condensate.Valve opening automatically adjusts to load conditions fromminimum on very light loads to full lift at maximum load.Restricted orifice in UMT451T (small opening at bottom ofvalve seat) prevents trap from discharging continuously onlight loads such as are encountered on tracer lines.
LIQUIDATOR 450 SERIESUNIVERSAL MOUNT THERMOSTATIC
STEAM TRAPSPressures to 450 PSIG (31 barg)Temperatures to 600°F (316°C)
Easily Maintained — Universal two bolt swivel mountingsimplifies removal from system. Kits allow flexibility toreplace or rebuild.Simple Installation — Stainless mounting block mountspermanently into system. Trap installs via two bolt universalconnection.Improved Energy Savings — High efficiency–maximumelimination of air and non-condensibles.Temperature Sensitive Actuators — One moving part.Stainless Steel, fail open, welded actuator for maximumcorrosion, thermal and hydraulic shock resistance.Hardened Stainless Steel Valve and Seat — Long life.Lapped as a matched set for water tight seal.Easily Maintained — Can be inspected and servicedwithout breaking pipe connections.Freeze Proof — Self draining when installed vertically.For Superheated Steam Applications — Because thetrap closes at saturated steam temperature, superheatedsteam cannot reach trap.
Air Vent — Efficient steam service air vent when equippedwith ISO filled Actuator and installed in air vent location.Guaranteed — Traps are guaranteed against defects inmaterials or workmanship for three years.Positive Shutoff and Long Life — Integral Stainless SteelStrainer helps prevent debris depositing on valve and seat.
MODELS
● UMT-TD10L–Low Capacity Trap● UMT-TD10–Standard Capacity Trap● UMTC–Standard connector (1/2" & 3/4" only)● UMTCY-RH–Right Hand Connector w/Y strainer*● UMTCY-LH–Left Hand Connector w/Y strainer*● UMTVS-BB–Connector with Isolation Valves, Strainer,
Blowdown Valve and Test Port For complete unit, order trap and connector as separate items.
*Add (-B) for Blowdown Valve.
APPLICATIONS
● Unit Heaters● Steam Tracing● Drip Legs● Tire Presses● Cooking Equipment● Laundry Equipment● Plating Tanks● Platen Presses● Air Vents
OPTIONS
● SLR - SLR Orifice*● ISO - ISO Filled Actuator*● SW - Socketweld● B - Blowdown Valve
*Not available on UMT451T
Canadian Registration # OE1388.6C
UMT SERIES TRAP AND UMTC CONNECTOR
OPERATING PRINCIPLE
For information on Big Block UMTVS-BB ConnectorSee Page 344
Connections: 1/2", 3/4" or 1" NPT or socketweld
SPECIFICATIONSSteam trap shall be of balanced pressure design with stainless steelwelded actuator capable of discharging condensate within 10°F ofsaturated temperature. Where greater sensitivity is required, SLRorifice and Sterilizer trim will be available to allow condensateevacuation at or near saturated temperatures. Where subcooling ofcondensate is desired alternate thermostatic actuator will be availableto allow condensate evacuation at or near 40°F below saturatedtemperatures. Thermostatic actuator shall employ a conical valvelapped in matched sets with the seat ring assuring tight shut off. Aminimum of two orifice sizes shall be available allowing for customcapacity sizing. Trap shall be stainless steel bodied suitable forpressures through 450 psig. Trap connection shall be two boltuniversal swivel mount. Mounting block shall be stainless steel andavailable in 1⁄2" through 1" NPT or socket weld.
MAXIMUM OPERATING CONDITIONS
Traps with Welded Stainless ActuatorPMO: Max. Operating Pressure 450 psig (31 barg)TMO: Max. Operating Temperature 600°F (316°C)Traps with Welded Stainless Actuator, ISOPMO: Max. Operating Pressure 450 psig (31 barg)TMO: Max. Operating Temperature 600°F (316°C)All TrapsPMA: Max. Allowable Pressure 450 psig (31 barg)TMA: Max. Allowable Temperature 750°F (399°C)
MATERIALS OF CONSTRUCTION
Body & Cover …………………ASTM A351 Grade CF8 (304)Cover Gasket . . . . . . . . . . . . . .304 stainless spiral wound
w/graphite fillActuator ……………………………………………Welded SS Strainer………………………….033 perf. 304 Stainless SteelValve & Seat …………………Hardened 416 Stainless SteelMounting Block ………………ASTM A351 Grade CF8 (304)
LIQUIDATOR 450 SERIESUNIVERSAL MOUNT THERMOSTATIC
STEAM TRAPS
Maximum Capacity—lbs/hr 10°F Below Saturation (Kg/hr 5°C Below Saturation)
TrapOrifice Differential PSIG (barg)Inch 5 10 20 50 100 125 150 200 250 300† 350 400 450(mm) (0.34) (0.7) (1.4) (3.4) (6.7) (8.4) (10.1) (13.4) (16.8) (20.1) (24.1) (27.6) (31.0)
UMT451T 5/64 84 119 168 265 348 375 398 439 472 502 529 553 575(2) (38) (54) (76) (120) (158) (170) (181) (199) (214) (228) (240) (251) (261)
UMT452T 1/8 216 265 375 592 778 838 890 980 1055 1121 1180 1235 1284(3) (98) (120) (170) (269) (354) (381) (405) (445) (480) (510) (536) (561) (584)
UMT453T 1/4 550 825 1210 1975 2825 3140 3425 3650 3960 4100 4230 4420 4600(6) (249) (374) (549) (896) (1281) (1424) (1554) (1656) (1796) (1860) (1919) (2005) (2086)
DIMENSIONS - INCHES (MM)WEIGHT
TRAP - 3.2 LBS. (1.4 KG)STD. MOUNTING BLOCK - 1.1 LBS. (0.5 KG)
Y STRAINER MOUNTING BLOCK - 2.3 LBS. (1.0 KG)
4.8(122)
2.6 sq.(66 sq.)
.75 (19)
2.81 (71)
UMT SERIESTRAP AND
UMTCCONNECTOR
ISO filled Actuator recommended for superheated steam.
UMTCYR
UMTCYL
3.5(8.89)
3.44(8.74)
1.25(3.18)
5(12.7)
3.5(8.89)
3.44(8.74)
1.25(3.18)
5(12.7)
- 337 -
LIQ
UID
ATO
R 4
50TH
ERM
OST
ATIC
TR
AP
- 338 -
LIQ
UID
ATO
R U
MT-
TDTH
ERM
ODY
NAM
IC T
RAP
Incoming air and condensate flow through thetrap body and into the Celtron® cartridge. Linepressure raises the disc off the seat allowingcomplete discharge. When flashing condensateenters the cartridge, flow velocity increases,creating low pressure underneath the disc.Flashing condensate at high velocity strikes theinside wall of the disc chamber and is
deflected to the top of the disc causing a pressure buildup.The disc is forced down onto the seat by this pressureimbalance. The trap remains closed as steam in the jacketprevents exposure of the Celtron® cartridge to ambienttemperatures. Pressure inside the cap is not lowered untilthe trapped flash vapor condenses. Condensing steamlowers the pressure above the disc. Disc is then lifted andthe cycle repeated.
LIQUIDATOR UMT-TDUNIVERSAL MOUNT
THERMODYNAMIC STEAM TRAPS
Pressures To 450 PSIG (31 barg)Temperatures to 750°F (400°C)
Easily Maintained — Universal two bolt swivel mountingsimplifies removal from system. Kits allow flexibility toreplace or rebuild.Simple Installation — Stainless mounting block mountspermanently into system. Trap installs via two bolt universalconnection.Improved Energy Savings — Lowers steam waste due tosteam jacketing. Trap cycle is unaffected by ambienttemperatures or precipitation.Extended Trap Life — Integral strainer keeps disc andseat clean. Non-violent discharge reduces wear. Heavy discprevents warpage and improves performance.Easily Maintained — Completely renewable withoutdisturbing piping connections by removing cover,unscrewing and replacing Celtron® cartridge. Celtron®replacement cartridges are packaged individually withcover and gaskets in a protective bag.Freeze Proof — When mounted vertically or on its sidehorizontally.Multi-functional — Integral check valve eliminates needfor additional fittings.Economical — First cost and maintenance cost are low.
MODELS
● UMT-TD10L–Low Capacity Trap● UMT-TD10–Standard Capacity Trap● UMTC–Standard connector (1/2" & 3/4" only)● UMTCY–Connector w/Y strainer ● UMTCYR–Right Hand Connector w/Y strainer ● UMTCYL–Left Hand Connector w/Y strainer● UMTVS-BB–Connector with Isolation Valves, Strainer,
Blowdown Valve and Test Port For complete unit, order trap and connector as separate items.
APPLICATIONS
● Steam Tracing● Drips● Light Process
OPTIONS
● SW - Socketweld Connections● B - Blowdown Valve
Celtron®
plastic-packedreplaceable cartridgefor fast and simplereplacement
UMT-TD SERIES TRAP AND UMTC CONNECTOR
For information on Big Block UMTVS-BB ConnectorSee Page 344
OPERATION
SPECIFICATIONSteam trap shall be of a thermodynamic capsule design. The bodyshall be of a 304 stainless steel 2 bolt universal swivel construction witha stainless steel in line renewable Celtron capsule. Celtron capsule shallcontain all working components. Capsule shall be hardenedthroughout. Seat shall be stress relieved to eliminate warping. Trapshall seal to body with spiral wound graphite gaskets. Trap shall besuitable for pressures through 450 psi and available in 1/2" through 1"NPT or socketweld connections.
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating Pressure 450 psig (31 barg)TMO Max. Operating Temperature 750°F (400°C)PMA: Max. Allowable Pressure 450 psig (31 barg)TMA: Max. Allowable Temperature 750°F (400°C)
MATERIALS OF CONSTRUCTION
Body & Cover: . . . . . . . . . . . . .ASTM A351 Grade CF8 (304)Cover Gasket: . . . . . . . . . . . . . . .304 stainless spiral wound
w/graphite fillCeltron® Cartridge: . . . . . . .416 Stainless Steel w/hardened
disc & seatStrainer: . . . . . . . . . . . . . . . . ..033 perf. 304 Stainless SteelMounting Block: . . . . . . . . . . .ASTM A351 Grade CF8 (304)
LIQUIDATOR UMT-TDUNIVERSAL MOUNT
THERMODYNAMIC STEAM TRAPS
Maximum Capacity—lbs/hr 10°F Below Saturation Differential – PSIG (barg)
Trap 5 10 25 50 75 100 200 300 400 450(0.34) (0.7) (1.7) (3.4) (5.2) (6.9) (13.8) (20.7) (27.6) (31)
UMT-TD10L 105 150 235 330 395 435 550 630 690 715UMT-TD10 240 265 420 590 700 770 980 1120 1240 1280
For Kg/Hr Multiply by .454
The UMT-TD Series trap works efficiently at all line pressures between 5 and 450 psi and back pressures to 80% of line pressure.
Connections: 1/2", 3/4" or 1" NPT or socketweld
DIMENSIONS - INCHES (MM)WEIGHT
TRAP - 3.2 LBS. (1.4 KG)STD. MOUNTING BLOCK - 1.1 LBS. (0.5 KG)
Y STRAINER MOUNTING BLOCK - 2.3 LBS. (1.0 KG)
4.8(122)
2.6 sq.(66 sq.)
.75 (19)
2.81 (71)
UMT-TDSERIES TRAP
AND UMTCCONNECTOR
UMTCYR
UMTCYL
3.5(8.89)
3.44(8.74)
1.25(3.18)
5(12.7)
3.5(8.89)
3.44(8.74)
1.25(3.18)
5(12.7)
- 339 -
LIQ
UID
ATO
R U
MT-
TDTH
ERM
ODY
NAM
IC T
RAP
DS2
00 S
ERIE
STH
ERM
OST
ATIC
TR
AP
- 340 -
Thermal actuator is filled at its free length with aliquid having a lower boiling point than water. Onstart-up, valve is normally open to discharge air,non-condensibles and condensate. When steamenters trap, thermal actuator fill vaporizes to a pres-sure higher than line pressure. This forces valve into
seat orifice to prevent any further flow. As condensatecollects, it takes heat from thermal actuator, loweringinternal pressure. Line pressure will then compress thermalactuator to open valve and discharge condensate. Valveopening automatically adjusts to load conditions fromminimum on very light loads to full lift at maximum load.
DS200 SERIESTHERMOSTATIC STEAM TRAPS
Pressures To 100 PSIG (6.9 barg)Temperatures to 338°F (170°C)
Stainless Steel Body—Body materials are Type 316LStainless Steel.Self Centering Valve—Leak tight shut off. Assembly ofactuator and valve to impingement plate allows valve toself-align with center of valve seat orifice. Provides longlasting valve and seat.Temperature Sensitive Actuator—One moving part.Inconel welded actuator for maximum corrosion, thermaland hydraulic shock resistance.Thermal and Hydraulic Shock Resistant—Impingementplate plus welded construction prevents damage to actuator.Valve and Seat—Long life, stainless steel valve and seatlapped and matched together for water tight seal.Maintenance—All models are sealed and maintenance free.Three Year Guarantee—Trap guaranteed for three yearsagainst defects in material or workmanship.Additional Features—Best air handling capability for faststart up and operation. Fastest response to condensateload or temperature changes. Broad application range.Selection of orifice and pipe sizes meet majority ofcondensate removal demands in deionized steam systems.Unique SLR Orifice Option—Provides drainage at satur-ated temperatures, instant reaction to load changes andguaranteed fail-open operation for extra critical operations.
MODELS
● DS202–Low capacity● DS203–Medium capacity● DS204–High capacity
APPLICATIONS
● Drainage of Steam Filters and Separators● Culinary Steam● WFI System Sterilization● Main Drips● Sterilizer Drainage and Air Venting
OPTIONS
● SLR - SLR Orifice
Canadian Registration # OE0591.9C
OPERATION
Connections: 3/8" – 1" NPT or Socketweld
Steam trap shall be of balanced pressure design with inconel weldedbellows capable of releasing condensate within 10°F of saturatedpressure. Where drainage at saturated temperatures is required, trapshall have SLR orifice. All other components shall be of 316 or 316Lstainless steel. Trap shall be self draining and normally open.
MAXIMUM OPERATING CONDITIONS
PMO: Max. Operating Pressure 100 psig (6.9 barg)TMO: Max. Operating Temperature 338°F (170°C)PMA: Max. Allowable Pressure 150 psig (10.3 barg)TMA: Max. Allowable Temperature 366°F (186°C)
MATERIALS OF CONSTRUCTION
Body ……………………… ASTM 743 CF-8M Stainless SteelWelded Actuator ………………………316L Fittings & PlatesValve & Seat ………………………………316L Stainless Steel
SLR ORIFICE OPTIONSpecify when immediate elimination of condensate and improvedsensitivity is desired. A 1/32" orifice at the apex of the valve allows forcontinuous discharge of condensate. Trap will nominally pass 50lbs/hr of condensate at 50 psi within 2°F of saturated temperature.
DS200 SERIESTHERMOSTATIC STEAM TRAPS
SPECIFICATION
B
A
Maximum Capacity—lbs/hr 10°F Below Saturation (Kg/hr 5°C Below Saturation)
TrapOrifice Differential PSIG (bar)
Inch 5 10 20 50 100 125 150 200 250 300 350 400 450 500(mm) (0.34) (0.7) (1.4) (3.5) (6.9) (8.6) (10.3) (13.8) (17.2) (20.7) (24.1) (27.6) (31.0) (34.5)
DS202 1/8 216 265 375 592 778 838 890 980 1055 1121 1180 1235 1284 1323(3) (98) (120) (170) (269) (354) (381) (405) (445) (480) (510) (536) (561) (584) (601)
DS2031/4 550 825 1210 1975 2825 3140 3425 3650 3960 4100 4230 4420 4600 4760(6) (249) (374) (549) (896) (1281) (1424) (1554) (1656) (1796) (1860) (1919) (2005) (2086) (2161)
DS2045/16 860 1220 1725 2725 3575 3850 4090 4505 4850 5155 5425 5675 5900 6110(8) (390) (554) (783) (1237) (1623) (1748) (1857) (2045) (2202) (2340) (2463) (2576) (2679) (2774)
DimensionsNPT or inches WeightSocket (mm) Lbs.weld A B (kg)
3/8", 1/2"33/4 13/4 1.1(95) (44) (0.5)
3/4" 315/16 13/4 1.2(100) (44) (0.54)
1" 43/8 13/4 1.6(111) (44) (0.73)
B
A
3/8" - 3/4" BODY
1" BODY
- 341 -
DS2
00 S
ERIE
STH
ERM
OST
ATIC
TR
AP
TRAPS &SPECIALTIES
SIZING
- 357 -
TRA
PS
&
SPEC
IALT
IES
SIZI
NG
- 358 -
BA
SIC
S O
F ST
EAM
TR
AP
SBASICS OF STEAM TRAPS
WHY DO WE NEED STEAM TRAPS?
In order to operate economically andefficiently, all steam systems must beprotected against 3 factors:
* CONDENSATE
* AIR
* NON-CONDENSIBLES
Condensate is formed in a systemwhenever steam gives up its useableheat. And, since condensate interfereswith the efficiency of the operation of asteam system, it must be removed.
Air, one of natures finest insulators,when mixed with steam, will lower itstemperature and hinder the the overalleffectiveness of an entire system. Forexample: A film of air 1/1000th of aninch thick offers as much resistance toheat transfer as 13" of copper or 3” ofsteel. For that reason, air MUST becontinuously bled from a system bysteam traps to have it operateefficiently and to conserve energy.
Non-condensibles, such as carbondioxide promote corrosion and otherdeterioration of equipment and inhibittheir function.
WHAT IS A STEAM TRAP?
A steam trap is basically an automaticvalve which discharges condensate,undesirable air and non-condensiblesfrom a system while trapping, or holdingin, steam. They fall into 4 major cate-gories; Thermostatic, Mechanical,Thermodynamic and Drain Orifice.Each type will be discussed in detail inthis section.
In every steam system, there are fourphases of operation in which traps playa vital role:
1) Start-up – During “start-up”, when thesystem is initially activated, air andnon-condensibles must be discharged.
2) Heat-up – During “heat-up”, as thesystem works to achieve the desiredtemperature and pressure, condensateis discharged.
3) At Temperature – “At temperature”,when the desired levels are reached,the valve must close to retain thesteam.
4) Using Heat – At the “using heat”level, the valve's job is to stay closedunless and until condensate occurs;then the valve must open, dischargethe condensate and close quickly andpositively, without allowing valuablesteam to escape.
WHAT ARE THE QUALITIES OF AGOOD STEAM TRAP?A good steam trap should:
● Discharge condensate, air andnon-condensibles.
● Be equal to the load over a widerange of pressures andtemperatures.
● Be freeze-proof wherenecessary.
● Be simple and rugged.● Have few moving parts.● Require low maintenance and
spare parts inventory.● Have a long life.
A good steam trap should not:● Discharge live steam.● Fail or malfunction if pressure
changes.● Respond slowly or hesitantly.● Open too often, too briefly or for
too long.● Require constant adjustment or
frequent repair.● Require a wide variety of
models, spare parts or orificesizes for different pressures.
THERMOSTATIC STEAM TRAPSThermostatic steam traps, as their nameimplies, operate in direct response tothe temperature within the trap. Thereare two primary types: BELLOWS andBIMETALLIC.
BELLOWS TRAPSOf all actuating devices, the bellows trapmost nearly approaches ideal operationand efficiency and is most economical.It is positive in both directions, is fastacting and does not require adjustment.Bellows traps employ only one movingpart - a liquid filled metal bellows -which responds quickly and precisely tothe presence or absence of steam.
During startup and warmup, a vacuumin the bellows keeps it retracted, withthe valve lifted well clear of the seatpermitting air and non-condensibles tobe freely discharged (Figure 13).
Next, condensate is discharged (Figure14). Then heat from arriving steam willcause the liquid in the bellows to vapor-ize and close the valve (Figure 15).At temperature, the valve will remainclosed indefinitely opening only whencondensate, air or other non-conden-sibles cause it to retract and open.When live steam re-enters the traphousing, the bellows extends immedi-ately, trapping the steam (Figure 15).
The bellows, unlike a disc trap, is atemperature sensitive rather than a timecycle device. There is no way that aircan be mistaken for steam and causebinding, since bellows react totemperature only. And unlike buckettraps, bellows traps do not require avariety of sizes for valves and seats forvarious pressures.
BIMETALLIC TRAPSBimetallic traps work like the differentialmetal strip in a thermostat, using theunequal expansion of two differentmetals to produce movement whichopens and closes a valve.Figure 16: When the cooler conden-sate contacts the bimetallic discs, thediscs relax. Inlet pressure forces the valveaway from its seat and permits flow.
Figure 17: When steam enters the trapand heats the bimetallic discs, thediscs expand forcing the valve againstits seat preventing flow.Bimetallic traps are simple and positivein both directions. However, they havea built-in delay factor which makesthem inherently sluggish. Moreover;they do not maintain their originalsettings because the elements tend totake a permanent set after use, whichrequires repeated adjustment tomaintain efficiency.
FIGURE 13
FIGURE 14
FIGURE 15
FIGURE 16 FIGURE 17
the bottom and the valve (B) fully opento allow condensate to flow out freely.
There are two basic types of mechan-ical steam traps:
1) FLOAT & THERMOSTATIC 2) INVERTED BUCKET
Inverted bucket traps, as their namesuggests, operate like an upside downbucket in water.Figure 1: During startup, the trap isfilled with water, with the bucket (A) at
Figure 2: Air trapped in the bucketescapes through a vent hole (C). On
FIGURE 1 FIGURE 2
MECHANICAL STEAM TRAPS
- 359 -
THER
MO
STAT
IC &
MEC
HA
NIC
AL
TRA
PS
- 360 -
MEC
HA
NIC
AL
TRA
PS
(CO
NTI
NU
ED)
MECHANICAL STEAM TRAPS CONT’D.some buckets, an additional vent hole iscontrolled by a bimetallic strip which iskept closed by the steam. Therefore, thevent only operates during startup. Thislimits bucket trap air handling capacity. Figure 3: At temperature, steam enters
under the bucket and causes it to floatup and close the valve (B). During heatuse, any condensate entering the line isforced up into the bucket. The bucketlooses buoyancy and drops down,reopening the valve and discharging thecondensate. (see Figure 1)Bucket traps are rugged and reliable,however, air building up in the bucketcan bind them closed causing conden-sate to back up in the line. Also, theycan waste steam if they lose their prime
(see Figure 4). Bucket traps requirepriming water in the trap which makesthem vulnerable to freeze up unlessexpensive insulation is added.
Because bucket traps rely on a fixedforce, the weight of the bucket, dischargeorifices must be sized by pressure. Forexample, a trap sized to operate at 50PSIG will not open at 150 PSIG.Float traps are manufactured in avariety of sizes, shapes and configur-ations. The most commonly used (forsteam service) is the float and thermo-static, or F & T. F & T traps combinethe excellent air venting capabilities ofa thermostatic trap with the liquid levelcontrolling capabilities of a float trap.
Figure 5: During startup, before conden-sate reaches the trap, the thermostaticelement is fully open to discharge air. Thefloat rests on the lower seat.
Figure 6: As hot condensate and steamreach the trap, the thermostatic elementexpands, closing the air vent. Conden-sate lifts the float, allowing condensateto flow out of the trap.
Figure 7: As the condensing ratedecreases, the float lowers, reducingflow through the trap. The buoyancy ofthe float will maintain a liquid level sealabove the lower seat ring, preventingthe escape of steam. As with invertedbucket traps, float and thermostatictraps rely on a fixed force (the buoy-ancy of the float). Discharge orificesmust be sized by differential pressure.Placing a low pressure float and therm-ostatic trap in high pressure service willresult in the trap locking up. Acontrasting characteristic of both thefloat and thermostatic and invertedbucket is the discharge cycle. A float &thermostatic trap tends to continuouslydischarge condensate while theinverted bucket trap dischargescondensate in cycles.
FIGURE 4
FIGURE 3
FIGURE 7
FIGURE 6
FIGURE 5
THERMODYNAMIC STEAM TRAPSEssentially, a thermodynamic steam trapis a time cycle device which respondsto imbalances of pressure applied to avalving device, usually a disc.
Figure 9: Pressure caused by air orcondensate lifts the disc permittingflow through the trap.
Figure 10: When steam arrives at theinlet port, blowby at a high velocitycreates low pressure under the disc.Some of the flashing condensate is
blown past the disc into the upperchamber, forcing the disc downward.
Figure 11: Further flow is stoppedwhen sufficient pressure is trapped inthe chamber above the disc. Duringoperation, a decrease in chamberpressure permits inlet pressure to liftthe disc and open the trap (Figure 9).
The decrease in the chamber pressureshould only be caused by the presenceof cooler condensate. Due to thedesign of most thermodynamic traps,especially in cold or wet conditions, thechamber may be prematurely cooledcausing improper or frequent cycling aswell as steam loss and increased wear.Advanced TD designs have a steamjacket which surrounds the chamberand prevents ambient conditionsaffecting the operation of the disc.
This type of trap is also subject to waterbinding. If water pressure is trappedabove disc, trap will fail closed.
Figure 12: Trap is easily affected bydirt and/or other foreign matter whichwill cause trap to fail open.
ORIFICE STEAM TRAPSOrifice type traps are engineered con-tinuous flow devices. Orifice traps dis-charge air, condensate and all othernon-condensible gases with minimallive steam loss.The fixed orifice size is calculated, fora given application, to discharge thecondensate load at maximum thermalefficiency. Approximately 10 to 25 per-cent of discharging hot condensateflashes to steam at the downstreamside of the orifice, at a constant pres-sure drop. This flashing effect furtherrestricts the flow of saturated steam. Inactual conditions, a minimum percen-tage of steam, by weight, is dischargedwith condensate, since the specific
volume of steam is relatively largecompared to that of the condensate.The velocity through the orifice ishighly turbulent. The initial calculatedsteam loss can be expected to remainrelatively constant over the expectedtrap life of 10 plus years.The major factor for energy efficientperformance is based on initial orificesizing for the application. Properly sized,thermal efficiencies of 98 percent pluscan be attained.While Orifice Traps can be applied atall pressures, they are ideally suited foruse on saturated or superheated steam250 PSIG or greater.1/2", 3/4" and 1" FNPT, or Socket Weld End
Connections available
60 Mesh Dome Strainerand Gasket Assembly
Gasket
Orifice Plate
FIGURE 9
FIGURE 10
FIGURE 11 FIGURE 12
- 361 -
THER
MO
DY
NA
MIC
&O
RIF
ICE
TRA
PS
- 362 -
SIZI
NG
STE
AM
TR
AP
S SIZING STEAM TRAPSHOW TO DETERMINE THE PROPERSIZE TRAP
Capacity tables that follow showmaximum discharge rates in poundsper hour. To select the correct size trapfrom these tables, the normal conden-sing rate should be converted to a“pounds per hour” basis and multipliedby a safety factor.
REASON FOR SAFETY FACTORS
For steam applications, the condensa-tion rate varies with:
(1) The starting or warming-upcondition.
(2) The normal operating condition.
(3) Any abnormal operating condition.
Of these, the condensing rate for thenormal condition is occasionally known,or it can be estimated with sufficientaccuracy for trap selection; the loadsimposed by warm-up and abnormalconditions are seldom known andpractically impossible to predict.
During warm-up the trap load is heavy,since air as well as large quantities ofcondensate must be discharged. Con-densate forms at a rapid rate as the coldequipment and connecting piping arebrought up to temperature. This usuallyresults in pressure drop at the trap inlet,thereby reducing its capacity during theperiod when the load is maximum.
Safety factors are therefore necessary,to compensate for start-up conditions,variation of steam pressure and productinitial temperature, the process cyclespeed required, and discrepanciesbetween assumed and actual condi-tions which determine the normalcondensing rate.
The selection of a safety factordepends on the type of trap and theoperating conditions. If the known orcalculated normal condensing rate ismultiplied by the recommended factorfrom the pages which follow, efficienttrapping will be assured.
EFFECT OF BACK PRESSURE ONTRAP CAPACITY
Most trap installations include pipingthe outlet into a common return systemor to an available disposal location. Ineither case a constant static back pres-
sure may exist, against which the trapmust discharge. This back pressuremay be unintentional or deliberatelyproduced.
Unintentional back pressure in conden-sate return piping is caused by liftingthe condensate to a higher level, pipingwhich is too small for the volume ofliquid conveyed, piping with insufficientor no pitch in the direction of flow, pipeand fittings clogged with rust, pipe scaleor other debris, leaking steam traps,etc. In steam service an intentionalback pressure is instigated by meansof a pressure regulating or spring-loaded valve in the discharge system,when a supply of flash steam at apressure less than the trap pressure isneeded.
If very hot condensate is discharged toa pressure less than that existing in thetrap body, some of it will flash into steam,with a tremendous increase in volumeand consequent choking and build-upof pressure in the trap's discharge orificeand the passages and piping adjacentthereto. For condensate at or close tosteam temperature, this flash pressureis quite high, usually considerablyhigher than any static back pressureexisting in the trap outlet piping.
For this reason, capacity tables forthermostatic and thermodynamic trapsare based on gage pressure at thetrap inlet, instead of on the differencebetween trap inlet and discharge pres-sures. Experiments have shown that,for the temperatures applying to thesetables, unless the static back pressurein the return piping exceeds 25% of thetrap inlet pressure, no reduction of thetrap capacity results. For back pres-sures greater than 25% of the trap inletpressure there is a progressive decreaseof trap capacity.
Thus, if the return piping static pressureis less than 25% of the trap inlet pres-sure, the capacities shown in thesetables should be utilized for trap selec-tion. If the return piping pressure isgreater than 25% of the trap inletpressure, reduce the table capacitiesby the percentage indicated in secondline of Table A on the following pages.
Above data does not apply to float andthermostatic traps, capacities are basedon differential pressure, obtained bysubtracting any static back pressurefrom trap inlet pressure.
WHEN THE NORMAL CONDENSINGRATE IS KNOWN
Normal condensing rate means thepounds of steam condensed per hourby the average conditions which prevailwhen the equipment drained is atoperating temperature.
If this amount is known, simply multiplyby the safety factor recommended forthe service and conditions, obtainedfrom the pages which follow, and deter-mine size directly from the capacitytables for the type of trap selected.
WHEN THE NORMAL CONDENSINGRATE IS UNKNOWN
Determine by utilizing proper formulafor the service and equipment to betrapped. Multiply the result by safetyfactor recommended for the operatingconditions. See examples on thefollowing pages.
SIZING STEAM TRAPS CONT’D.EXPLANATION OF SYMBOLS USEDIN NORMAL CONDENSING RATEFORMULAS
A = Heating surface area, square feet(see Table B)
B = Heat output of coil or heater, BTUper hour
C = Condensate generated bysubmerged heating surfaces,Ibs/hr/sq ft (Table F)
D = Weight of material processed per hourafter drying, pounds
F = Steam flow, Ibs/hr
G= Gallons of liquid heated per unit time
H = Heat loss from bare iron or steelheating surface, BTU/sq ft/°F/hr
L = Latent heat of steam at pressureutilized, BTU/lb (see Table Cor obtain from Steam Table)
M = Metal weight of autoclave, retortor other pressure vessel, pounds
Qh = Condensate generated, Ibs/hr
Qu = Condensate generated, Ibs/unittime (Always convert to Ibs/hrbefore applying safety factor. SeeExamples using formulas 7 and10 on next page).
S = Specific heat of material processed,BTU/lb/°F
Ta = Ambient air temperature, °F
Tf = Final temperature of materialprocessed, °F
Ti = Initial temperature of materialprocessed, °F
Ts = Temperature of steam at pressureutilized, °F (see Table C orobtain from Steam Table)
U = Overall coefficient of heat transfer,BTU/sq ft/°F/hr (see Table E)
V = Volume of air heated, cubicfeet/minute
Wg= Liquid weight, Ibs/gallon
Wh = Weight of material processed perhour, Ibs
Wu = Weight of material processed perunit time, Ibs
X = Factor for Tf-Ti (obtain from Table D)L
Y = Factor for H(Ts-Ta) ,Ibs/hr/sq ft L
(obtain from Table C)
AIR HEATING
Steam Mains; Pipe Coil Radiation;Convectors; Radiators; etc. (NaturalAir Circulation)
(1) Qh = A Y Recommended Safety Factors
For Steam MainsAmbient Air Above Freezing:1st Trap After Boiler………………. 3At End of Main ………………………3Other Traps …………………………2Ambient Air Below Freezing:At End of Main ……………………. 4Other Traps …………………………3
Steam mains should be trapped at allpoints where condensate can collect,such as at loops, risers, separators,end of mains, ahead of valves, wheremains reduce to smaller diameters,etc., regardless of the condensate load.Installation of traps at these locationsusually provides ample capacity.
For Pipe Coil Radiation,Convectors and RadiatorsSingle Continuous Coil …………... 2Multiple Coil ……………………….. 4
Damp Space Pipe Coil Radiation;Dry Kilns; Greenhouses; DryingRooms; etc. (Natural Air Circulation)
(2) Qh = 2.5 A Y Recommended Safety Factors
Single Continuous Coil ………….. 2Multiple Coil ……………………….. 4
Steam Line Separators; Line Purifiers(3) Qh = .10 F
Recommended Safety FactorsIndoor Pipe Line ………………….. 2Outdoor Pipe Line ………………... 3If Boiler Carry-Over Anticipated… 4 to 6(Depending on probable severity of
conditions)
Unit Heaters; Blast Coils (Forced AirCirculation)
(4) When BTU Output is Known:Qh = B
L
(5) When BTU Output is Unknown, Heat Transfer Area is Known:
Qh = 5 A Y(6) When Volume of Air Heated is Known:
Qh = 1.09 V XRecommended Safety Factors
Intake Air Above Freezing - Constant Steam Pressure ………. 3Intake Air Above Freezing - Variable Steam Pressure ………... 4Intake Air Below Freezing - Constant Steam Pressure ………. 4Intake Air Below Freezing - Variable Steam Pressure ………… 5
Example: 11,500 cubic feet of air perminute heated by blast coil from 50°Fto 170°F with 50 PSIG constantsteam pressure.
Solution: By formula (6), Qh = 1.09 x11,500 x .132 = 1655 Ibs/hr. Recom-mended safety factor, 3 for intake airabove freezing and constant steampressure. 3 x 1655 = 4965 Ibs/hr trapcapacity required.
- 363 -
SIZI
NG
STE
AM
TR
AP
S(C
ON
TIN
UED
)
- 364 -
SIZI
NG
STE
AM
TR
AP
S(C
ON
TIN
UED
)SIZING STEAM TRAPS CONT’D.
LIQUID HEATING
Submerged Coils; Heat Exchangers;Evaporators; Stills; Vats; Tanks;Jacketed Kettles; Cooking Pans; etc.
(7) When Quantity of Liquid to be Heated in a Given Time is Known:
Qu = G Wg S X
(8) When Quantity of Liquid to be Heated is Unknown:
Qh = A U X
(9) When Heating Surface Area is Larger than Required to Heat Known
Quantity of Liquid in a Given Time:
Qh = A C
When maximum heat transfer efficiencyis desired, or when in doubt, use formula(9) in preference to formulas (7) and (8).
Recommended Safety Factors
For Submerged Coil Equipment;Heat Exchangers; Evaporators; etc.
Constant Steam Pressure:Single Coil, Gravity Drainage …… 2Single Coil, Siphon Drainage …… 3Multiple Coil, Gravity Drainage …. 4Variable Steam Pressure:Single Coil, Gravity Drainage …… 3Single Coil, Siphon Drainage …… 4Multiple Coil, Gravity Drainage …. 5
For Siphon Drained Equipment, specifytraps with “Steam Lock Release Valve”.
For Jacketed Equipment; CoolingKettles; Pans; etc.Slow Cooking:
Gravity Drainage ……………… 3Siphon Drainage ……………… 4
Moderately Fast Cooking:Gravity Drainage ……………… 4Siphon Drainage ……………… 5
Very Fast Cooking: Gravity Drainage ……………… 5Siphon Drainage ……………… 6
For Siphon Drained Equipment, specifytraps with “Steam Lock Release Valve”.
Example: Heat exchanger with singlesubmerged coil, gravity drained,heating 1250 gallons of petroleum oil
of 0.51 specific heat, weighing 7.3Ibs/gal, from 50°F to 190°F in 15minutes, using steam at 100 PSIG.
Solution: By formula (7), Qu = 1250 X7.3 x .51 x .159 = 740 pounds ofcondensate in 15 minutes, or 4 x 740= 2960 Ibs/hr. Recommended safetyfactor is 2 for single coil, gravitydrained. 2 x 2960 = 5920 Ibs/hr trapcapacity required.
DIRECT STEAM CONTACT HEATING
Autoclaves; Retorts; Sterilizers;Reaction Chambers; etc.
(10) Qu = Wu S X + .12 M X Recommended Safety Factors
Slow Warm-up Permissible …….. 3Fast Warm-up Desired ………….. 5
Example: An autoclave which weighs400 pounds before loading is chargedwith 270 pounds of material having aspecific heat of .57 and an initialtemperature of 70°F. Utilizing steamat 50 PSIG, it is desired to bring thetemperature up 250°F in the shortestpossible time.
Solution: By formula (10), Qu = (270 x.57 x .198) + .12(400 x .198) = 40pounds of condensate. Using safetyfactor of 5 recommended for fastwarm-up and assuming 5 minutes asthe time required to complete thereaction, a trap capacity of 40 x 12 x5 = 2400 Ibs/hr is required.
INDIRECT STEAM CONTACTHEATING
Cylinder Dryers, Drum Dryers,Rotary Steam Tube Dryers,Calenders; etc.
(11) Qh = 970 (W- D) + Wh XL
Recommended Safety Factors
For Siphon or Bucket DrainedRotating Cylinder, Drum and SteamTube Dryers; Cylinder Ironers; etc.
Small or medium Size,Slow Rotation ………………………4
Small or Medium Size,Fast Rotation ………………………6
Large Size, Slow Rotation ………. 6Large Size, Fast Rotation ……….. 8
For Siphon or Bucket Drained Equip-ment, specify traps with “Steam LockRelease Valve”. Each cylinder shouldbe individually trapped.
For Gravity Drained Chest TypeDryers and Ironers
Each Chest Individually Trapped… 2Entire Machine Drained By
Single Trap …………………... 4 to 6Depending on number of Chests
For Platen Presses
Each Platen Individually Trapped … 2*Entire Press Drained by Single Trap,Platens Piped in Series ……………3*Entire Press Drained by Single Trap,Platens Piped in Parallel …… 4 to 6Depending on number of Platens
Example: A medium size rotary steamtube dryer with condensate lifted toa discharge passage in the trunion,dries 4000 Ibs/hr of granular materialto 3300 pounds, with 15 PSIG steam,initial temperature of material 70°F,final temperature 250°F.
Solution: By formula (11) Qh =
970 (4000 - 3300) + (4000 x .191) 945
= 1483 Ibs/hr. Using safety factor of4 recommended for medium size,slow rotation: 4 x 1483 = 5932 Ibs/hrtrap capacity required.
*A separate trap for each heatingsurface (coil, chest, platen, etc.) isrecommended for maximum heatingefficiency. Sluggish removal of con-densate and air is certain when morethan one unit is drained by a singletrap, resulting in reduced tempera-tures, slow heating and possiblewater-hammer damage.
Back Pressure as Percent of Inlet Pressure 10 20 25 30 40 50 60 70 80 90Percent Reduction of Trap Capacity 0 0 0 2 5 12 20 30 40 55
TABLE A — EFFECT OF BACK PRESSURE ON STEAM TRAP CAPACITY
Nominal Pipe Size (In.) 1/2 3/4 1 11⁄4 11⁄2 2 21⁄2 3 4 5 6 8 10 12 14 16 18 20 24
Area, Sq. Ft. per Lineal Ft. .22 .28 .35 .44 .50 .63 .76 .92 1.18 1.46 1.74 2.26 2.81 3.34 3.67 4.19 4.71 5.24 6.28
Tf-Ti STEAM PRESSURE - PSIG
°F 1 2 5 10 15 20 25 50 75 100 150 200 250 300 350 400 450 500 600
40 .041 .041 .042 .042 .042 .043 .043 .044 .045 .045 .047 .048 .049 .050 .051 .052 .052 .053 .055
60 .062 .062 .062 .063 .064 .064 .064 .066 .067 .068 .070 .072 .073 .075 .076 .077 .079 .080 .082
80 .083 .083 .083 .084 .085 .085 .086 .087 .089 .091 .093 .096 .098 .100 .101 .103 .105 .106 .110
100 .103 .103 .104 .105 .106 .106 .107 .110 .112 .114 .117 .120 .122 .124 .127 .129 .131 .133 .137
120 .124 .124 .125 .126 .127 .128 .129 .132 .134 .136 .140 .144 .146 .149 .152 .155 .157 .160 .165
140 .145 .145 .146 .147 .148 .149 .150 .154 .156 .159 .163 .167 .171 .174 .177 .180 .183 .186 .192
160 .165 .166 .167 .168 .169 .170 .172 .176 .179 .182 .187 .191 .195 .199 .203 .206 .210 .213 .220
180 .187 .189 .191 .192 .193 .198 .201 .204 .210 .215 .220 .224 .228 .232 .236 .240 .248
200 .211 .212 .213 .214 .219 .224 .227 .234 .239 .244 .249 .253 .258 .262 .266 .275
220 .235 .236 .242 .246 .250 .257 .262 .268 .274 .279 .283 .288 .293 .303
240 .263 .268 .273 .280 .286 .292 .299 .304 .309 .314 .319 .330
260 .290 .296 .304 .310 .317 .324 .329 .335 .340 .346 .357
280 .313 .319 .327 .334 .342 .349 .354 .361 .367 .373 .385
300 .350 .358 .366 .373 .380 .387 .393 .400 .412
TABLE D — FACTOR X = (Tf–Ti)/L
AVERAGE DESIGN VALUESTYPE OF HEAT EXCHANGER NATURAL CIRCULATION FORCED CIRCULATION
STEAM TO WATER 125 300STEAM TO OIL 20 45STEAM TO MILK 125 300STEAM TO PARAFFIN WAX 25 80STEAM TO SUGAR & MOLASSES SOLUTIONS 75 150
TABLE E — FACTOR U, HEAT TRANSFER COEFFICIENTSBTU/HR/SQ FT/°F TEMP. DIFFERENTIAL
HEATING DIFFERENCE BETWEEN STEAM TEMPERATURE AND MEAN WATER TEMPERATURE*
SURFACE 25 50 75 100 125 150 175 200 225 250 275 300
IRON OR STEEL 1.6 5 10 17 25 34 45 57 70 84 99 114
BRASS 2.6 8 16 27 40 54 72 91 112 134 158 182
COPPER 3.2 10 20 34 50 68 90 114 140 168 198 228
Coefficients shown are suggested average design values. Higher or lower figures will be realized for many conditions. Use forsteam trap selection only.
TABLE F — FACTOR C, APPROXIMATE CONDENSING RATE FOR SUBMERGED SURFACES,LBS/HR/SQ FT
* Mean water temperature is 1/2 the sum of inlet temperature plus outlet temperature. Table based on heatingsurfaces submerged in water with natural circulation. Safety factor of 50% has been included to allow for moderatescaling. If surface will remain bright, multiply above figures by 2. Use for steam trap selection only.
- 365 -
TRA
P S
IZIN
G T
AB
LESTABLE B – SQUARE FEET OF SURFACE PER LINEAL FOOT OF PIPE
Steam Pressure - PSIG 1 2 5 10 15 20 25 50 75 100 150 200 250 300 350 400 450 500 600
Steam Temperature - °F 215 219 227 239 250 259 267 298 320 338 366 388 406 422 436 448 460 470 489
Latent Heat - BTU/lb 968 966 961 952 945 939 934 911 895 879 856 839 820 804 790 776 764 751 728
Factor Y Cond - lbs/hr/sq.ft. 0.45 0.46 0.49 0.53 0.56 0.59 0.71 0.84 1.02 1.10 1.34 1.47 1.58 1.80 1.91 2.00 2.35 2.46 2.65
TABLE C - FACTOR Y - H(Ts-Ta)/L - APPROXIMATE CONDENSING RATE FOR BARE IRON AND STEEL PIPE*
*Based on still air at 60F, recommended safety factors compensate for air at other temperatures. Used for steam trap selection only.
- 366 -
SIZI
NG
CO
ND
ENSA
TER
ETU
RN
LIN
ES
NO
MIN
AL
PIP
E SI
ZE (I
NC
H)
UP
STR
EAM
PR
ESSU
RE
(PSI
G)
EXAMPLE
PIV
OT
LIN
E
END
PRES
SURE
(PSI
G)
CONDENSATE FLO
W (LB/HR)
600500410350275220170130100
60
30
180100
50
3020
10
5
0
60K
40K
30K
20K
15K
10K
5K
1K
10
8
6
5
4
3
1
SIZING CONDENSATE RETURNLINES
When condensate passes through asteam trap orifice, it drops from the up-stream pressure in the heat exchangerto the downstream pressure in the con-densate return line. The energy in theupstream condensate is greater than theenergy in the downstream condensate.As the condensate passes through thesteam trap, the additional energy fromthe upstream condensate forms a per-centage of flash steam that changes
based upon the upstream and down-stream pressures (this percentage canbe seen in Table 5 in the CondensateCommander section).
When sizing condensate return linesafter the steam trap, it is important totake into account the amount of flashsteam created when hot, saturated con-densate undergoes a pressure drop.The flash steam has very large volumeand can cause very high velocities if thereturn line is not sized properly. Thesehigh velocities can create high backpres-
sure in the return line that often leadsto poor steam trap performance.
We will size the condensate return linebased upon flash steam velocities, Thepercentage of flash steam versus con-densate (water) is usually on the orderof 20 to 1, so the effect of the water inthe system sizing is usually small.Choosing a velocity of flash steam isoften subjective and different manufac-turers will suggest different values. Thenomograph below sizes return linesbased upon 50 feet/second.
EXAMPLE: Inlet Trap Pressure = 100 psigOutlet Pressure (return) = 0 psig (atmospheric)Actual condensate flow rate = 5,000 lb/hr.
Start at the Upstream Pressure line at 100 psig. Make astraight line through the End (Downstream) Pressure of 0psig and stop at the pivot line. From that point, make astraight line through the Condensate Flow Rate of 5,000and stop at the Nominal Pipe size line. It intersectsslightly higher than 4”. You may select the 4” line sizewithout concern for undersizing the line because a lowvelocity of 50 ft/sec was used.
Note: If design requirements dictate using a velocity otherthan the 50 ft/sec value in the Nomograph, a ratio can bemade of the pipe size because the velocity is proportionalto the Pipe Diameter squared. For example, if you requirea Pipe Diameter for 80 ft/sec, use the following equation:
50 FT/SECNomograph Diameter x ____________________√New Velocity (FT/SEC)
Example: The Nomograph Diameter determined in the previousexample is 4.2". Using the above formula, the Pipe Diameter for80 ft/sec is 3.3".
SIZING CONDENSATE RETURN LINES
V.1.1 INTRODUCTION
Steam tracing is one of many ways topreheat, add heat and prevent heatloss from piping systems and theircomponents. Some other ways are:
☛ Jacketed piping
☛ Hot water and oil tracing
☛ Dowtherm tracing
Jacketed piping systems are used pri-marily to maintain a constant high tem-perature. Due to its high cost of con-struction, jacketed systems are seldomused except where temperature controlis critical. Hot water and oil must bepumped at a high velocity to maintaina desired temperature, and must havea separate return header as does Dow-therm. Hot water, oil or dowtherm arealso an additional system which add tothe cost of a plant.
Steam tracing is most often selectedbecause:
☛ There is generally available a surplusof low and/or medium pressuresteam.
☛ Steam has a high latent heat andheat-transfer-coefficient.
☛ Steam condenses at a constanttemperature.
☛ Steam flows to end-point withoutthe aid of pumps (when designedcorrectly).
☛ A small amount of return piping isneeded due to existing condensateheaders.
V.1.2 USES
Freeze Protection (winterizing)
☛ Adding sufficient heat to above-grade piping systems and equip-ment which are exposed to ambienttemperatures below the freezingpoint of their media prevents freezing.
Maintaining A Desired Temperature
☛ The viscosity of some liquidsbecomes higher as their tempera-tures become lower causing moredifficult and costly pumping andleading to down-time for cleaning.
☛ Condensation may occur in somegases if the ambient temperaturefalls below the dewpoint which isharmful and expensive in suchsystems as:
-Natural Gas where control valvesfreeze up and burners malfunction.
-Compressor Suction Lines wherecompressors can be damaged.
V.1.3 MATERIAL
Steam tracing material is normally asfollows:
-Use the material specified for steampiping from the steam header (throughthe distribution manifold, if applicable)to and including the tracer block valve.
-Use 1/4” through 7/8” O.D. copper orstainless steel tubing (depending on thedesign conditions) from the block valveto the steam trap. Though sizes mayvary with different applications, 3/8”and 1/2” O.D. are the most often used.Tube fittings and adapters are normallyflareless compression type or 37degree flared type.
-Use the material specified forcondensate piping from the steam trap(through the collection manifold, ifapplicable) to the condensate headeror end-point (drain or grade).
V.1.4 DESIGN GUIDELINES
1. Steam piping should be run within12” of the line or equipment beingtraced to minimize exposed tubing.
2. Spiral tracing should be limited tovertical piping using multipletracers on horizontal lines whichrequire more heat.
3. Tracers should be designed so thatthe flow is always down. Avoidpockets! ! Where vertical flow isunavoidable, steam pressureshould be a minimum of 25 PSIGfor every 10’ of rise.
4. Tracers should be a maximum of100' long and continuous from thesupply to the collection manifold orendpoint. For lines over 100’ long,provide another tracer and overlapthe two 3 inches to avoid coldspots.
5. Tracers should have no branch teesexcept as indicated in Section V.3.
6. Provide each tracer with a separatestrainer and steam trap.
7. Manifolds can be horizontal or verti-cal depending upon the designconditions.
8. Tracers should be attached to thepipe at 8” to 10” maximum intervalswith stainless steel wire. Wiretension should be sufficient to holdthe tracer secure and flush againstthe pipe.
9. Some piping materials, such as linedpipe, might require spacer blocksto avoid “hot spots”.
10. Tracer loops with unions arenecessary:
☛ when joining tubing lengths.
☛ at all break flanges and unions.
☛ at all flanged valves.
11. Tracer discharge lines should be asshort as possible since long dis-charge lines can freeze even with afully functioning steam trap.
STEAM TRACING DESIGN GUIDELINES
- 367 -
STEA
M T
RA
CIN
GD
ESIG
N G
UID
ELIN
ES
- 368 -
CLE
AN S
TEAM
& P
IPIN
GD
ESIG
N G
UID
ELIN
ES
1. Extra care should be taken for ex-pansion stresses due to the highercoefficient of expansion for stain-less steel.
2. Branch connections are to be madefrom the top of headers with theblock valve as close as possible tothe header.
3. The recommended types ofbranch connections are tees andreducing tees.
4. Steam lines should slope down totraps (recommended 1% min.).
5. A dirt leg with trap station isrecommended at every change ofelevation (no undrainable pockets).
6. Extra care should be taken in pipesupports to eliminate sagging.
7. Instruments in general should bekept to a minimum. However, whererequired, it is recommended that:A) All are installed in tees.B) Pressure gauges be installed
with diaphragm seals.C ) Flow meters be installed in the
vertical flow-up position toeliminate pockets
D) Pressure reducing stations bekept to a minimum.
8. Traps should be installed in thevertical flow-down position toeliminate pockets.
9. Trap block valves should be locatedas close as possible to the user.
10. Condensate lines should besloped (recommended 1% min.) tothe end point. Note thatcontaminated condensate shouldalways be piped to a processsewer. Uncontaminated conden-sate (from drip legs) may berecovered, if cost effective, andused elsewhere in the plant (not asClean Steam make-up).
11. Condensate terminal points shouldcontain an air break (2” or 2 pipediameters, whichever is greater)between the end of the pipe andthe drain, floor or grade.
12. Test connections for traps arerecommended-trap efficiency isessential for Clean Steam.
PIPING & TRAPPING DESIGN GUIDELINES
CLEAN STEAM DESIGN GUIDELINESClean Steam is a general term used todescribe a range of steam pureness. Itmay be generated by such methods as:● Filtration of plant steam typically
requiring the removal of particleslarger than 5 microns
● An independent steam generator.E.g. Stainless steel reboiler fed withdistilled water.
● One stage of a multi-effect still withinthe overall water purification system.
Uses for Clean Steam vary by industry,however typical applications include:● In-line sterilization of storage tanks
and equipment● Powering sterilizers and autoclaves● Cleaning and sterilizing process
piping systems withoutdisassembling the piping system -commonly known as CIP (Clean inPlace)
● Pasteurization utilizing Ultra HighTemperature Processing (UHT)
The highest quality clean steam how-ever, is typically used by the Pharma-ceutical and Biotechnical industries.This steam, occasionally referred to as“Pure Steam”, is most often suppliedby an independent steam generatorutilizing Water for Injection (WFI) asfeed water. WFI is typically producedby a Reverse Osmosis (RO) generator
and then distilled thus removing anytraces of organics, bacteria, and pyro-gens. Pure steam is required for thesterilization of cell culture processingequipment such as incubators wherecontaminants could adversely affectcell growth. Other uses include pharm-aceutical manufacture and direct steaminjection pasteurization where contami-nants could collect in products intendedfor human consumption.
Clean steam produced from high puritymake up water is highly corrosive dueto the minimal ion content. High puritywater, pure steam and the resultantcondensate will aggressively attempt toabsorb or leach ions from their environ-ment to achieve a more natural balance.Additionally, chemicals used to passi-vate steam and condensate in conven-tional systems are generally prohibitedfrom clean steam system as suchchemicals could contaminate or altersensitive end products. Should corrosionbegin, the oxidation byproducts maytravel through the steam system cataly-zing corrosion throughout in a processknown as ‘rouging’.
To combat the corrosive nature of cleansteam, design practices require piping,fittings and valving to be comprised ofcorrosion resistant materials. Currentindustry accepted materials include
304L, 316 and 316L stainless steel andhigher alloys such as Inconel. Whilethese materials have proventhemselves in practice, it should benoted that there are currently no U.S.governmental standards specifyingmaterials for clean steam service.Regulatory agencies concern them-selves with the purity and quality of theproduct, leaving the design standardsentirely up to the manufacturer.
In addition to the use of corrosionresistant materials in sanitary systems,features designed to inhibit bacterialgrowth are often required. Piping, valvesand fittings should be free draining andmaintain industry standard surfacefinishes. Free draining valves andfittings are designed not to retain or‘Puddle’ condensate when installedcorrectly. After shut down of the steamsystem, any puddled condensate couldpotentially promote bacterial growth.Inadequate surface finishes reduce theeffectiveness of system sterilizationtechniques, increasing the possibility ofbacterial contamination. Industrystandard surface finishes are measuredin micro inches, the lower the numberthe smoother, and are expressed as anarithmetic average (Ra). Typical industryspecified surface finishes range from32 to 10 µ in. Ra.
- 369 -
SIZI
NG
ELI
MIN
ATO
RST
EAM
SEP
AR
ATO
RSSIZING ELIMINATOR STEAM SEPARATORS
SIZING FOR STEAM APPLICATIONS
Using your system pressure and capacity, select asize from the Pressure Drop Tables below that willyield a pressure drop in boldface type. This willprovide the most efficient separation with velocitiesbetween 30 and 100 ft/s for sizes up to 21⁄2" andbetween 30 and 90 ft/s for sizes 3" and above.
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600100 0.71 0.45 0.33 0.26 0.15 0.1 0.07 0.06 0.05200 2.83 1.8 1.32 1.05 0.62 0.39 0.3 0.24 0.2300 6.37 4.04 2.97 2.36 1.39 0.88 0.67 0.54 0.46400 11.33 7.18 5.28 4.19 2.47 1.56 1.19 0.96 0.81500 17.7 11.22 8.26 6.55 3.86 2.44 1.86 1.5 1.27600 25.49 16.16 11.89 9.43 5.55 3.52 2.69 2.16 1.82
1/2 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600100 0.22 0.14 0.1 0.08 0.05 0.03 0.02 0.02 0.02200 0.89 0.57 0.42 0.33 0.19 0.12 0.09 0.08 0.06300 2.01 1.27 0.94 0.74 0.44 0.28 0.21 0.17 0.14400 3.57 2.26 1.66 1.32 0.78 0.49 0.38 0.3 0.25500 5.57 3.53 2.6 2.06 1.21 0.77 0.59 0.47 0.4600 8.02 5.09 3.74 2.97 1.75 1.11 0.85 0.68 0.57
3/4 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600300 0.76 0.48 0.35 0.28 0.17 0.1 0.08 0.06 0.05500 2.11 1.34 0.98 0.78 0.46 0.29 0.22 0.18 0.15700 4.13 2.62 1.93 1.53 0.9 0.57 0.44 0.35 0.3900 6.83 4.33 3.19 2.53 1.49 0.94 0.72 0.58 0.491100 10.21 6.47 4.76 3.78 2.22 1.41 1.08 0.87 0.731300 14.26 9.04 6.65 5.27 3.11 1.97 1.5 1.21 1.021500 18.98 12.03 8.85 7.02 4.14 2.62 2 1.61 1.36
1 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600500 0.69 0.44 0.32 0.26 0.15 0.1 0.07 0.06 0.05750 1.56 0.99 0.73 0.58 0.34 0.22 0.16 0.13 0.111100 3.36 2.13 1.57 1.24 0.73 0.46 0.35 0.29 0.241250 4.34 2.75 2.02 1.6 0.95 0.6 0.46 0.37 0.311500 6.25 3.96 2.91 2.31 1.36 0.86 0.66 0.53 0.451750 8.5 5.39 3.97 3.14 1.85 1.17 0.9 0.72 0.612000 11.11 7.04 5.18 4.11 2.42 1.53 1.17 0.94 0.79
1-1/4 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600400 0.24 0.15 0.11 0.09 0.05 0.03 0.03 0.02 0.02500 0.37 0.24 0.17 0.14 0.08 0.05 0.04 0.03 0.031000 1.49 0.95 0.7 0.55 0.33 0.21 0.16 0.13 0.112000 5.98 3.79 2.79 2.21 1.3 0.82 0.63 0.51 0.433000 13.45 8.52 6.27 4.97 2.93 1.86 1.42 1.14 0.964000 23.91 15.16 11.15 8.84 5.21 3.3 2.52 2.03 1.71
1-1/2 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 6001000 0.54 0.34 0.25 0.2 0.12 0.07 0.06 0.05 0.042000 2.17 1.37 1.01 0.8 0.47 0.3 0.23 0.18 0.163000 4.88 3.09 2.28 1.8 1.06 0.67 0.51 0.41 0.354000 8.67 5.5 4.04 3.21 1.89 1.2 0.91 0.74 0.625000 13.55 8.59 6.32 5.01 2.95 1.87 1.43 1.15 0.976000 19.51 12.37 9.1 7.22 4.25 2.69 2.06 1.66 1.4
2 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 6001000 0.27 0.17 0.12 0.1 0.06 0.04 0.03 0.02 0.022000 1.07 0.68 0.5 0.39 0.23 0.15 0.11 0.09 0.083000 2.4 1.52 1.12 0.89 0.52 0.33 0.25 0.2 0.174000 4.27 2.71 1.99 1.58 0.93 0.59 0.45 0.36 0.315000 6.68 4.23 3.11 2.47 1.45 0.92 0.7 0.57 0.486000 9.61 6.09 4.48 3.55 2.09 1.33 1.01 0.82 0.697000 13.08 8.29 6.1 4.84 2.85 1.81 1.38 1.11 0.94
2-1/2 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 6002000 0.45 0.28 0.21 0.17 0.1 0.06 0.05 0.04 0.034000 1.79 1.13 0.83 0.66 0.39 0.25 0.19 0.15 0.136000 4.02 2.55 1.87 1.49 0.88 0.55 0.42 0.34 0.298000 7.15 4.53 3.33 2.64 1.56 0.99 0.75 0.61 0.5110000 11.17 7.08 5.21 4.13 2.43 1.54 1.18 0.95 0.812000 16.08 10.19 7.5 5.95 3.5 2.22 1.69 1.37 1.1514000 21.89 13.87 10.21 8.09 4.77 3.02 2.31 1.86 1.56
3 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 6004000 0.6 0.38 0.28 0.22 0.13 0.08 0.06 0.05 0.046000 1.34 0.85 0.63 0.5 0.29 0.19 0.14 0.11 0.18000 2.39 1.51 1.11 0.88 0.52 0.33 0.25 0.2 0.17
10000 3.73 2.37 1.74 1.38 0.81 0.51 0.39 0.32 0.2712000 5.37 3.41 2.51 1.99 1.17 0.74 0.57 0.46 0.3814000 7.32 4.64 3.41 2.71 1.59 1.01 0.77 0.62 0.5216000 9.55 6.06 4.46 3.53 2.08 1.32 1.01 0.81 0.68
4 INCH ELIMINATOR
#/HRPRESSURE (PSIG)
25 50 75 100 200 300 400 500 6005000 0.18 0.11 0.08 0.07 0.04 0.02 0.02 0.02 0.0110000 0.72 0.46 0.33 0.27 0.16 0.1 0.08 0.06 0.0515000 1.62 1.02 0.75 0.6 0.35 0.22 0.17 0.14 0.1220000 2.87 1.82 1.34 1.06 0.63 0.4 0.3 0.24 0.2125000 4.49 2.85 2.09 1.66 0.98 0.62 0.47 0.38 0.3230000 6.46 4.1 3.01 2.39 1.41 0.89 0.68 0.55 0.4635000 8.8 5.58 4.1 3.25 1.92 1.21 0.93 0.75 0.63
6 INCH ELIMINATOR
EXAMPLE
For a system under 400 PSIG with a capacity of500#/hr, a 1/2" or 3/4" separator is recommended.
a. A 1/2" separator will provide a 1.86 PSIGpressure drop.
b. A 3/4" separator will provide a 0.59 PSIGpressure drop.
ELIMINATOR PRESSURE DROP TABLES – STEAM
- 370 -
SIZI
NG
ELI
MIN
ATO
RST
EAM
SEP
AR
ATO
RS SIZING ELIMINATOR STEAM SEPARATORS
SIZING FOR AIR APPLICATIONS
Using your system pressure and capacity, select asize from the Pressure Drop Tables below that willyield a pressure drop in boldface type. This willprovide the most efficient separation with velocitiesbetween 8 and 60 ft/s for sizes up to 21⁄2" andbetween 8 and 50 ft/s for sizes 3" and above.
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
10 0.07 0.04 0.03 0.02 0.01 0.01 0.01 0.01 020 0.27 0.17 0.12 0.09 0.05 0.03 0.03 0.02 0.0230 0.61 0.37 0.27 0.21 0.11 0.08 0.06 0.05 0.0440 1.08 0.66 0.48 0.37 0.2 0.14 0.1 0.08 0.0750 1.69 1.03 0.75 0.58 0.31 0.21 0.16 0.13 0.1160 2.43 1.49 1.07 0.84 0.45 0.31 0.23 0.19 0.16
1/2 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
10 0.02 0.01 0.01 0.01 0 0 0 0 025 0.13 0.08 0.06 0.05 0.02 0.02 0.01 0.01 0.0150 0.53 0.33 0.23 0.18 0.1 0.07 0.05 0.04 0.0370 1.04 0.64 0.46 0.36 0.19 0.13 0.1 0.08 0.0790 1.72 1.05 0.76 0.59 0.32 0.22 0.16 0.13 0.11110 2.57 1.58 1.14 0.89 0.47 0.32 0.25 0.2 0.17
3/4 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
25 0.05 0.03 0.02 0.02 0.01 0.01 0 0 050 0.2 0.12 0.09 0.07 0.04 0.03 0.02 0.02 0.0175 0.45 0.28 0.2 0.16 0.08 0.06 0.04 0.03 0.03100 0.8 0.49 0.36 0.28 0.15 0.1 0.08 0.06 0.05125 1.26 0.77 0.56 0.43 0.23 0.16 0.12 0.1 0.08150 1.81 1.11 0.8 0.63 0.33 0.23 0.17 0.14 0.12
1 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
50 0.07 0.04 0.03 0.02 0.01 0.01 0.01 0.01 0100 0.26 0.16 0.12 0.09 0.05 0.03 0.03 0.02 0.02150 0.59 0.37 0.26 0.21 0.11 0.08 0.06 0.05 0.04200 1.06 0.65 0.47 0.37 0.2 0.13 0.1 0.08 0.07250 1.65 1.01 0.73 0.57 0.31 0.21 0.16 0.13 0.11300 2.38 1.46 1.05 0.82 0.44 0.3 0.23 0.18 0.15
1-1/4 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
50 0.04 0.02 0.02 0.01 0.01 0 0 0 0100 0.14 0.09 0.06 0.05 0.03 0.02 0.01 0.01 0.01150 0.32 0.2 0.14 0.11 0.06 0.04 0.03 0.02 0.02200 0.57 0.35 0.25 0.2 0.11 0.07 0.05 0.04 0.04250 0.89 0.55 0.39 0.31 0.16 0.11 0.09 0.07 0.06300 1.28 0.79 0.57 0.44 0.24 0.16 0.12 0.1 0.08
1-1/2 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
100 0.05 0.03 0.02 0.02 0.01 0.01 0 0 0200 0.21 0.13 0.09 0.07 0.04 0.03 0.02 0.02 0.01300 0.46 0.29 0.21 0.16 0.09 0.06 0.04 0.04 0.03400 0.83 0.51 0.37 0.29 0.15 0.1 0.08 0.06 0.05500 1.29 0.79 0.57 0.45 0.24 0.16 0.12 0.1 0.08600 1.86 1.14 0.82 0.64 0.34 0.23 0.18 0.14 0.12
2 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
100 0.03 0.02 0.01 0.01 0 0 0 0 0250 0.16 0.1 0.07 0.06 0.03 0.02 0.02 0.01 0.01500 0.64 0.39 0.28 0.22 0.12 0.08 0.06 0.05 0.04750 1.43 0.88 0.63 0.5 0.26 0.18 0.14 0.11 0.091000 2.54 1.56 1.13 0.88 0.47 0.32 0.24 0.2 0.161250 3.97 2.44 1.76 1.38 0.73 0.5 0.38 0.31 0.26
2-1/2 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
200 0.04 0.03 0.02 0.01 0.01 0.01 0 0 0400 0.17 0.1 0.08 0.06 0.03 0.02 0.02 0.01 0.01600 0.38 0.23 0.17 0.13 0.07 0.05 0.04 0.03 0.02800 0.68 0.42 0.3 0.24 0.13 0.09 0.07 0.05 0.041000 1.06 0.65 0.47 0.37 0.2 0.13 0.1 0.08 0.071200 1.53 0.94 0.68 0.53 0.28 0.19 0.15 0.12 0.1
3 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
250 0.02 0.01 0.01 0.01 0 0 0 0 0500 0.09 0.05 0.04 0.03 0.02 0.01 0.01 0.01 0.011000 0.36 0.22 0.16 0.12 0.07 0.04 0.03 0.03 0.021500 0.8 0.49 0.35 0.28 0.15 0.1 0.08 0.06 0.052000 1.42 0.87 0.63 0.49 0.26 0.18 0.14 0.11 0.092500 2.22 1.36 0.98 0.77 0.41 0.28 0.21 0.17 0.14
4 INCH ELIMINATOR
SCFMPRESSURE (PSIG)
25 50 75 100 200 300 400 500 600
500 0.02 0.01 0.01 0.01 0 0 0 0 01000 0.07 0.04 0.03 0.02 0.01 0.01 0.01 0.01 02000 0.27 0.17 0.12 0.09 0.05 0.03 0.03 0.02 0.023000 0.62 0.38 0.27 0.21 0.11 0.08 0.06 0.05 0.044000 1.09 0.67 0.48 0.38 0.2 0.14 0.1 0.08 0.075000 1.71 1.05 0.76 0.59 0.32 0.22 0.16 0.13 0.11
6 INCH ELIMINATOR
EXAMPLE
For a system under 400 PSIG with a capacity of 500SCFM, a 2" or 21⁄2" separator is recommended.
a. A 2" separator will provide a 0.12 PSIGpressure drop.
b. A 21⁄2" separator will provide a 0.06 PSIGpressure drop.
ELIMINATOR PRESSURE DROP TABLES – AIR
- 371 -
TRA
PS
&
SPEC
IALT
IES
NOTES: