Steam Trap

172
GESTRA Condensate Manual

Transcript of Steam Trap

Page 1: Steam Trap

GESTRACondensate Manual

Page 2: Steam Trap

1st Edition 1980 2nd Revised Edition 1982 3rd Revised Edition 1986 4th Revised Edition 1987 5th Revised Edition 1991 6th Revised Edition 1995 7th Revised Edition 2003 8th Revised Edition 2004 9th Revised Edition 2005 10th Revised Edition 2008

Page 3: Steam Trap

PageTable of Contents

Abbreviations 4

1. Steam Traps 9

2. Basic Principles of Steam Trapping 27(with Examples)

3. Selection of Steam Traps 40

4. The Most Common Steam Trap Applications 43(Selecting the Most Suitable Steam Trap)

5. Monitoring of Steam Traps 83

6. Using the Sensible Heat of the Condensate 91

7. Air-Venting of Heat Exchangers 94

8. Condensate Return Systems 95

9. Drainage of Compressed Air Lines 99

10. Sizing of Condensate Return Lines 107

11. Sizing of Steam Lines 117

12. Calculation of Condensate Flowrates 118

13. Pressure and Temperature Control 125

14. The Use of GESTRA DISCO Non-Return Valves 133

15. Check Valves 137

16. Capacity Charts for GESTRA Steam Traps 141

17. Valves for Special Purposes 155

Symbols according to DIN 2481 161

International Symbols and Abbreviations 165

Material Designations 166

Index

Page 4: Steam Trap

4

AbbreviationsThe following abbreviations are used in this booklet for the corresponding GESTRAequipment:

AK GESTRA automatic drain valve for start-up drainage

BK GESTRA Duo steam trap BK Thermostatic/thermodynamic steam trap with regulator of DUO stainless steel

MK GESTRA steam trap Flexotherm MK. Thermostatic trap with membraneregulator

DK Thermodynamic steam trap

UNA Duplex GESTRA float trap UNA with thermostatic bellows or capsule for automaticair-venting

UNA Simplex GESTRA float trap UNA without thermostatic element

GK GESTRA Super steam trap GK. Thermodynamic steam trap with stagenozzle

RK GESTRA DISCO non-return valve in wafer design

TK GESTRA Duo Super steam trap TK. Thermostatic steam trap with thermo-static pilot control by membrane regulators

TD GESTRA mechanical drier for steam

TP GESTRA mechanical drier and purifier for compressed air and gases

UBK GESTRA steam trap UBK. Thermostatic trap for condensate dischargewithout flashing

UNA 2 GESTRA float trap UNA 23/25/26/27

Page 5: Steam Trap

5

UNA 1 GESTRA float trap UNA 14/16

VK GESTRA Vaposcope. Sightglass

VKP GESTRA VAPOPHONE: Ultrasonic detector for monitoring steam traps forloss of live steam

VKP-Ex GESTRA VAPOPHONE: Ultrasonic detector for monitoring steam traps forloss of live steam (Ex protected)

VKE GESTRA test set VKE for monitoring steam traps

ZK GESTRA drain and control valve with radial-stage nozzle

H capsule GESTRA thermostatic capsule for opening temperatures 5 K below satu-ration temperature

N capsule GESTRA thermostatic capsule for opening temperatures 10 K below satu-ration temperature

U capsule GESTRA thermostatic capsule for opening temperatures 30 K below satu-ration temperature

DN Dimension, nominal. The nominal size of a pipe or fitting in mm

PN Pressure, nominal. The nominal pressure rating (maximum cold-water workingpressure) in bar

Page 6: Steam Trap

Technical Advice and Training Seminars

provide an in-depth and up-to-date exposition of the topic, placing great emphasis on the latest developments and technological trends.

Optimization of steam and condensate systems for cost-efficient and trouble-free operation

Solving practical problems, exchanging experience and active presence of theparticipants

Various installation examples based on actual projects will illustrate problemsand their respective solutions

GESTRA Diploma

The seminars are rounded off with some practicaldemonstrations given at our in-house testing facilities:

Open steam system

Closed steam system

Transparent testing and demonstration facility

The GESTRA Academy offerstraining programs and projectmanagement assistance fortechnical staff to help implementfuture-oriented and complexprojects in all fields of steam, condensate and process fluidcontrol.

The tremendously fast progress of technology combined with the recenteconomic developments are placingever greater demands on the trainingand qualification of employees andmanagers alike. A company’s wealth of technical knowledge and the know-how of itspersonnel in particular constitutenowadays the most important non-material asset of an enterprise. In many seminars held over the lastfew years our customers have often expressed a keen interest inauthoritative theoretical and practicalsupport.

To assist with this objective, theGESTRA Academy was set up inorder to provide comprehensivetechnical literature and conductworkshops, seminars andpersonalized consulting and trainingprograms.

Our hands-on seminars place greatemphasis on the exchange ofexperience and the active presenceand collaboration of the participants.Various practical examples of projectsalready implemented in different indu-stries will be considered in order tooutline the problems involved andtheir solutions.

The focus of the training seminars is on the following subjects:

Fundamental principles of steam and condensate

Sizing and design of pipework

Efficient utilization of energy in steam systems

Boiler automation and operation(without constant supervision for 72 hrs)

and other related topics and practical examples.

GESTRA training seminars are geared to the needs of technical staff working for engineering companies, project-, design- and plant engineers, foremen, interested specialists and personnel responsible for commissioning, servicing and maintenance. Our seminars on Steam and Condensate Systems

Objective

Certificate

systems

Page 7: Steam Trap

To be able to operate a plant over a long period with an optimum efficiency the choice of the correctvalves is of vital importance.Amongst these valves are steam traps which have an important role to play. Steam must be trappedwithin heating equipment until it has surrendered all heat energy, at which point the condensate therebyformed must be immediately discharged. The optimum efficiency of a steamheated plant is dependent upon the performance of steam traps.One type of steam trap cannot be equally well suited for the various applications and requirements, therefore GESTRA offers a comprehensive steam trap range developed and refined on practical applications over the years.The choice of the steam trap typedepends, of course, on the plant condition. We are willingly prepared to assist you in selecting the most economic solution for your particular application.

What are Steam Traps?

The three different steam trap types

BKThe BK is a thermostatic steam trap with Duo stainless (bimetallic) regulator. Advantage: particularly robust

MKThe MK is a thermostatic steam trap with membrane regulator.Advantage: very sensitive response characteristic.

UNAThe UNA is a float trap.Advantage: condensate discharge at extreme and sudden condensate flowrate and pressure fluctuations.

Page 8: Steam Trap

Page1. Steam Traps

1.1 Evaluation Criteria 9

1.2 The Various Steam-Trap Systems of GESTRA 12

1.2.1 Combined thermostatic/thermodynamic steam trapswith bimetallic Duo stainless steel regulator, BK range 12

1.2.2 Thermostatic steam traps with membrane regulator,MK range 14

1.2.3 Rhombusline is more than just a new family ofGESTRA steam traps 15

1.2.4 Thermostatic pilot-operated steam traps forvery high flowrates, TK range 17

1.2.5 Thermostatic steam traps for condensatedischarge without flash steam, UBK range 17

1.2.6 Ball float traps, UNA range 18

1.2.7 Thermodynamic steam traps, DK range 19

1.2.8 Thermodynamic steam traps with stage nozzle,GK range, and with radial stage nozzle, ZK range 20

1.2.9 New drainage systems for use in power stations 21

Page 9: Steam Trap

1. Steam Traps

1.1 Evaluation CriteriaThere is no such thing as a universal steam trap. It is therefore important to studythe requirements of a particular application to choose the trap which will give thebest results. The following points, amongst others, should be considered whenselecting a steam trap:- its control characteristics and flowrate capacity, depending on the application

either as a single unit (e.g. use for large pressure ranges, for large pressure fluctu-ations, for large flowrates, for large flowrate fluctuations) or jointly (e.g. for largefluctuations in flowrate and pressure);

- its ability to vent itself and the plant;- the possibilities provided for installation and maintenance; and- its service life; its suitability for back pressure etc. (see Fig. 1).The most important technical criteria for evaluation, together with the corres-ponding assessment of the steam trap types manufactured by GESTRA, aresummarized in Fig. 2.

Properties of the Steam Trap

Basic requirementsDischarging the required quantity of condensate without loss of live steamAutomatic air-venting

Additional requirementsNo impairment of the heating process, no banking-upUtilization of the sensible heat of the condensate by holding it backUniversal application - Large pressure range

- Works with high or low back-pressures- Wide range of flowrates- Accommodates large fluctuations in flowrate

and pressure- For controlled installations

Low effort - Easy installation- Minimum maintenance- Corrosion-resistant- Unaffected by dirt- Can withstand freezing- Resistant to waterhammer- Long service life- As few variants as possible

Fig. 1

9

Page 10: Steam Trap

10

Fig. 2 Steam trap selection table

Page 11: Steam Trap

Important Criteria for the Evaluation

1.1.1 Easy installation can significantly reduce costs. A lightweight trap whichcan be installed in any position might save its manufacturing cost com-pared to making pipework alterations or constructing support brackets fora large and heavy steam trap, which can also lose a considerable amountof heat by radiation.

1.1.2 A poorly vented and incompletely drained heat exchanger takes a longtime to warm up – this can lead to higher manufacturing costs (owing toprolongation of the required heating times) or can even damage the pro-duct due to uneven temperatures in the heat exchanger (see Fig. 3).

1.1.3 Certain types of steam traps inherently blow off some steam, even whennew. It is possible for the cost of the energy loss to exceed the purchaseprice of the trap within only a few months of operation. All steam trapsoperating according to the thermodynamic principle (e.g. the thermo-dynamic disc-type traps and inverted-bucket traps) suffer from this problem and will always waste a certain amount of steam.

11

Fig. 3 Partial pressure of the steam and the corresponding saturated temperature asa function of the pressure for various percentages of air in steam.

Page 12: Steam Trap

12

1.1.4 Sometimes it is desirable to hold back the condensate in a heater to utilize the sensible heat. Use of an appropriate steam trap can yield con-siderable savings of energy (undercooling).

1.1.5 Freezing of the traps and the condensate piping in outside installationscan cause serious production problems.

1.1.6 In the long run, using a cheap, non-repairable steam trap will require moreeffort in terms of time and money than a more expensive trap that can beremoved and repaired.

1.1.7 The use of only a few trap types with wide applications throughout theplant will reduce costs, thanks to simplified stock-keeping as well as quickrepair and maintenance by staff who are familiar with the traps.

1.2 The Various Steam-Trap Systems of GESTRA have been developed to meet the special needs and expectations of the plantoperators. Both technical requirements and economical considerations arealways kept in mind.

1.2.1 Combined thermostatic/thermodynamic steam traps with bimetallicDuo stainless steel regulator, BK range (Fig. 4).

Condensate discharge is controlled by the regulating element of the trapas a function of pressure and temperature. The trap opens at a slightundercooling and closes immediately before saturation temperature isreached.

Fig. 4 GESTRA Duo steam trap BK

Page 13: Steam Trap

13

The high-lift effect (a thermodynamic process) produces the instantane-ous opening of the trap and a consequently high hot-water capacity (see Fig. 5).

The discharge temperature of the condensate can be varied by using a regulator adjusted for undercooling. An increase in the condensate under-cooling, provided the heating process permits, will lead to heat savings, whereas a reduced undercooling may lead to faster and more even heating.

Features of the BK range:- Robust regulator unaffected by waterhammer, aggressive condensate

and freezing; millions of installed units are giving excellent performance- Stage nozzle with non-return valve action- Automatic air-venting- Available for all pressures and temperatures. Trap with long service life

A point to consider: The condensate undercooling required for opening increases with rising

back-pressure.

Fig. 5 Opening curves of various steam trapsCurve 1 – UNA Curve 3 – BK 45 Duo stainless steelCurve 2 – MK Curve 4 – standard bimetallic

Page 14: Steam Trap

14

1.2.2 Thermostatic steam traps with membrane regulator, MK range (Fig. 6)

Condensate discharge is controlled by the membrane regulator, a vapour-expansion thermostat, as a function of temperature. The control charac-teristic of the trap practically follows the saturated steam curve, and gives more accurate control than any other thermostatic trap (see Fig. 5). Owing to the sensitive response and the instant reaction to changes in tempera-ture, the MK traps are particularly suited for heat exchangers where even the slightest banking-up of condensate would impair the heating process, such as vulcanizing presses, ironing presses and laboratory equipment.

Two different capsules are available for the membrane regulator:- “N” (normal) capsule for condensate discharge practically without any

banking-up. Discharge temperature approx. 10 K below saturation temperature.

- “U” (undercooling) capsule for additional savings in energy (utilization of the sensible heat through banking-up in the heating surface, reduction of the amount of flash steam). Discharge temperature approx. 30 K below saturation temperature.

Fig. 6GESTRA steam trap MK 45-1

Fig. 6a Function of the membrane regulator with flat seat

Page 15: Steam Trap

15

Operation of the membrane regulator Opening: The capsule of the membrane regulator is filled with a liquid

having an evaporation temperature which is just a few degrees below the saturation temperature of water. During shut-down or start-up of the plant, i.e. if cold condensate is present, the liquid filling is completely con-densed. The pressure in the capsule is lower than the surrounding pres-sure (service pressure); the membrane with the valve disc is pushed in the opening direction.

Closing: With rising condensate temperature, the liquid filling starts to evaporate. The pressure in the capsule rises; the membrane with the valve disc is moved in the closing direction. Just before the condensate has reached its saturation temperature, the trap is closed completely.

Features:- Operation is unaffected by back pressure. The capsule is corrosion-

resistant and practically impervious to waterhammer.- Readjustment of the regulator is not possible (it is also unnecessary),

which prevents steam losses as a result of tampering.- Automatic air-venting.- Thermostatic steam trap with perfect control.- For small condensate flowrates, the capsule with tandem shut-off (dual

seat) is recommended.- For larger condensate flowrates, use the “H” capsule for condensate

discharge practically without any banking-up (discharge temperature 5 K below saturation temperature).

Various regulators with flat seat are available for this purpose: Depending on the condensate flowrate, with 1, 2, 3, 4 or 9 flat-seat

membranes.

Fig. 6b Function of the membrane regulator with tandem shut-offThe self-centering valve cone ensures steamtight closure. With rising tempera-tures, the additional flat seat closes too and provides a further guarantee of tightness, even in the presence of dirt particles. Moreover, the pressure drop over two stages reduces wear and enhances the life of the trap.

1

2

1

2

During plant operationSeat 1 closes (regulator is pushed to the closed position)

Trap closedBoth seats are tightly shut off

Page 16: Steam Trap

16

1.2.3 RHOMBUSline is more than just a new family of GESTRA steam traps The wide-ranging experience gained with the proven BK 15 steam traps

resulted in an optimization of the traps for the new RHOMBUSline. A patented Duo stainless steel plate arrangement in the regulator of the

BK 45, consisting of a plate stack, reacts much faster than the previous version to parameter changes in the steam and in condensate lines.

Benefits of the RHOMBUSline traps:1. The new regulator reacts more quickly to changes in the influencing

factor steam/condensate (BK 45).2. The shape of the RHOMBUSline casing permits the use of standard

flange connecting bolts, both from the trap casing and from the coun-ter-flanges.

3. It is no longer necessary to exchange the gasket between cover and casing every time the cover is removed from the trap.

4. The trap cover is mounted with only two bolts instead of four.5. The Y-shaped strainer (with large filtering area for separating out impu-

rities) simplifies the strainer cleaning process.6. The sealing of the regulator (base bushing pressed into the casing)

prevents internal leaks.7. Retightening of the bolts after the initial commissioning is no longer

required.8. The overall length complies with the applicable codes.9. Maintenance of the traps is simplified.

Fig. 7a RHOMBUSline steam traps

MK 45

BK 45

AK 45

Page 17: Steam Trap

17

1.2.4 Thermostatic pilot-operated steam traps for very high flowrates, TK range (Fig. 7b)

The control element consists of a thermostatic pilot control with membraneregulators and a main valve. The regulating characteristic of the TK traps issimilar to that of the MK traps, where the valve is directly operated by themembrane regulator.

Features:- Easy to install in spite of large flowrate. Overall length corresponding to

DIN standards for valves, low weight, installation in any position.- Automatic air-venting, unaffected by dirt and aggressive condensate.

1.2.5 Thermostatic steam traps for condensate discharge without flashsteam, UBK range.This steam trap is a special version of the BK range with bimetallic Duostainless steel regulator (see Fig. 5). With the factory setting, the conden-sate discharge temperature is < 100°C for pressures up to 19 barg (275 psig) and < 116°C for pressures up to 32 barg (465 psig).The UBK traps are suitable for all applications where banking-up of con-densate does not impair the heating process. A typical case is steam tracing with condensate discharge to atmosphere, and another exampleis steam trapping of instrument heating, i.e. all heating processes where areduction of the heating capacity (by banking-up) is of advantage.With no additional effort, the UBK traps ensure noticeable steam savingsbesides reducing environmental pollution by preventing flash-steamclouds and utilizing the sensible heat of the condensate.

Fig. 7b GESTRA Duo Super steam trap TK 23/24 DN 50

Page 18: Steam Trap

18

1.2.6 Ball float traps, UNA range (Fig. 8a)

Condensate discharge is controlled directly by the float-operated valve as a function of the amount of condensate formed. The condensate is discharged immediately as it is formed. The operation of the trap is unaffected by the condensate temperature, by back pressure or by any pressure fluctuations (see Fig. 5).

Automatic air-venting of the plant is ensured by the UNA 2 float traps with “Duplex” control (thermostatic bellows). Thanks to its functional principle, this trap range is suitable for all process applications. It is ideal in plants controlled on the steam side: for heating processes with extreme pressure and flowrate fluctuations and very low pressures down to vacuum, and for trapping steam driers and flash vessels whilst maintaining the level at the required height. If the steam is relatively wet, trapping of steam mains with float traps might be advantageous.

Float traps are the only traps that can be used for removing air and also for draining condensate (e.g. from compressed air installations), distillates and other chemical products having a saturation curve differing from that of water. They can also be used with flash vessels or discharge controls for maintaining a certain condensate level (Simplex design).

Features:- No banking-up of condensate- Operation unaffected by back pressure- Automatic air-venting with thermostatic bellows (Duplex design) opening

the main valve- Relatively small-sized for a float trap.- Versions for horizontal and vertical installation- UNA 2 v traps with Duplex control for vertical installation can withstand

freezing

Fig. 8a GESTRA float trap UNA 23/25/26

Page 19: Steam Trap

19

1.2.7 Thermodynamic steam traps, DK range (Fig. 8b)Thermodynamic traps have a simple design and small size. In addition,they are resistant to waterhammer and freezing. During operation, thesetraps require a small amount of steam for control purposes.The thermodynamic steam traps are made of stainless steel in the follo-wing variants:DK 57 L - for small condensate flowratesDK 57 H - for large condensate flowratesDK 47 L - as above, additionally equipped with a strainerDK 47 H - as above, additionally equipped with a strainer

Further data:PN 63, DN 10/15/20/25 mmScrewed sockets3/8", 1/2", 3/4", 1" BSP or NPT

Fig. 8b Thermodynamic steam trap DK 47

Page 20: Steam Trap

20

1.2.8 Thermodynamic steam traps with stage nozzle, GK range, and withradial stage nozzle, ZK range (Fig. 9)

The state of the condensate prevailing in the nozzle system (cold – con-densate only; hot – condensate + flash steam; boiling hot – minimum con-densate + maximum flash steam) controls the condensate flowratewithout any modification of the cross-sectional area. The traps can there-fore be used without any mechanical readjustment being necessary, evenif the operating conditions vary to a certain extent; it suffices to adjustthem once to suit the operational situation. Because of their excellentregulating characteristic and high wear resistance, the ZK valves are ideally suited as proven low-noise control valves in control systems with ahigh pressure drop, e.g. injection cooling, leak-off control and level control. The stage-nozzle traps with handwheel operation are used for the dischargeof high flowrates with a relatively constant amount of condensate forming,such as evaporators, tank heating, rotating drying cylinders etc.

Features:- High flowrates, little weight, reduced dimensions- No moving parts, simple and reliable- High wear resistance- Unaffected by dirt

Fig. 9 GESTRA drain and control valve with radial stage nozzle ZK 29

Page 21: Steam Trap

21

1.2.9 Drainage systems for use in power stations In modern power stations, the demands on drain valves of the type ZK are

increasing together with the efficiency. These valves are characterized by high resistance to wear, tight sealing and low maintenance costs, making a significant contribution to economical operation of the power station. In addition, new capacitance probes are able to detect condensate of low conductivity independently of the pressure and temperature. This now enables level-dependent (controlled) drainage at positions where the tem-peratures had previously ruled out their use. Plant components can be protected from damage caused by undetected quantities of condensate. The controlled drainage equipment is only opened when condensate is actually present. In presence of superheated steam, the valves are closed, thereby preventing steam losses and achieving a high degree of operating safety.

For instance, before the steam turbine of a power station can be started, the steam lines must be freed of condensate and warmed to their speci-fied start-up temperature. Fig. 10a shows an example of the drainage for the turbine plant of a conventional power station. The live steam line is additionally heated by a separate warm-up valve.

The drainage points marked with the steam trap symbol consist of two independent traps. The ZK drain valve is used for the condensate dis-charge during start-up and for any further warming-up which may be needed. This valve is closed after a preset time has elapsed or when a certain temperature has been reached in the relevant part of the plant. It opens at the earliest when the power station block is shut down. In parallel to this procedure, controlled drainage using level probes is also possible. Owing to heat losses in the drain line, small quantities of condensate are produced and these are discharged by a thermostatic steam trap. This continuous drainage is necessary to prevent the condensate from rising in the drain lines, which sometimes extend over long distances (Fig. 10b).

Page 22: Steam Trap

22

Fig. 10a Drainage scheme for a turbine plant

Page 23: Steam Trap

23

Fig

. 10b

Drainag

e scheme fo

r a high-p

ressure superheated

steam line

Page 24: Steam Trap

Control Valve ZK 29

3K 130 m /h, VS

1.490367 bar, (972 psig)588 °C

H. P. preheater in a nuclear power plant equipped with a condensate drain control valve type ZK 29

Page 25: Steam Trap

Page

2. Basic Principles of Steam Trappingwith Examples

2.1 � 2.6 General 27

2.7 Separate Trapping 29

2.8 Banking-Up of Condensate (Pro and Contra) 31

2.9 Measures for Preventing Waterhammer 32

2.10 Air-Venting 38

3. Selection of Steam Traps(For the dimensioning of steam traps, see Section 12.2) 40

Page 26: Steam Trap

Our Mobile Testing Station

For more informationplease contact++49 - 421-35 03 311.

The mobile testing station will comedirectly to your plant accompanied byqualified and experienced engineersfrom GESTRA who will give practicaldemonstrations of steam andcondensate applications. All we needfrom you is steam, water andelectricity.

Page 27: Steam Trap

27

2. Basic Principles of Steam Trapping with Examples

2.1 The condensate should be freely discharged downwards from the heatexchanger (Fig. 11)

2.2 A certain differential pressure (pressure drop) is required by the steam trap(Fig. 12)

2.3 If the condensate downstream of the trap is lifted, the differential pressure is re-duced by approximately 1 bar for 7 m of lift, or 2 psi for 3 feet of lift (Fig. 13)

Fig. 11

Dp = p - p [bar]D G

pD

pGFig. 12

7 m = 1 bar

Condensate dampening pot

pD

�p = p - (p +1) [bar]D G

pG

Fig. 13

Page 28: Steam Trap

28

2.4 If the condensate upstream of the trap has to be lifted, a water seal or lift fitting is required (Fig. 14)

2.5 Condensate pipework should be adequately sized to handle flash steam, sothat high back-pressures do not build up (Fig. 15)

2.6 The condensate and, if possible the flash steam, should be collected and re-used (Fig. 16)

Fig. 14 Use of a condensate dampening pot, type ED

Fig. 15

Fig. 16

Page 29: Steam Trap

29

2.7 Each heat exchanger should be trapped separately

2.7.1 Separate trapping of each individual heat exchanger (individual drainage)(Fig. 17)

2.7.2 Drainage of several heat exchangers connected in parallel with a singletrap (group trapping = one large condensate tank instead of many smallones) (Fig. 18)

2 bar

0 bar 0 bar

1.8 bar

2 bar 1.8 bar

1.8 bar2 bar

DISCO non-return valve RK

Steam trap

Fig. 18 Group trapping should be avoided. Pressure drops through each controlvalve and heat exchanger will inevitably be different. This leads to one ormore heat exchangers being short-circuited on the condensate side. Con-densate will bank up and waterhammer will occur.

Fig. 17 Separate drainage ensures condensate discharge without banking-up.Individual steam-side control is then possible. Banking-up and waterham-mer in the heating spaces is prevented. Additionally installed DISCO non-return valves RK stop condensate returning to the heat exchanger when,for example, the steam pressure in the heat exchanger drops owing to thecontrol valve throttling or closing. Vaposcopes downstream of the heatingsurfaces permit visual monitoring. Banking-up is detected reliably.

Page 30: Steam Trap

30

2.7.3 Drainage of several heat exchangers connected in series (e.g. multi-platen presses) (Fig. 19)

2 bar

1,8 bar

Fig. 19 Series connection of heat exchangersSmall identical heat exchangers (such as the steam plates of multi-platenpresses) can successfully be connected in series, provided that there is a con-tinuous fall from the steam inlet to the trap. To obtain perfectly equal surfacetemperatures in the heating spaces, there must be no banking-up of conden-sate in the steam space at all. In many cases, this can only be prevented bymeans of a certain steam leakage through the trap (BK regulated correspon-dingly). Because steam losses then occur, separate trapping may be the moreeconomical solution, even for very small heat exchangers.

Page 31: Steam Trap

31

2.8 Banking-Up of Condensate (Pros and Cons)

2.8.1 Banking-up of condensate in the heating exchanger reduces the rate ofheat transfer (Fig. 20)

2.8.2 Banking-up of condensate in the heat exchanger will improve fuel econ-omy by saving steam. It must, however, be considered that this maycause waterhammer.

Fig. 20 Heating with superheated steam and banking-up of condensateThe above drawing shows the heat exchange and temperature gradient in asteam-heated water heater (counterflow heat exchanger).Example: The heating surface is heated up with superheated steam, satura-ted steam and condensate in turn; the medium to be heated is water. Thisresults in the following heat transition coefficients: For superheated steam k ~ 92 W/m2K (335 kJ/m2hK)For saturated steam k ~ 1160 W/m2K (4187 kJ/m2hK)For condensate k ~ 400 W/m2K (1465 kJ/m2hK)The rate of heat transfer for saturated steam is about 12 times greater than forsuperheated steam and about 4 times greater than for condensate.

Page 32: Steam Trap

32

2.9 Measures for Preventing Waterhammer

2.9.1 Condensate-free heating surfaces through proper installation(Figs. 21, 22 and 23)

Vacuum breaker

a) If the steam supply is cut off, vacuum is formed in the steam space as theremaining steam condenses. The condensate may then be sucked backinto the heating space or not completely discharged. When the plant isrestarted, the steam flows across the water surface, condenses suddenlyand causes waterhammer.

b) Installation of a GESTRA DISCO non-return valve as a vacuum breakerprevents the formation of vacuum. The condensate cannot be suckedback, and the remaining condensate will flow off. Waterhammer is there-fore avoided. If the condensate line is under pressure, the installation of aDISCO non-return valve downstream of the steam trap is recommended.

Fig. 21 Waterhammer in heat exchangers

Page 33: Steam Trap

33

Steam bubbles

Steam flowing acrossthe water surface –formation of steambubbles in the con-densate, leading towaterhammer.

Horizontal heat

exchanger

Waterhammer

causedof

by banking-upcondensate

Float trap

Fig. 22 Waterhammer in horizontal heat exchangers controlled on the steam side. Waterhammer is avoided if the condensate is completely discharged from theheating surface at all load conditions (no banking-up). Waterhammer canoccur if part of the heating surface is flooded. The condensate cools down,and so the steam flows across the cold water surface. This leads to steambubbles in the condensate which condense abruptly, causing waterhammer.

Possible causes for banking-up.Inadequate steam trap (e.g. wrong working principle, condensate dischargenot instantaneous, insufficient trap size).Trap operation imperfect (e.g. trap does not open, or opens with too highundercooling).Differential pressure for steam trap too low, because of too high a pressuredrop across the heat exchanger at low load conditions (e.g. back pressure incondensate line downstream of trap > 1 bar absolute, pressure in heatexchanger at low load < 1 bar absolute).

Measures for preventing waterhammer.Use only float traps of the type UNA Duplex, to ensure instantaneous con-densate discharge without banking-up.Ensure that the trap is large enough, since at low load conditions the pressureupstream of the trap might be extremely low (even vacuum). The latter requi-res that there is no building-up of back pressure and no lifting of condensatedownstream of the trap, and that an additional pressure head is provided byinstalling the trap at a lower point. If it is possible that a vacuum may form inthe heat exchanger, the installation of a vacuum breaker (non-return valve RK)on the steam main downstream of the controller is recommended.

Page 34: Steam Trap

34

2.9.2 “Dry” condensate lines (sufficient fall, no formation of water pockets)

2.9.3 Dry steam piping and steam manifolds (steam consumption from mani-folds or piping always from the top; proper drainage, with installation of a steam drier if necessary) (see Figs. 23, 23a, 23b, 24 and 30).

Fit a drainage pocket at least every 100 m along the steam main, and also wherever the main rises.

Fig. 23 Undesired formation of water pockets

Fig. 23a Drainage and steam consumption from steam header

Page 35: Steam Trap

35

D1 mm 50 65 80 100 125 150 200 250 300 350 400 450 500 600D2 mm 50 65 80 80 80 100 150 150 200 200 200 250 250 250

Fig. 23b Steam-line drainage

Page 36: Steam Trap

2.9.4 Steam traps in continuous operation Thermostatic steam traps often discharge the condensate intermittently

and are therefore only to be recommended for low condensate flowrates. It is advisable to drain heat exchangers, and here in particular hot-water heat exchangers controlled on the steam side, by means of float traps type UNA!

2.9.5 Buffer vessels and water seals if condensate is lifted (Fig. 25)

36

Fig. 24 Waterhammer in steam linesa) Whenever the stop valve is closed, the steam remaining in the line conden-

ses. The condensate collects in the lower part of the line and cools down. When the valve is reopened, the inflowing steam meets the condensate. The result is waterhammer.

b) If the run of the pipe cannot be changed, the line should be drained, even if it is relatively short.

Fig. 25 Waterhammer if condensate is lifteda) Waterhammer often occurs if condensate if lifted.b) The remedy is to install a condensate dampening pot, which by its cushioning effect neutralizes the waterhammer.

Page 37: Steam Trap

37

2.9.6 Proper planning and arrangement of the various condensate branchesand the header (Figs. 26 and 27)

Fig. 27 The condensate from the various steam traps should be fed into the headerin the direction of flow

a) The condensate from the heat exchanger on the far end cools downstrongly on its way to the condensate tank. The condensate with the flashsteam from the heat exchangers that are closer to the condensate tankmixes with this cold condensate. The flash steam condenses abruptly andwaterhammer will result.

b) Waterhammer will be avoided if the condensate is sent to the condensatetank via separate headers. Condensate from heat exchangers using diffe-rent steam pressures should also be fed to the condensate tank by sepa-rate headers.

Fig. 26 Waterhammer in condensate lines

Page 38: Steam Trap

38

2.10 Air or other non-condensable gases in the steam reduce the temperature andheating capacity of heat exchangers, and may lead to uneven temperatures.For an air percentage of 10 %, the heating capacity drops by approx. 50 %(disadvantageous for e.g. presses, rotating drying cylinders) (Figs. 3 and 28).

2.10.1 Large steam spaces may require separate air vents (Fig. 29, 29a)

Small and medium-sized heat exchangers are adequately ventedthrough steam traps with additional automatic air-venting.

Fig. 29 Venting of evaporators heated with flash steam

ts P Percentage of air in steam by volume

Saturated Gauge 1 % 3 % 6 % 9 % 12 % 15 %steam pressure

temperature with pure Necessary gauge pressure[°C] steam [barg] for air-contaminated steam [barg]

120.23 1 1.02 1.06 1.13 1.20 1.27 1.35

133.54 2 2.03 2.09 2.19 2.32 2.41 2.53

143.62 3 3.04 3.12 3.25 3.40 3.52 3.71

158.84 5 5.06 5.18 5.38 5.60 5.82 6.06

184.05 10 10.11 10.34 10.70 11.09 11.50 11.94

201.36 15 15.16 15.48 16.02 16.58 17.20 17.82

214.84 20 20.21 20.65 21.34 22.07 22.87 23.70

Fig. 28

Page 39: Steam Trap

39

a) Heat exchangers with tube bundles

b) Jacketed heat exchangers

c) Autoclaves

Fig. 29a For larger vessels 2 or more vents necessary.

Page 40: Steam Trap

40

3. Selection of Steam Traps(For the sizing of steam traps, see Section 12.2)

Great care should be taken in choosing the steam trap best suited for a particularapplication.

3.1 The trap should be sized so that even the peak condensate flow is dischargedproperly. If the plant is operated with varying pressure (e.g. controlled plants), thecapacity characteristics of heat exchanger and steam trap should be compared.The capacity characteristic of the steam trap must be at least equal to that of theheat exchanger at the possible service pressures (e.g. controlled plants) or, ifpossible, even higher. An insufficiently sized trap leads to banking-up of conden-sate, the inevitable consequences being waterhammer and a reduction in theheating capacity.

3.2 The traps should not be oversized either. They would then have a tendencytowards overcontrolling and intermittent operation, which may lead to waterham-mer. This point has to be considered particularly with thermodynamic disc-typetraps and inverted-bucket traps.

3.3 The steam trap should provide automatic air-venting during operation. Air in thesteam space will prolong the heating-up period and reduce the heating capacityduring normal operation (see Fig. 28).

3.4 Normally, the steam trap should drain the condensate promptly so that it cannotwaterlog the heating surface.

3.5 The design of the steam traps should allow condensate discharge with a certainamount of undercooling, so that part of the sensible heat of the condensate canbe utilized, provided the system permits (heating surface large enough, andappropriate layout of heat exchanger and pipelines to avoid waterhammer). Sui-table traps from the GESTRA range are: BK with large undercooling adjustment,MK with “U” capsule and UBK). The degree of undercooling allowable dependson the desired temperature of the product to be heated.

Page 41: Steam Trap

Page4. The Most Common Steam Trap Applications -

Selecting the Most Suitable Steam Trap

4.1 Steam Piping 43

4.1.1 Steam driers (steam separators) 43

4.1.2 Saturated steam mains (without steam separator) 44

4.1.3 Superheated steam mains 45

4.1.4 Pressure regulators - see Section 13.1 125

4.1.5 Temperature controllers - see Section 13.2 128

4.2 Steam Headers - see Section 4.1 43

4.3 Steam Radiators, Finned-Tube Heaters, Radiant Panels, Convectors for Space Heating 46

4.4 Unit Air Heaters 47

4.4.1 Air heaters, controlled on the air side 47

4.4.2 Air heaters, controlled - see Section 4.6.1 49

4.5 Heating Coils, Horizontal Heaters 48

4.6 Air Conditioning Plants 49

4.6.1 Air heaters controlled on the steam side 49

4.6.2 Air humidifiers 50

4.7 Storage Calorifiers, Controlled 50

4.8 Counterflow Heat Exchangers, Controlled 51

4.8.1 Horizontal counterflow heat exchangers 51

4.8.2 Vertical counterflow heat exchangers 52

4.8.3 Vertical counterflow heat exchangers with use of the sensible heat 52

4.9 Process Heat Exchangers 53

4.10 Digesters 55

4.10.1 Process digesters and pans (sugar factories, chemical industry, cellulose production) 55

4.10.2 Boiling pans with heating coils 56

4.10.3 Jacketed boiling pans 57

4.10.4 Tilting pans 58

4.11 Brewing Pans (Coppers, Mash Tubs) 59

Page 42: Steam Trap

Page

4.12 High-Capacity Evaporators 60

4.13 Stills 61

4.14 Rotating Drying Cylinders 62

4.15 Baths and Tanks (e.g. for Cleaning and Pickling) 63

4.15.1 Heating coils with uniform fall and condensate discharge at base 63

4.15.2 Acid baths 64

4.16 Band Driers 65

4.17 Hot Tables, Drying Platens 66

4.18 Multi-Platen Presses 67

4.18.1 Multi-platen presses connected in parallel 67

4.18.2 Multi-platen presses connected in series 68

4.19 Tyre Presses (Vulcanizing Presses) 69

4.20 Vulcanizers 70

4.21 Autoclaves 71

4.22 Ironing Presses, Garment Presses 72

4.23 Steaming Mannequins - see Section 4.22 73

4.24 Ironers and Calenders (Hot Mangles) 74

4.25 Dry-Cleaning Machines 75

4.26 Tracer Lines 76

4.27 Jacketed Tracing Lines 77

4.28 Instrument Tracing 78

4.29 Tank Heating 79

Page 43: Steam Trap

43

4. The Most Common Steam Trap Applications – Selecting the Most Suitable Steam Trap

4.1 Steam Piping

4.1.1 Steam driers (steam separators) (Fig. 30)

Steam that is not superheated (i.e. saturated steam) is always, in fact, wet steam and contains a certain quantity of water droplets in suspension which reduce its heating capacity. If the percentage of water is too high, water-hammer may be caused in the steam main. Too high a moisture content may also be undesirable for ironing presses, in air-conditioning plants etc.

Special requirements of the trap: The condensate, which is very close to saturation temperature, should be

discharged instantly. Furthermore, the steam trap should air-vent the steam line automatically.

It is necessary to use float traps.

Fig. 30 GESTRA steam separator drained by a UNA 2 steam trap

Page 44: Steam Trap

44

Recommended equipment:UNA Duplex ball float trap and GESTRA steam separator type TD.Quite often, the usual drainage of the steam main by means of a steamtrap is not sufficient. In these cases (e.g. if the steam is generated in a coil-type boiler, or if the steam is to be injected into the product), the use of asteam separator operating on the centrifugal principle is recommended,which will remove the water droplets and lead them to the trap.

4.1.2 Saturated steam mains (without steam separator)The steam trap by itself can only remove the condensate formed in thesteam line, but not the water droplets in suspension in the steam. The latter requires a steam separator (see Section 4.1.1). During warming-upof the pipeline (start-up), large amounts of condensate are formed; the lowpressures then prevailing in the line further impede the process. Duringplant operation, small amounts of condensate are continuously being formed, depending on the pipeline insulation. Drain points should be pro-vided, for instance at low points, at the end of the line, in front of risers, atthe steam distribution manifold and, in the case of horizontal lines, atregular distances of not more than 100 m (300 ft) (see Figs. 23 and 24).For effective steam-line drainage, a water pocket (e.g. a T-piece) shouldbe provided (see Fig. 23). For large mains and long lines, the installationof a free-drainage valve (manually or automatically operated) of the typeAK 45 is recommended to discharge the large start-up load and to blowthe dirt directly to drain.Special requirements of the trap:- During start-up, the trap should air-vent the plant and simultaneously

discharge the relatively large condensate load at rather low differentialpressures without too much delay.

- In continuous operation, on the other hand, small amounts of conden-sate are continuously being formed at almost saturation temperature.

- During periods of shut-down, the trap � in outdoor plants at least �should drain the pipeline and itself to avoid freezing.

Recommended traps:- UNA Duplex for vertical installation; alternatively for small condensate

flowrates during continuous operation, BK and MK with N capsule. Ifthe traps discharge into the open by way of exception, the flash steamformed may be a nuisance. If the trap is not installed close to the drain-age point of the steam main, but a few metres away, the MK with U capsule or the BK with undercooling adjustment (∆t max. 30 � 40 K)may be used.

Page 45: Steam Trap

45

4.1.3 Superheated steam mains Normally no condensate is formed during continuous operation. Heat losses

through the pipeline, as a rule, reduce only the superheat temperature. Condensate is formed only during start-up of the plant and whenever there is no or very little steam consumption, i.e. when the steam flowrate along the main is very small. The amount of condensate reaching the trap during continuous operation depends solely on the heat losses of the line leading to the trap.

If the steam main operates at its design flowrate and no condensate is expected to be formed, only start-up drainage is needed in frost-proof areas. In outdoor plants which may freeze, the condensate formed in the pipe leading to the trap may be discharged at a temperature which just prevents freezing. This is of particular importance for open-air discharge, as the low discharge temperature reduces the unwanted flashing to a minimum (Fig. 31).

The amount of condensate, and consequently also the amount of flash steam formed, are the lower the shorter the condensate line is upstream of the trap. The trap should therefore be installed as close as possible to the steam main, with the condensate line and steam trap sufficiently insu-lated.

Special requirements of the trap:- Large flowrate during start-up (high cold-water capacity) at relatively

low pressures and a good air-venting capability, steam-tight closure and, if required, condensate discharge with more undercooling but ensuring large cold-water capacity.

Recommended traps:- If, even during continuous operation, condensate may form in the super-

heated steam line, if only for short periods: UNA or BK with factory setting.

- If condensate is only formed during start-up: BK with undercooling adjust-ment. For relatively large condensate flowrates at very low pressures during start-up, the GESTRA valve type AK is of particular advantage. During start-up, the AK is completely open and does not close unless the preset differential pressures reached. From this moment, the "normal" steam trap will ensure condensate discharge and air-venting.

Fig. 31

Page 46: Steam Trap

46

- In outdoor plants which may freeze, the condensate line immediately upstream of the AK should be drained and, in addition, the AK and the condensate line should be insulated.

4.1.4 Pressure regulators – see Section 13.1

4.1.5 Temperature controllers – see Section 13.2

4.2 Steam Headers – see Section 4.1 “Steam Piping”

4.3 Steam Radiators, Finned-Tube Heaters, Radiant Panels, Convectors for Space Heating (Fig . 32)

Low heating temperatures with the correspondingly low vapour pressures (e.g. flash steam reduced from a higher pressure range) are advantageous from a hygienic and physiological viewpoint. If the heating services are adequately sized (overdimensioned), they can be partly flooded with condensate, which will lead to steam savings, at least for higher pressures. The reduction in the heating temperature is not normally important.Special requirements of the trap:- In low-pressure plants, sufficient flowrate even at an extremely low pressure head - At higher pressures, condensate discharge with a certain amount of under-

cooling- Unaffected by dirt (e.g. particles of rust forming during intermittent operation

and long periods of shutdown of the heating installation during the summer)- Corrosion-resistant internalsRecommended traps:- For low-pressure plants: MK 20. For higher pressures: MK 35/32 with U capsule- BK with large undercooling adjustment- If a condensate discharge temperature as low as 85 °C is acceptable (suffi-

ciently large heating surface and no danger of waterhammer): UBK

Fig. 32

Page 47: Steam Trap

47

4.4 Unit Air Heaters

4.4.1 Air heaters, controlled on the air side (Fig. 33)

Separate space heaters or unit heaters (not including those in air condi-tioning plants or for air preheating in manufacturing and drying plants) are, in general, controlled on the air side only, for instance by switching the fan on and off.

In this case, either very high or very low condensate loads are to be expected. In air heaters heated with low-pressure steam, the pressure in the steam space may vary considerably (the pressure drops with increas-ing condensate load).

At higher steam pressures, an additional utilization of the sensible heat of the condensate in the air heater through banking-up is advantageous if it is not used otherwise in operation.

A prerequisite here, however, is that the heating capacity of the air heater is still adequate and that the heating plates are arranged to prevent water-hammer (vertically).

Special requirements of the trap:- In low-pressure plants, a relatively large flowrate, even at a low pressure

head- In plants with medium heating-steam pressures, in which it is possible

to use the sensible heat of the condensate through banking-up, the steam trap must be able to discharge the condensate with undercoo-ling. In both cases, the trap should air-vent the plant automatically.

Recommended traps:- MK 45-2, UNA Duplex- MK with U capsule

Fig. 33

Page 48: Steam Trap

48

4.4.2 Air heaters, controlled.See Section 4.6 “Air Conditioning Plants”.

4.5 Heating Coils, Horizontal Heaters (Fig. 34)

To avoid waterhammer, the pipe run between the steam inlet and steam trap mustbe arranged to fall in the direction of flow. Groups of heaters should be connect-ed in parallel and drained separately (see Section 2.7).Special requirements of the trap:- Discharge of the condensate without banking-up, even for high ambient tem-

peratures (e.g. installation close to the heater)- Automatic air-ventingRecommended traps:- MK with N capsule (MK with H capsules for large flowrates); UNA Duplex

Fig. 34

Page 49: Steam Trap

49

4.6 Air Conditioning Plants (Fig. 35)

4.6.1 Air heaters controlled on the steam side For air heaters controlled on the steam side, the following applies with

regard to condensate discharge (see also Section 4.8. “Counterflow Heat Exchangers, Controlled”):

The pressure in the steam space and the condensate load may vary con-siderably, and at low-load conditions even a vacuum may form at times. Air will then enter the steam space and will have to be discharged rapidly when the heating capacity has to be increased again. To avoid thermal stratification in the heated air and also to prevent waterhammer, banking-up of condensate must be avoided even at low load. This requires a sufficient pressure head (no back pressure); the condensate should drain by gravity.

Special requirements of the trap:- As with all controlled systems, the steam trap must immediately

respond to varying operating conditions (pressure, flowrate) to avoid the accumulation of condensate.

- Even at a very low pressure head, the condensate that is formed must be discharged.

- The steam trap should air-vent the plant automatically, both at start-up and in continuous operation.

Recommended traps:- UNA Duplex, MK with N capsule (MK with H capsules for large flowrates)

Fig. 35

Page 50: Steam Trap

50

4.6.2 Air humidifiers To obtain a uniform air humidity without droplets of water, the steam

should be dry. Therefore, it should be dried mechanically before being fed to the steam pipe (jet tube) (see Section 4.1.1 “Steam driers”).

Special requirements of the trap: The condensate, which is practically at saturation temperature, should be

discharged without any delay (no banking-up). Recommended traps:

- UNA Duplex- If there is a cooling leg, also MK with N capsule

4.7 Storage Calorifiers, ControlledE.g. for heating water (Fig. 36)

Warm water is not withdrawn continually, but more or less intermittently. Conse-quently, the heating process is also intermittent. Periods with a very light con-densate load (to make up the heat losses) at a very low pressure head alternate with periods of very heavy load at the maximum pressure head. To avoid water-hammer during low-load operation – where even a vacuum may form – the con-densate should be allowed to drain by gravity (no back pressure).Special requirements of the trap:- Immediate response to large fluctuations in pressure and flowrate- Good air-venting capacity, because air may enter the calorifier during periods

of low load; this air will have to be discharged when the load is increased again.

- Relatively large flowrate at a very low pressure headRecommended traps:- UNA Duplex, MK with N capsule (MK with H capsules for large flowrates)

Fig. 36

Page 51: Steam Trap

51

4.8 Counterflow Heat Exchangers, Controlled

4.8.1 Horizontal counterflow heat exchangers (Fig. 37)

These heat exchangers operate over the whole pressure range, from very low pressures (light load) down to vacuum, if only for short moments and up to the maximum admissible pressures.

The condensate flowrate varies accordingly. The extremely low operating pressures that are possible make drainage of the condensate by gravity desirable, not only upstream but also downstream of the trap.

Back pressure on the trap or lifting of the condensate is not recommen-ded. If this rule is not followed, waterlogging of the heating surface during periods of low load may cause waterhammer (see also Figs. 21 and 22). Banking-up of condensate can also be caused if the steam trap is too small.

For sizing the trap, besides considering the maximum flowrate at the maximum admissible pressure, the capacity of the heat exchanger in the low-load range has to be compared with the capacity of the trap at the reduced operating pressure. The trap has to be suitable for the worst possible conditions. If the data for low load cannot be obtained, the following rule of thumb can be applied: Effective differential pressure (working pressure) is approximately 50 % of the service pressure.

Assumed condensate flowrate for trap sizing = max. flowrate to be ex-pected at full load of heat exchanger.

Special requirements of the trap: No noticeable banking-up of condensate at all operating conditions, rela-

tively large flowrate at low pressures, perfect operation even in the vacuum range, automatic air-venting at start-up and during continuous operation.

Recommended traps:- UNA Duplex

Fig. 37

Page 52: Steam Trap

52

4.8.2 Vertical counterflow heat exchangersNo special measures need be taken.

4.8.3 Vertical counterflow heat exchangers with use of the sensible heatIn horizontal heat exchangers, waterlogging of the heating surface tendsto produce waterhammer, at least in cases where the steam is flowingthrough the tubes.In vertical heat exchangers, waterhammer will not normally occur, even ifthe heating surface is flooded. The sensible heat of the condensate maybe used directly by flooding part of the heating surface.Quite often the heat output of the heat exchanger is controlled through achange in the size of the heating surface (more or less banking-up) bymeans of a temperature control valve fitted in the condensate outlet (seeFig. 38).

If the heat exchanger is controlled on the steam side, a constant level canbe maintained by a float trap functioning as the level controller (see Fig.16). If the heat exchanger is controlled on the condensate side, live steamcan be prevented from passing (e.g. during start-up, at full load or on fai-lure of the regulator), by fitting a steam trap upstream of the temperaturecontroller.Special requirements of the trap:Control on the steam side:- Maintenance of a given constant condensate levelControl on the condensate side:- At low condensate temperatures, free passage as far as possible (little

flow resistance); closed at saturation temperature, at the latest

Product

Steam trap

Thermostatic

temperature controller

Steam

Air vent

Fig. 38 Constant pressure in the heating spaceVarying amounts of condensate accumulation, depending on load.

Page 53: Steam Trap

53

Additional requirement:As the condensate level has to be constantly maintained, the air in thesteam space can no longer escape by the condensate line. The steam space has to be provided with a separate air vent.Recommended traps:- Control on the steam side: UNA Duplex- Control on the condensate side: MK with N capsule or BK- For air-venting: MK or, for superheated steam, BK

4.9 Process Heat ExchangersHeat exchangers (preheaters) are used for heating the most varied products con-tinuously flowing through them. The steam supply pressures vary, depending onthe product temperature required. The heat exchangers may be controlled as afunction of the product outlet temperature or sometimes operated without any control.It is therefore only possible to give a few basic hints.Horizontal heat exchangers with the heating steam flowing through the tubestend to produce waterhammer if condensate is banked up. Therefore steam trapsshould be used which discharge the condensate without any banking-up. U-tube

bundles have less tendency to waterhammer (see Figs. 37 and 39).Vertical heat exchangers with the heating steam flowing through the tube bundleoperate without waterhammer, even if condensate is banked up (for an example,see Fig. 38). Heat exchangers with the product to be heated flowing through thetube bundle and the steam circulating around the individual tubes also normallyhave no tendency to waterhammer.The rated capacity of a heat exchanger is generally based on calculations assumingthat the heating surface is completely filled with steam. This point has to be con-sidered when choosing and sizing the traps for all types of heaters.Banking-up of condensate reduces the heating capacity.As far as controlled heat exchangers are concerned, the recommendations givenfor controlled counterflow units apply as appropriate (see Section 4.8).

Fig. 39

Page 54: Steam Trap

54

Special requirements of the trap:- These depend on the individual operating conditions (pressure, flowrate, bank-

ing-up of condensate allowable or even desirable, controlled or uncontrolled).- In any case, the steam trap should air-vent the preheaters automatically.Recommended traps:For controlled preheaters:- UNA Duplex, MK with N capsule (MK with H capsules for large flowrates)For uncontrolled preheaters, if banking-up is undesirable:- MK with N capsule, UNA DuplexFor uncontrolled preheaters, if banking-up is desirable:- MK with U capsule; BK with large undercooling adjustment

Page 55: Steam Trap

55

4.10 Digesters

4.10.1 Process digesters and pans (e.g. sugar factories, chemical industry, cellulose production) (Fig. 40)

During heating-up of a process batch, the steam consumption and con-sequently the amount of condensate formed are, in general, several times those during the boiling process. However, if the product is boiled and evaporated in one process (e.g. sugar boiling pans), the steam consump-tion and condensate flowrate remain quite high.

If the boiling process is not also an evaporation process (e.g. cellulose digesters), only the heat lost by radiation has to be replaced.

Compared to the starting condensate load – quite often even larger because of the low initial temperature of the product – the amount of con-densate formed when boiling is extremely small. Considering the size of the heating surface, air-venting through the steam trap alone may not be sufficient. The steam space has to be air-vented separately by thermosta-tic traps. This is of the utmost importance if the heating steam contains a large percentage of incondensable gases (for instance, sugar boiling pans heated with beet-juice vapour containing a considerable percentage of ammonia).

Special requirements of the trap:- Perfect discharge of very high condensate flowrates, the flowrate

during the heating-up process (possibly even at lower pressures) being a multiple of that formed during the boiling process

Additional requirement:- A separate air vent should be fitted to the steam space.

Recommended equipment:- For sugar pans and similar heat exchangers with very little pressure head

and no excessive differences in flowrate between the heating-up and boil-ing processes, the standard staged nozzle trap GK will do the job, other-wise TK.

- For higher pressures, UNA Duplex.- As air vent, MK with N capsule

Fig. 40

Page 56: Steam Trap

56

4.10.2 Boiling pans with heating coils (Fig. 41)

The same considerations apply to all boiling processes: The amount ofcondensate formed during heating-up is a multiple of that formed duringthe boiling process. This point should be considered when choosing andsizing the trap, particularly as banking-up of condensate caused by aninsufficient flowrate might lead to waterhammer. The steam trap shouldalso air-vent the boiling pan automatically, otherwise the time required forheating-up will be longer.Special requirements of the trap:- Large start-up load- Good air-venting capacityRecommended traps:- At low pressures and up to medium flowrates: MK 20, otherwise MK

with N capsule

Fig. 41

Page 57: Steam Trap

57

4.10.3 Jacketed boiling pans (Fig. 42)

The condensate load is highest during heating-up and lowest during the boiling process (see also Section 4.10.1). Because of the large steam space, a considerable amount of air has to be discharged during start-up. For small boiling pans, a steam trap with automatic air-venting capacity is sufficient. For large boiling pans, a thermostatic trap should be fitted as a separate air vent.

To prevent the jacket collapsing if a vacuum is formed, a GESTRA DISCO non-return valve RK should be used as vacuum breaker.

Special requirements of the trap:- Large start-up and air-venting capacity

Additional requirement:- In the case of large boiling pans, a separate air vent should be fitted to the

steam space; provide a vacuum breaker if it is possible that a vacuum may form.

Recommended traps, also as air vents:- MK with N capsule- At extremely low steam pressures (< 0.5 barg ): UNA Duplex- RK as vacuum breaker

Venting:- MK with H capsule or N capsule

Fig. 42

Page 58: Steam Trap

58

4.10.4 Tilting pans (Fig. 43)

The condensate is drained via a siphon which starts at the bottom of the steam jacket. The condensate must be lifted to the rotating joint of the pan and hence flow towards the trap. This process requires a trap with a con-stant and sufficiently large pressure head which if necessary must be pro-duced artificially (e.g. using a bypass for a float trap).

Special requirements of the trap:- Generation of a sufficient pressure head (the trap should not shut off

tight) and good air-venting capacity Additional requirement:

- For large boiling pans at least, a thermostatic trap should be fitted as air vent.

- Provide a vacuum breaker for the reasons mentioned in Section 4.10.3.- Arrange air venting opposite to steam inlet.

Recommended traps:- UNA 14/16 Simplex R with venting pipe- RK as vacuum breaker

Venting:- MK with H capsule or N capsule

Fig. 43

Page 59: Steam Trap

59

4.11 Brewing Pans (Coppers, Mash Tubs) (Fig. 44)

These are mainly large jacketed heating pans, frequently with various heating zones and different steam pressures.Characteristics of the mashing process:- High steam consumption during heating-up,- alternating with relatively low consumption during cooking.Characteristics of the brewing process:- Large steam consumption during heating-up, whereby the pressure may drop

considerably as a result of overloading of the steam system This is followed by a uniform steam consumption at constant pressure during the entire evaporation phase. In both cases, a large amount of air has to be discharged at start-up.Special requirements of the trap:- Discharge of very large condensate flowrates without any banking-up, to avoid

waterhammer and to obtain the full heating capacity at each stage of the evap-oration process

- Particularly good air-venting capacityAdditional requirements:- Separate air-venting of the heating surface with thermostatic traps (type MK)- Prevent the formation of vacuumRecommended traps:- For small and medium pans: UNA 14/16 Duplex.- For large pans: UNA 2 Duplex, large-capacity trap with thermostatic pilot

control TK- RK as vacuum breakerVenting:- MK with H capsule

Fig. 44

Page 60: Steam Trap

60

4.12 High-Capacity Evaporators (Fig. 45)

Besides distilling (see Section 4.13) and brewing (see Section 4.11), there are many industries where evaporation processes are necessary to boil down (i.e. concentrate) the product by evaporating part of its liquid content. This can be effected in a continuous, multiple-effect evaporation plant (e.g. sugar factory) or in batches. During continuous evaporation, apart from the start-up phase, the condensate load remains stable at a relatively constant pressure head. Batch evaporation is different: the condensate load during heating-up is considerably larger (depending on the initial temperature of the product to be heated) than during the evaporation phase, and then remains relatively constant.To obtain maximum evaporation capacity, proper air-venting of the steam space is of the utmost importance.In this connection, the following has to be considered:a) In the case of the continuous process, the vapours of the product to be evap-

orated – e.g. from an evaporator stage operating at higher pressure – can be reused as heating steam having a correspondingly high percentage of gas;

b) The steam space is relatively large, so that air-venting – even with batch evap-oration – by the steam traps without causing steam losses is very difficult. It is therefore recommended that thermostatic traps be fitted as additional air vents.

Special requirements of the trap:- Discharge of large flowrates, often at a very low pressure head- Good air-venting capacity Additional requirement:- Separate air-venting of the steam space

Fig. 45

Page 61: Steam Trap

61

Recommended traps:- For the continuous evaporation process, the type GK can be used (manual

stage nozzle; robust and simple design).- For the batch evaporation process, the TK is better suited (thermostatic pilot

control permits automatic adaptation to varying operating conditions).- For high pressures, UNA Duplex.- As air vent, MK with N capsule.

4.13 Stills (Fig. 46)

To obtain maximum evaporation capacity, the heating surface should always be kept free of condensate. Even the slightest banking-up of condensate may con-siderably affect the capacity of small stills, such as those used in the pharmaceu-tical industry for the production of essences and in laboratories.Special requirements of the trap:- The trap should drain the condensate as it forms, which is of particular impor-

tance for small stills and is complicated by the fact that the condensate is relatively hot (very little undercooling).

- A frequent change of the batches requires perfect start-up venting of the still.Additional requirement:- If required, fit a separate air vent and vacuum breaker.Recommended traps: - MK with N capsule, UNA 14/16, UNA 2 Duplex- RK as vacuum breakerVenting:- MK with H capsule or N capsule

Fig. 46

Page 62: Steam Trap

62

4.14 Rotating Drying Cylinders (e.g. for paper machines, calenders, corrugated-cardboard machines) (Fig. 47)

For drying and glazing processes, exact and uniform maintenance of the requi-red cylinder surface temperature is of prime importance. This can only be obtai-ned by trouble-free condensate drainage from the cylinder. Air concentrations inthe cylinder must be avoided, as they would lead to a local reduction in heatingtemperature and consequently lower surface temperatures. The condensate is lifted from the cylinder by a bucket or a siphon pipe.If a bucket is used for condensate handling, the steam trap and the pipeline lea-ding to the trap must be able to take up the whole bucket contents. Efficient air-venting of the cylinder, particularly during start-up, is important.If the cylinder is provided with a siphon, an adequate pressure drop towards thetrap must be provided to ensure that the condensate is lifted out of the cylinder.For low-speed machines in laundries etc. a standard thermostatic trap (MK) isnormally adequate. For high-speed machines, it is necessary to ensure a certainleakage of steam in relation to the rotational speed, in order to prevent formationof a condensate film. This can be done with the BK through adjustment for a cer-tain steam leakage and with the UNA through internal or external bypass.Special requirements of the trap:- Automatic air-venting at start-up and during continuous operation- For cylinders with siphon drainage, the trap must ensure a constant pressure

drop (i.e. must not close during operation) and must permit a slight leakage oflive steam, particularly at higher cylinder speeds.

EBypass

if required

Fig. 47

Page 63: Steam Trap

63

Additional requirements:- The steam trap should be monitored for banking-up of condensate through a

sightglass (to be installed upstream of the trap, see GESTRA Vaposcope). Insome cases, it is required that the traps do not close when faulty.

Recommended traps:- UNA Duplex, if necessary with internal or external bypass, with lifting lever and

sightglass cover.

4.15 Baths and Tanks(e.g. for cleaning and pickling)

4.15.1 Heating coils with uniform fall and condensate discharge at base(Fig. 48) With this arrangement, waterhammer does not normally occur. For temperature-controlled baths, this is the only recommended arrangementof the heating coils. In general, the following applies to controlled plants:At low heating capacities, when the control valve is throttled strongly, thepressure in the heating coil may drop to vacuum. To prevent banking-up ofcondensate, the condensate should drain by gravity (no back pressure).Special requirements of the trap:- These depend on the operation of the heat exchanger (controlled or

uncontrolled).Recommended traps:- For simple, manually controlled heating processes: BK, MK

with N capsul.- For controlled heating processes: UNA Duplex, MK with N capsule

Fig. 48

Page 64: Steam Trap

64

4.15.2 Acid baths

For safety reasons, the heating coil must not be led through the wall of thevat. The condensate must be lifted (immersion heater principle). To pre-vent waterhammer, the condensate should fall towards a compensator(see Fig. 49a). For small-sized pipes, it suffices to provide a loop seal (seeFig. 49b).Special requirements of the trap:- No intermittent operation, which might cause waterhammer by an

abrupt stop or start of the flowRecommended traps:- BK (if the plant layout is unfavourable, the tendency to waterhammer

may be eliminated by special adjustment of the trap)- MK with N capsule

a) b)

Fig. 49

Page 65: Steam Trap

65

4.16 Band Driers (Fig. 50)

To obtain the rated drying capacity (guaranteed performance), it is essential thatthe individual heating units can produce the maximum heat. This implies that theheating surfaces are completely filled with steam and there is no banking-up ofcondensate and no air in the steam spaces (efficient air-venting). The heatingunits require individual drainage by means of an appropriate trap. If the flashsteam cannot be utilized anywhere else in the plant, it may be useful to heat anadditional heating unit (e.g. inlet section) with the flash steam or even with all thecondensate formed in the other heaters. When choosing the steam trap, thesmall space available for installation should be considered as well as the fact thatthe fitting of the steam traps inside the machine casing, which is frequentlyrequested, results in relatively high ambient temperatures. Special requirements of the trap:- Condensate discharge without any banking-up

at relatively high ambient temperatures - Automatic air-venting- Small dimensionsRecommended traps:- MK with N capsule- If there is sufficient space available, UNA Duplex

Fig. 50

Page 66: Steam Trap

66

4.17 Hot Tables, Drying Platens (Fig. 51)

These are used in many different process plants for drying and heating. Themaintenance of uniform surface temperatures which may have to be varied is offundamental importance. The best method of achieving this is to connect the different sections in paralleland to provide a separate steam supply and steam trap for each section. Thisprevents the various sections interfering with each other (e.g. as a result of thedifferent pressure drops).If they are connected in series, which is often the case, condensate accumulatesin heating platen at the end of the system, which may cause a reduction in thesurface temperature. Furthermore, the single steam trap cannot air-vent the sec-tions efficiently. To attain a heating performance which is equivalent to that of aparallel arrangement, at least “blow-through” steam traps are needed.Special requirements of the trap:- Condensate discharge without banking-up at relatively high temperatures- Efficient air-ventingRecommended traps:- MK with N capsule- UNA Duplex

Fig. 51

Page 67: Steam Trap

67

4.18 Multi-Platen Presses (Fig. 52)

4.18.1 Multi-platen presses connected in parallel

These presses require uniform and equal temperatures over the completesurfaces of individual platens, which means that the individual heating surfa-ces must be fed with steam of the same heating capacity. The steam shouldtherefore be dry (drainage of steam main), the steam pressure in all platensmust be equal (no air inclusions reducing the partial steam pressure) and thesteam space must be free of condensate (poor heat transmission, lower hea-ting temperature than steam). The letter requires a free flow of the conden-sate towards the trap.There is no guarantee that the pressure drop across the various platens is thesame. To avoid banking-up of condensate, each parallel heating surfaceshould be drained by its own trap.Special requirements of the trap:- As the condensate is to be discharged without any banking-up, the

steam trap must drain the condensate practically at saturation tempe-rature. At the same time, it must air-vent the plant properly. The fasterthis is done at start-up, the shorter the heating-up period.

Recommended traps:- MK with N capsule- UNA Duplex

Fig. 52

Page 68: Steam Trap

68

4.18.2 Multi-platen presses connected in series (Fig. 53)

As already explained in Section 4.18.1, the drainage of heating platensconnected in parallel by a single trap is problematic, as this may lead tobanking-up of condensate in the individual platens and consequently to areduction in the surface temperatures.Small heating platens may be connected in series, provided the conden-sate is free to flow towards the trap.Special requirements of the trap:- The trap must discharge the condensate as it forms, so that banking-

up of condensate in heating space is reliably avoided.Recommended traps:- MK with N capsule- UNA 14/16 Duplex

Fig. 53

Page 69: Steam Trap

69

4.19 Tyre Presses (Vulcanizing Presses) (Fig. 54)

For vulcanizing, uniform surface temperatures are absolutely vital. This necessi-tates feeding of the heating surface with pure steam only (no condensate in thesteam space), equal steam pressures in the individual sections (same tempera-ture drop) and no air inclusions in the steam (impairing the heat transfer).The layout of the press, the steam line and the condensate line should guaranteea free flow of the condensate.Good steam distribution giving equal steam pressures in the individual sectionsis not possible unless the sections are connected in parallel. To avoid banking-up of condensate, each section should be drained by its own trap.Special requirements of the trap:- Condensate discharge without banking-up, but also without loss of live steam- Good air-venting capacity (for short heating-up periods)Recommended traps:- MK with N capsule

Fig. 54

Page 70: Steam Trap

70

4.20 Vulcanizers (Fig. 55)

The jacket and the steam-injected vulcanizing chamber require separate drainage. Draining the jacket is no particular problem.In general, any steam trap with good air-venting capacity will do the job satis-factorily.The vulcanizing chamber must be drained (see Section 4.21 “Autoclaves”) with-out any condensate remaining. In addition, when selecting the steam trap, it should be noted that the condensate may be acidic.Separate air-venting of the large chamber by means of a thermostatic trap is recommended, even if the air is initially vented through a manually operated valve.Special requirements of the trap:- Drainage of the chamber without any banking-up of condensate- Resistant to acid condensateAdditional requirement:- Efficient air-venting of the steam spaces, whereby the vulcanizing chamber

should be vented separatelyRecommended traps:- For the jacket: MK, BK- For the vulcanizing chamber: MK with N capsule, BK, UNA Duplex For contaminated condensate, UNA Duplex is the better choice. For acid condensate, the particularly robust BK and UNA Duplex completely of

austenitic materials (18 % chromium steel) should be used.- As air vent, MK with N capsule or H capsule.

Fig. 55

Page 71: Steam Trap

71

4.21 Autoclaves (Fig. 56)

The steam is fed directly into the chamber containing the product. There shouldnot be any condensate in the autoclaves, as splashes from the boiling conden-sate might damage the product and condensate collecting in the bottom of theautoclave may cause high thermal stresses. Frequently, air accumulations in therelatively large steam space (which may lead to layers of varying temperature)cannot be discharged by the steam trap alone and air vents are also required. Asa rule, the condensate is more or less heavily contaminated.Special requirements of the trap:- Condensate discharge without any banking-up, even at start-up, with the low

pressures and large amounts of condensate formed; unaffected by dirt; highstart-up air-venting capacity

Additional requirement:- Automatic thermostatic air-vent- For heavily contaminated condensate, provide a vessel for trapping the dirt

particles upstream of the trap (e.g. settling tank with GESTRA blowdown valve;see Fig. 56b)

Recommended traps:- UNA Duplex- MK with N capsule

Fig. 56a

PA

Fig. 56b

Page 72: Steam Trap

72

4.22 Ironing Presses, Garment Presses (Fig. 57)

Here we have to differentiate between presses used only for ironing and thoseused for ironing and/or steaming.In the first case, only the heating surfaces have to be drained, which presents noreal problems. Most important is that the condensate is free to flow towards thetrap. Fundamental rule: Each ironing unit is drained by its own trap.Under unfavourable conditions, it may happen that the upper and lower part of apress are not properly drained by a single trap unless the trap is adjusted to passa slight amount of live steam.As this causes live-steam wastage, it is more economic in the long run to draineach part individually by its own trap.Dry steam is required for the steaming process; if necessary, a steam drier shouldbe mounted upstream of the press. Sudden opening of the steaming valve mustnot cause carry-over of condensate particles, as this would spoil the garment. Ifdifficulties occur due to a poor plant layout, these may perhaps be compensatedby a trap adjusted to pass live steam, which of course leads to steam losses.The replacement of a trap operating entirely without live-steam loss (e.g. in thecase of wet ironing presses) by a trap passing live steam in order to change a“wet” press into a “dry” press is therefore not recommended.

Fig. 57

Page 73: Steam Trap

73

Special requirements of the trap:- Operation without steam loss, and as far as possible without banking-up of

condensate- Good air-venting capacity, which reduces the heating-up period when starting

the unitAdditional requirement:- Provide steam driers to obtain dry steamRecommended traps:- MK with N capsule

4.23 Steaming Mannequins(See Section 4.22, steaming process) (Fig. 58)

Fig. 58

Page 74: Steam Trap

74

4.24 Ironers and Calenders(Hot mangles) (Fig. 59)

High and uniform temperatures over the whole heating surface are very important.A large drying capacity is also expected (for a high ironing speed). This requiressteam traps discharging the condensate as it forms and efficient air-venting of thebed. For multi-bed machines, each bed should be drained separately by its owntrap. As the bed is rather wide, even a trap with a good air-venting capacity maynot be able to properly air-vent the bed without causing live-steam loss. If air isincluded in the steam, the temperature drops in some places, mostly at the endsof the bed. Therefore the bed should be air-vented separately at either end by athermostatic trap.Special requirements of the trap:- Condensate discharge without any banking-up, even at high ambient tempe-

ratures, as the steam traps are usually installed within the enclosed machine- Good air-venting capacity, both at start-up and during continuous operationAdditional requirement:- Air-venting the beds is of particular importance. Frequently, surface tempera-

tures that are too low can be caused by insufficient air-venting. A good solu-tion is to fit MK traps as thermostatic air vents at both ends of the bed.

Recommended traps:- UNA Duplex- MK with N capsule, MK with H capsules for large flowrates (if required for the

first bed)

Fig. 59

Page 75: Steam Trap

75

4.25 Dry-Cleaning Machines

The air heater, the still and, if possible, the steam supply line at its lowest pointhave to be drained. The batch operation requires rapid discharge of the air enter-ing the machine when it is shut down (reduction of the heating-up times). Steamtraps ensuring automatic air-venting should therefore be preferred. Particularly inthe still, banking-up of condensate may be undesirable, as the distilling time willbe extended. New machines can also present a problem, since there may well bedirt (such as welding beads, scale etc.) still left inside the machine.Special requirements of the trap:- Condensate discharge without banking-up (important for the still); automatic

air-venting- Unaffected by dirt or protected against dirt particles- Small dimensions; installation in any position to be able to fit the traps inside

the machine without any difficulty- Unaffected by waterhammer, as the steam is frequently admitted by solenoid

valvesRecommended traps:- MK with N capsule

Fig. 59a

Condensate drying

Condensate distillation

Page 76: Steam Trap

76

4.26 Tracer Lines (Fig. 60)In many cases, the heating steam does not transmit any heat to the productduring normal operation. Steam tracing only ensures that in the case of pumpfailure, for example, the product temperature does not fall below the minimumtemperature allowable.The condensate flowrate during normal operation is therefore mainly determinedby the heat losses (through radiation and convection) of the condensate line be-tween tracer and steam trap. Noticeable heat savings can be obtained by re-ducing the heat losses of the condensate lines. Apart from the obvious methodsof good insulation and the shortest possible distance between the product lineand steam trap, banking-up in the condensate line (reduction of the length ofpipe filled with steam) can further limit heat losses. One point, however, must beconsidered: in the case of a failure (such as a product pump stopping), the con-densate flowrate can increase considerably, producing a larger accumulation ofcondensate with a corresponding undercooling. The maximum allowable degreeof undercooling depends on the minimum product temperature to be maintained.

Fig. 60 Maximum length of tracer linesThe maximum length of the tracer lines depends on the number of risers andwater pockets as well as on the number of pipe bends. A tracer line with arelatively straight run might have a length of 80 m (260 ft), including the sup-ply line from the steam header and the length to the condensate header. Inprocess plants, the tracer lines must be considerably shorter, because of themany risers and changes in direction. The sum of all rising lines should thennot exceed 4 m.

Page 77: Steam Trap

77

For products with pour points < 0 °C, heating is only required if there is frost. The amount of steam required for winterizing can be considerably reduced if heating of the product is restricted to periods with actual frost or the risk of frost.Special requirements of the trap:- If the heating process permits, a certain amount of banking-up in the conden-

sate line upstream of the trap is advantageous (heat savings)Recommended traps:- Thermostatic traps only, such as BK, possibly with large undercooling adjust-

ment- MK with U capsule (t 30 K below saturation temperature)- UBK for low discharge temperatures > 80 °C, e.g. with open condensate

discharge

4.27 Jacketed Tracing Lines (Fig. 61)

Jacketed tracing lines are normally used for heating heavy products, such as sulphur and bitumen. The entire heating surface should be fed only with dry steam. Each tracer line should not exceed a length of 30 m (100 ft).In the case of a high heat load, the tracer line should be provided with an addi-tional steam trap.Special requirements of the trap:- No banking-up of condensate in the heating surfaceRecommended traps:- BK- MK with N capsule

Fig. 61

Page 78: Steam Trap

78

4.28 Instrument Tracing (Fig. 62)

Instrument tracing in refineries and petrochemical plants is characterized by verysmall condensate flowrates, while often the individual instruments must be hea-ted only to low temperatures. In this case, the effective heating surface should beheated with condensate only.Special requirements of the trap:- Discharge of very low flowrates with a high undercoolingRecommended traps:- MK with U capsule (t 30 K below saturation temperature)- UBK with a discharge temperature > 80 °C

Measuring orifice

Product line

TracerInstrumentsensing lines

VFrom steam header

Instrument casewithheating coil

Condensate header

Pre-insulated tracer lines

If removable pipe connections are desired:

provide cutting-ring joints

Fig. 62

Page 79: Steam Trap

79

4.29 Tank Heating (Fig. 63)

Tank heating may vary considerably, depending on the size and the purpose ofthe tank.Heating may be temperature-controlled or uncontrolled, which affects the con-densate discharge. Condensate discharge is further influenced by the layout ofthe heating sections (horizontal, in the form of heating coils or finned-tube heat-ers with little fall towards the trap, or vertical as immersion heating elements).

Safetyembankment

Condensatelin

e

Steamlin

eDN 20

DN 20

Condensate discharge from tanks

Condensate discharge from asphalt tanks

Safetyembankment

Condensatelin

e

Steamlin

e

Fig. 63 Condensate discharge from heated tanks

Page 80: Steam Trap

80

Uncontrolled heating is frequently applied if little heat is required to maintain the product storage temperature. Because of the reduced steam flow (perhaps because of a manual control valve heavily throttled), the pressure in the heating section is decreased considerably. It is possible that the small pressure head available may no longer be sufficient to completely discharge the condensate. The consequence is banking-up of condensate, which may be desirable for reasons of heat savings (use of the sensible heat of the condensate), but on the other hand may cause waterhammer. As a basic rule for uncontrolled heating systems, the following applies:It is essential that the heating elements and condensate lines to the trap be arran-ged to maintain a constant fall in the direction of flow. For the use of the sensible heat of the condensate by banking-up upstream of the trap, vertical heating sec-tions are ideal (no danger of waterhammer). The steam trap should be sized to ensure a sufficient flowrate.As regards controlled tank heating (with immersion heat exchangers, for in-stance), in principle the same applies as for storage calorifiers (see Section 4.7).The condensate line leading to the trap should be arranged to provide a constant fall, i.e. no back pressure downstream of the trap.Special requirements of the trap:- Discharge of relatively large condensate flowrates, also at a low pressure head- If necessary and required, discharge of the condensate with undercooling- For controlled tanks, a rapid response to fluctuations in pressure and flowrate- Automatic air-venting- Ability to withstand frostRecommended traps:- For uncontrolled plants: BK, MK with U capsule- TK for large flowrates- For controlled plants: UNA Duplex, MK with N capsule- MK with H capsules for large flowrates

Page 81: Steam Trap

Page5. Monitoring of Steam Traps

5.1 Visual Monitoring of the Discharge 83

5.1.1 Checking traps with open discharge by the size of the “steam cloud” 83

5.1.2 Checking with a sightglass downstream of the trap 84

5.1.3 Checking with a sightglass upstream of the trap or with a test set 84

5.1.4 Checking the operation of float traps 84

5.2 Checking by Temperature Measurement 86

5.3 Checking by Sound 86

5.4 Continuous Monitoring of Steam Traps 88

Page 82: Steam Trap

Steam Trap Technology Tailored to Your Needs

Rhombusline – Fitted for the Future

Features

Compact, rhombus-shaped cover

design makes for easy installation and

maintenance

Recessed cover gasket

Large-surface strainer

Wide variety of end connections:

flanges to DIN and ANSI, butt-weld

ends, socket-weld ends, screwed

sockets

Optional extra: integrated steam

trap monitoring

Page 83: Steam Trap

83

5. Monitoring of Steam Traps

Effective checking that steam traps are operating correctly without banking-up or loss of live steam is a subject often discussed. The many checking methods that are used in practice range from useful to practically useless.

5.1 Visual Monitoring of the Discharge

5.1.1 This involves checking traps with open discharge by the size of the “steam cloud”. This is the most uncertain method, since it is not possible to distinguish between flash steam and live steam. The size of the steam cloud depends mainly on the service pressure and the amount of con-densate formed; they determine the amount of flash steam (see Fig. 64).

Fig. 64 ExampleFor an expansion from p1 = 10 bar to p2 = 0 bar; the volume of cold water remains practically the same,that of saturated steam increases from V1 = 1 m3 to V2 = 9.55 m3,that of boiling hot water increases from V1 = 1 m3 to V2 = 245 m(due to the formation of flash steam), andthat of hot water 20 °C below saturation temperature increases from V1 = 1 m3 to V2 = 189 m3.

Page 84: Steam Trap

84

Particularly at high service pressures, it is impossible to determine whetherlive steam is escaping with the condensate or not. Only with steam trapsoperating intermittently (e.g. thermodynamic, disc-type traps) may it bepossible to detect increasing wear over a period resulting in a higher liftfrequency of the valve disk.

5.1.2 Checking with a sightglass downstream of the trap.In principle, the same applies as mentioned in Section 5.1.1. However,there is even less evidence of trap operation, because in the small sight-glass space a small amount of flash steam produces a relatively high flowvelocity with the corresponding turbulence. In the case of steam trapsoperating intermittently, it is only possible to determine whether the trapis open or closing, but not whether live steam is escaping.

5.1.3 Checking with a sightglass upstream of the trap or with a test set. A properly designed sightglass installed upstream of the trap enables thesteam trap to be checked exactly. Checking is not masked by flash steam.In comparison to sightglasses mounted downstream of the trap, the onesmounted upstream must be capable of higher pressures and temperatures.This requires high-pressure bodies and glasses of high quality, which is anexplanation of their higher price.The Vaposcopes available from the GESTRA product range are perfectlysuited for visual monitoring of steam traps (see Fig. 65). Vaposcopesinstalled immediately upstream of the trap ensure ideal monitoring of thetrap. They then not only reveal the slightest live steam loss, but also thesmallest amount of banking-up of condensate. Banking-up in the con-densate line only is of no importance for the heating process. To monitorthe heating surface for banking-up, the installation of a second Vaposcopeimmediately downstream of the heat exchanger is recommended for themore critical heating processes (see Fig. 66).

5.1.4 Checking the operation of float traps.The UNA 23 is available with a sightglass cover, so that it is possible tosee whether the trap is waterlogged or whether live steam can escape viaits orifice.

Page 85: Steam Trap

85

Fig. 65 Functional principle of the GESTRA Vaposcope

Normal service condition

Banking-up of condensate

Loss of live steam

Condensate, steam and air are direc-ted through the water seal by the deflector. As the specific gravity of steam is lower than that of conden-sate, the steam passes over the condensate and depresses the con-densate level.

The deflector is immersed in the water.

Complete flooding of the Vaposcope indicates banking-up of condensate. If the Vaposcope is installed immedi-ately downstream of the heat exchanger, it is to be expected that this too will be at least partially filled with water.

The water level is being considerably depressed by passing live steam. The steam, which is invisible, fills the space between deflector and water level.

Page 86: Steam Trap

86

5.2 Checking by Temperature Measurement

The measurement of the temperature in the pipeline upstream of the steam trap is another problematic method frequently applied to heat exchangers where banking-up of condensate is undesirable.Under certain circumstances, the operation of a trap may be judged by measuring the surface temperature at different points of the pipeline, e.g. immediately up stream of the trap, immediately downstream of the heat exchanger, or at the steam inlet.It must, however, not be forgotten that the temperature depends on the service pressure at the measurement point, the percentage of incondensable gases in the heating steam (with the consequent reduction in the partial steam pressure and hence the temperature) and the condition of the pipeline surface. When selecting the measurement point, it must also be considered that even without banking-up the condensate temperature may be below the saturated steam temperature.Measuring the temperature downstream of the trap can only serve as an indication of the pressure in the condensate line. Checking the steam by this method is not possible.

5.3 Checking by SoundThe method of checking trap operation by means of a stethoscope, which is quite often encountered, is only of some practical use in the case of traps with intermittent operation. With these traps, the opening and closing process can be clearly differentiated. The lift frequency of the valve disc permits conclusions to be drawn as to the mode of operation of the trap; whether live steam is escaping or not, however, cannot be determined.Ultrasonic measurements of the structure-borne noise produced by the trap are of far greater importance. This method is based on the fact that steam flowing through a throttling element produces higher ultrasonic vibrations than flowing water (condensate) does. The GESTRA Vapophone ultrasonic detector VKP has given proof of its excellent performance.The mechanical ultrasonic vibrations generated at the seat or orifice of a steam trap are picked up by the probe of the VKP and converted into electrical signals, which are then amplified and indicated on a meter.

Fig. 66

Page 87: Steam Trap

87

When evaluating the measurement results, however, it must be taken into account that the noise intensity depends only partly on the amount of flowing steam. It is also influenced by the condensate amount, the pressure head, and the source of sound, i.e. the trap type. With some experience on the part of the tester, good results are obtained when checking traps with condensate flowrates up to about 30 kg/h and pressures up to 20 bar (290 psi), whereby steam losses as low as approx. 2 - 4 kg/h can be detected.

At the casing surface of a steam trap, the VKP 10 detects the structure-borne sound of flowing steam. The display is evaluated manually by the operator.Thanks to the GESTRA steam trap testing and diagnostic system VKP 40, the checking of steam traps has been automated. The system can be used individually for all types and makes of steam traps. A preprogrammed data collector is used in the system to record the measurement values. Trap-specific software settings are taken into account during the measurement! After the data have been transferred and stored in a PC, their evaluation can commence. Comparison with the historic data within the software package forms the basis of a steam trap management system.

Fig. 66a Ultrasonic detector for checking trap operation – Vapophone VKP 10

Fig. 66b Ultrasonic system for monitoring trap operation – TRAPtest VKP 40

Page 88: Steam Trap

88

5.4. Continuous Monitoring of Steam TrapsThe test set VKE is used for monitoring steam traps to detect the leakage of live steam, the banking-up of condensate, and electrical problems. Up to 16 steam traps can be monitored continuously by means of the central monitoring unit NRA 1-3. All the limit values of the test system are preset at the factory. The plant-specific set points are automatically collected and stored by the NRA 1-3. Because the plant temperature is registered, false alarms caused by start-up and shut-down processes in the installation are detected and corrected by the test system. To optimize the process, the operator can access an error log in the test set. A preset maintenance interval reminds the customer when the test set is due for servicing.Individual adaptations of the test set can easily be carried out by the customer.In the event of steam loss, condensate banking-up or an electrical problem, this is indicated at the test station by a display and red LEDs. The test set can be adjusted with the aid of a keyboard at the monitoring station NRA 1-3.Relay output contacts are available as an interface to other control units.The test system can be used for steam traps of all types and makes.Float traps used in time-critical applications can be monitored in a special evalu-ation mode with a response time < 15 seconds.

Fig. 67 System VKE * Combination possible

Remote monitoring Rhombusline*

Remote monitoring with Universal Test Chamber*

Page 89: Steam Trap

Page6. Using the Sensible Heat of the Condensate

6.1 Basic Considerations 91

6.2 Examples for the Use of the Sensible Heat of Condensate 91

6.2.1 Banking-up in the heat exchanger 91

6.2.2 Flash-steam recovery (closed condensate system) 93

7. Air-Venting of Heat Exchangers 94

8. Condensate Return Systems 95

Page 90: Steam Trap

Seite9. Entwässerung von Druckluftanlagen 99

Seite9. Entwässerung von Druckluftanlagen 99

Steam Trap TechnologyTailored to Your Need

Rhombusline – Fitted for the Future

The following optional items forRhombusline steam traps BK 45, BK 46, MK 45 and UBK 46 areavailable on request.Integrated temperature monitoring

(PT 100 element with connector for monitoring steam traps for banking-up of condensate). Strainer remains fitted.

Integrated level probe for detecting steam loss (in combination with hand-held test unit NRA 1-2 or remote test unit NRA 1-1). Strainer omitted.

Features

Compact, rhombus-shaped coverdesign makes for easy installation andmaintenanceRecessed cover gasketLarge-surface strainerWide variety of end connections:

flanges to DIN and ANSI, butt-weld ends, socket-weld ends, screwed sockets

Optional extra: integrated steam trap monitoring

Page 91: Steam Trap

91

6. Using the Sensible Heat of the Condensate

6.1. Basic ConsiderationsIn a steam-heated heat exchanger, normally only the heat of vaporization (latent heat) is transmitted to the product being heated. To achieve the maximum rate of heat transfer, the condensate has to be discharged immediately it is formed. The heat contained in the condensate (the sensible heat) is discharged with the con-densate. It forms a considerable percentage of the total heat content, which increases with the pressure. At a service pressure of 1 bar, for example, the pro-portion of sensible heat is 19 % of the total heat content of the steam, whilst at a pressure of 10 barg it is 28 % and at a pressure of 18 barg 32 % (see steam tables in Fig. 83).If the condensate is discharged into the open and not re-used, a large part of the heat energy required for steam generation is lost. In addition, further costs are incurred because the feedwater has to be completely made up.It is therefore general practice to collect the condensate as far as possible and to re-use it for steam generation or at least as service water for the plant.The use of the flash steam formed as a result of the pressure drop of the con-densate – from the service pressure in the heat exchanger to the pressure in the condensate line – poses greater problems. If the condensate is discharged to atmosphere (open condensate system) then flashing, besides being a nuisance to the environment, may lead to considerable heat losses even if the conden-sate is re-used. Thus the heat losses referred to the total heat energy produced are 3.2 % at a service pressure of 1 barg, 13 % at 10 bar, and 17 % at 18 bar. The amount of flash steam formed at various pressures and back pressures is shown in Fig. 68.

6.2 Examples for the Use of the Sensible Heat of Condensate

6.2.1 Banking-up in the heat exchanger Through banking-up, part of the heat contained in the condensate is used

directly for the heating process. In extreme cases, the amount of heat withdrawn from the condensate can be so high that flashing no longer occurs when the condensate is discharged. This requires, however, an extra-large heat exchanger so that the necessary heating capacity and temperature are reached. In addition, the heat exchanger must be design-ed to avoid waterhammer (e.g. vertical counterflow heat exchanger or pre-heater, as shown in Fig. 38).

In heat exchangers without temperature control, banking-up can easily be effected with thermostatic traps discharging the condensate with a given undercooling (BK with undercooling adjustment; MK with U capsule; UBK).

In controlled heat exchangers, the control valve must be fitted on the con-densate side and not on the steam side.

Page 92: Steam Trap

92

00.2 0.3 0.4 0.6 0.8 1.0 2 3 4 5 6 8 10 20 30 40 50

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.25

0.5

1

2

1.5

3

4

56 7 8

15

25

30

402

0

109

Gauge pressure upstream of steam trap [bar]

Fla

sh

ste

am

inkg

/kg

co

nd

ensate

0G

auge

pre

ssure

dow

nst

ream

ofst

eam

trap

[bar]

Fig. 68 Amount of flash steamAmount of flash steam formed when boiling condensate is reduced in pressure.

Page 93: Steam Trap

93

6.2.2 Flash-steam recovery (closed condensate system). The flash steam is used for heating secondary heat exchangers and the condensate is re-turned to the boiler house. This method cannot be applied unless at least two different steam pressures are required in a plant (Fig. 69).

In smaller plants, the flash steam formed may be completely used in a single heat exchanger, such as a calorifier, heat exchanger for the pro-duction of warm water etc. (see Fig. 70).

Use of flash steam

Fig. 69 If the steam supply from the flash vessel is not sufficient, live steam is added via the pressure-reducing valve.

Fig. 70 Simple flash steam recovery with thermosiphon circulation. The amount of flash steam depends on the condensate flowrate and cannot be adapted to varying demand.

Page 94: Steam Trap

94

7. Air-Venting of Heat Exchangers

Air and other incondensable gases enter a steam plant particularly during periods ofshut-down. Insufficient deaeration of the feedwater is another way gases can get intothe plant. The use of vapours from evaporation processes as heating steam is yet an-other cause in some industries.Air and the other gases impair the heat transfer and, in addition, reduce the partialpressure of the steam and consequently the steam temperature. If a mixture of steamand air exists, the pressure gauge will indicate the total pressure in the steam space;the temperature measured here, however, corresponds only to the partial steam pres-sure and is lower than the saturation temperature relative to the total pressure. Theheat transfer rate drops in accordance with the reduced temperature difference be-tween steam and product (see Fig. 28).At a total pressure of 11 bara, for example, the temperature is 183 °C with no air pres-ent. The temperature drops to 180 °C with a proportion of air present of 10 % and to

170 °C with an air proportion of 35 %. We can conclude from this example that theair concentration is highest where the heating surface is coldest. This fact has to beconsidered when fitting the air vents.For small and medium heat exchangers, sufficient air-venting is generally provided bysteam traps with automatic air-venting capacity (all GESTRA steam traps ensure auto-matic deaeration).In large heat exchangers, such as boiling pans, evaporators and autoclaves, gasestend to concentrate at certain points, owing to the design of the steam space and theresulting flow conditions. In these cases, the steam space has to be deaerated sepa-rately at one or several points. GESTRA thermostatic traps of the BK and MK range areperfect as air vents, with the MK type especially suited for saturated steam systems.To speed up the air discharge from the steam space, it is recommended that an uninsulated pipe having a length of at least 1 m is fitted upstream of the air vent. Thecondensation of the steam in this pipe causes a local concentration of air with a corresponding temperature reduction, so that the trap opens more quickly and wider.An effective arrangement of air vents on a large heat exchanger is shown in Fig. 29.

Page 95: Steam Trap

95

8. Condensate Return Systems

To convey the condensate back to the steam generating plant, for example, a sufficient pressure head is required, be it purely by gravity, by using the steam pressure or by a combination of both. In large plants (with large condensate flowrates) or if the condensate has to be lifted, the back pressure might rise to an unacceptable level (e.g. in control plants, see inter alia Section 4.8.1). In this case, it is best to collect the condensate from the various sections of the plant separately.The condensate from the condensate tank is conveyed to the feedwater tank by level-controlled pumps (see Fig. 71).

Equipment1. Condensate recovery system consisting of1.1 GESTRA condensate tank1.2 Pressure gauge assembly1.3 Water-level indicator1.4 Pressure relief valve1.5 Drain valve2. Level control equipment2.1 GESTRA level-control electrode2.2 GESTRA measuring pot

2.3 Slide valve2.4 GESTRA switch cabinet3. Pump unit3.1 Condensate pump3.2 GESTRA DISCO non-return valve3.3 GESTRA stop valve3.4 GESTRA stop valve with throttling cone3.5 Pressure gauge assembly for pressure line

Fig. 71 GESTRA condensate collecting and return systems

Page 96: Steam Trap

96

To convey small to medium flowrates from distant parts of the plant, the use of a GESTRA condensate return system operating with a pump is a very economical solution. In this arrangement, steam is used to drive the condensate. The condensate flows into the condensate tank, which is at atmospheric pressure. As soon as the con-densate reaches the other level, a level-control electrode transmits a closing pulse to the solenoid valve in the vent line and simultaneously an opening pulse to the solenoid valve in the booster steam line. As soon as the minimum condensate level required in the tank is reached, a second electrode transmits a closing pulse to the steam valve and an opening pulse to the vent valve (see Fig. 72).

GESTRA steam-powered condensate-return units type FPS are available with float control requiring no auxiliary electrical energy.

Fig. 72 GESTRA condensate-return system operating without a pump type KH

Page 97: Steam Trap

Page9. Drainage of Compressed Air Lines 99

Page 98: Steam Trap

What are the advantages of GESTRA steam traps?

Easy maintenance – our traps can be checked, cleaned and repaired without being removed from the pipework

Interchangeable – our various trap types have standardized facetoface dimensions, sizes and end connections and are therefore interchangeable without any modification to the pipe layout.

Tight shutoff, without loss of live steam. Automatic airventing. Unaffected by dirt. Production tested – besides the legally required tests (e.g. hydraulic test)

our trap regulators are tested under operating conditions (steam, condensate). Complies with recognized standards –

our traps meet the relevant DIN standards and regulations and are in accordance with the AD bulletins (AD – Arbeitsgemeinschaft Druckbehälter = German pressure vessel regulations authority) with regard to choice of material, pressure and temperature ratings. On request test certificates to EN 10204.

Page 99: Steam Trap

99

9. Drainage of Compressed Air Lines

Atmospheric air always contains a small amount of water vapour. This amount can be equal to 100 % saturation, but not higher. 100 % saturation may be expressed as the maximum weight of water vapour in grams contained in 1 cubic metre of air and depends solely on the air temperature (Fig. 73).The amount of water vapour in the air – also called the absolute atmospheric humidity – is identical to the specific gravity of the saturated vapour at this temperature. The absolute humidity increases with rising temperatures and decreases with falling tem-peratures. The amount of vapour exceeding the saturation limit will condense.The actual weight of water vapour contained in 1 m3 of air, expressed as a percentage of the maximum amount of water vapour, is the relative humidity (100 % relative humi-dity = saturation quantity = absolute humidity).

Example:1 m3 of saturated air at 23 °C contains 20.5 g of vapour (absolute humidity). If this air is compressed from 1 bara to 5 bara and the air temperature is kept constant at 23 °C by cooling, the air volume will drop to 1/5 m3. This air volume can no longer hold the 20.5 g of vapour contained in the original 1 m3 of air, but only 1/5 of it, i.e. 4.1 g. The rest of 20.5 - 4.1 = 16.4 g condenses in the form of water.The maximum amounts of condensate that are possible at an intake pressure of 0 barg, but with different intake temperatures and a compressed-air temperature of 20 °C, are given in Fig. 74. The values indicated in this table each have to be multiplied with the actual amount of air in m3, which may have to be derived from the flowrate, e.g. m3/h or litres/min.

Example:Every hour, 1000 m3 of air are compressed to 12 barg. Intake temperature 10 °C, com-pressor-air temperature 20 °C. According to the table, the maximum amount of conden-sate is 8 g/m3, i.e. for 1000 m3/h = 8,000 g/h = 8 kg/h.The water separated from the compressed air has to be removed from the plant, as it would lead to erosion and corrosion, amongst other things. The entire air system should be drained, as water is continually being separated from the air until the air has cooled down to ambient temperature. It is recommended that the coolers of the compressors are drained, together with the air receivers, the air lines at regular intervals, and at least at the lowest points and upstream of risers if the line changes its direction (see Fig. 75).In all cases where dry air is required, water separators operating on the centrifugal prin-ciple should be used (GESTRA drier and purifier TP) or, for more critical applications, water absorbers. If oil-free air is required in addition, oil absorbers or oil separators should be used.For automatic drainage, special design combinations of GESTRA float traps are available.

Page 100: Steam Trap

100

30

40

50

60

70

80

90

100

- 1010 20 30 40

0

+ 10

+ 20

+ 30

+ 40

+ 50

3Moisture in g/m

Relative humidity of air in %

Tem

pera

ture

of

air

in°C

Fig. 73 Moisture content of air

Page 101: Steam Trap

101

MoistureIn- content

take at 100 %/tempe- saturation Maximum amount of condensate in g per m3

rature (see Fig. 74) of intake air at gauge pressure

4 bar 8 bar 12 bar 16 bar 22 bar 32 bar

-10 °C 12.14 g/m3 0 0 0.6 1 1,3 1.5

0 °C 14.84 g/m3 1 2.7 3.4 3.7 4 4.2

+10 °C 19.4 g/m3 5.8 7.3 8.0 8.3 8.6 8.8

+20 °C 17.3 g/m3 13.7 15.3 16.0 16.2 16.5 16.8

+30 °C 30.4 g/m3 26.9 28.5 29.1 29.4 29.6 29.9

+40 °C 51 g/m3 47.7 49.1 49.7 50 53 50.5

Fig. 74 Maximum amount of condensate formed in 1 m3/h of intake air, p = 0 barg,intake temperature see table above, temperature of compressed air 20 °C,moisture content of air on intake = 100 %.

Page 102: Steam Trap

102

For the correct drainage of compressed-air lines, the following points have to be con-sidered when laying the pipework and installing the steam traps:a) The condensate should drain by gravity with a constant slope from the drain point

to the trap; b) The pipeline should be laid to provide a sufficient fall. In horizontal lines, a water

pocket may even form in a stop valve. As upstream and downstream of the waterpocket there is the same pressure, the water cannot be pushed out, and it becomesa water seal. As a result, the condensate can no longer flow towards the trap;

c) Float traps require a certain condensate level in the trap body to open. This cannotform unless the air pocket has escaped from the body.With a very small amount of condensate and with a relatively large pipeline (withregard to the flowrate) provided with a sufficient and constant fall (vertical if possi-ble), GESTRA float traps ensure that the air can escape. As condensate enters thetrap, air can flow back up the line in the opposite direction to the condensate.If the amount of condensate formed is rather large, e.g. if the condensate line iscompletely filled on start-up of the plant or by a surge of water, the air is confinedwithin the trap body. The condensate level required to open the trap is formed rather slowly, if at all, and condensate discharge is insufficient. In this case, it isrecommended that a connection be provided between trap and air-line by a “balancepipe”. The air can then escape and the condensate is discharged without any delay(Fig. 76).

Compressor

Air receiver

Cooler

Water separator

Fig. 75

Page 103: Steam Trap

103

d) Small oil quantities, as are normally contained in the air of oil-lubricated compres-sors, do not impair the operation of the GESTRA traps. If the condensate is heavilyoil-contaminated, the installation of a settling tank upstream of the trap is recom-mended. Hence the oil foam may be discharged from time to time, e.g. by a hand-operated valve (Fig. 77).

Instead of the trap, it is also possible to use a solenoid valve operated by a timing delay.This valve is opened for a few seconds at predetermined intervals. The outflowing airwill at the same time clean the valve seat. Note: Air losses!

e) Outdoor plants: Provide heating for pipeline and traps, otherwise there is the dangerof freezing. Before commissioning a new plant for the first time, fill the float trap with water.

Collectingpocket

Balancepipe

Balance pipe

Float trap forhorizontal installation

With or without valve,valve stem horizontal

Air-line or vessel etc.

Air-line or vessel etc.

Collectingpocket

Float trap forvertical installation

With orwithout valve

Balance pipe

e.g.water separator,cooler,vessel

Valve

Fig. 76

Ze.g.water separator,cooler,vessel,pipeline

Short pipe section

Float trap forhorizontal installation

Float trap forvertical installation

Oil discharge

Balance pipe

Adequateintake height

oil water

Fig. 77

Page 104: Steam Trap

Live steam leakage is detected by sound in the ultrasonic rangecaused by flowing steam. Themechanical ultrasonic vibrations are detected by the probe and converted into electric signals which areamplified in the measuring instrument and indicated on a meter. The equipment is intrinsically safeacc. to classification EEx ib IIC T4(Test No. PTB Ex84/2063) andsuitable for use in explosionriskareas. Protection: IP 41

Steam Trap Testing

mhinte
Platziertes Bild
Page 105: Steam Trap

Page10. Sizing of Condensate Return Lines

10.1 Basic Considerations 107

10.2 Examples 113

Page 106: Steam Trap

Easy maintenance – our traps can be

checked, cleaned and repaired without

being removed from the pipework

Interchangeable – our various trap types

have standardized facetoface dimen

sions, sizes and end connections and are

therefore interchangeable without any

modification to the pipe layout.

Tight shutoff, without loss of live steam.

Automatic airventing.

Unaffected by dirt.

Production tested – besides the legally

required tests (e.g. hydraulic test) our trap

regulators are tested under operating

conditions (steam, condensate).

Complies with recognized standards –

our traps meet the relevant DIN standards

and regulations and are in accordance

with the AD bulletins (AD – Arbeits

gemeinschaft Druckbehälter = German

pressure vessel regulations authority)

with regard to choice of material, pressure

and temperature ratings. On request test

certificates to EN 10204.

What are the advantages of GESTRA steam traps?

Page 107: Steam Trap

107

10. Sizing of Condensate Return Lines

10.1 Basic Considerations

10.1.1 The diameter of the pipeline between the heat exchanger and the steam trap is normally chosen to fit the nominal size of the trap.

10.1.2 When choosing the diameter of the condensate line downstream of the trap, flashing has to be considered. Even at very low pressure differentials, the volume of flash steam is many times that of the liquid if the conden-sate is at saturation temperature upstream of the trap (e.g. during flashing from 1.2 bara to 1.0 bara, the volume increases approximately 17 times).

In these cases, it is sufficient to dimension the condensate line solely in accordance with the amount of flash steam formed. The flow velocity of the flash steam should not be too high, otherwise waterhammer (e.g. through the formation of waves), flow noises and erosion may occur.

A flow velocity of 15 m/s at the end of the pipeline before the inlet into the collecting tank or pressure-relief unit is a useful empirical value.

The required inside diameter of the pipeline can be taken from Fig. 78. For long pipelines(> 100 m) and large condensate flowrates, the pres-

sure drop should be calculated to prevent the back pressure becoming too high; here the velocity of the flash steam may be used as a basis for the calculations (Figs. 79 and 80).

10.1.3 When the condensate is mainly in the liquid state (e. g. high degree of undercooling, extremely low pressure), the flow velocity of the condensate should, if possible, be rated at ≤ 0.5 m/s when determining the pipeline diameter. The pipeline diameter as a function of the selected flow velocity can be chosen from the chart in Fig. 81. If the condensate is pumped, the condensate in the pump discharge line can only be in the liquid phase.

For choosing the pipeline diameter, the mean velocity can be rated at 1.5 m/s. Again, the chart in Fig. 81 may be used to obtain the pipe diameter.

Page 108: Steam Trap

State of the condensate before flashing

Pressure Related boiling Pressure at the end of the condensate line [bar absolute]bara temperature absolute °C

0.2 0.5 0.8 1.0 1.2 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 6 7 8 9 10 12 15 18 20

1.0 99 35.7 16.0 7.41.2 104 37.9 18.0 10.0 6.11.5 111 40.1 20.6 12.9 9.5 6.82.0 120 44.2 23.5 15.8 12.6 10.3 7.62.5 127 46.8 25.5 17.7 14.5 12.3 9.2 5.33.0 133 48.8 27.1 19.2 16.0 13.9 10.7 7.3 4.53.5 138 50.4 28.4 20.4 17.1 15.0 11.9 8.5 6.0 3.84.0 143 52.0 29.6 21.5 18.2 18.0 12.9 9.7 7.3 5.3 3.54.5 147 53.3 30.5 22.3 19.0 16.9 13.7 10.5 8.1 6.3 4.7 3.05.0 151 54.3 31.5 23.1 19.8 17.7 14.4 11.2 8.9 7.1 5.6 4.2 2.86.0 155 55.7 32.3 23.9 20.5 18.4 15.2 11.9 9.6 7.9 6.5 5.1 4.0 2.77.0 158 56.5 33.0 24.5 21.1 18.9 15.7 12.4 10.1 8.4 7.0 5.7 4.6 3.5 2.18.0 170 59.9 35.5 26.7 23.1 20.9 17.6 14.2 11.9 10.2 8.9 7.7 6.7 5.8 4.8 4.09.0 175 61.3 36.4 27.5 23.9 21.7 18.3 14.9 12.6 10.9 9.5 8.4 7.4 6.6 5.5 4.8 2.4

10.0 179 62.3 37.2 28.2 24.6 22.3 18.9 15.5 13.1 11.4 10.0 8.9 7.9 7.1 6.0 5.3 3.3 2.112.0 187 64.4 38.7 29.5 25.7 23.5 19.9 16.5 14.1 12.3 11.0 9.8 8.9 8.0 7.0 6.2 4.5 3.6 2.815.0 197 66.9 40.5 31.0 27.2 24.8 21.5 17.7 15.2 13.4 12.0 10.8 9.9 9.1 8.0 7.2 5.6 4.8 4.2 2.918.0 206 69.0 42.0 32.3 28.4 26.0 22.3 18.7 16.2 14.3 12.9 11.7 10.8 9.9 8.8 8.0 6.5 5.7 5.1 3.9 2.520.0 211 70.2 42.9 33.0 29.0 26.6 22.9 19.2 16.7 14.8 13.4 12.2 11.2 10.4 9.2 8.4 7.0 6.2 5.6 4.4 3.1 1.725.0 223 72.9 44.8 34.7 30.6 28.1 24.2 20.4 17.9 15.9 14.5 13.2 12.2 11.4 10.2 9.3 7.9 7.1 6.5 5.4 4.2 3.1 2.530.0 233 75.1 46.3 36.0 31.8 29.2 25.3 21.4 18.8 16.8 15.3 14.0 13.0 12.1 10.9 10.0 8.6 7.8 7.2 6.1 4.9 4.0 3.435.0 241 76.8 47.5 37.0 32.7 30.1 26.1 22.1 19.5 17.5 15.9 14.6 13.6 12.7 11.4 10.5 9.2 8.4 7.8 6.7 5.5 4.5 4.040.0 249 78.5 48.7 38.0 33.6 31.0 26.9 22.9 20.1 18.1 16.5 15.2 14.1 13.2 12.0 11.0 9.7 8.6 8.2 7.1 6.0 5.0 4.545.0 256 80.0 49.7 38.8 34.4 31.7 27.5 23.5 20.7 18.6 17.0 15.7 14.6 13.7 12.4 11.4 10.1 9.3 8.6 7.5 6.3 5.4 4.950.0 263 81.4 50.7 39.6 35.2 32.5 28.2 24.1 21.2 19.1 17.5 16.2 15.1 14.2 12.8 11.8 10.5 9.6 9.0 7.9 6.7 5.7 5.2

To determine the actual diameter (mm), the above values must be multiplied with the following factors:

kg/h 100 200 300 400 500 600 700 800 900 1.000 1.500 2.000 3.000 5.000 8.000 10.000 15.000 20.000Factor 1.0 1.4 1.7 2.0 2.2 2.4 2.6 2.8 3.0 3.2 3.9 4.5 5.5 7.1 8.9 10.0 12.2 14.1

Fig. 78 Sizing of condensate lines (calculation examples on page 107 and following)Basic assumptions for determining the inside pipe diameter:1. Only the flash steam amount is considered.2. The flow velocity of the flash steam is assumed to be 15 m/s.

Page 109: Steam Trap

109

10 15 25 32 40 50 65 80 100 150 200 300 400 5000.1

0.2

0.3

0.5

1

2

3

4

5

6

78

910

20

0.3

0.4

0.5

0.7

1

2

5

3

4

710

20 30 4050

70

Co

eff

icie

nt

of

resis

tan

ce

C

Nominal size (DN)

Gate valve

90° elbow

Pipeline, length100

m

Corrugated-tube compensator (bellows)

Speciallv

vae (Koswa

or similar)

Angle valve

Tee-piece

Standard globe valve

Fig. 79 Pressure drop in steam linesThe coefficients of resistance C for all pipeline components of the same sizeare read from Fig. 80. The total pressure drop ∆p in bar can be determined fromthe sum of all individual components ΣC and the operating data; see Fig. 81.

Page 110: Steam Trap

110

0 50100

150200

250300

350400

450500

50

4030

2015

1086

54

32

1

140120

10080

7060

5040

3025

2015

10m

/s

1

2

20

100 bar

5040

30

5

4

3

10

2.0

1.0

0.5

0.3

0.2

0.05

0.1

0.01

0.02

0.03

Pre

ssu

red

rop

pin

bar

1.5

Pressure pin bara

0.8

1.2

Velocity w

Coefficient of

Satu

ration

line

resistance C

Temperature in C�

Example.Pipeline components DN 50:Pipeline length 20 m C = 8.111 angle valve C = 3.322 special valves C = 5.601 tee-piece C = 3.102 elbows 90° C = 1.00

∑C = 21.10

Operating data:Temperature t = 300 °CSteam pressure, abs.p = 16 barVelocity w = 40 m/s

Result ∆p =1.1 bar

Fig. 80

Page 111: Steam Trap

0.10.1

1 100010010

1

10

20

30

0.2 0.3 0.4 0.6 0.8 2 3 4 5 7 20 30 50 70 200 300 500

0.2

0.3

0.4

0.6

0.5

0.8

2

3

4

5

8

6

DN

10

DN

15

DN

20D

N25

DN

32D

N40

DN

50D

N65

DN

80D

N10

0D

N12

5

DN

150

DN

200

DN

250

DN

300

DN

400

·Flow rate in mv3

Flo

wvelo

city

win

m/s

Fig. 81 Flowrates in pipelines

Page 112: Steam Trap

112

�in

°C

200 100 60150300 50 40 30 20 10 8 7 6 5 4 23 1 0.515

Specific gravity in kg/m�

5070 40 30 20 15 10 8 6 5 4 3 2 1.5 1 0.8 0.6 0.4 0.3 0.2 0.15100

150

200

250

300

350

400

450

1.5

0.50.60.70.80.91.01.21.41.61.822.533.5456789

450

101214161820253035405060708090

25

32

40

50

75

100

125

150

175

200

250

300

350

400

500

550

600

700

150

100

80

6050

40

30

20

15

108

65

43

2

1

0.8

0.6

0.5

0.4

0.2

0.1

80

Saturated steam

Ste

ampre

ssure

100

bara

Ste

am

tem

pera

ture

3

Steam

flowra

tein

t/h

Nominal size

(DN)

Flow velocity w in m/s

Fig. 82 Flow velocity in steam linesExample: Steam temperature 300 °C, steam pressure 16 bara,

steam flowrate 30 t/h, nominal size (DN) 200.Result: Flow velocity = 43 m/s.

Page 113: Steam Trap

113

10.2 Examples

10.2.1 Choosing the pipe size from the amount of flash steam

10.2.1.1 Pressure before flashing (service pressure) 5 bara, pressure atend of condensate line 1.5 bara, condensate temperature approximately at boiling temperature, 151 °CCondensate flowrate 1200 kg/hFrom Fig. 78, Table 1, the diameter coefficient = 14.4.From Fig. 78, Table 2, the diameter factor for 1200 kg = 3.5.Thereforediameter = 14.4 x 3.5 = 50.4 mmChoose DN 50 mm.

10.2.1.2 Same operating data as for 10.2.1.1, but condensate with 20 Kundercooling (20 K below ts).According to Table 1, the boiling temperature at 5 bar is 151°C,and sothe actual condensate temperature is 151 - 20 = 131 °C,and the diameter coefficient at 131 °C 10.2(by interpolation of diameter coefficients at 127 °C and 1.5 barback pressure = 9.2and at 133 °C at 1.5 bar back pressure = 10.7),multiplied by the factor 3.5 (from Table 2 for 1200 kg/h)this yields a diameter of 10.2 x 3.5 = 35.7 mm.Choose DN 40 mm.

10.2.2 Choosing the pipe size from the water flowrate, i.e. if there is no or hardlyany flash steam being formed.Same operating data as for 10.2.1.1 above, i.e. condensate flowrate 1200 kg/h 1200 l/h 1.2 m3/h, upstream pressure 5 bara, back pressure1.5 bara,but condensate with 40 K undercooling (40 K below ts).According to Fig. 78, Table 1, the boiling temperature at 5 bar is 151 °C;therefore the actual condensate temperature 151 - 40 = 111 °C,the boiling temperature at 1.5 bar = 111 °C, and hence no flash steam isformed.Determination of the diameter of condensate line from Fig. 81, based ona flow velocity of 0.5 - 0.6 m/s:Choose DN 25 mm.

Page 114: Steam Trap

114

0.10 45.84 14.6757 0.06814 191.83 2584.8 2392.9 0.15 54.00 10.0231 0.09977 225.97 2599.2 2373.2 0.20 60.08 7.6511 0.13020 251.45 2609.9 2358.4 0.25 64.99 6.2035 0.16120 271.99 2618.3 2346.3 0.30 69.12 5.2301 0.19120 289.30 2625.4 2336.1 0.40 75.88 3.9936 0.25040 317.65 2636.9 2319.2 0.50 81.35 3.2404 0.30860 340.56 2646.0 2305.4 0.60 85.95 2.7315 0.36610 359.93 2653.6 2293.6 0.70 89.97 2.3646 0.42290 376.77 2660.1 2283.3 0.80 93.52 2.0868 0.47920 391.72 2665.8 2274.0 0.90 96.72 1.8692 0.53500 405.21 2670.9 2265.6 1.00 99.64 1.6938 0.59040 417.51 2675.4 2257.9 1.50 111.38 1.1590 0.86280 467.13 2693.4 2226.2 2.00 120.23 0.8857 1.12900 504.70 2706.3 2201.6 2.50 127.43 0.7184 1.39200 535.34 2716.4 2181.0 3.00 133.54 0.6057 1.65100 561.43 2724.7 2163.2 3.50 138.87 0.5241 1.90800 584.27 2731.6 2147.4 4.00 143.62 0.4623 2.16300 604.67 2737.6 2133.0 4.50 147.92 0.4137 2.41700 623.16 2742.9 2119.7 5.00 151.84 0.3747 2.66900 640.12 2747.5 2107.4 5.50 155.46 0.3367 2.97000 655.78 2751.7 2095.9 6.00 158.84 0.3155 3.17000 670.42 2755.5 2085.0 7.00 164.96 0.2727 3.66700 697.06 2762.0 2064.9 8.00 170.42 0.2403 4.16200 720.94 2767.5 2046.5 9.00 175.35 0.2148 4.65500 742.64 2772.1 2029.5 10.00 179.88 0.1943 5.14700 762.61 2776.2 2013.6 11.00 184.05 0.1774 5.63700 781.13 2779.7 1958.5 12.00 187.95 0.1632 6.12700 798.43 2782.7 1984.3 13.00 191.60 0.1511 6.61700 814.70 2785.4 1970.7 14.00 195.04 0.1407 7.10600 830.08 2787.8 1957.7 15.00 198.28 0.1316 7.59600 844.67 2789.9 1945.2 16.00 201.36 0.1237 8.08500 858.56 2791.7 1933.2 17.00 204.30 0.1166 8.57500 871.84 2793.4 1921.5 18.00 207.10 0.1103 9.06500 884.58 2794.8 1910.3 19.00 209.78 0.1047 9.55500 896.81 2796.1 1899.3 20.00 212.37 0.0995 10,05000 908.59 2797.2 1888.6 21.00 214.84 0.0948 10.54000 919.96 2798.2 1878.2 22.00 217.24 0.0907 11.03000 930.95 2799.1 1868.1 25.00 223.93 0.0799 12.51000 961.96 2800.9 1839.0 30.00 233.83 0.0666 15.01000 1008.40 2802.3 1793.9 40.00 250.33 0.0498 20.10000 1087.40 2800.3 1712.9 50.00 263.91 0.0394 25.36000 1154.50 2794.2 1639.7 60.00 275.56 0.0324 30.83000 1213.70 2785.0 1571.3 70.00 285.80 0.0274 36.53000 1267.40 2773.5 1506.0 80.00 294.98 0.0235 42.51000 1317.10 2759.9 1442.8 90.00 303.32 0.0205 48.79000 1363.70 2744.6 1380.9 100.00 310.96 0.0180 55.43000 1408.00 2727.7 1319.7 120.00 324.63 0.0143 70.01000 1491.80 2689.2 1197.4 140.00 336.36 0.0115 86.99000 1571.60 2642.4 1070.7 160.00 347.32 0.0093 107.40000 1650.50 2584.9 934.3 180.00 356.96 0.0075 133.40000 1734.80 2513.9 779.1 200.00 365.70 0.0059 170.20000 1826.50 2418.4 591.9 220.00 373.69 0.0037 268.30000 2011.10 2195.6 184.5 221.20 374.15 0.0032 315.50000 2107.40 2107.4 0

Fig. 83 Steam table(The detailed steam tables are commercially available.).

Ab

solu

te p

ress

ure

ρ, b

ara

Tem

per

atur

et s

, °C

Spe

cific

ste

am

volu

me

v",

m3 /

kg

Ste

am d

ensi

tyρ"

, kg

/m3

Ent

halp

y of

wat

er

h',

kJ/k

g

Ent

halp

y of

ste

amh"

, kJ

/kg

Hea

t of

eva

pora

t ion

r, kJ

/kg

Page 115: Steam Trap

Page11. Sizing of Steam Lines 117

12. Calculation of Condensate Flowrates

12.1 Basic Formulae (Sl Units) 118

12.2 Sizing of Steam Traps 121

Page 116: Steam Trap

GESTRA DISCO® Non-Return Valves

Today GESTRA can look back with pride on hundred years of experience in valve manufacture. The company offers a broad range of non-return valves tailored to fulfil the most diverse of applications and customer requirements. All valves are made of diverse materials to meet particular demands, and the individual valve components are optimally coordina-ted with each other. Through this ideal mixture of different components in the range of standard valves, the best valve can be delivered for almost every application. Here it does not matter whether a thermally critical application must be safeguarded, or whether a non-return valve must be designed for operation in oxygen, for example. It is even possible to manu-

® facture the DISCO valve, which has proven its worth a million times over,

® DISCO

in a special material to answer speci-fic needs.

All GESTRA non-return valves are of the wafertype and have extremely short overall lengths. Thanks to their excellent design and hydrodynamic features, these valves offer clear advantages over conventional types:

Compact designLow weightMounting in any position

Low installation costs

Wide choice of materialsSpace-saving stockkeepingSafe operation of industrial plants

Low pressure drop

The name GESTRA is a guarantee of high manufacturing quality for the GESTRA non-return valves.

®DISCO

mhinte
Platziertes Bild
Page 117: Steam Trap

117

11.Sizing of Steam Lines

When sizing steam lines, care must be taken that the pressure drop between the boil-er and steam users is not too high. The pressure drop depends mainly on the flow velocity of the steam.The following empirical values for the flow velocity have proven to be satisfactory:

Saturated steam lines 20 - 40 m/sSuperheated steam lines 35 - 65 m/sThe lower values should be used for smaller flowrates.

For a given flow velocity, the required pipe diameter can be chosen from the chart inFig. 82.The pressure drop can be calculated from the charts in Figs. 79 and 80.

Page 118: Steam Trap

118

12.Calculation of Condensate Flowrates

12.1 Basic Formulae on the Basis of SI Units [J, W]

12.1.1 If the amount of heat required is known (e.g. specified on the name plateof the heat exchanger), then the condensate flowrate M can be calculatedfrom

and hence

Here kW is the amount of heat required in kJ/s (kilo-Joule per second) andthe quotient 2100 is the latent heat of steam kJ/kg for medium pressures;the factor 1.2 is added to compensate for heat losses.

12.1.2 If the amount of heat Q required per hour is not known, it can be calcula-ted from the weight M of the product to be heated up in one hour, the spe-cific heat

and the difference between the initial temperature t1 and the final tempera-ture t2 (∆t = t2 – t1) as follows:

Example:50 kg of water are to be heated from 20 °C to 100 °C in one hour.The amount of heat required is

The amount of condensate is then

M = 1.2 ·kW

2100· 3600 [kg/h]

·

ckJ

kg K[ ]

M 2.1 kW· [kg/h]~~·

Q = 504.1903600

(100 - 20) = 4.656 [kW]· ··

Q = Mc

3600[kW]· ·

· ·

M = 2.1 · 4.656 9.8 [kg/h]~~·

kJkg K )( c = 4.190water

··

·

Page 119: Steam Trap

119

Now if the 50 kg of hot water are to be vapourized in one hour, the latentheat of approx. 2100 kJ/kg has to be added.

The total amount of heat required, and consequently the total amount ofcondensate formed, can be calculated as follows:M 2.1 (4.656 + 29.167) 71.0 kg/hIt must be noted that each product has its own specific heat.

Specific heat c

Water 4.190Milk 3.936Mash 3.894Jam 1.256Wax 2.931Iron 0.502Fats 0.670Rubber 1.424Saline solution, saturated 3.266Sulphur 0.754Alcohol 2.428Air 1.005Machine oil 1.675Benzine 2.093

Further properties of substances can be found in the applicable specialistliterature.

kJkg K

Q = 50 · 2100 = 105,000 kJ/h = = 29.167 [kW]105,0003600

·

·

Page 120: Steam Trap

120

12.1.3 If the size of the heating surface and the temperature rise (difference be-tween initial and final temperature) of the product are known, the conden-sate flowrate M can be calculated with sufficient accuracy as follows:

Where

M = amount of condensate in kg/hF = heating surface in m2

k = coefficient of overall heat transfer in

tD = temperature of steamt1 = initial temperature of product t2 = final temperature of product (quite often, it is sufficient if the

average temperature is known, e.g. room temperature)r = latent heat in kJ/kg (as an approximation for medium pressures,

2100 can be assumed)

A few empirical values for the coefficient of overall heat transfer k aregiven below.The lower values apply to unfavourable operating conditions (such as lowflow velocity, viscous product, contaminated and oxidized heating sur-faces), whereas the higher values apply to very favourable conditions (e.g.high flow velocity, highly fluid product, and clean heating surfaces).

Insulated steam line 0.6 – 2.4Non-insulated steam line 8 – 12Heating unit with natural circulation 5 – 12Heating unit with forced circulation 12 – 46Jacketed boiling pan with agitator 460 – 1500As above, with boiling liquid 700 – 1750Boiling pan with agitator and heating coil 700 – 2450As above, with boiling liquid 1200 – 3500Tubular heat exchanger 300 – 1200Evaporator 580 – 1750As above, with forced circulation 900 – 3000

M =r

F · k · (tD )t + t1 2

2 36001000·

·

W

m K[ ]2

W

m K[ ]2

·

·

Page 121: Steam Trap

121

12.2 Sizing of Steam Traps (See also Sections 3.1 and 3.2)The formulae given in the Section 12.1 above make it possible to calculate theaverage amount of condensate formed during entire heating process. However,these formulae show clearly that, other conditions being equal, the amount ofcondensate increases with the difference between the steam temperature andthe temperature of the product. This means that the condensate flowrate is largest when the product is at its lowest temperature, i. e. at start-up.A further point is the fact that the pressure drop in the steam line and the heatingsurface is highest when the steam consumption is largest. This means that theservice pressure and consequently the differential pressure (difference betweeninlet and outlet pressure), which determines the capacity of the trap, are lowestat start-up.Extreme conditions are, for example, encountered in the case of steam line drainage. If saturated steam is used, the quantity of condensate formed at start-up may be twenty times that formed in continuous operation. If superheatedsteam is used, there is practically no condensate formed during continuous operation.Very high flow and pressure fluctuations also occur in controlled plants and inmany boiling processes.If only the mean steam consumption (condensate flowrate) is known, a safetyfactor has to be added for float traps. Their maximum capacity at medium pressures (at a condensate temperature of ≤ 100 °C) can be assumed to be 1.4 times that of the hot-water capacity indicated in the capacity chart.The maximum capacity of thermostatic traps (cold-water capacity) on the otherhand is several times their hot-water capacity, and is given in the capacity charts.

Page 122: Steam Trap

For pressures from PN 6 to PN 40,the RK 86/86A can be used, forexample – and for the pressurerange PN 10–40 the RK 16C ofHastelloy. The RK 49 valve coversthe pressure rating up to PN 160.

Depending on the medium flowingthrough the piping of your installation, a valve is then selected fromthe most suitable material. Forneutral liquids or gases, valveranges are available in the materialsbrass, bronze, steel and chromiumsteel. In the case of corrosive vapours and gases, acids and alkalis,the versions of austenitic steel and

Hastelloy are used. For specialrequirements, e.g. in the foodstuffindustry, at low temperatures or forapplications with drinking water,valve ranges of cast bronze,austenitic steel and Hastelloy C are available.

Special features:

Springs for low opening pressures

Springs for reduced closing timesSprings for applications at high

temperaturesSoft seatsAntistatic connectionPickled, free of oil and greaseSpecial connections

GESTRA DISCO® Non-Return Valves RK

mhinte
Rechteck
mhinte
Textfeld
For industrial plants, GESTRA offers a broad spectrum of non-return valves which are designed for diverse pressure ratings and media.
Page 123: Steam Trap

Page13. Pressure and Temperature Control

13.1 Pressure-Reducing Valves 125

13.2 Temperature Control at the Heat Exchangers 128

13.2.1 Control on the steam side 128

13.2.2 Control on the condensate side 129

Page 124: Steam Trap

GESTRA DISCOCHECK® Dual-Plate Check Valves BB

Valves with adjustable dampersfrom DN 200 (8")

In complex pipeline systems, majorflow decelerations may be causedwhen pumps are switched off or asa result of failures, leading to waterhammer and possibly disastrousconsequences for the plant. Ourengineers will be happy to assistyou with the correct design of thedualplate check valves for yourinstallation.

The answer in tight spotsThe answer in tight spots

Page 125: Steam Trap

125

13.Pressure and Temperature Control

13.1 Pressure-Reducing ValvesThe boiler pressure is often higher than the pressure required for the heating pro-cess. In such cases, it is generally more economical to reduce the steam pressure in a pressure-reducing valve. The purchase price for low-pressure heatexchangers is lower, the amount of latent heat that can be utilized is higher, andthe amount of flash steam is lower.

13.1.1 In most cases, the control accuracy of a proportional controller, as shownbelow, is sufficient. It is a balanced single-seat valve operating withoutauxiliary energy. The reduced pressure acts via the water-seal pot and thepilot line onto the lower side of the diaphragm.The force of the spring acts in the opposite direction. It is adjusted withthe handwheel and determines the reduced pressure.

Fig. 84 GESTRA pressure-reducing valve

Page 126: Steam Trap

126

13.1.2 Correct installation is important to obtain good control of the reduced pres-sure (Fig. 85).

Pressure-reducing valves operate for most of time in the throttled position. Even small dirt particles may therefore lead to trouble. Every pressure-reducing valve should therefore be protected by a strainer. Water particles entrained in the steam passing through the strongly throttled valve at high velocity will, through cavitation and erosion, cause wear and eventual destruction of the valve and seat.

Also, when the plant is shut down, the remaining steam condenses in the pipeline. The condensate collects at the lowest point upstream of the pressure-reducing valve. At start-up, the steam flows across the cold con-densate.

Waterhammer may result, and the resulting shock may lead to premature fai lure of the regulating membranes and the pressure-balance bellows. For these reasons, the steam line upstream of each pressure-reducing valve should be drained. If the line downstream of the reducing valve rises, a second drain point should be provided downstream.

Drainage immediately upstream of the valve can be omitted if it is installed in a vertical line with upward flow.

Examples for the correct installation of pressure-reducing valves are given in Fig. 85, whereby for the valve according to Fig. 84 it is recommended that the sensing point is approximately 1 m downstream of the valve to allow the flow to stabilize.

Fig. 85 Examples for installation of steam pressure-reducing valves

1. Condensate collecting point 5. Pressure-reducing valve2. Steam trap 6. Water-seal pot3. Stop valve 7. Sensing line4. Strainer 8. Sensing point

Page 127: Steam Trap

127

13.1.3 If a relatively high pressure must be reduced to a very low pressure, it is pos-sible that the reducing capability of one valve is no longer sufficient. It is thennecessary to install two pressure-reducing valves in series (see Fig. 86). If thepressure drop is relatively high (P2 < P1/2), it is recommended that a valvewith a perforated plug be used, operated by an electrical or pneumatic actu-ator. If this is not possible, two pressure-reducing valves can be connectedin series (see Fig. 86). The steadying zone upstream of the first pressure-reducing valve should be designed with a length of 8 x DN. The damping lineshould have a length of 5 m.

The most favourable reduction relationship is obtained for the two valveswhen the second is dimensioned to be two nominal sizes larger.The same applies for the downstream pipeline.

13.1.4 If the steam pressure fluctuates greatly between the minimum and maxi-mum values and if the pressure is to be regulated precisely even for mini-mum demand, two valves of differing size must be connected in parallel(Fig. 87)

Fig. 86 Series-connected pressure regulator for the stepped reduction of highsteam pressures

Fig. 87 Parallel-connected pressure regulators for strongly fluctuating steam con-sumption

1. Condensate collecting point 5. Pressure-reducing valve2. Steam trap 6. Water-seal pot3. Stop valve 7. Sensing line4. Strainer

1. Condensate collecting point 5. Pressure-reducing valve2. Steam trap 6. Water-seal pot3. Stop valve 7. Sensing line4. Strainer

Page 128: Steam Trap

128

The larger valve must be adjusted so that it closes at a slightly higherreduced-pressure than the smaller one. This ensures that both pressureregulators are open at full load. At low load, the reduced pressure increa-ses a little, so that the larger valve closes and the smaller one alone per-forms the task of pressure regulation.

13.2 Temperature Control at the Heat Exchangers

13.2.1 Temperature control is mainly applied to the steam side. A common tem-perature controller from the GESTRA product range that functions withoutauxiliary power is shown in Fig. 88. Here a thermostat measuring the tem-perature of the product transfers its pulses to a positioning cylinder thatcontrols the throttling valve, which is closed when the desired temperatureis attained.For the steam trapping, it must be considered that, due to the openingand throttling of the controller, the steam pressure in the heat exchangerfluctuates constantly within a wide range (see also Section 4.7).

Safety spring(overtemperatureprotection)

Capillary tube

Adjusting ring

Positioning piston

Thermostat

Stuffing boxSet-point scale(printed)

Valve

Feeler

Set-point adjustor

Positioningcylinder

Fig. 88 Self-acting temperature controller. Thermostat with rod feeler and two-wayclosing valve (single-seated valve, closes with increasing temperature).

Page 129: Steam Trap

129

13.2.2 Control on the condensate side (see Section 4.8.3 and Fig. 38) offers the advantage that a constant pressure is maintained in the heat exchanger.

At the same time, it is possible to utilize the sensible heat of the conden-sate. However, in comparison to control on the steam side, a noticeably more sluggish operation (overshooting) must be taken into account. Furthermore, heating surfaces that are unaffected by waterhammer (e.g. vertical preheaters) must be provided.

For control on the condensate side, the valve shown in Fig. 88 can also be used, with the valve arranged on the condensate side. A steam trap must be fitted between the heat exchanger and the valve. This is required to prevent the loss of live steam when the valve is fully open (e.g. on start-up of the plant).

Control on the steam side Control on the condensate side

Fig. 89 Control of heat exchangers

Depending on the load, the pressure in the heating space will vary.No banking-up of condensate.

Constant pressure in the heating space.Varying amounts of condensate accu-mulation, depending on load.

Page 130: Steam Trap

GESTRA DISCO® Non-Return Valves RK 86 and 86A

Our experience gives you the quality,our visions give you the innovativeenergy. On this foundation, GESTRAhas developed a nonreturn valvefor industrial applications thatcombines many requirements in asingle valve – and therefore not onlyfulfils but also far surpasses yourwishes and expectations.

Patented centering

The new centering mechanism ofthe RK 86/86A (patents pending)functions directly through the bodyitself. It has four integrated guideribs arranged so that, independentlyof the flange standard, the valvedisc of the RK 86/86A always liesagainst two of the guide ribs. Thenonreturn valves of othermanufacturers are fitted with onlythree guide ribs at best, whichmeans that the valve disc,depending on installation, usuallyonly has contact with one of them.

All international standards

Whether for DIN, ASME or BSflange, this new DISCO nonreturnvalve is prepared for all internationalstandards.

mhinte
Platziertes Bild
Page 131: Steam Trap

Page14. The Use of GESTRA DISCO Non-Return Valves 133

15. GESTRA DISCOCHECK Dual-Plate Check Valves 137

Page 132: Steam Trap

A positive safeguard against waterhammerDual-plate check valves BB areavailable with patented adjustabledampers to protect the installationagainst damage caused bywaterhammer.

GESTRA's extensivecustomer adaptation anduncompromising qualitystandards guaranteeoutstanding productreliability coupled witheconomic efficiency andincreased plant safety

.

Leakproof bodyThe body of the dual-plate checkvalve has no external through-hole,hence no need for unnecessary platereplacements due to a leaky valvebody.

Suitable for use in aggressive fluidsThe dual-plate check valves BB areavailable with Levasint® or hard-rubber lining for application inseawater and corrosive fluids.

No early wear on hinge pins orspringsDual-plate check valves BB featuretwo hinge pins and four closingsprings for lower opening pressures.

Seat not subject to wear or damageDuring the opening process the hingeside of the plates opens first, therebyeliminating wear of the seatingsurfaces (soft or metal-to-metal seat)and extending the service life of thedual-plate check valves BB.

mhinte
Textfeld
The Power of Quality
Page 133: Steam Trap

133

14. The Use of GESTRA DISCO Non-Return Valves

Non-return valves are important in steam and condensate systems. They contribute to the automation of the process, increase safety and may even replace an expensive valve.The space-saving GESTRA DISCO design simplifies the installation of the non-return valves. With their extremely short face-to-face dimensions, valves of the type RK are simply sandwiched between two flanges. Figs. 90a and 90b below illustrate their operation and installation.

Fig. 90a The valves are opened by the pressure of the fluid and closed by the integral spring as soon as the flow stops – before any back flow occurs. The valve spring can also prevent gravity circulation, if required.

Fig. 90b DISCO-RK, PN 6 – 40, DN 15 – 100 with spiral centering ring or body cen-tering cams for sandwiching between pipe flanges to DIN, BS or ASME 150/300 RF.

Open Closed

Page 134: Steam Trap

134

14.1 If heat exchangers are installed in parallel, non-return valves prevent the return ofcondensate when the heat exchanger is shut down (prevention of waterhammerat the next start-up) (Fig. 91).

14.2 Preventing the formation of vacuum in the steam space:a) By fitting an RK in parallel with the steam trap. The RK will open as soon as

the pressure in the heat exchanger drops below that in the condensate line(see Fig. 92). Note: Only meaningful for vertical heat exchangers.

Fig. 91

Fig. 92

Page 135: Steam Trap

135

b) By fitting an RK in parallel with a thermostatic air vent or by itself, as shown inFig. 93. The RK will open as soon as the pressure in the heat exchanger dropsbelow atmospheric pressure.

c) By fitting an RK at a flash vessel (see Fig. 94).

Thermostaticair vent

RK as vacuum breaker

RK to prevent reverseflow of condensate

Fig. 93

Flash vessel

To boiler house

Condensate from theusers (heat exchangers)

RK I

RK II

Flash steam

Fig. 94 RKI: Vacuum breakerRK II: Pump foot valve

Page 136: Steam Trap

136

14.3 If one coil is used for both heating and cooling, the installation of RKs protects the plant against damage caused by operating errors (see Fig. 95). Here steam cannot enter the cooling water line nor cooling water the steam line.

Fig. 95

Page 137: Steam Trap

137

15. GESTRA DISCOCHECK® Dual-Plate Check Valves BB

These GESTRA valves are a logical extension of the GESTRA DISCO non-return valves, e.g. in the range of larger sizes.Their special advantages include extremely low flow resistances, short overall lengths, e.g. to DIN API, ISO and EN up to “extremely short versions”, and a wide range of materials for practically all media. The GESTRA DISCOCHECK dual-plate check valves of the type BB are designed for an especially long service life and extremely low pressure drops.

Fig. 96 Functional principle of the GESTRA DISCOCHECK dual-plate check valves BB

Closing positionThe valve plates – with metal-to-metal or O-ring sealing – make even contact with the seat.

Starting to openThe opening process begins with the hinge sides of the plates first lifting off the centre pin, thereby reducing wear of the seating surfaces by the kinematic effect.

Valve fully openThe rotary movement of the plates is limited by stop lugs to 80°. Additional hinge stop lugs ensure a stable position of the plates when fully open.

Starting to open

Valve fully open

Closing position

Page 138: Steam Trap

Measuring up to market needs has been the GESTRA philosophy for decades. Backed by many years‘ experience in the design andmanufacture of non-return (check)valves, we offer our customerssuperior solutions for their specificrequirements.Whether your are looking foreconomical non-return valves for hvac services, special non-return valves for chemical applications ordual-plate check valves with(adjustable) dampers – we guaranteeperformance without compromise.

GESTRA – always one step ahead.

These are just some examples ofcustomer requirements which are metby our new DISCO non-return valve RK 86.

“We need non-return valves that conformto as many international standards forend connections as possible.”

“The flange design should preventsquashing of the gasket duringinstallation and guarantee leakproofsealing.”

“Non-return valves should featuredependable bonding connections.”

Tailored to Your Needs

Page 139: Steam Trap

Page

16. Capacity Charts for GESTRA Steam Traps

16.1 Thermostatic/Thermodynamic Steam Traps, up to PN 40, BK Range 141

16.2 Thermostatic/Thermodynamic Steam Traps, PN 63-630, BK Range 142

16.3 Thermostatic Traps with Pilot Control by Membrane Regulators, up to PN 40, MK Range 143

16.4 Thermostatic Traps with Pilot Control by Membrane Regulators, up to PN 25, TK Range 144

16.5 Thermostatic Traps for Constant Discharge Temperatures, up to PN 40, Type UBK 46 145

16.6 Float Traps, up to PN 16 146

16.7 Float Traps, PN 25 and PN 40 147

16.8 Float Traps, PN 63 148

16.9 Float Traps, PN 100 149

16.10 Float Traps, PN 160 150

16.11 Float Traps, PN 16/25 152

16.12 Thermodynamic Traps with Stage Nozzle, PN 16 152

Page 140: Steam Trap

GESTRA DISCOCHECK®

These GESTRA check valves are ofthe wafer type with short overalllengths. The reduced weight offerssignificant advantages for transport,stockkeeping and installation. Allthree basic types BB, CB and WBare characterized by excellenthydrodynamic properties.

These high-quality dual-platecheck valves keep your runningcosts very low – by cutting thecosts for pumping power andmaintenance, and providingsafe, low-wear operation with along service life.

The low zeta value means that therequired pump output is reduced, so that you save energy and can usea pump with lower power consumption. Stress and wear are reducedbecause the plate halves lift off fromthe centre pin before the main opening action, the plates are separatelysuspended (two pivots), and twosprings are provided per plate half.Stop lugs at the plate halves, withadditional lugs on the body, limit theopening angle to 80° and ensure astable open position. As a result, along and maintenancefree productlifetime is achieved.

Dual-Plate Check Valves BB

The answer in tight spots

Page 141: Steam Trap

141

16. Capacity Charts for GESTRA Steam Traps

16.1 Thermostatic/Thermodynamic Steam Traps, up to PN 40, BK Range The capacities given in the chart are those obtained with approximately 10 K

undercooling below saturation temperature. Traps with larger capacities have more undercooling. The capacities of cold con-

densate (during start-up of the plant) are several times the capacities indicated in the chart. See the individual data sheets.

BK45 PN 40 DN 15, 20, 25 up to 22 bar of differential pressure BK15 PN 40 DN 40, 50 up to 22 bar of differential pressure BK46 PN 40 DN 15, 20, 25 up to 32 bar of differential pressure

Page 142: Steam Trap

142

16.2 Thermostatic/Thermodynamic Steam Traps, PN 63-630, BK RangeThe capacities given in the chart are those obtained with approximately 10 K undercooling below saturation temperature.Traps with larger capacities have more undercooling. The capacities of cold con-densate (during start-up of the plant) are several times the capacities indicated in the chart. See the individual data sheets.BK27N PN63 DN 40, 50, ΔPMX. 45 barBK37 PN63 DN 15, 20, 25, ΔPMX. 45 barBK28 PN100 DN 15, 20, 25, ΔPMX. 85 barBK29 PN160 DN 15, 20, 25, ΔPMX. 110 barBK212 PN630 DN 15, 20, 25, ΔPMX. 250 bar

Page 143: Steam Trap

143

16.3 Thermostatic Traps with Pilot Control by Membrane Regulators, up to PN 40, MK RangeThe capacities given in the chart are those obtained with approximately 10 K under-cooling below saturation temperature. The capacities of cold condensate (during start-up) are several times the capacities indicated in the chart.See the individual data sheets, especially for application of the U capsule (“under-cooling” capsule).MK 45-1, MK 45-2, MK 35/2S, MK 35/2S3, PN 40 DN 15, 20, 25MK 35/31; MK35/32 PN 25 DN 3/8", 1/2"; MK 36/51; PN 40 DN 1/4", 3/8", 1/2", 3/4";MK 25/2; PN 40 DN 40, 50MK 25/2S; PN 40 DN 40, 50

Page 144: Steam Trap

144

16.4 Thermostatic Traps with Pilot Control by Membrane Regulators, up to PN 25,TK RangeThe capacities given in the chart are those obtained with approximately 5 Kundercooling below saturation temperature. The capacities of cold condensate(during start-up of the plant) are several times the capacities indicated in thechart (see the corresponding data sheet).TK 23 PN16 DN 50, 65, 80, 100TK 24 PN25 DN 50, 65, 80, 100

Differential pressure

Page 145: Steam Trap

145

16.5 Thermostatic Traps for Constant Discharge Temperatures, up to PN 40, Type UBK 46With the factory setting, this trap opens at condensate temperatures <100 °C forpressures up to 19 barg (e.g. 80 °C at 4 barg, 85 °C at 8 barg), and at conden-sate temperatures ≥ 100 °C for pressures > 20 barg (e.g. 116 °C at 32 barg).The capacity given in the chart is obtained at a condensate temperature that isslightly below the corresponding opening temperature.The capacities of cold condensate (during start-up of the plant) are several timesthe capacities indicated in the chart (see individual data sheets).UBK 46 PN 40 DN 15, 20, 25

1 2 3 4 5 6 7 8 9 10 12 16 20 26 3220

30

40

50

60

70

80

90

100

150

3015 20 40 50 60 90 100 150 170 230 290 380 465

[bar]

[psi]

40

70

90

110

130

160

180

200

220

300

250

60

350

[lb/h] [kg/h]

Cap

acity

UBK

46PN

40DN

15, 20, 25

Page 146: Steam Trap

146

16.6 Float Traps up to PN 16, UNA 23 DN 15–50; UNA Special Type 62 DN 65–100Maximum capacity of boiling hot condensate for the different sizes and orifices that are available. The maximum allowable differential pressure (working pres-sure) depends on the cross-sectional areas of the orifice.

Page 147: Steam Trap

147

16.7 Float Traps, PN 25 and PN 40, UNA 25/26 DN 15–50; UNA Special DN 65–100Maximum capacity of boiling hot condensate for the different sizes and orifices that are available. The maximum allowable differential pressure (working pres-sure) depends on the cross-sectional areas of the orifice.

Page 148: Steam Trap

148

16.8 Float Traps, PN 63Maximum capacity of boiling hot condensate for the different sizes and orifices that are available. The maximum allowable differential pressure (working pres-sure) depends on the cross-sectional areas of the orifice.UNA 27 DN 25, 40, 50UNA Special DN 65, 80, 100

Page 149: Steam Trap

149

16.10 Float Traps, PN 100Maximum capacity of boiling hot condensate.The maximum allowable differential pressure (working pressure) depends on the cross-sectional areas of the orifice.UNA 38 PN100 DN 15, 20, 25, 40, 50

Page 150: Steam Trap

150

16.10 Float Traps, PN 160, UNA 39Maximum capacity of boiling hot condensate.The maximum allowable differential pressure (working pressure) depends on the cross-sectional areas of the orifice.UNA 39 PN 160 DN 15, 25, 50

Page 151: Steam Trap

151

16.11 Float Traps, PN 25/40 DN 15, 20, 25 UNA 14/16

Maximum capacity of boiling hot condensate.The maximum allowable differential pressure (working pressure) depends on the cross-sectional areas of the orifice.

Page 152: Steam Trap

16.12 Thermodynamic Traps with Stage Nozzle, PN 16, DN 50–150Maximum capacity of hot condensate at continuous load with 3/4 valve lift; the cold water capacity is approximately 70 % higher.GK 21 DN 50GK 11 DN 65, 80, 100, 150

Page 153: Steam Trap

Page17. Valves for Special Purposes

17.1 Condensate Drain Valve AK 45 155

17.2 Steam Traps for Sterile Applications, SMK 22 for the Pharmaceutical Industry 159

Page 154: Steam Trap

Proven Technology. New Ideas. Modern Production.

Once again GESTRA is at the fore-front of steam trap technology withthe new SMK 22 STERIline trap. This compact lightweight steam trapfor pharmaceutical production plants is setting new standards in pure-steam sterilization. It is the perfectsolution for all sterile and asepticapplications, superseding expensiveand complex systems for condensatedischarge control.

GESTRA, alwaysone step ahead.

“Our installations require fast andreliable sterilizing.”

“The immediate removal of pure-steamcondensate even in the event ofsudden and extreme pressure and loadfluctuations is critical for efficient andreliable operation.”

“We are looking for a trap that can alsobe used for air-venting in vessels.”

These are just some examples ofcustomer requirements which aremet by our new SMK 22 STERIlinesteam traps.

STERIline®STERIline®STERIline®STERIline®STERIline®

Page 155: Steam Trap

155

17.Valves for Special Purposes

17.1 Condensate Drain Valve AK 45When steam-heated plants are taken into operation, the incoming steam con-denses very quickly but the pressure only builds up slowly. In the process, a rela-tively large quality of condensate is produced but the existing steam trap is notyet able to discharge this start-up condensate without banking up. This prolongsthe start-up time. Dangerous thermal waterhammer can occur. When a plant is shut down, the residual steam condenses. The pressure dropsand a vacuum may result. There may be negative consequences:- Deformation of the heating surfaces by vacuum- Increased corrosion due to shut-down, and danger of freezing through residual

condensate- Waterhammer on start-up

Remedy:Start-up drainage, evacuation and ventilation should be provided in addition tothe steam trap. This can be done with manually operated valves, but is bettereffected automatically with the GESTRA drain valve AK 45 (see Fig. 97).

Fig. 97 AK 45, DN 15, 20, 25

Page 156: Steam Trap

156

Automatic drainage offers the following benefits in relation to manual draining:- Labour-saving- Excludes human error or negligence- Prevents steam losses by open valves- Prevents waterhammer and frost damage- Reduces the risk of accidents at poorly accessible points- Averts the need for an air-inlet valve

The functional principle of the GESTRA AK 45 is based on a pressure-controlledseal plug. When there is no pressure, the AK 45 is held in the open position by aspring. When the plant is taken into operation, the condensate can drain freelyout of the plant. Only when a certain steam pressure is reached (the closing pressure) does the valve close automatically. If the plant is shut down, causingthe pressure to drop, the AK 45 opens at about the same pressure as the closingpressure in the start-up phase (i.e. opening pressure = closing pressure). A hand purging knob is provided, so that the AK 45 can be opened manually withthe system under pressure to clear any deposits from the valve seat area.

Differential pressure

.

. . . . . .

Fig. 98 AK 45 capacities for cold condensate

Page 157: Steam Trap

157

When taking a steam line which has risers into service (e.g. a remote steam line), the steam trap is not able to discharge the condensate which is generated on start-up. Through friction between the two phases, the steam entrains the cold condensate and transports it into the rising part of the line. Pulsation and thermal waterhammer can result. Here too, the GESTRA AK 45 can provide the solution (Fig. 99).

Fig. 99 Installation example for AK 45

Page 158: Steam Trap

158

For heat exchangers operating in batch mode (e.g. boiling apparatus, autoclaves or evaporators), fast start-up and shut-down with frequent batch changes is required. The GESTRA AK 45 permits rapid start-up, because the condensate produced at start-up can be discharged freely. Waterhammer can no longer occur. When the plant has been shut down, the GESTRA AK 45 allows the resid-ual condensate to drain, thereby preventing frost damage and distortion through the formation of vacuum and also reducing the downtime corrosion (see Fig. 100).

Fig. 100 Installation example for AK 45

Page 159: Steam Trap

159

17.2 Steam Traps for Sterile Applications, SMK 22 for the Pharmaceutical Industry (Fig. 101)

This thermostatic steam trap features a minimum of stagnant area and a corro-sion-resistant membrane regulator unaffected by waterhammer, and is used for the discharging of condensate and the venting of steam in sterile and aseptic applications (SIP).Reliable sterilization is safeguarded through rapid heating and drainage with absolutely no banking up during the sterilization process. The try-clamp (a joint-ed clamp) permits easy maintenance of the SMK.The membrane regulator has a self-centering valve cone that can move freely, thereby ensuring steam-tight shut-off unimpaired by particulate matter.High sensitivity, thanks to reduced dimensions of the regulator (evaporation ther-mostat). Automatic air-venting and discharge of condensate without any ban-king-up within the rated pressure/temperature range. The opening temperature is approximately 5 K below the boiling point. Maximum differential pressure Δp = 6 barg.All parts in contact with the fluid are of stainless steel. The body gasket is of EPDM (O-ring) in accordance with the regulations specified by the Food and Drug Administration (FDA).The surface roughness Ra of the wetted surfaces is ≤ 0.8 µm.

Fig. 101 Steam traps for sterile applications

SMK 22 SMK 22-51

Page 160: Steam Trap

160

Fig. 102 Capacity chart for SMK 22 and SMK 22-51 1 Max. capacity of hot condensate 2 Max. capacity of cold condensate

Page 161: Steam Trap

Boilers, Heat Exchangers and Equipment

Steam boiler

Steam boiler with superheater

Desuperheater with water injection

Steam converter

Surface heat exchanger

Separator

Flash vessel

Steam user without heating surface

Steam user with heating surface

Media and Lines

Steam

Condensate, feedwater

Sensing line

Air

Line with heating or cooling

Intersection of two lines with junction

Branch point

Intersection of two lines without junction

Tundish

Discharge vent (canopy)

161

Symbols according to DIN 2481

Page 162: Steam Trap

162

Boilers, Heat Exchangers and Equipment

Space heating

Open tank

Vessel, general

Vessel with dished end

Vessel with deaeration

Steam accumulator

Steam trap

Vaposcope

Machines

Steam turbine

Electric motor, general

Liquid pump,general

Compressor,general (vacuum pump)

Valves

Shut-off valve, general

Shut-off valve, manually operated

Shut-off valve, motorized

Shut-off valve, solenoid-operated

Shut-off valve, piston-operated

Page 163: Steam Trap

Shut-off valve, diaphragm-operated

Shut-off valve, float-operated

Valve

Angle valve

Spring-loaded safety valve

Pressure-reducing valve

Gate valve

Cock

Three-way cock

Check valve

Swing check valve

DISCO non-return valve RK

Butterfly valve

163

Valves

Page 164: Steam Trap

164

Instruments

Pressure gauge, general

Thermometer, general

Flowmeter, general

Liquid level

Conductivity

pH meter

Control Equipment

Controller, general

Drain controller

Desuperheater with water injection and temperature controller

Pressure-reducing valve opens with decreasing pressure in line b

Pressure-reducing valve opens with decreasing pressure in line a

Page 165: Steam Trap

165

International Symbols and Abbreviations

Symbols

Process linesSteamWaterAirInstrument linesLines, generalCapillary systemsPneumatic signalling linesElectrical signalling lines

Circular symbols for equipmentLocally fittedPanel mountingRack mounting

Letters used in multi-letter symbolsas first letter as successive letters

C Conductivity A AlarmD Density C ControlF Flowrate, quantity D Difference1

H Hand (manual operation) G Gauge (sightGlass)L Level I IndicatingM Moisture R RecordingP Pressure S Switching2

S Speed, velocity, T Transmitterfrequency V Valve

T Temperature

1 PD= pressure difference; TD = temperature difference etc.2 S = Switch (switching) can also mean Safety.

Example for the composition and meaning of a multi-letter symbol:The quantity to be measured, e.g. pressure (P), is to be indicated (I) and controlled (C).Then PIC 110 means: Pressure lndicating Controller for control circuit 110.

Page 166: Steam Trap

166

Material Designations

Old material designation (DIN) EN designation EN designation ASTM

Brief name Number Brief name Number Equivalent material1) Category

GG-25 0.6025 EN-GJL-250 EN-JL 1040 A 126-B Grey cast iron

GGG-40 0.7043 EN-GJS-400-15 EN-JS 1030 A 536 60-40-18 S.G. (ductile) iron

GGG-40.3 0.7043 EN-GJS-400-18-LT EN-JS 1025 – S.G. (ductile) iron

GTW-40 0.8040 EN-GJMW-400-5 EN-JM 1030 – Malleable cast iron, white

RSt 37-2 1.0038 S235JRG2 1.0038 A 283-C Structural steel

C22.8 1.0460 P250GH 1.0460 A 105 Forged steel, unalloyed (carbon steel)

GS-C 25 1.0619 GP240GH 1.0619 A 216-WCB Cast steel (carbon steel)

15 Mo 3 1.5415 16Mo3 1.5415 A 182-F1 Forged steel, heat resistant

GS-22 Mo 4 1.5419 G20Mo5 1.5419 A 217-WC1 Cast steel, heat resistant

13 CrMo 4 4 1.7335 13CrMo4-5 1.7335 A 182-F12-2 Forged steel, heat resistant

GS-17 CrMo 5 5 1.7357 G17CrMo5-5 1.7357 A 217-WC6 Cast steel, heat resistant

G-X 8 CrNi 13 1.4008 GX7CrNiMo12-1 1.4008 – Cast steel, stainless

G-X 6CrNi 18 9 1.4308 GX5CrNi19-10 1.4308 A 351-CF8 Stainless steel (casting), austenitic

G-X 6CrNiMo 18 10 1.4408 GX5CrNiMo19-11-2 1.4408 A 351-CF8M Stainless steel (casting), austenitic

X 6 CrNiTi 18 10 1.4541 X6CrNiTi18-10 1.4541 – Stainless steel (forged), austenitic

X 6 CrNiNb 18 10 1.4550 X6CrNiNb18-10 1.4550 A 182-F347 Stainless steel (forged), austenitic

G-X 5 CrNiNb 18 9 1.4552 GX5CrNiNb19-11 1.4552 A 351-CF8C Stainless steel (casting), austenitic

X 6 CrNiMoTi 17 12 2 1.4571 X6CrNiMoTi17-12-2 1.4571 – Stainless steel (forged), austenitic

G-X 5 CrNiMoNb 18 10 1.4581 GX5CrNiMoNb19-11-2 1.4581 – Stainless steel (casting), austenitic

CuZn 39 Pb 3 2.0401 CuZn38Pb2 CW608N – Hot-pressed brass

CuZn 35 Ni 2 2.0540 CuZn35Ni3Mn2AlPb CW710R – Brass

G-CuAl 9 Ni 2.0970.01 CuAl10Ni3Fe2-C CC332G – Bronze

G-CuSn 10 2.1050.01 CuSn10-Cu CC480K – Bronze

GC-CuSn 12 2.1052.04 CuSn12-C CC483K – Bronze

1) Note the differences in chemical and physical properties!

Page 167: Steam Trap

Index

PageAAcid baths 64Air conditioning plants 49Air heaters 49Air humidifiers 50Air vents (DISCO

non-return valves RK) 133

BBand driers 65Banking-up of condensate 31Baths (for cleaning and pickling) 63Boilers 50Boiling pans 56Brewing pans 59

CCalenders 62, 74Capacity charts for steam traps 141Cleaning machines - dry cleaning 75Condensate drain valves 155Condensate flowrates- in steam systems 118- in compressed-air systems 101Condensate-line sizing 107Condensate-return systems 95Convectors for space heating 46Coppers 59Counterflow heat exchangers 51Cylinder drainage 62

DDigesters 55Drainage- compressed-air lines 99- pipes 43Driers 43, 62, 65Dry-cleaning machines 75Drying cylinders 62Drying platens 66

EEvaluation criteria

for steam trap systems 9Evaporators 60Examples of application 27

PageFFinned-tube heaters 46Flash steam- amount 92- recovery systems 93Flow velocity in steam lines 112Flowrates in pipelines 111

GGroup trapping of heat exchangers 29

HHeat exchangers 43Heaters 48Heating coils 48, 63Hot mangles 74Hot tables 66

IIndividual trapping

of heat exchangers 29Instrument tracing 78Ironers 72Ironing presses 72

JJacketed tracing lines 77

LLaundry equipment 72

MMash tubs 59Monitoring of steam traps 83Multi-platen presses 67

NNominal size of pipework 107Non-return valves 133

PPans 55, 56Preheaters 53Presses 67-69, 72Pressure control 125Pressure drop in steam lines 109Pressure-reducing valves 125

Page 168: Steam Trap

PagePrinciples of steam trapping 27Process digesters 55Process heat exchangers 53Process pans 55

RRadiant panels 46Radiators 46Rotating drying cylinders 62

SSaturated steam mains- drainage 44Selection of steam traps 40Sensible heat of

condensate, utilization 91Sizing- condensate return lines 107- steam traps 121- steam lines 107, 117Stain-removing tables 72Steam lines- drainage 43- sizing 117Steam mains 44Steam manifolds (46) 43Steam radiators 46Steam separators 43Steam tables 114Steam trapping- examples 27- general principles 27Steam traps- evaluation 9- monitoring 83- selection 10, 40- sizing 121- sterilizing steam 159- systems 12Steaming mannequins 73Stills 61Superheated steam mains 45Symbols 161-164

PageT Tank heating 79Temperature control

on the condensate side 128Temperature control

on the steam side 128Temperature controllers 128Tracer lines 76Tube preheaters 53Tyre presses 69

UUnit air heaters 47Utilizing the sensible heat 91

VVulcanizers 70Vulcanizing presses 69

WWater separators 43Waterhammer 32

Page 169: Steam Trap

170

GESTRA Product Overview

Steam Traps

- Thermostatic Steam Traps with Duo S.S. (Bimetallic) Regulator or Membrane Regulator- Ball Float Traps- Thermodynamic Steam Traps- Steam Trap Units for Universal Connectors- Steam Trap Monitoring Equipment

Non-Return Valves

Gravity Circulation Checks- DISCO®-Non-Return Valves- DISCO®-Check Valves- DISCOCHECK®-Dual-Plate Check Valves

Cooling-Water Control Valves

Direct-acting proportional controllers maintain the cooling water outlet temperature at a preset value as a function of the discharge temperature.

Return-Temperature Control Valves

These directly controlled return-temperature control valves maintain constant return tempe-ratures within their proportional range.

Page 170: Steam Trap

171

GESTRA Product Overview

Pressure Control Valves

Direct-acting pressure-reducing valve with large set-point ranges for steam, neutral gases and liquids.

Temperature Control Valves

Self-acting temperature control valves operate as normal- and reverse-acting valves with exter-nal feeler. Suitable for applications in heating and cooling processes with steam, gas and liquids.

Control Valves

- Control valves with electric and pneumatic actuators- Control valves with radial stage nozzle

Safety Valves

Strainers

Stop Valves

Special Equipment and Vessels for Heat Recovery

- Condensate Recovery and Return System- Desuperheaters- Steam Regenerators- Feedwater Deaerating Plants- Blowdown Receiver (Mixing Cooler)- Condensate Dampening Pots- Air/Steam Driers and Purifiers

Page 171: Steam Trap

172

GESTRA Product Overview

Equipment for Energy Supply Centres

All components for improving operational safety and monitoring steam and pressu-rized hot water plants in accordance with TRD 701 / 601 / 602 / 604 24h / 604 72h

- Level Control, Monitoring and Alarm- Temperature Control and Alarm- Conductivity Monitoring- Continuous and Intermittent Blowdown Valves- Programme-Controlled Blowdown Systems- Liquid Monitoring- Flowmeters for Steam, Gases and Liquids- Bus Technology

Page 172: Steam Trap

GESTRA AGMünchener Str. 77, D-28215 BremenP.O. Box 10 54 60, D-28054 BremenTelephone +49 (0) 421-35 03-0Telefax +49 (0) 421-35 03-393E-mail [email protected] www.gestra.de

810580-05/608 EMA · © 2008 · GESTRA AG · Bremen · Printed in Germany With Energy into the Future