OXYGEN
OXYGEN
VACUUM
VACUUM
OXYGEN
MEDICAL AIR
MEDICAL AIR
CENTER EMBED 4"
5/8" DOWEL 12" ON
3/4" 45° CHAMFERED EDGE
FLOOR SLAB
T.O.S.
PLAN DIMENSION AS REQ'D
FOR EQUIPMENT (COORDINATE
W/APPROVED SHOP DRAWINGS)
6X6-W1.4XW1.4 W.W.F.
COUNTERTOP
6"
1/2" DCW
WALL BOX
FLOOR SLAB
NO WEIGHT PERMITTED
SUPPORTS. ABSOLUTELY
PIPE JACKET &
INSULATION
PIPE WITH INDEPENDENT
PIPE
TO BEAR ON SLEEVE.
FLOOR SLAB
BACKER ROD OR MINERAL
WOOL DAMMING MATERIAL
PIPE SLEEVE
FIRE BARRIER CAULK.THICKNESS BASED ONMANUFACTURER'SRECOMMENDATIONS ANDPRODUCT LISTING.
FIRE RATED "LINKSEAL"BRAND MECHANICALSEAL MODEL FS/FD
FIRE BARRIER CAULK.THICKNESS BASED ONMANUFACTURER'SRECOMMENDATIONS ANDPRODUCT LISTING.
INSULATION
PIPE JACKET &
PIPE SLEEVE WITHWATER STOP
BACKER ROD ORMINERAL WOOLDAMMING MATERIAL
WALL/FLOOR PENETRATION W/CAST IN PLACE SLEEVE WALL/FLOOR PENETRATION THROUGH CORE DRILLED HOLE
MIN. 2"
MIN. 2"
SUPPLY STOP (TYP)COPPER TUBING
ADAPTER (TYP)
INSULATE(INSIDE WALL)DOMESTIC HOTWATER SUPPLY(130°F)
FLEX CONNECTORBRAIDED-STAINLESS STEEL3/8"C X 1/2" FIP -16" FAUCETSUPPLY (TYP.)
NOTE:
1. 4" OR 8" CENTER TO CENTER ILLUSTRATION
SHOWN. SINGLE HOLE FAUCET SUPPLIES
SIMILAR FOR SINKS.
FRONT VIEW SIDE VIEW
PIPING TO PRESSURE TRANSDUCERIN ALARM PANEL
ALARM MONITORING PANEL, AP
(COORDINATE LOCATION
WITH HOSPICE STAFF)
OXYGEN
VACUUM
FINISHED FLOOR
CRASH RAIL
3"
MIN
.3
" M
IN.
WALL FRAMING
CEILING
MEDICAL GAS
VALVE CABINET
VC
VERIFY HEIGHTW/ ARCHITECT
USE SIDESOURCE SIDE
5"
TY
P.
48"
UN
LE
SS
NO
TE
D O
TH
ER
WIS
E
(SLIDE)
TYP.
5"
TYP.
5"
20"
GO1
GO3
5"
INS
ULA
TE
IN
SID
E
WA
LL T
O E
LB
OW
/LA
ST
FIT
TIN
G (
TY
P.)
4-SIDES
1/2" ANGLE VALVE W/ 3/8" COMPRESSION
FITTING, 3/8" CONTINUOUS PRESSURE TYPE
DOUBLE CHECK VALVE (FDA APPROVED)
60" OF 3/8" CLEAR (NSF APPROVED) TUBING,
AND UNION. MAKE FINAL CONNECTION.
JDETAILTYPICAL PIPE TRAPEZE HANGER N.T.S.
12 GAUGE STEEL (ASTM A570) 2 7__16
" HEIGHT x
15/8" WIDTH POWER-STRUT PS-150 CHANNEL, TOLCO
OR APPROVED EQUAL, CONTINUOUS SLOT W/
INTURNED LIPS, INTERMITTENT SLOTTED BOTTOM,
AND GALVANIZED AFTER FABRICATION PER ASTM
A123.
TO STRUCTURE
2" WIDE x 1/4" THICK STEEL BAR
LENGTH AS REQ'D. (BEND TO SUIT)
(EVERY THIRD SUPPORT)
2.5 PCF RIGID INSULATIONSATISFIES 25/50 FLAME-SMOKERATING PER ASTM E-84 (TYP.)
G90 180° CARBON STEELFLARED EDGE SADDLE, RIBBEDTO PREVENT SADDLE MOVMENTINSIDE HANGER.
3/4"
3/4" NPT
PRESSURE RELIEF VALVE
SET AT 75 PSIG
THRU EXTERIOR WALL10'-0" ABOVE GRADETURN DOWN ELBOWW/STAINLESS STEELSCREEN
TO SYSTEM
¾"
1" NPTEMERGENCY OXYGENSUPPLY CONNECTION
FINISHED FLOOR
36"
RECESSED, WEATHERTIGHTBOX W/PADLOCK
5"
TY
P.
48"
UN
LE
SS
NO
TE
D O
TH
ER
WIS
E
20"
GO2
5"
TY
P.
48"
UN
LE
SS
NO
TE
D O
TH
ER
WIS
E
PAD HEIGHTVARIES (REFERTO DETAILS)
INSULATE (INSIDEWALL) DOMESTICCOLD WATER SUPPLY
120V SINGLE POINTPOWER SUPPLY TOASSEMBLY BY E.C.
RECIRCULATION PUMPPOWER SWITCH
MIXING VALVE (CASTBRONZE BODY) W/INTEGRAL CHECKS& SCREEN (ASSE1070) SET @110°F ADJUSTABLE
S
S
PUMP SEQUENCINGOPERATION BY BMS
1"
1"
RCP1
RCP2
NOTE: ONE PUMP OPERATESCONTINUOUSLY. ALTERNATEPUMP OPERATION WEEKLY.INTER LOCK PUMP OPERATIONw/ SOLENOID VALVE.
1" 1"
DHWR(130°F)
MED AIR
M
CEILING2" DCW(INSIDE PIPE CHASE)
SHUT OFFVALVE
ACCESS PANEL
PROVIDE ½" STUB OUT W/ SHUT OFFVALVE AND PNEUMATIC FITTINGFOR BLOW DOWN (WINTERIZATION)
DC
W
DC
W
TO IRRIGATIONSYSTEM
TO POND
FINISHEDGRADE
PIPE SLEEVEL
P6-2 FINISHED FLOOR
2"BFP2
2" DEDUCTWATER METER
DCW
DCW
REMOTEREADER
CHECK VALVE
(SLIDE)
FOR LOCATIONS
AIR COMPRESSOR(OIL-LESSRECIPROCATING)
FINISHED FLOOR
3" HIGH CONCRETEHOUSEKEEPING PAD(REFER TO DETAIL F)
½" DRAIN CONN.
2"DISCHARGEFLANGE
2½"
2"
3" HIGH CONCRETEHOUSEKEEPING PAD(REFER TO DETAIL F)
1¼" FNPT INLETCONNECTION
FINISHED FLOOR
2"
¾" FNPT SYSTEMDISCHARGECONNECTION
2"
TERMINATE ½" FNPTCONDENSATE DRAINABOVE / NEARFLOOR DRAIN
1"
REFER TO SPECIFICATION SECTION 22 63 00FOR FURTHER REQUIREMENTS
TERMINATECONDENSATEABOVEFLOOR DRAIN
TERMINATE 2" VACUUMEXHAUST / DISCHARGE PIPING48" ABOVE ROOF w/ TURNDOWNOUTSIDE AIR INTAKE
(TURNED DOWN ANDSCREENED ORFILTERED)
CO
2" INLETFLANGE (BACKSIDE)
FLEX CONNECTOR
TERMINATETANK DRAINABOVEFLOOR DRAIN
FILTER (TYP.)
GFWH1
(130º F DOMESTICHOT WATER)
ET1
2½" SW FROMDCW SOURCE
DHW (130º F)TO DISTRIBUTIONSYSTEM
DC
W
DHW (130º F)
G (2 PSIG)1½" FROMGAS MAIN
1¼"
3/4" NPTDRAIN CONN.
1½"CONN.
2
6
3
1 3
GPR1REDUCER
1½"CONN.
FINISHED FLOOR5
DOMESTIC HOT WATER GENERATION SYSTEM DETAIL CODED NOTES
1. DOWN - FIRED POWERED BURNER.
2. CSA CERTIFIED AND ASME RATED T & P RELIEF VALVE.
3. CONNECT TO FACTORY PROVIDED DIRECT VENTING CONNECTION AT
THIS LOCATION.
4. 3" HIGH CONCRETE HOUSEKEEPING PAD W/ 3/4" CHAMFERED EDGES.
5. TERMINATE DRAIN 6" ABOVE FINISH FLOOR.
6. MAKE FINAL CONNECTION TO GAS SUPPLY TRAIN.
2½"
2½"
DC
W
GFWH2
(130º F DOMESTICHOT WATER)
STORAGE100 GALLON
STORAGE100 GALLON
6
1 3
GPR2
FULL SIZEDIRT LEG
3/4" NPTDRAIN CONN.
1½"CONN.
2
5
3
1½"1¼"
THERMOMETER(TYP.)
2½"
2½"
2½"
C
P6.1D
C
P6.1D
1¼"
4G
P6.1G
VACUUM RELIEF VALVE(BOTTOM FED WATER HEATER)
4"
VACUUM RELIEF VALVE(BOTTOM FED WATER HEATER)
CONCENTRIC VENTKIT TERMINATION(TYP.)
ROOF
4"
4"
4"4"
SW
1½"CONN.
FULL SIZEDIRT LEG
REDUCER
3" HIGH CONCRETEHOUSEKEEPING PAD (TYP.)REFER TO DETAIL F.
MDETAILICE MAKER CONNECTION N.T.S.
FDETAILMAINTENANCE/HOUSEKEEPING PAD N.T.S.
KDETAILTYPICAL PIPE HANGER N.T.S.
LDETAILFLOOR/WALL PENETRATION N.T.S.
ADETAILDOMESTIC HOT WATER GENERATION SYSTEM N.T.S.
HDETAILASSE 1070 CONNECTION (TYPICAL UNDER
SINK/LAVATORY WATER SUPPLY PIPING)
N.T.S.
DDETAILMEDICAL GAS VALVE CABINET
/ALARM MONITORING PANEL
N.T.S. ETYPICAL DETAILMEDICAL GAS OUTLETS
REFER TO P3 SERIES (PLUMBING) AND ARCHITECTURAL PLANS
N.T.S.
REFER TO SPEC. SECTION 22 63 00FOR FURTHER REQUIREMENTS FOR FURTHER REQUIREMENTS
NDETAILWATER SERVICES FOR IRRIGATION AND POND N.T.S.
CDETAILMEDICAL VACUUM PUMP, MVS1 N.T.S.REFER TO SPEC. SECTION 22 62 00FOR FURTHER REQUIREMENTS
BDETAILMEDICAL AIR SYSTEM, MAS1 N.T.S.
GDETAILEMERGENCY OXYGEN SUPPLY CONNECTION
REFER TO SPEC. SECTION 22 63 00
N.T.S.
PIPE
CLAMP
UNISTRUT
CHANNEL
HANGER
ROD
PIPE
INSULATION
PROVIDE A SECTION OF HIGH
COMPRESSION STRENGTH
INSULATION AT EACH HANGER
POINT. INSULATION MAY BE
HALF ROUND OR FULL ROUND
& EXTEND 2" BEYOND
GALVANIZED SHIELD EACH WAY.
GALVANIZED%%032CARBON
STEEL%%032SHIELD
PIPE
INSULATION
PRECOMPRESSED
FIBERGLASS
BLOCK
BLOCK
FIBERGLASS
PRECOMPRESSED
SUPPORT FROM STRUCTURE
LOOSE FIT 3/8"∅
U-BOLT
(TYPICAL)1/2"∅ HANGER ROD
NOTE:
EACH CHANNEL TO
BE INDEPENDENTLY
SUPPORTED FOR
MULTITIER
ARRANGEMENT.
PRECOMPRESSED
FIBERGLASS
BLOCK (TYPICAL)
PIPE (TYPICAL)U-BOLT (TYPICAL)
FROM MEDICALGAS (OXYGEN)MANIFOLD
1" DHWR(130°F)
¾"
PROJECT NUMBER:
CHECKED BY:
DESIGNED BY:
1650 WATERMARK DRIVE
COLUMBUS, OHIO 43215SUITE 200
DRAWN BY:
1 2 3 4 5
A
B
C
D
MKC JOB #:
SUBMITTED:
DEVELOPER / OFFEROR
THIS DRAWING SHALL NOT BE REPRODUCED, PUBLISHED, STORED IN AN ELECTRONIC RETRIEVAL SYSTEM, OR USED IN ANY WAY WITHOUT WRITTEN PERMISSION OF THE ARCHITECT. COPYRIGHT C 2015 MKC ASSOCIATES, INC
6
E
55 Monument Circle, Suite 450Indianapolis, Indiana 46204
GENERAL CONTRACTOR
Phone: 317-573-4600www.ambrosegp.com
9550 W. Higgins Road, Suite 200Rosemont, Illinois 60018
Phone: 847-292-4300Fax: 847-292-4312www.mcshaneconstruction.com
ENGINEERINGStructural, Mechanical, Electrical, Plumbing,Fire Protection
1650 Watermark Drive, Suite 200Columbus, Ohio 43215
Phone: 614-487-1650Fax: 614-487-8981www.korda.com
LANDSCAPE & SITE DESIGN
330 West Spring Street, Suite 350Columbus, Ohio 43215
Phone: 614-486-3343Fax: 614-486-3344www.edgela.com
CIVIL ENGINEERING
SFO: VA-101-12-I-0063
MISHAWAKA, INDIANA
VA ST. JOSEPHCOUNTY CBOC
PHYSICAL SECURITY / FORCE PROTECTION
2015-0211
100% CONSTRUCTION DOCUMENTS
C:\
Local R
evit\R
evit 2
016\1
6-5
0211 V
A S
outh
Bend P
LU
MB
ING
(yu c
hen).
rvt
9/9
/2016 1
0:0
0:1
3 A
M
JUNE 1, 2016
PLUMBING DETAILS
P6-2
15-089
Steve Glinsky
Bill Rezabek
W. P. Stafa
1 07-15-2016 Addendum 1
2 08-03-2016 Bulletin 1, Rev 2
3 09-09-2016 RFP 3, Steam VE
1
2
3