Inspected By Pyae Phyo Hein Page 12
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT Reference Image No.
01-R
Circuit Information Circuit No: CHWP / A-5 Type of component: 50A Contactor
Current Loading R / L1 Y / L2 B / L3 N
20.9A 20.8A 21.2A -
Reference Temperature Fault Temperature Temperature Difference
56.9oC 87.9oC 31oC
Ambient Temperature 30oC Temperature
Category 2
ANALYSIS OF THERMOGRAM
Thermal Anomaly was detected on Phase 3 incoming cable of 50A contactor. Possible fault is due to poor contact of Phase 3 incoming cable termination of contactor. In addition, we opined that there are heat generated from the contactor.
RECOMMENDATIONS Forward this thermal graphic report to LEW in-charge for necessary corrective measure. Recommended corrective actions are tightening or check for improper cable termination. Verify the type rating of the contactor. For contactor used in switching of capacitor, AC-6 rating shall be used. Carry out infrared thermal scan upon the completion of corrective action.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-5
Thermogram Photo
Sp2
Sp1
27.5
117.6 °C
40
60
80
100
Sp1 Temperature 87.9 °C
Sp2 Temperature 56.9 °C
Inspected By Pyae Phyo Hein Page 13
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
02-R
Circuit Information Circuit No: CH / A-5 Type of component: 50A Contactor
Current Loading R / L1 Y / L2 B / L3 N
25.3A 28.1A 23.8A -
Reference Temperature Fault Temperature Temperature Difference
- 84.4oC -
Ambient Temperature 30oC Temperature
Category 2
ANALYSIS OF THERMOGRAM
Thermal Anomaly was detected on both input and output cable termination of the contactor. Possible faults are due to poor internal contact of contactor. we opined that there are heat generated from the contactor internal contacts.
RECOMMENDATIONS
Forward this thermal graphic report to LEW in-charge for necessary corrective measure. Verify the type rating of the contactor. For contactor used in switching of capacitor, AC-6 rating shall be used. Carry out infrared thermal scan upon the completion of corrective action.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-5
Thermogram Photo
Sp2
Sp3
Sp4
Sp1
26.5
110.6 °C
40
60
80
100
Sp1 Temperature 84.4 °C
Sp2 Temperature 74.5 °C
Sp3 Temperature 78.0 °C
Sp4 Temperature 75.6 °C
Inspected By Pyae Phyo Hein Page 14
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
03-R
Circuit Information Circuit No: CWP / A-1 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
30.1A 30.3A 31.2A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 12 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-1-2
Thermogram Photo
Sp2 Sp3
Sp5 Sp6Sp4
Sp1
27.7
53.7 °C
30
40
50
Sp1 Temperature 40.1 °C
Sp2 Temperature 31.5 °C
Sp3 Temperature 32.3 °C
Sp4 Temperature 31.1 °C
Sp5 Temperature 31.8 °C
Sp6 Temperature 31.6 °C
Inspected By Pyae Phyo Hein Page 15
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
04-R
Circuit Information Circuit No: CHWP / A-1 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
21.5A 21.4A 21.9A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 12 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-1-2
Thermogram Photo
Sp2
Sp6Sp5Sp4
Sp1Sp3
27.8
59.7 °C
30
40
50
Sp1 Temperature 32.9 °C
Sp2 Temperature 33.0 °C
Sp3 Temperature 33.5 °C
Sp4 Temperature 30.9 °C
Sp5 Temperature 30.5 °C
Sp6 Temperature 30.7 °C
Inspected By Pyae Phyo Hein Page 16
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
05-R
Circuit Information Circuit No: HEP / A-1 Type of component: OUTPUT MCB
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 12 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-1-2
Thermogram Photo
Sp2 Sp3
Sp5Sp4 Sp6
Sp1
25.7
56.5 °C
30
40
50
Sp1 Temperature 31.4 °C
Sp2 Temperature 30.1 °C
Sp3 Temperature 32.7 °C
Sp4 Temperature 29.6 °C
Sp5 Temperature 29.5 °C
Sp6 Temperature 29.8 °C
Inspected By Pyae Phyo Hein Page 17
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
06-R
Circuit Information Circuit No: CWP / A-2 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-2-2
Thermogram Photo
Sp2
Sp6
Sp3
Sp5Sp4
Sp1
28.1
59.8 °C
30
40
50
Sp1 Temperature 36.0 °C
Sp2 Temperature 34.4 °C
Sp3 Temperature 33.2 °C
Sp4 Temperature 30.6 °C
Sp5 Temperature 31.3 °C
Sp6 Temperature 30.6 °C
Inspected By Pyae Phyo Hein Page 18
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
07-R
Circuit Information Circuit No: CHWP / A-2 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-2-2
Thermogram (date) Photo
Sp2
Sp5Sp6Sp4
Sp3Sp1
28.1
59.3 °C
30
40
50
Sp1 Temperature 32.0 °C
Sp2 Temperature 32.8 °C
Sp3 Temperature 33.7 °C
Sp4 Temperature 29.6 °C
Sp5 Temperature 30.3 °C
Sp6 Temperature 30.5 °C
Inspected By Pyae Phyo Hein Page 19
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
08-R
Circuit Information Circuit No: HEP / A-2 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-2-2
Thermogram Photo
Sp2
Sp6Sp5Sp4
Sp1 Sp3
28.0
55.4 °C
30
40
50
Sp1 Temperature 31.8 °C
Sp2 Temperature 31.8 °C
Sp3 Temperature 32.8 °C
Sp4 Temperature 30.2 °C
Sp5 Temperature 30.4 °C
Sp6 Temperature 30.2 °C
Inspected By Pyae Phyo Hein Page 20
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
09-R
Circuit Information Circuit No: CWP / A-3 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
28.9A 30.7A 31.6A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-3-2
Thermogram Photo
Sp2
Sp4
Sp5
Sp1 Sp3
28.0
60.5 °C
30
40
50
60
Sp1 Temperature 34.9 °C
Sp2 Temperature 34.6 °C
Sp3 Temperature 33.7 °C
Sp4 Temperature 42.7 °C
Sp5 Temperature 40.7 °C
Inspected By Pyae Phyo Hein Page 21
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
10-R
Circuit Information Circuit No: CHWP / A-3 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
22.3A 22.7A 23.6A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-3-2
Thermogram Photo
Sp2
Sp5Sp4
Sp6
Sp1 Sp3
27.6
59.8 °C
30
40
50
Sp1 Temperature 31.4 °C
Sp2 Temperature 32.0 °C
Sp3 Temperature 33.0 °C
Sp4 Temperature 29.8 °C
Sp5 Temperature 30.0 °C
Sp6 Temperature 30.0 °C
Inspected By Pyae Phyo Hein Page 22
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
11-R
Circuit Information Circuit No: HEP / A-3 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
21.8A 22.2A 22.3A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-3-2
Thermogram Photo
Sp3Sp2
Sp5Sp4 Sp6
Sp1
28.7
60.7 °C
30
40
50
60
Sp1 Temperature 34.3 °C
Sp2 Temperature 34.1 °C
Sp3 Temperature 35.8 °C
Sp4 Temperature 30.9 °C
Sp5 Temperature 31.3 °C
Sp6 Temperature 30.9 °C
Inspected By Pyae Phyo Hein Page 23
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
12-R
Circuit Information Circuit No: CWP / A-4 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
26.4A 28A 28.1A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-4-2
Thermogram Photo
Sp2
Sp3 Sp5
Sp1
Sp4
27.0
62.9 °C
30
40
50
60
Sp1 Temperature 46.4 °C
Sp2 Temperature 48.0 °C
Sp3 Temperature 29.7 °C
Sp4 Temperature 29.8 °C
Sp5 Temperature 31.7 °C
Inspected By Pyae Phyo Hein Page 24
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
13-R
Circuit Information Circuit No: CHWP / A-4 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
21A 19.9A 21A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-4-2
Thermogram Photo
Sp2
Sp4Sp1
Sp3
Sp5
27.1
58.4 °C
30
40
50
Sp1 Temperature 38.6 °C
Sp2 Temperature 35.8 °C
Sp3 Temperature 29.7 °C
Sp4 Temperature 29.5 °C
Sp5 Temperature 29.1 °C
Inspected By Pyae Phyo Hein Page 25
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT
Reference Image No.
14-R
Circuit Information Circuit No: HEP / A-4 Type of component: Capacitors
Current Loading R / L1 Y / L2 B / L3 N
21.2A 21.2A 21.1A -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Power Plant Room 2 Level 1 Name of Switchboard / Equipment
: ACSB / A-4-2
Thermogram Photo
Sp2
Sp5
Sp4
Sp3Sp1
27.5
40.8 °C
30
35
40
Sp1 Temperature 43.4 °C
Sp2 Temperature 39.7 °C
Sp3 Temperature 30.1 °C
Sp4 Temperature 30.3 °C
Sp5 Temperature 30.3 °C
Inspected By Pyae Phyo Hein Page 26
Report No: 1508-04 IRTS
INFRARED THERMAL SCAN REPORT Reference Image No.
15-R
Circuit Information Circuit No: F(E) 1-21 Type of component: Contactor and Relay
Current Loading R / L1 Y / L2 B / L3 N
- - - -
Reference Temperature Fault Temperature Temperature Difference
- - -
Ambient Temperature 30oC Temperature
Category 0
ANALYSIS OF THERMOGRAM
No Thermal Anomaly was detected.
RECOMMENDATIONS
To carry Out Thermogaphy inspection at least once a year.
General Information Customer : NTT SGDC Date of Inspection : 14 August 2015
Location : Beside Storage Room level 1 Name of Switchboard / Equipment
: SCP 1-7
Thermogram Photo
Sp2
Sp3
Sp1
34.8
71.0 °C
40
50
60
70
Sp1 Temperature 55.2 °C
Sp2 Temperature 49.5 °C
Sp3 Temperature 48.8 °C