12-22 For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E January 2001 Molded Case Circuit Breakers 12 10 – 225 Amperes F-Frame Vol. 1, Ref. No. [0488] Table 12-35. Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units 1 Not UL listed. 5 kAIC interrupting rating. 2 UL listed for SWD applications, see NEC Article 240-83 (d). Note: Instruction Leaflet/FRED Number 29C101 Table 12-36. Types HFD and FDC Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units 3 UL listed for SWD applications, see NEC Article 240-83(d). Note: Instruction Leaflet/FRED Number 29C101 Max. Cont. Ampere Rating @ 40°C 600V AC Maximum, 250V DC 277V AC Maximum, 125V DC 600V AC Maximum, 250V DC 14 kAIC @ 600V AC 25 kAIC @ 277V AC 25 kAIC @ 480V AC Type FDB (Includes Terminals on Load End Only) Type FD (Includes Terminals on Load End Only) 2-Pole 3-Pole 4-Pole 1-Pole 2-Pole 3-Pole 4-Pole Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ 10 1 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 FDB2010 FDB2015 FDB2020 FDB2025 FDB2030 FDB2035 FDB2040 FDB2045 FDB2050 FDB2060 FDB2070 FDB2080 FDB2090 FDB2100 FDB2110 FDB2125 FDB2150 435. 435. 435. 435. 435. 435. 435. 393. 435. 435. 565. 565. 565. 565. 1,260. 1,260. 1,260. FDB3010 FDB3015 FDB3020 FDB3025 FDB3030 FDB3035 FDB3040 FDB3045 FDB3050 FDB3060 FDB3070 FDB3080 FDB3090 FDB3100 FDB3110 FDB3125 FDB3150 570. 570. 570. 570. 570. 570. 570. 570. 570. 570. 695. 695. 695. 695. 1,565. 1,565. 1,565. FDB4010 FDB4015 FDB4020 FDB4025 FDB4030 FDB4035 FDB4040 FDB4045 FDB4050 FDB4060 FDB4070 FDB4080 FDB4090 FDB4100 FDB4110 FDB4125 FDB4150 910. 910. 910. 910. 910. 910. 910. 910. 910. 1,110. 1,110. 1,110. 1,110. 1,110. 2,495. 2,495. 2,495. FD1010 FD1015 2 FD1020 2 FD1025 FD1030 FD1035 FD1040 FD1045 FD1050 FD1060 FD1070 FD1080 FD1090 FD1100 FD1110 FD1125 FD1150 299. 299. 299. 299. 299. 299. 299. 299. 299. 299. 335. 335. 335. 335. 760. 760. 760. FD2015 FD2020 FD2025 FD2030 FD2035 FD2040 FD2045 FD2050 FD2060 FD2070 FD2080 FD2090 FD2100 FD2110 FD2125 FD2150 FD2175 FD2200 FD2225 735. 735. 735. 735. 735. 735. 735. 735. 735. 855. 855. 855. 855. 1,915. 1,915. 1,915. 1,920. 1,920. 1,920. FD3015 FD3020 FD3025 FD3030 FD3035 FD3040 FD3045 FD3050 FD3060 FD3070 FD3080 FD3090 FD3100 FD3110 FD3125 FD3150 FD3175 FD3200 FD3225 865. 865. 865. 865. 865. 865. 865. 865. 865. 975. 975. 975. 975. 2,205. 2,205. 2,205. 2,205. 2,205. 2,205. FD4015 FD4020 FD4025 FD4030 FD4035 FD4040 FD4045 FD4050 FD4060 FD4070 FD4080 FD4090 FD4100 FD4110 FD4125 FD4150 FD4175 FD4200 FD4225 1,360. 1,360. 1,360. 1,360. 1,360. 1,360. 1,360. 1,360. 1,360. 1,495. 1,495. 1,495. 1,495. 3,080. 3,080. 3,080. 3,080. 3,080. 3,080. Max. Cont. Ampere Rating @ 40°C 277V AC Maximum, 125V DC 600V AC Maximum, 250V DC 600V AC Maximum, 250V DC 65 kAIC @ 277V AC 65 kAIC @ 480V AC 100 kAIC @ 480V AC Type HFD (Includes Terminals on Load End Only) Type FDC Current Limiting (Includes Terminals on Load End Only) 1-Pole 2-Pole 3-Pole 4-Pole 2-Pole 3-Pole 4-Pole Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 HFD1015 3 HFD1020 3 HFD1025 HFD1030 HFD1035 HFD1040 HFD1045 HFD1050 HFD1060 HFD1070 HFD1080 HFD1090 HFD1100 HFD1110 HFD1125 HFD1150 366. 366. 366. 366. 366. 366. 366. 366. 366. 427. 427. 428. 427. 1,001. 1,001. 1,005. HFD2015 HFD2020 HFD2025 HFD2030 HFD2035 HFD2040 HFD2045 HFD2050 HFD2060 HFD2070 HFD2080 HFD2090 HFD2100 HFD2110 HFD2125 HFD2150 HFD2175 HFD2200 HFD2225 885. 885. 885. 885. 885. 885. 885. 885. 885. 1,130. 1,130. 1,130. 1,130. 2,510. 2,510. 2,510. 2,720. 2,720. 2,720. HFD3015 HFD3020 HFD3025 HFD3030 HFD3035 HFD3040 HFD3045 HFD3050 HFD3060 HFD3070 HFD3080 HFD3090 HFD3100 HFD3110 HFD3125 HFD3150 HFD3175 HFD3200 HFD3225 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 1,140. 3,120. 3,120. 3,120. 3,120. 3,120. 3,120. HFD4015 HFD4020 HFD4025 HFD4030 HFD4035 HFD4040 HFD4045 HFD4050 HFD4060 HFD4070 HFD4080 HFD4090 HFD4100 HFD4110 HFD4125 HFD4150 HFD4175 HFD4200 HFD4225 1,940. 1,940. 1,940. 1,940. 1,940. 1,940. 1,940. 1,940. 1,940. 2,445. 2,445. 2,445. 2,445. 4,405. 4,405. 4,405. 4,370. 4,370. 4,370. FDC2015 FDC2020 FDC2025 FDC2030 FDC2035 FDC2040 FDC2045 FDC2050 FDC2060 FDC2070 FDC2080 FDC2090 FDC2100 FDC2110 FDC2125 FDC2150 FDC2175 FDC2200 FDC2225 1,325. 1,325. 1,325. 1,325. 1,325. 1,325. 1,325. 1,325. 1,325. 1,690. 1,690. 1,690. 1,690. 3,780. 3,780. 3,780. 3,780. 3,780. 3,780. FDC3015 FDC3020 FDC3025 FDC3030 FDC3035 FDC3040 FDC3045 FDC3050 FDC3060 FDC3070 FDC3080 FDC3090 FDC3100 FDC3110 FDC3125 FDC3150 FDC3175 FDC3200 FDC3225 1,710. 1,710. 1,710. 1,710. 1,710. 1,710. 1,710. 1,710. 1,710. 2,095. 2,095. 2,095. 2,095. 4,685. 4,685. 4,685. 4,685. 4,685. 4,685. FDC4015 FDC4020 FDC4025 FDC4030 FDC4035 FDC4040 FDC4045 FDC4050 FDC4060 FDC4070 FDC4080 FDC4090 FDC4100 FDC4110 FDC4125 FDC4150 FDC4175 FDC4200 FDC4225 2,910. 2,910. 2,910. 2,910. 2,910. 2,910. 2,910. 2,910. 2,910. 3,600. 3,600. 3,600. 3,600. 6,610. 6,610. 6,610. 6,610. 6,610. 6,610. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2

Transcript of 12-22 Molded Case Circuit Breakers 10 – 225 Amperes January … · 2015-07-15 · Molded Case...

Page 1: 12-22 Molded Case Circuit Breakers 10 – 225 Amperes January … · 2015-07-15 · Molded Case Circuit Breakers 12 10 – 225 Amperes F-Frame Vol. 1, Ref. No. [0488] Table 12-35.

12-22

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

January 2001

Molded Case Circuit Breakers

12

10 – 225 AmperesF-Frame

Vol. 1, Ref. No. [0488]

Table 12-35. Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units

1 Not UL listed. 5 kAIC interrupting rating.2 UL listed for SWD applications, see NEC Article 240-83 (d).Note: Instruction Leaflet/FRED Number 29C101

Table 12-36. Types HFD and FDC Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units

3 UL listed for SWD applications, see NEC Article 240-83(d).Note: Instruction Leaflet/FRED Number 29C101

Max.Cont.AmpereRating@ 40°C

600V AC Maximum, 250V DC 277V AC Maximum, 125V DC

600V AC Maximum, 250V DC

14 kAIC @ 600V AC 25 kAIC @ 277V AC 25 kAIC @ 480V AC

Type FDB (Includes Terminals on Load End Only) Type FD (Includes Terminals on Load End Only)

2-Pole 3-Pole 4-Pole 1-Pole 2-Pole 3-Pole 4-Pole

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

10 1152025303540455060708090

100110125150175200225

FDB2010FDB2015FDB2020FDB2025FDB2030FDB2035FDB2040FDB2045FDB2050FDB2060FDB2070FDB2080FDB2090FDB2100FDB2110FDB2125FDB2150———

435.435.435.435.435.435.435.393.435.435.565.565.565.565.

1,260.1,260.1,260.

———

FDB3010FDB3015FDB3020FDB3025FDB3030FDB3035FDB3040FDB3045FDB3050FDB3060FDB3070FDB3080FDB3090FDB3100FDB3110FDB3125FDB3150———

570.570.570.570.570.570.570.570.570.570.695.695.695.695.

1,565.1,565.1,565.

———

FDB4010FDB4015FDB4020FDB4025FDB4030FDB4035FDB4040FDB4045FDB4050FDB4060FDB4070FDB4080FDB4090FDB4100FDB4110FDB4125FDB4150———

910.910.910.910.910.910.910.910.910.

1,110.1,110.1,110.1,110.1,110.2,495.2,495.2,495.

———

FD1010FD1015 2

FD1020 2

FD1025FD1030FD1035FD1040FD1045FD1050FD1060FD1070FD1080FD1090FD1100FD1110FD1125FD1150———

299.299.299.299.299.299.299.299.299.299.335.335.335.335.760.760.760.

———

—FD2015FD2020FD2025FD2030FD2035FD2040FD2045FD2050FD2060FD2070FD2080FD2090FD2100FD2110FD2125FD2150FD2175FD2200FD2225

735.735.735.735.735.735.735.735.735.855.855.855.855.

1,915.1,915.1,915.1,920.1,920.1,920.

—FD3015FD3020FD3025FD3030FD3035FD3040FD3045FD3050FD3060FD3070FD3080FD3090FD3100FD3110FD3125FD3150FD3175FD3200FD3225

865.865.865.865.865.865.865.865.865.975.975.975.975.

2,205.2,205.2,205.2,205.2,205.2,205.

—FD4015FD4020FD4025FD4030FD4035FD4040FD4045FD4050FD4060FD4070FD4080FD4090FD4100FD4110FD4125FD4150FD4175FD4200FD4225

1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,360.1,495.1,495.1,495.1,495.3,080.3,080.3,080.3,080.3,080.3,080.

Max.Cont.AmpereRating@ 40°C

277V AC Maximum, 125V DC

600V AC Maximum, 250V DC 600V AC Maximum, 250V DC

65 kAIC @ 277V AC 65 kAIC @ 480V AC 100 kAIC @ 480V AC

Type HFD (Includes Terminals on Load End Only)

Type FDC Current Limiting (Includes Terminals on Load End Only)

1-Pole 2-Pole 3-Pole 4-Pole 2-Pole 3-Pole 4-Pole

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

Catalog Number

PriceU.S. $

152025303540455060708090

100110125150175200225

HFD1015 3

HFD1020 3

HFD1025HFD1030HFD1035HFD1040HFD1045HFD1050HFD1060HFD1070HFD1080HFD1090HFD1100HFD1110HFD1125HFD1150———

366.366.366.366.366.366.366.366.366.427.427.428.427.

1,001.1,001.1,005.

———

HFD2015HFD2020HFD2025HFD2030HFD2035HFD2040HFD2045HFD2050HFD2060HFD2070HFD2080HFD2090HFD2100HFD2110HFD2125HFD2150HFD2175HFD2200HFD2225

885.885.885.885.885.885.885.885.885.

1,130.1,130.1,130.1,130.2,510.2,510.2,510.2,720.2,720.2,720.

HFD3015HFD3020HFD3025HFD3030HFD3035HFD3040HFD3045HFD3050HFD3060HFD3070HFD3080HFD3090HFD3100HFD3110HFD3125HFD3150HFD3175HFD3200HFD3225

1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.1,140.3,120.3,120.3,120.3,120.3,120.3,120.

HFD4015HFD4020HFD4025HFD4030HFD4035HFD4040HFD4045HFD4050HFD4060HFD4070HFD4080HFD4090HFD4100HFD4110HFD4125HFD4150HFD4175HFD4200HFD4225

1,940.1,940.1,940.1,940.1,940.1,940.1,940.1,940.1,940.2,445.2,445.2,445.2,445.4,405.4,405.4,405.4,370.4,370.4,370.

FDC2015FDC2020FDC2025FDC2030FDC2035FDC2040FDC2045FDC2050FDC2060FDC2070FDC2080FDC2090FDC2100FDC2110FDC2125FDC2150FDC2175FDC2200FDC2225

1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,325.1,690.1,690.1,690.1,690.3,780.3,780.3,780.3,780.3,780.3,780.

FDC3015FDC3020FDC3025FDC3030FDC3035FDC3040FDC3045FDC3050FDC3060FDC3070FDC3080FDC3090FDC3100FDC3110FDC3125FDC3150FDC3175FDC3200FDC3225

1,710.1,710.1,710.1,710.1,710.1,710.1,710.1,710.1,710.2,095.2,095.2,095.2,095.4,685.4,685.4,685.4,685.4,685.4,685.

FDC4015FDC4020FDC4025FDC4030FDC4035FDC4040FDC4045FDC4050FDC4060FDC4070FDC4080FDC4090FDC4100FDC4110FDC4125FDC4150FDC4175FDC4200FDC4225

2,910.2,910.2,910.2,910.2,910.2,910.2,910.2,910.2,910.3,600.3,600.3,600.3,600.6,610.6,610.6,610.6,610.6,610.6,610.

Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2

TAB1201.fm Page 22 Wednesday, October 25, 2000 9:37 PM

Page 2: 12-22 Molded Case Circuit Breakers 10 – 225 Amperes January … · 2015-07-15 · Molded Case Circuit Breakers 12 10 – 225 Amperes F-Frame Vol. 1, Ref. No. [0488] Table 12-35.

12-20

For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog CAT.200.01.T.E

January 2001

Molded Case Circuit Breakers

12

10 – 225 AmperesF-Frame

Vol. 1, Ref. No. [0486]

Dimensions/WeightsTable 12-30. Dimensions in Inches (mm) Table 12-31. Approximate Shipping Weight, Lbs. (Kg)

Product SelectionThis information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbers for circuit breakers or trip units.

Table 12-32. Circuit Breaker Catalog Numbering System

Number of Poles

Width Height Depth

12

1.375 (35)2.75 (70)

6 (152)6 (152)

3.375 (86)3.375 (86)

34

4.125 (105)5.5 (140)

6 (152)6 (152)

3.375 (86)3.375 (86)

Breaker Type Number of Poles

1 2 3 4

ED, EDH, EDC — 3 (1.361) 4.5 (2.041) —

EHD, FDB, FD, HFD, FDC 2 (.907) 3 (1.361) 4.5 (2.041) 6 (2.721)

Circuit Breaker Type

EHDFDBFDHFDFDC

Number of Poles

1 = 1 Pole2 = 2 Poles3 = 3 Poles4 = 4 Poles

Trip Amperes

010015020025030035040045050060070080090100110125150175 (FD, HFD, FDC, 2-, 3-, 4-Pole Only)200 (FD, HFD, FDC, 2-, 3-, 4-Pole Only)225 (FD, HFD, FDC, 2-, 3-, 4-Pole Only)

Suffix

E = 100% Protected (4-Pole only) Neutral PoleEH = 50% Protected (4-Pole only)K = High Magnetic Molded Case SwitchL = Line and Load TerminalsS = Stainless Steel TerminalsV = 50°C CalibrationW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (≤ 100 Amperes)

F D C 3 1 0 0 L

E D C 3 2 0 0 L

Circuit Breaker Type

EDEDHEDC

Number of Poles

2 = 2-Pole3 = 3-Pole

Trip Amperes

100125150175200225

Suffix

L = Line and Load TerminalsW = Without TerminalsY = Line Terminals OnlyZ = Aluminum Terminals (100 Amperes)

TAB1201.fm Page 20 Wednesday, October 25, 2000 9:37 PM

Page 3: 12-22 Molded Case Circuit Breakers 10 – 225 Amperes January … · 2015-07-15 · Molded Case Circuit Breakers 12 10 – 225 Amperes F-Frame Vol. 1, Ref. No. [0488] Table 12-35.

12-2

For more information contact Cutler-Hammer at:

www.ch.cutler-hammer.com/catalog

CAT.200.01.T.E

January 2001

Molded Case Circuit Breakers

12

Product Line Overview

Vol. 1, Ref. No. [0468]

Product Line Description

Cutler-Hammer Molded Case Circuit Breakers are designed to provide circuit protection for low voltage distribution systems. They are described by NEMA as, “. . . a device for closing and inter-rupting a circuit between separable contacts under both normal and abnormal conditions,” and furthermore as, “. . . a breaker assembled as an integral unit in a supporting and enclosing housing of insulating material.” The NEC describes them as, “A device designed to open and close a circuit by non-automatic means, and to open the circuit automatically on a predetermined overload of current, without injury to itself when properly applied within its rating.”

So designed, Cutler-Hammer circuit breakers protect conductors against overloads and conductors and con-nected apparatus, such as motors and motor starters, against short circuits.

In low voltage distribution systems, there are many varied applications of molded case circuit breakers. Cutler-Hammer offers the most comprehensive family of molded case circuit breakers in the industry.

This family of circuit breakers includes:

Thermal Magnetic Trip Breakers

Electronic rms Trip Breakers

Molded Case Switches

Motor Circuit Protectors

Current Limiting Breakers

Special Application Breakers

World Breakers

Special Calibration

Special non-UL-listed calibrations are available for certain ambient temperatures other than 40°C and for frequencies other than 50/60 Hz or DC. Reduced interrupting ratings will apply for 400 Hz applications. Maximum thermal calibration is limited to 135A at 400 Hz.

50°C Calibration

Add suffix

V

to Catalog Number for complete breaker, listed above, when ordering listed ampere ratings for breakers to be used in 50°C ambients.

Moisture-Fungus Treatment

All circuit breaker cases are molded from glass-polyester which does not support the growth of fungus. Any parts which are susceptible to the growth of fungus will require special treatment.

Freeze-Tested Circuit Breakers

The circuit breakers may be ordered with freeze testing. This option uses special lubrication and mechanical operation is verified at -40°C.

Marine Applications

F-Frame circuit breakers can be sup-plied to meet the following marine specifications:

U.S. Coast Guard CFR 46 ABS — American Bureau of Shipping IEEE 45

These specifications generally require molded case circuit breakers to be supplied with 50°C ambient calibration, special nameplating, and plug-in adapter kits. When plug-in adapter kits are used, no terminals need be supplied.

Circuit breakers can also be supplied to meet UL489 Supplement SA (Marine Use) and UL489 Supplement SB (Naval Use).

UL489 Supplement SA applies to vessels over 65 feet in length. Requirements include 40°C ambient calibration, spe-cial labeling, and no use of aluminum conductors or terminals.

UL 489 Supplement SB requires 50°C ambient calibration, vibration testings, special nameplating and no use of aluminum conductors or terminals.

Standards and Certifications

Molded case circuit breakers are designed to conform with the follow-ing standards:

Underwriters Laboratories, Inc., Standard UL489, Molded Case Circuit Breakers and Circuit Breaker Enclosures

National Electrical Manufacturers Association Standards Publication No. AB1-1993, Molded Case Circuit Breakers

Australian Standard AS 2184, Molded Case Circuit Breakers

British Standards Institution Standard BS 4752: Part 1, Switchgear and Control Gear Part 1: Circuit Breakers

Canadian Standards Association Standard C22.2 No. 5, Service Entrance and Branch Circuit Breakers

International Electrotechnical Commission Recommendations IEC 157-1, Circuit Breakers

Japanese T-Mark Standard Molded Case Circuit Breakers

South African Bureau of Standards, Standard SABS 156, Standard Specification for Molded Case Circuit Breakers

Swiss Electro-Technical Association Standard SEV 157-1, Safety Regula-tions for Circuit Breakers

Union Technique de l’Electricite Standard NF C 63-120, Low Voltage Switchgear and Control Gear Circuit Breaker Requirements

Verband Deutscher Elektrotechniker (Association of German Electrical Engineers) Standard VDE 0660, Low Voltage Switchgear and Control Gear, Circuit Breakers

Conformance with these standards satisfies most local and international codes, assuming user acceptability and simplified application.

Molded case circuit breakers equal or exceed Federal Specification Classifi-cation W-C-375b requirements for the particular class associated with the cir-cuit breaker frame being considered.

Note:

For further information, see Circuit Breaker, CD-ROM SA.74A.01.T.E.

Suffix

H01

400 Hz 20% Adder

Suffix

J01

Fungus Treated $325. + 20% Adder

Suffix

F01

Freeze Tested 20% Adder

Suffix

H08

“Marine” 10% Adder

Suffix

H09

“Naval” 10% Adder

TAB1201.fm Page 2 Wednesday, October 25, 2000 9:37 PM

Page 4: 12-22 Molded Case Circuit Breakers 10 – 225 Amperes January … · 2015-07-15 · Molded Case Circuit Breakers 12 10 – 225 Amperes F-Frame Vol. 1, Ref. No. [0488] Table 12-35.

CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

12-19January 2001

Molded Case Circuit Breakers

12

10 – 225 AmperesF-Frame

Vol. 1, Ref. No. [0485]

ContentsDescription Page

Product Description . . . . . . . . 12-19

Technical Dataand Specifications . . . . . . . . 12-19

Dimension/Weights . . . . . . . . 12-20

Product Selection . . . . . . . . . . 12-20

F-Frame

Typical F-Frame Breaker

Product Description■ All F-Frame Circuit Breakers are

HACR rated.■ All circuit breakers 10 through

50 amperes are suitable for HID (high intensity discharge) use.

■ All F-Frame circuit breakers are suitable for reverse feed use.

Technical Data and SpecificationsTable 12-28. UL489 Interrupting Capacity Ratings

1 DC ratings apply to substantially non-inductive circuits.2 2-pole circuit breaker, or two poles of 3-pole circuit breaker.3 Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.

Table 12-29. IEC 157-1 (P1) Interrupting Capacity Ratings (P1)

4 DC ratings apply to substantially non-inductive circuits.5 2-pole circuit breaker, or two poles of 3-pole circuit breaker.6 Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds minimum at 22 kA.

Circuit Breaker Type

Number of Poles

Interrupting Capacity (Symmetrical Amperes) (kA)

Volts AC (50/60 Hz) Volts DC 1

240 277 480 600 125 250 23

ED EDH EDC

2, 3 2, 3 2, 3

65 100200

———

———

———

101010

———

EHD 12, 3

—18

14—

—14

——

10—

—10

FDB 2, 3, 4 18 — 14 14 — 10

FD 12, 3, 4

—65

25—

—25

—18

10—

—10

HFD 12, 3, 4

—100

65—

—65

—25

10—

—22

FDC 2, 3, 4 200 — 100 35 — 22

Circuit Breaker Type

Number of Poles

Interrupting Capacity (Symmetrical Amperes) (kA)

Volts AC (50/60 Hz) Volts DC 4

220, 240 380, 415 440 500 125 250 56

ED EDH EDC

2, 32, 32, 3

65100200

———

———

———

101010

———

FDB 2, 3, 4 18 14 14 14 — 10

FD 12, 3, 4

25 65

—35

—35

—18

10—

—10

HFD 12, 3, 4

65 100

—65

—65

—25

10—

—22

FDC 2, 3, 4 200 100 100 35 — 22