Molded Case Circuit Breakers 12-103 800 – 2500 Amperes · 2015. 7. 15. · IEC 947-2 Interrupting...

4
CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog 12-103 January 2001 Molded Case Circuit Breakers 12 800 – 2500 Amperes R-Frame Vol. 1, Ref. No. [0569] 100% Rated Digitrip RMS 310 Electronic Circuit Breakers The NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°C ampacity. Order as individual components: Breaker Frame (which includes Trip Unit) and Rating Plug. Table 12-158. 100% Rated Digitrip RMS 310 Electronic Circuit Breakers 12 1 See Table 12-159 below for prices. 2 Includes B2016RDL rear connectors. Refer to FRED 29170716 for dimensions. 3 For SCR application use 2000 ampere frame. 4 Add R to Catalog Number for ground fault remote indication compatibility, i.e. CRD316T33R W. Note: Instruction Leaflet/FRED Number 29C107 for Breaker; Number 29C883 for Digitrip 310 Trip Unit Table 12-159. 100% Rated Digitrip RMS 310 Electronic Circuit Breakers Prices Maximum Continuous Ampere Rating @ 40°C Circuit Breaker Frame Only Digitrip RMS 310 Rating Plug Only L Adjustable Long Delay Pickup (By Adjustable Rating Plug) S– Adjustable Short Delay Pickup with Fixed Short Delay Time (I 2 t Response) or Adjustable Short Delay Time (Flat Response) I Adjustable Instantaneous Pickup by Setting Short Delay Time to Instantaneous G– Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (Flat Response) Ampere Rating Fixed Rating Plug Adjustable Rating Plug Adjustable Ampere Ratings LS LSI LSG 4 LSIG 4 Catalog Number Catalog Number 3-Pole Standard Interrupting Capacity 600V AC Rated 65 kAIC @ 480V AC 1600 3 CRD316T33W CRD316T32W CRD316T35W CRD316T36W 800 1000 1200 1250 1400 1500 1600 16RES08T 16RES10T 16RES12T 16RES125T 16RES14T 16RES15T 16RES16T Adjustable Settings are: 800, 1000, 1200, 1600 A16RES16T1 2000 CRD320T33W CRD320T32W CRD320T35W CRD320T36W 1000 1200 1250 1400 1600 2000 20RES10T 20RES12T 20RES125T 20RES14T 20RES16T 20RES20T Adjustable Settings are: 1000, 1200, 1600, 2000 A20RES20T1 3-Pole High Interrupting Capacity 600V AC Rated 100 kAIC @ 480V AC 1600 3 CRDC316T33W CRDC316T32W CRDC316T35W CRDC316T36W 800 1000 1200 1250 1400 1500 1600 16RES08T 16RES10T 16RES12T 16RES125T 16RES14T 16RES15T 16RES16T Adjustable Settings are: 800, 1000, 1200, 1600 A16RES16T1 2000 CRDC320T33W CRDC320T32W CRDC320T35W CRDC320T36W 1000 1200 1250 1400 1600 2000 20RES10T 20RES12T 20RES125T 20RES14T 20RES16T 20RES20T Adjustable Settings are: 1000, 1200, 1600, 2000 A20RES20T1 Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ Catalog Number Price U.S. $ A16RES16T1 A20RES20T1 CRDC316T32W CRDC316T33W CRDC316T35W 148. 148. 21,240. 19,760. 22,240. CRD316T32W CRD316T33W CRD316T35W CRD316T36W CRD320T32W 19,270. 17,780. 20,260. 21,750. 20,700. 16RES12T 16RES125T 16RES14T 16RES15T 16RES16T 112. 112. 112. 112. 112. 20RES20T 112. CRDC316T36W CRDC320T32W CRDC320T33W CRDC320T35W CRDC320T36W 23,730. 21,340. 22,460. 23,820. 24,940. CRD320T33W CRD320T35W CRD320T36W 16RES08T 16RES10T 19,210. 21,690. 23,190. 112. 112. 20RES10T 20RES12T 20RES125T 20RES14T 20RES16T 112. 112. 112. 112. 112. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2

Transcript of Molded Case Circuit Breakers 12-103 800 – 2500 Amperes · 2015. 7. 15. · IEC 947-2 Interrupting...

  • CAT.200.01.T.E For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    12-103January 2001

    Molded Case Circuit Breakers

    12

    800 – 2500 AmperesR-Frame

    Vol. 1, Ref. No. [0569]

    100% Rated Digitrip RMS 310 Electronic Circuit BreakersThe NEC allows the breaker to be rated at 100% of its frame size in an assembly, provided that 90°C wire is applied at 75°C ampacity. Order as individual components: Breaker Frame (which includes Trip Unit) and Rating Plug.

    Table 12-158. 100% Rated Digitrip RMS 310 Electronic Circuit Breakers 12

    1 See Table 12-159 below for prices.2 Includes B2016RDL rear connectors. Refer to FRED 29170716 for dimensions.3 For SCR application use 2000 ampere frame.4 Add R to Catalog Number for ground fault remote indication compatibility, i.e. CRD316T33RW.Note: Instruction Leaflet/FRED Number 29C107 for Breaker; Number 29C883 for Digitrip 310 Trip Unit

    Table 12-159. 100% Rated Digitrip RMS 310 Electronic Circuit Breakers Prices

    MaximumContinuousAmpereRating@ 40°C

    Circuit Breaker Frame Only Digitrip RMS 310 Rating Plug Only

    L – Adjustable Long Delay Pickup (By Adjustable Rating Plug)S – Adjustable Short Delay Pickup with Fixed Short Delay Time

    (I2t Response) or Adjustable Short Delay Time (Flat Response)I – Adjustable Instantaneous Pickup by Setting Short Delay Time to InstantaneousG – Adjustable Ground Fault Pickup with Adjustable Ground Fault Time (Flat Response)

    AmpereRating

    FixedRatingPlug

    Adjustable Rating Plug

    Adjustable Ampere Ratings

    LS LSI LSG 4 LSIG 4

    Catalog Number Catalog Number

    3-Pole Standard Interrupting Capacity 600V AC Rated 65 kAIC @ 480V AC1600 3 CRD316T33W CRD316T32W CRD316T35W CRD316T36W 800

    100012001250140015001600

    16RES08T16RES10T16RES12T16RES125T16RES14T16RES15T16RES16T

    Adjustable Settings are:800, 1000, 1200, 1600A16RES16T1

    2000 CRD320T33W CRD320T32W CRD320T35W CRD320T36W 100012001250140016002000

    20RES10T20RES12T20RES125T20RES14T20RES16T20RES20T

    Adjustable Settings are:1000, 1200, 1600, 2000A20RES20T1

    3-Pole High Interrupting Capacity 600V AC Rated 100 kAIC @ 480V AC1600 3 CRDC316T33W CRDC316T32W CRDC316T35W CRDC316T36W 800

    100012001250140015001600

    16RES08T16RES10T16RES12T16RES125T16RES14T16RES15T16RES16T

    Adjustable Settings are:800, 1000, 1200, 1600A16RES16T1

    2000 CRDC320T33W CRDC320T32W CRDC320T35W CRDC320T36W 100012001250140016002000

    20RES10T20RES12T20RES125T20RES14T20RES16T20RES20T

    Adjustable Settings are:1000, 1200, 1600, 2000A20RES20T1

    Catalog Number

    PriceU.S. $

    Catalog Number

    PriceU.S. $

    Catalog Number

    PriceU.S. $

    Catalog Number

    PriceU.S. $

    A16RES16T1A20RES20T1CRDC316T32WCRDC316T33WCRDC316T35W

    148.148.

    21,240.19,760.22,240.

    CRD316T32WCRD316T33WCRD316T35WCRD316T36WCRD320T32W

    19,270.17,780.20,260.21,750.20,700.

    16RES12T16RES125T16RES14T16RES15T16RES16T

    112.112.112.112.112.

    20RES20T————

    112.————

    CRDC316T36WCRDC320T32WCRDC320T33WCRDC320T35WCRDC320T36W

    23,730.21,340.22,460.23,820.24,940.

    CRD320T33WCRD320T35WCRD320T36W16RES08T16RES10T

    19,210.21,690.23,190.

    112.112.

    20RES10T20RES12T20RES125T20RES14T20RES16T

    112.112.112.112.112.

    —————

    —————

    Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CB-2

    TAB1204.fm Page 103 Wednesday, October 25, 2000 9:31 PM

  • CAT.200.01.T.E For more information contact Cutler-Hammer at:

    www.ch.cutler-hammer.com/catalog

    12-97

    January 2001

    Molded Case Circuit Breakers

    12

    800 – 2500 Amperes

    R-Frame

    Vol. 1, Ref. No. [0563]

    Contents

    Description Page

    Product Description

    . . . . . . . .

    12-97Technical Data

    and Specifications

    . . . . . . . .

    12-97Dimensions/Weights

    . . . . . . .

    12-99Product Selection

    . . . . . . . . . .

    12-99

    R-Frame

    Typical R-Frame Circuit Breaker

    Product Description

    R-Frame Circuit Breakers are avail-able as frame (which includes trip unit), rating plug and terminals.

    All R-Frame circuit breakers are suitable for reverse feed use.

    Technical Data and Specifications

    Table 12-148. UL489/CSA Interrupting Capacity Ratings

    1

    1

    Utilization Category A circuit breakers.

    2

    100% Rated breakers.

    Note:

    See

    Page 12-98

    for Trip Unit Specifications.

    Table 12-149. IEC 947-2 Interrupting Capacity Ratings

    3

    3

    Utilization Category A circuit breakers.

    CircuitBreaker Type

    Number of Poles

    Interrupting Capacity (Symmetrical Amperes) (kA)

    Volts AC (50/60 Hz)

    240 277 480 600

    RD 3, 4 125 — 65 50

    CRD

    2

    3, 4 125 — 65 50

    RDC 3, 4 200 — 100 65

    CRDC

    2

    3, 4 200 — 100 65

    CircuitBreakerType

    Number ofPoles

    Interrupting Capacity (Symmetrical Amperes) (kA)

    Volts AC (50/60 Hz)

    240 415 690

    RDIcuIcs

    3, 4135100

    7050

    2513

    RDCIcuIcs

    3, 4200100

    10050

    3518

    TAB1204.fm Page 97 Wednesday, October 25, 2000 9:31 PM

  • 12-98

    For more information contact Cutler-Hammer at:

    www.ch.cutler-hammer.com/catalog

    CAT.200.01.T.E

    January 2001

    Molded Case Circuit Breakers

    12

    800 – 2500 Amperes

    R-Frame

    Vol. 1, Ref. No. [0564]

    R-Frame Digitrip Specifications

    Table 12-150. Specifications

    1

    Adjust by rating plug.

    2

    Except 2500 ampere frame is 200 – 600%.

    3

    Varies by frame.

    4

    LS/LSG only.

    5

    Not to exceed 1200 amperes.

    6

    By OPTIMizer/BIM.

    7

    Optional. Add suffix “R” to Catalog Number.BIM = Breaker Interface Module

    (A) = GF AlarmIs = Sensor RatingIn = Rating PlugIr = Long Delay Pickup Setting x In

    Trip Unit Type Digitrip RMS 310

    Digitrip RMS 510

    Digitrip RMS 610

    Digitrip RMS 810

    Digitrip RMS 910

    Digitrip OPTIM 1050

    RMS Sensing Yes Yes Yes Yes Yes Yes

    Breaker Type

    Frame R R R R R RAmpere Range 800A-2500A 800A – 2500A 800A – 2500A 800A – 2500A 800A – 2500A 800A – 2500AInterrupting Rating @ 480V 65, 100 (kA) 65, 100 (kA) 65, 100 (kA) 65, 100 (kA) 65, 100 (kA) 65, 100 (kA)

    Protection

    Ordering Options LS, LSG LSI, LSIG LI, LS, LSI, LIG,LSG, LSIG

    LI, LS, LSI, LIG,LSG, LSIG

    LI, LS, LSI, LIG,LSG, LSIG

    LI, LS, LSI, LIG,LSG, LSIG

    LSI(A), LISG

    Fixed Rated Plug (In) Yes Yes Yes Yes Yes Yes YesOvertemperature Trip Yes Yes Yes Yes Yes Yes Yes

    Long Delay Protection (L)

    Adjustable Rating Plug (In) Yes Yes No No No No NoLong Delay Pickup 0.5 – 1.0 (In)

    1

    0.5 – 1.0 (In)

    1

    0.5 – 1.0 x (In) 0.5 – 1.0 x (In) 0.5 – 1.0 x (In) 0.5 – 1.0 x (In) 0.4 – 1.0 x (In)Long Delay Time I

    2

    t 12 Seconds 12 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 Seconds 2 – 24 SecondsLong Delay Time I

    4

    t No No No No No No 1 – 5 SecondsLong Delay Thermal Memory Yes Yes Yes Yes Yes Yes YesHigh Load Alarm No No No 0.85 x Ir 0.85 x Ir 0.85 x Ir 0.5-1.0 x Ir

    Short Delay Protection (S)

    Short Delay Pickup 200 – 800% x (In)

    2

    200 – 800% x (In)

    2

    200 – 600% S1&S2 x (Ir)

    200 – 600% S1&S2 x (Ir)

    200 – 600% S1&S2 x (Ir)

    200 – 600% S1&S2 x (Ir)

    150-800% x (Ir)

    23

    Short Delay Time I

    2

    t 100 mS No 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSShort Delay Time Flat No Inst – 300 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSShort Delay Time ZoneSelective Interlocking

    No No Yes Yes Yes Yes Yes

    Instantaneous Protection (I)

    Instantaneous Pickup No 200 – 800% x (In)

    200 – 600%M1&M2 x (In)

    200 – 600%M1&M2 x (In)

    200 – 600%M1&M2 x (In)

    200 – 600%M1&M2 x (In)

    200 – 800% x (In)

    3

    Discriminator No No Yes

    4

    Yes

    4

    Yes

    4

    Yes

    4

    YesInstantaneous Override Yes Yes Yes Yes Yes Yes Yes

    Ground Fault Protection (G)

    Ground Fault Alarm

    5

    No No No No No No 25 – 100% x (In)Ground Fault Pickup

    5

    Varies by Frame

    Varies by Frame

    25 – 100% x (Is) 25-100% x (Is) 25 – 100% x (Is) 25 – 100% x (Is) 25 – 100% x (In)

    Ground Fault Delay I

    2

    T No No 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSGround Fault Delay Flat Inst – 500 mS Inst – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mS 100 – 500 mSGround Fault ZoneSelective Interlocking

    No No Yes Yes Yes Yes Yes

    Ground Fault Thermal Memory Yes Yes Yes Yes Yes Yes Yes

    System Diagnostics

    Status LEDs Yes Yes Yes Yes Yes Yes YesCause of Trip LEDs No No Yes Yes Yes Yes YesMagnitude of Trip Information No No No Yes Yes Yes YesRemote Signal Contacts Yes

    7

    Yes

    7

    No Yes Yes Yes Yes

    System Monitoring

    Digital Display No No No Yes Yes Yes Yes

    6

    Current No No No Yes Yes Yes YesVoltage No No No No No Yes NoPower and Energy No No No No Yes Yes YesPower Quality — Harmonics No No No No No Yes YesPower Factor No No No No Yes (Over

    Cutler-Hammer PowerNet Only)

    Yes Yes

    Communications

    Cutler-Hammer PowerNet No No No No Yes Yes Yes

    Testing

    Testing Method Test Set Integral Integral Integral Integral OPTIMizer, BIM, Cutler-Hammer PowerNet

    TAB1204.fm Page 98 Wednesday, October 25, 2000 9:31 PM

  • CAT.200.01.T.E For more information contact Cutler-Hammer at:

    www.ch.cutler-hammer.com/catalog

    12-99

    January 2001

    Molded Case Circuit Breakers

    12

    800 – 2500 Amperes

    R-Frame

    Vol. 1, Ref. No. [0565]

    Dimensions/Weights

    Table 12-151. Dimensions in Inches (mm)

    Table 12-152. Approximate Shipping Weight, Lbs. (kg)

    Product Selection

    This information is presented only as an aid to understanding Catalog Numbers. It is not to be used to build Catalog Numbers for circuit breakers or trip units.

    Table 12-153. Circuit Breaker/Frame Catalog Numbering System

    1

    For complete list of available trip types refer to

    Pages 12-100

    12-113

    .

    Number of Poles

    Width Height Depth

    3 15.5 (394) 16 (406) 9.75 (248)

    4 20 (508) 16 (406) 9.75 (248)

    BreakerType

    Complete Breaker

    Number of Poles

    3 4

    1600A

    RD, CRD, RDC, CRDC 102 (46.3) 135 (61.2)

    2000A

    RD, RDC 102 (46.3) 135 (61.2)

    CRD, CRDC 130 (59.0) 175 (79.4)

    2500A

    RD, RDC 135 (61.2) 182 (82.6)

    R D 3 1 6 T 3 2 W

    Circuit Breaker/Frame Type

    RDRDCCRDCRDC

    Number of Poles

    3 = 3 Poles4 = 4 Poles

    Circuit Breaker/Frame Ampere Rating

    16 = 1600A20 = 2000A25 = 2500A

    Trip Type 1

    T32 = Digitrip RMS 310 LSIT53 = Digitrip RMS 510 LST65 = Digitrip RMS 610 LSGT86 = Digitrip RMS 810 LSIGT96 = Digitrip RMS 910 LSIGT106 = Digitrip OPTIM 1050 LSIGT107 = Digitrip OPTIM 1050 LSIA

    Suffix

    W = Without TerminalsP = 100% Protected Neutral PoleR = Ground Fault Remote

    (310 Only)K = Molded Case Switch

    TAB1204.fm Page 99 Wednesday, October 25, 2000 9:31 PM

    Back To Welcome2: ContentsD: Contents: