100523924 Power Transformer Testing Procedures

4
6 Short Circuit Test and Differential Stability. 6 Short Circuit Test and Differential Stability. Stable Condition. Apply 3-Ph AC Voltage Diff Relay P1 S1 300/1 A S2 S1 N R Y B S2 S1 S2 S1 P2 S2 B-Ph Y-Ph R-Ph Id Id P1 S1 500/1 A S1 S2 Id S1 S2 S2 P2 Temporary Short

description

DONE

Transcript of 100523924 Power Transformer Testing Procedures

Page 1: 100523924 Power Transformer Testing Procedures

6 Short Circuit Test and Differential Stability.6 Short Circuit Test and Differential Stability.

Stable Condition.

Apply 3-Ph AC Voltage

Diff RelayP1 S1

300/1 AS2

S1

N R Y B

S2S1

S2S1

P2 S2

B-Ph

Y-Ph

R-Ph

Id

Id

P1 S1

500/1 AS1

S2

Id

S1S2

S2

P2

Temporary Short

Page 2: 100523924 Power Transformer Testing Procedures

Example:Short Circuit Current Calculation.

Rating : 100MVAHV LV

Voltage 220 kV 132kVCurrent 262.43 A 437.40 A% of Impedance (%Z)

HV MVA = LV MVA = 100MVA

√3 x 220000 x I1 = √3 x 123000 x I2 = 100,000,000√3 x 220000 x I1 = 100,000,000I1 = 100,000,000 / (√3 x 220000)I1 = 262 43A

= 8.05%

I1 = 262.43A

√3 x 123000 x I2 = 100,000,000I2 = 100,000,000 / (√3 x 132000)I2 = 437.40A

%Zv = = 220kV x % of impedance

8.05% 220kV x % of impedance = 220000 x (8.05/100)

%Zv = 17,710 V

If We may apply 415 V to HV sideHV I primary = (415 x 262.43) / 17710HV I primary = 6.15 AHV sec = 6.15 / 300HV 0 0205AHV sec = 0.0205A

LV I primary = (415 x 437.4) / 17710LV I primary = 10.25 ALV sec = 10.25 / 500LV sec = 0.0205 A

Page 3: 100523924 Power Transformer Testing Procedures

Unstable Condition

S1

Apply 3-Ph AC Voltage

S2S1

S2S1

S2

Id

Id

S1

S2

Id

Id

S1S2

S1S2

S2

Temporary Short

Page 4: 100523924 Power Transformer Testing Procedures