Current Transformer Theory & Testing Jay Anderson – Omicron [email protected] www.OmicronEnergy.com Hands On Relay School 2016

Transcript of Current Transformer Theory & Testing

Page 1: Current Transformer Theory & Testing

Current Transformer Theory & Testing

Jay Anderson – [email protected]

www.OmicronEnergy.com

Hands On Relay School 2016

Page 2: Current Transformer Theory & Testing

Agenda

• Introduction

• Current Transformer Basics

• Construction & Types

• Industry Standards

• Applications

• Testing

Page 3: Current Transformer Theory & Testing

Current Transformer Basics

© OMICRON Page 3

Page 4: Current Transformer Theory & Testing

Function of Current Transformers

January 19, 2016 Page: 4

• Convert Primary Power Signals to Manageable Values for

• Indicating Meters• Revenue Metering• Protective Relay Systems• Power Generation• Plant Monitoring Systems• Fault Recorders• SCADA• Overall Electric Grid Monitoring (Local Dispatch & ISO Level)• Building (Energy) Management Systems (HVAC,refrigeration...)• Load Control

Page 5: Current Transformer Theory & Testing

Current Transformers

January 19, 2016 Page: 5

• Insulation from High Voltages and Currents

• Isolation from other systems

• Safety

• Standardization

• Accuracy ( Ratio & Phase)

• Typically Low Power Rating

• Thermal Considerations

• Burden Considerations

Page 6: Current Transformer Theory & Testing

Current Transformers

January 19, 2016 Page: 6

• Insulation Consistent With Voltage Use

• Wide Range of Current to Replicate (Unlike VTs)

• Metering or Protective Class Ratings

• Typically Unprotected

• Dangerous When Open Circuited

Page 7: Current Transformer Theory & Testing

Compliance & Standards

IEEE

ANSI

IEC in Europe & Asia

NERC Reliability Standards in US

Instrument Transformers Are Expected to Perform & Conform

Page 8: Current Transformer Theory & Testing

Supported standards

© OMICRON Page 8

• IEEE C57.13standard requirements for instrument transformers

• IEEE C57.13.6standard for high-accuracy instrument transformers

• IEC 60044-1current transformers

• IEC 60044-6requirements for protective current transformers for transient performance

• IEC 61869-2additional requirements for current transformers

Page 9: Current Transformer Theory & Testing

Basic Transformer

~ Z

Ф

Ф

N2N1

Page 10: Current Transformer Theory & Testing

How it Works

Ignoring Magnetic and Resistive losses for the moment:

1

2

2

1

21

II

nnü

• The Current in the Seconday is Directly Proportional to thePrimary Current by the Factor of the Turns Ratio

In An Ideal CT

Page 11: Current Transformer Theory & Testing

In a Real CT - CT Analyzer Model

The 3 parts of the CTA model:

• Winding Ratio (Purely the Ratio of Turns)• Magnetic & Core Losses from Hysteresis, Gaps, Inductance, Eddy Currents• Winding Resistance Losses

ZBLm

P1

P2 S2

S1VcoreNp Ns

Page 12: Current Transformer Theory & Testing

CT Construction Types

• Window or Bus Type• Split Core• Freestanding• Outdoor versus Indoor

Page 13: Current Transformer Theory & Testing

Construction Types

© OMICRON Page 13

Window or Bus Bar

Page 14: Current Transformer Theory & Testing

Construction TypesSplit Core

Page 15: Current Transformer Theory & Testing

Construction Types

• Wound or Inductive

• Could be GIS Encapsulated

• HV Outdoor Freestanding Shown

Page 16: Current Transformer Theory & Testing

High Voltage Current Transformer

January 19, 2016 Page: 16

Page 17: Current Transformer Theory & Testing

Construction Types

• Wound or Inductive

• Bushing Mounted

• External

• GIS Breaker

Page 18: Current Transformer Theory & Testing

CT Cores

January 19, 2016 Page: 18

Page 19: Current Transformer Theory & Testing

CT with Multiple Cores

January 19, 2016 Page: 20

Page 20: Current Transformer Theory & Testing

Insulation of a Core Pile

January 19, 2016 Page: 21

Page 21: Current Transformer Theory & Testing

• H1 on HV side

• X1 on LV Side

Polarity and Terminal Marking

Page 22: Current Transformer Theory & Testing

January 19, 2016

Current Transformer Secondary Types

IEEE C57.13 IEC 60044-1

• Can be Expressed in 5 Amp or 1 Amp Ratio

• Example 2000:5 or 200/1

Page 23: Current Transformer Theory & Testing

Page 24© OMICRON

Multi-Ratio ExampleCurrent Transformer Secondary Types

Page 24: Current Transformer Theory & Testing

19 January 2016Page 25

CTs for Protection and Metering Applications

• A distinction has to be made between a metering class and a protection class current transformer.

• The designs of the magnetic cores are different.

• This insures that they perform according to the needs of theparticular connected device.

Page 25: Current Transformer Theory & Testing

Metering vs Protection Classes

January 19, 2016 Page: 26

Metering core

A metering core is designed to work more accurately within the ratedcurrent range designated. When current flow exceeds that rating, themetering core will become saturated, thereby limiting the amount ofcurrent level within the device. This protects connected meteringdevices from overloading in the presence of fault level current flows. Itbuffers the meter from experiencing excessive torques that might becreated during those faults.

High accuracy in a smaller range.

Less core material is needed

Leads to Lower Saturation Voltages

Page 26: Current Transformer Theory & Testing

Protection core

A protection core is designed to transform a distortion-free signaleven well into the overcurrent range. This enables the protectiverelays to measure the fault current value accurately, even in very high current conditions.

Relays are required to perform in fault current type situations

Moderate accuracy over a wider range

More core material is needed

Metering vs Protection Classes

Page 27: Current Transformer Theory & Testing

Protection CT Classes (IEEE C57.13-2008)

C 200C Rating: - Less than 3% ratio error at rated current- Less than 10% ratio error at 20 times rated current- Standard burden 200V/ (5A x 20) = 2Ω

200: - Secondary terminal voltage which the CT must maintain

within the C Rating which is 200V in this example.

- In CTAnalyzer – This is known as Vb

Page 28© OMICRON

CT Classes defines the Performance of a CT

Page 28: Current Transformer Theory & Testing

Actual Transformer Label (Protection Class)

1. Manufacturer’s name or trademark

2. Manufacturer’s type

3. Rated primary and secondary current

4. Continuous thermal current rating factor (RF)

5. Accuracy classes

6. Rated frequency (Hz)

7. Insulation and Basic impulse insulation level (BIL kV)

Page 29© OMICRON

FLEX-CORECURRENT TRANSFORMERRATIO 3000:5A. CAT 781-302MRRF 1.5 ACC CLASS C20050-400 HZ 600V INS CLASS 10kV BIL

Page 29: Current Transformer Theory & Testing

Other Protection CT Classes (IEEE C57.13-2008)

© OMICRON Page 30

• C – Ratio error can be determined by Calculation from the Excitation Curve

• K – Same as C class, except the Knee-point must be greater than 70% of the VB rating

• T – Ratio error must be determined by Test due to significant leakage flux

• PX – User defined CT performance (e.g. Vk, Ik, Rct )

Page 30: Current Transformer Theory & Testing

Metering CT Classes (IEEE C57.13-2008)

© OMICRON Page 31

0.3 0.9B

• At 100% rated current, the error limit is 0.3%

• At 10% rated current, the error limit is 0.6% (doubled)

Metering Class CT

Maximum Burden (e.g. 0.9Ω )

Page 31: Current Transformer Theory & Testing

Ratio Error

© OMICRON Page 32

Page 32: Current Transformer Theory & Testing

Rating Factor (RF)

© OMICRON Page 33

Multiples of Rated Current to which the CT can maintain its accuracy

Typical RF: 1, 1.5, 2, 3, 4

Example: 200/5A CT with RF 2

CT will maintain it’s accuracy certification up to 400A

Page 33: Current Transformer Theory & Testing

Metering CT Accuracy

© OMICRON Page 34

Page 34: Current Transformer Theory & Testing

Actual Transformer Label (Metering)

© OMICRON Page 35

INSTRUMENT TRANSFOMERS,INC.CURRENT TRANSFORMERRATIO 400:5 A. CAT 115-401RF 2.0 ACC CLASS 0.3B0.9 C5050-400 HZ 600V INS CLASS 10kV BIL

1. Manufacturer’s name or trademark

2. Manufacturer’s type

3. Rated primary and secondary current

4. Continuous thermal current rating factor (RF)

5. Accuracy classes

6. Rated frequency (Hz)

7. Insulation and Basic impulse insulation level (BIL kV)

Page 35: Current Transformer Theory & Testing

Actual Transformer Label (Meter Class)

Page 36: Current Transformer Theory & Testing

Error Parallelogram: Metering CTs

© OMICRON Page 37

Source: IEEE C57.13-2008

Page 37: Current Transformer Theory & Testing

CT Selection

© OMICRON Page 38

Page 38: Current Transformer Theory & Testing

Residual Magnetism (Remanence flux)

• When excitation is removed from the CT, some of the magnetic domains retain a degree of orientation relative to the magnetic field that was applied to the core

• Residual magnetism in CTs can be described by amount of flux left in the core

Page 39© OMICRON

Page 39: Current Transformer Theory & Testing

Causes of Residual Magnetism

Residual Magnetism Can Occur Due To:

• High Transient Fault Currents

• Circuit Breaker Arc During Trip Operations

• DC Currents Due to Winding Resistance Measurement

• Other Tests

Page 40© OMICRON

Page 40: Current Transformer Theory & Testing

Residual Magnetism – How to get rid of?

Page 41© OMICRON

Demagnetization process

Done automatically by the CTAnalyzer at the very end of the measurement

Page 41: Current Transformer Theory & Testing

Testing CTs

• When ?• Initial Commissioning• Investigation• Scheduled

Page 42© OMICRON

• Why ?• Verify Factory Tests• Ordered/Delivered Correctly• Insure no damage

Page 42: Current Transformer Theory & Testing

Test Methods

• Primary Injection

• Secondary Injection – Fixed Frequency

• Secondary Injection – Variable Frequency

Page 43: Current Transformer Theory & Testing

Test Requirements

• Excitation to Determine Knee/Saturation Point

• Insulation

• Polarity

• Winding Resistance

• Primary Ratio

• Secondary Ratio

• Burden Check

• Documentation

Page 44: Current Transformer Theory & Testing

Why So Many Tests?

© OMICRON Page 45

• Ensure proper Relay Operation

• Certify Billing Accuracy

• Reduce Possibility of Failure when Energized

• Reduce Possibility of Injury Due to Failure

• Manufacturing Defects Do Happen

• Installation Errors Do Happen

Page 45: Current Transformer Theory & Testing

What is This Relic ???

Page 46© OMICRON

Page 46: Current Transformer Theory & Testing

Test Setup

Page 47© OMICRON

Test Set or Variac or DC

SourceV V

A

Page 47: Current Transformer Theory & Testing

Excitation curves for multi-ratio C class CT

Page 48© OMICRON

Page 48: Current Transformer Theory & Testing

Relay Class Test Result

Page 49© OMICRON

Page 49: Current Transformer Theory & Testing

Page 50© OMICRON

Relay Class Test Result

Page 50: Current Transformer Theory & Testing

Test Results

Page 51© OMICRON

Page 51: Current Transformer Theory & Testing

Actual Test Results - Pass

© OMICRON Page 52

Page 52: Current Transformer Theory & Testing

Actual Test Results - Failure

© OMICRON Page 53

Page 53: Current Transformer Theory & Testing

Thank youwww.OmicronEnergy.com

© OMICRON Page 54

Jay Anderson – [email protected]

Questions ?