1 Stratos D Dual Volute 2 Models Stratos D 2.0 3 x 40 (two 1.5 3 x 40) Stratos D 3.0 3 x 40 Built in...

8
1 Stratos D Stratos D Dual Volute 2 Models Stratos D 2.0 3 x 40 (two 1.5 3 x 40) Stratos D 3.0 3 x 40 Built in “check” valve IF Modules Extra EFFICIENT! ECM Product – Electrical Variable flow – System Installation Launch at ASHRAE/AHR

Transcript of 1 Stratos D Dual Volute 2 Models Stratos D 2.0 3 x 40 (two 1.5 3 x 40) Stratos D 3.0 3 x 40 Built in...

1

Stratos D

Stratos D• Dual Volute• 2 Models

• Stratos D 2.0 3 x 40 (two 1.5 3 x 40)• Stratos D 3.0 3 x 40

• Built in “check” valve• IF Modules Extra• EFFICIENT!

• ECM Product – Electrical• Variable flow – System• Installation

• Launch at ASHRAE/AHR

2

Two parallel pumps (powerheads) in one volute.

> Single operation, one main, one standby (factory default)

> Parallel operation, both pumps running when needed (set via red button or Infra-Red device)

NOTE: Position of integrated diverting check valve

Stratos D

3

Stratos D

4

Stratos D – WILO Select

5

The Stratos D twin-head pump provides the following functions:

> Dual pump management

> Energy management

> Automatic fault actuated changeover

> On fault of one of the two pump heads

> Parallel operation

> High flow operation with both pump heads running as required

> Main / standby operation

> Daily duty alternation

> Even operation time of both pump heads (alternation ever 24 hours of run time)

> Master/ Slave Function

> Automatic control of the twin-head pump by the master (control inputs into the master only)

Stratos D

Mounting positions

Single-head pumps Twin-head pumps

6

Stratos D – Introductory Training

7

Stratos D

All IF modules have the capability of connection / communication to one other Stratos (IF module required for both pumps). This enables dual control (master/slave) in parallel applications. Benefits include:

• Stand-by operation in the event of a failure (5 min delay)

• 24 hour run time automatic alternation

• Optional operation of both pumps when necessary

• Master/Slave function

• On start-up both controllers flash “MA”

• Press in either red button to set master

• Slave pump follows adjustments made by master

• Ext control wired to master IF Module

Stratos D – IF Module Wiring