APPENDIX
ENTECELECTRIC & ELECTRONIC CO., LTD
ENTEC
Release Date: Oct 2006
Copyright © 2002 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation
APPENDIX http://www.entecene.co.kr
3ENHANCED TECHNOLOGY
TABLE OF CONTENTS
Appendix A. OPTO INPUT FUNCTION ………………………………………………………...4
Appendix B. RELAY OUTPUT FUNCTION ……………………………………………………5
Appendix C. SYSTEM STATUS ………………………………………………………………….6
Appendix D. DIAGNOSTIC EVENT …………………………………………………………….8
Appendix E. MENU MESSAGE & HELP MESSAGE DESCRIPTION ..……...……………..9
Appendix F. Ordering Guide …………………….………………………..................................21
APPENDIX http://www.entecene.co.kr
4 ENHANCED TECHNOLOGY
APPENDIX A. OPTO INPUT FUNCTION Table A-1. OPTO INPUT FUNCTION Function Explanation NONE Not in use TRIP Use for Trip(open) Order CLOSE Use for Close Order PROTEC E/D Use for PROTECTION Enable/Disable function GND E/D Use for GROUND Enable/Disable function SEF E/D Use for SEF Enable/Disable function REC E/D Use for RECLOSE Enable/Disable function C LOCK E/D Use for CONTROL Locked/Unlocked function
ALT E/D Use to change the setting value of ALTERNATE SETTINGS Enable/Disable to Primary/Alternate
PG1 E/D Use for PROGRAM1 Enable/Disable function PG2 E/D Use for PROGRAM2 Enable/Disable function HLT E/D Use for HOT LINE TAG Enable/Disable function FI RESET Use for FAULT INDICATION Reset function BATT LT Use for BATTERY LOAD TEST function OUT1~8 RESET Use for OUTPUT RELAY 1~8 RESET function
APPENDIX http://www.entecene.co.kr
5ENHANCED TECHNOLOGY
Appendix B. RELAY OUTPUT FUNCTION
Table B-1. RELAY OUTPUT FUNCTION Function Explanation NONE Not in use TRIP Use for External Output when TRIP order occurs CLOSE Use for External Output when CLOSE order occurs FAIL TRIP Use for External Output when TRIP fails FAIL CLOSE Use for External Output when CLOSE fails FAIL AC Use for External Output when AC lost FAIL BATT Use for External Output when Battery discharges 27 Use for External Output when 27 Element appears 59 Use for External Output when 59 Element appears 25 Use for External Output when 25 Element appears 81 Use for External Output when 81 Element appears 79 RS Use for External Output when 79 Element appears 79 CY Use for External Output when 79 Cycle appears 79 LO Use for External Output when 79 Lockout appears SELFCHECK Use for External Output when Self check appears PRO ENABLE Use for External Output when Protection Enable GND ENABLE Use for External Output when Ground Enable SEF ENABLE Use for External Output when SEF Enable RECL ENABLE Use for External Output when RECLOSE Enable CONTR LOCK Use for External Output when Control locked REM ENABLE Use for External Output when Remote Enable ALT ENABLE Use for External Output when Alternate Settings Enable PG1 ENABLE Use for External Output when Program1 Enable PG2 ENABLE Use for External Output when Program2 Enable HLT ENABLE Use for External Output when HOT LINE TAG Enable FAULT INDI Use for External Output when Fault indicator appears ALARM Use for External Output when Alarm 52A Use for External Output when 52A on (close status) INPUT01~08 Use for External Output when Input01~08 input appears
APPENDIX http://www.entecene.co.kr
6 ENHANCED TECHNOLOGY
Appendix C. SYSTEM STATUS
Table C-1. SYSTEM STATUS (1/2) Element LCD Text Explanation
PHASE F Phase fast protection element
PHASE D Phase delay protection element
GROUND F Ground fast protection element
GROUND D Ground delay protection element
NEUTRAL F Neutral fast protection element
NEUTRAL D Neutral delay protection element
NEG SEQ F Negative Sequence fast protection element
NEG SEQ D Negative Sequence fast protection element
P HIGH LO Phase High Current lockout protection element
G HIGH LO Ground High Current lockout protection element
N HIGH LO Neutral High Current lockout protection element
NEG HIGH LO Negative Sequence High Current lockout protection element
P HIGH TR Phase High Current Trip protection element
G HIGH TR Ground High Current Trip protection element
N HIGH TR Neutral High Current Trip protection element
NEG HIGH TR Negative Sequence High Current Trip protection element
SEF TR Sensitive Earth Fault protection element
P-DEMT TR Phase demand Trip element
G DEMT TR Phase demand Trip element
FREQ TR Frequency Protection element
UNDER1VOLT Under-voltage 1 protection element
UNDER2VOLT Under-voltage 2 protection element
OVER1 VOLT Over-voltage 1 protection element
OVER2 VOLT Over-voltage 2 protection element
PROTECTION
SYNCH CHK Syncro Check
52A CONTACT 52A 52A contact status
79 RESET Sequence reset status
79 CYCLE Sequence cycle status SEQUENCE STATUS
79LOCKOUT Sequence lockout status
LOCAL CL Front Panel CLOSE pushbutton FRONT PANEL CONTROL
LOCAL OP Front Panel OPEN pushbutton
APPENDIX http://www.entecene.co.kr
7ENHANCED TECHNOLOGY
Table C-1. SYSTEM STATUS (2/2) Element LCD Text Explanation
LOCAL FI/R Front Panel FI RESET pushbutton
LOCAL BT Front Panel BATTERY LOAD TEST pushbutton
PROT EN Front Panel PROTECTION ENABLED pushbutton
GND EN Front Panel GROUND ENABLED pushbutton
SEF EN Front Panel SEF ENABLED pushbutton
RECLOSE EN Front Panel SEF ENABLED pushbutton
CONTR LOCK Front Panel SEF ENABLED pushbutton
REMOTE EN Front Panel SEF ENABLED pushbutton
ALT EN Front Panel SEF ENABLED pushbutton
PROG1 EN Front Panel SEF ENABLED pushbutton
PROG2 EN Front Panel SEF ENABLED pushbutton
FRONT PANEL CONTROL
HOTLINE EN Front Panel SEF ENABLED pushbutton
AC SUPPLY AC POWER AC supply status
EXT OPEN External OPEN element EXTERNAL CONTROL
EXT CLOSE External CLOSE element
CB LOCK Circuit Breaker (Recloser) LOCK
FAIL TRIP FAIL TRIP FAIL OPERATION
FAIL CLOSE FAIL CLOSE
EXTERNAL INPUT STATUS EXT IN01-08 External INPUT01-08 Active
SYSTEM ALARM SYS ALARM System Alarm Active
TRIP/CLOSE TRIP-SIG
CLOSE-SIG
Trip Signal
Close Signal
APPENDIX http://www.entecene.co.kr
8 ENHANCED TECHNOLOGY
Appendix D. DIAGNOSTIC EVENT
Table D-1. DIAGNOSTIC EVENT Element LCD TEXT Explanation
AC FAIL External power FAIL CHGBD FAIL Battery charge circuit FAIL BATT DISCHG Battery Discharge (Value < 21V) NO BATTERY NO Battery (Value < 15V) BATT FAIL Battery Discharge or No Battery SYSPOW FAIL System power FAIL +12V FAIL System power +12V FAIL +5 V FAIL System power +5V FAIL
SYSTEM POWER
-12V FAIL System power -12V FAIL SLEEP MODE SLEEP MODE Panel sleep mode POWER DOWN MODE POWER DOWN Power down mode
GAS LOW Gas pressure Low (Value < 0.1 Bar) GAS STATUS
GAS HIGH Gas pressure High (Value > 1.5 Bar) AD BUSY A/D conversion FAIL REF1V FAIL A/D converter reference voltage 1 FAIL A/D CONVERSION REF2V FAIL A/D converter reference voltage 2 FAIL
SETTING SET CHANGE Setting Changed SYSTEM RESTART RESTART System restarted
P-ROM FAIL Parallel EEPROM FAIL S-ROM FAIL Serial EEPROM FAIL D-RAM FAIL Data RAM FAIL S-RAM FAIL Setting RAM FAIL R-RAM FAIL RTC NV RAM FAIL RTC FAIL RTC Time FAIL RTC BAT LO RTC Battery LOW I-VAL FAIL Initial Value FAIL
MEMORY
I-SET FAIL Initial Setting Value FAIL C-BD FAIL Commuicaton Option Board FAIL
COMMUNICATION COLD RST Cold Restarted
APPENDIX http://www.entecene.co.kr
9ENHANCED TECHNOLOGY
Appendix E. MENU MESSAGE & HELP MESSAGE DESCRIPTION
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (1/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
SELECT SETBANK Primary Select BANK for Primary Setting (BANK1-BANK6) BANK1
Alternate Select BANK for Alternate Setting (BANK1-BANK6) BANK2
Edit Select BANK for EditBank Setting (BANK1-BANK6) BANK3
PRIMARY / ALTERNATE / EDITBANK SETTING
1.RELAY SETUP 1.PASSCODE : Passcode Change Setup 2.COMMUNICATION 1. REMOTE METHOD
Select Remote protocol (DNP3.0,MODBUS,IEC104) IEC104
2. COMM SETTING (DNP3.0) Line Speed DNP line speed (1200,2400,4800,9600,19200 bps) 1200
Line Type DNP line type (2,4 wire) 4
D/L Confirm Enable data link layer confirm (NO,YES,SOMETIMES) SOME
D/L Retries Data link layer retries (0-2) 1 0
D/L Timeout Data link layer time-out (1-255 sec) 1 15
A/L Retries Application layer retries (0-2) 1 0
A/L Timeout Application layer time-out (1-255 sec) 1 15
PowUp Unsol Enable unsolicited reporting at power-up (DISABLE,ENABLE) DISABLE
Unsol time Age of oldest event to transmit on (0-255 sec) 1 5
Master Addr Master station address (0-65535) 1 65534
SBO Time Select before operate time-out (1-255 sec) 1 15
DNP Address DNP address (0-65535) 1 1
Multi Inter Transmission interval at multiframe (0.01-300.00 sec) 0.01 0.10
Tx Delay Transmission time delay (0.00(OFF), 0.01-300.00 sec) 0.01 0.05
RTS Off Dly RTS off Time delay (0.01-300.00 sec) 0.01 0.05
CTS Chk Out CTS check-out time (0.01-300.00 sec) 0.01 5.00
DCD Timeout DCD check-out time (0.01-300.00 sec) 0.01 5.00
VOC1 Lev(%) Value of change event 1 setting (OFF,1-50 %) 1 OFF
VOC1 Min(CT) Value of change event 1 limit value (0.04-3.20 xCT ratio) 0.01 0.50
VOC2 Lev(%) Value of change event 2 setting (OFF,1-50 %) 1 OFF
VOC2 Min(VT) Value of change event 2 limit value (0.00-1.25 xVT ratio) 0.01 0.10
VOC3 Lev(%) Value of change event 3 setting (OFF,1-50 %) 1 OFF
APPENDIX http://www.entecene.co.kr
10 ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (2/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
VOC3 Min Value of change event 3 limit value (0-60000) 1 0
Class 1 Enable unsolicited class 1 (DISABLE,ENABLE) DISABLE
Class 2 Enable unsolicited class 2 (DISABLE,ENABLE) DISABLE
Class 3 Enable unsolicited class 3 (DISABLE,ENABLE) DISABLE
Time Req(m) Time Synch’ Request Interval (OFF,1-30000 minute) 1 OFF
Use Port Use port of control (PORT2-232,PORT3-422,PORT3-485) PORT2-232
2. COMM SETTING (MODBUS) Line Speed Modbus line speed (1200,2400,4800,9600,19200 bps) 1200
Parity Chk Parity Check Select (NONE,ODD,EVEN) NONE
Data Bit Data Bit Select (7,8) 8
Stop Bit Stop Bit Select (1,2) 1
Modbus Type Modbus protocol type ( RTU or ASCII) RTU
Slave Address Modbus address (1-254) 1 1
Line Type Modbus line type (485line, 422 line) 485LINE
Tx Delay Transmission time delay(0.000-0.500 sec) 0.001 0.005
2. COMM SETTING (IEC60870-5-104)
IP Addr’ 1 IP address 1 (0~255) 1 0
IP Addr’ 2 IP address 2 (0~255) 1 0
IP Addr’ 3 IP address 3 (0~255) 1 0
IP Addr’ 4 IP address 4 (0~255) 1 0
Gateway Addr’ 1 Gateway address 1 (0~255) 1 0
Gateway Addr’ 2 Gateway address 2 (0~255) 1 0
Gateway Addr’ 3 Gateway address 3 (0~255) 1 0
Gateway Addr’ 4 Gateway address 4 (0~255) 1 0
S/M Subnet mask (255.000.000.000~255.255.255.252) 255.255.255.000
Tcp Port No Tcp port number (1~65535) 1 2404
ASDU Addr Application service data unit address (0~65535) 1 0
Cyclic Period Cyclic period (1~60000 sec) 1 60
3.CLOCK : Present Time Change Setup 4.TIME DISP’TYPE Time Disp’Type Time Display Type (YMD, MDY) YMD
5.EVENT RECORDER Fault Cycle Fault cycle event record (OFF,ON) ON
Len' of Pre F Length of prefault in fault cycle (0-14 cycle) 1 4
Load Profile Load profile event record (OFF,ON) ON
L.P save time(m) Load profile save interval (5,10,15,20,30,60 min) 15
6.CLEAR SAVED DATA : Stored Value Clear 7.FATORY DEBUG : Fatory Debug Setup
APPENDIX http://www.entecene.co.kr
11ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (3/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
8.GAS SENSOR TYPE Type Select Gas sensor type (NONE,TYPE1,TYPE2) TYPE2
2.SYSTEM SETUP 1.CURRENT SENSING PHA CT Ratio Phase current transformer ratio (1-1200:1) 1 1000
GND CT Ratio Ground current transformer ratio (1-1200:1) 1 1000
SEF CT Ratio SEF current transformer ratio (1-1200:1) 1 1000
2.LINE VS SENSING Connect Type Line VT connect type (NONE, WYE, DELTA, CVD-W, CVD-D) NONE
VT 2nd(v) Line VT secondary nominal volt (50.0-250.0 V) 0.1 100.0
VT Ratio Line VT Ratio (10.0-760.0:1) 0.1 86.6
3.LINE VL SENSING Connect Type Line VT connect type (NONE, WYE, DELTA, CVD-W, CVD-D) NONE
VT 2nd(v) Line VT secondary nominal volt (50.0-250.0 V) 0.1 100.0
VT Ratio Line VT Ratio (10.0-760.0:1) 0.1 86.6
4.SYSTEM POWER Frequency Power line nominal frequency (50,60 Hz) 50
Phase Rotation Power line phase rotation (ABC,ACB) ABC
5.PANEL SLEEP TIME Interval(m) Display panel sleep time (0(OFF),1-100 min) 1 5
6.OPTO INPUT SET I1 Func Opto input 1 function (NONE,TRIP,..,OUT8 RESET) NONE
OPTO INPUT FUNCTION
NONE TRIP CLOSE PROTEC E/D GND E/D SEF E/D
REC E/D C LOCK E/D ALT E/D PG1 E/D PG2 E/D HLT E/D
FI RESET BATT LT OUT1 RESET OUT2 RESET OUT3 RESET OUT4 RESET
OUT5 RESET OUT6 RESET OUT7 RESET OUT8 RESET
I1 Debounce Opto input 1 debounce time (0.01-9.99 sec) 0.01 0.02
I2 Func Opto input 2 function (NONE,TRIP,..,OUT8 RESET) NONE
I2 Debounce Opto input 2 debounce time (0.01-9.99 sec) 0.01 0.02
I3 Func Opto input 3 function (NONE,TRIP,..,OUT8 RESET) NONE
I3 Debounce Opto input 3 debounce time (0.01-9.99 sec) 0.01 0.02
I4 Func Opto input 4 function (NONE,TRIP,..,OUT8 RESET) NONE
I4 Debounce Opto input 4 debounce time (0.01-9.99 sec) 0.01 0.02
I5 Func Opto input 5 function (NONE,TRIP,..,OUT8 RESET) NONE
I5 Debounce Opto input 5 debounce time (0.01-9.99 sec) 0.01 0.02
APPENDIX http://www.entecene.co.kr
12 ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (4/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
I6 Func Opto input 6 function (NONE,TRIP,..,OUT8 RESET) NONE
I6 Debounce Opto input 6 debounce time (0.01-9.99 sec) 0.01 0.02
I7 Func Opto input 7 function (NONE,TRIP,..,OUT8 RESET) NONE
I7 Debounce Opto input 7 debounce time (0.01-9.99 sec) 0.01 0.02
I8 Func Opto input 8 function (NONE,TRIP,..,OUT8 RESET) NONE
I8 Debounce Opto input 8 debounce time (0.01-9.99 sec) 0.01 0.02
7.OUTPUT RELAY SET O1 Func Output relay 1 function (NONE,..,INPUT08) NONE
OUTPUT RELAY FUNCTION
NONE TRIP CLOSE FAIL TRIP FAIL CLOSE FAIL AC
FAIL BATT 27 59 25 81 79RS
79CY 79LO SELFCHECK PRO ENABLE GND ENABLE SEF ENABLE
REC ENABLE CONTR LOCK REM ENABLE ALT BNABLE PG1 ENABLE PG2 ENABLE
HLT ENABLE FAULT INDI ALARM 52A INPUT01 INPUT02
INPUT03 INPUT04 INPUT05 INPUT06 INPUT07 INPUT08
O1 Type Output relay 1 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O1 Pulse T Output relay 1 pulse output time (0.01-99.99 sec) 0.01 0.05
O2 Func Output relay 2 function (NONE,..,INPUT08) NONE
O2 Type Output relay 2 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O2 Pulse T Output relay 2 pulse output time (0.01-99.99 sec) 0.01 0.05
O3 Func Output relay 3 function (NONE,..,INPUT08) NONE
O3 Type Output relay 3 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O3 Pulse T Output relay 3 pulse output time (0.01-99.99 sec) 0.01 0.05
O4 Func Output relay 4 function (NONE,..,INPUT08) NONE
O4 Type Output relay 4 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O4 Pulse T Output relay 4 pulse output time (0.01-99.99 sec) 0.01 0.05
O5 Func Output relay 5 function (NONE,..,INPUT08) NONE
O5 Type Output relay 5 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O5 Pulse T Output relay 5 pulse output time (0.01-99.99 sec) 0.01 0.05
O6 Func Output relay 6 function (NONE,..,INPUT08) NONE
O6 Type Output relay 6 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O6 Pulse T Output relay 6 pulse output time (0.01-99.99 sec) 0.01 0.05
O7 Func Output relay 7 function (NONE,..,INPUT08) NONE
O7 Type Output relay 7 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
O7 Pulse T Output relay 7 pulse output time (0.01-99.99 sec) 0.01 0.05
O8 Func Output relay 8 function (NONE,..,INPUT08) NONE
O8Type Output relay 8 output type (PULSE,LATCH,SELF RESET LATCH) S/R LATCH
APPENDIX http://www.entecene.co.kr
13ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (5/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
O8 Pulse T Output relay 8 pulse output time (0.01-99.99 sec) 0.01 0.05
8.LOOP CONTROL Type Select Select Recloser Type (NONE,SEC,MID,TIE) NONE
VRS - S/M Voltage response side to SEC & MID (VS,VL) VS
VRS - Tie Voltage response side to TIE (VS,VL,VS&VL) VS
VS wire Line VS wire (3PN,3PP,1PN(A),1PN(B),1PN(C),1PP(AB),
1PP(BC),1PP(CA)) 3PN
VL wire Line VL wire (1PN(A),1PN(B),1PN(C),1PP(AB),1PP(BC),1PP(CA)) 1PN(A)
Cng Alt - Mid Select auto change to Alternate Setting at Mid Point (OFF, ON) OFF
Cng Alt - Tie Select auto change to Alternate Setting at Tie Point
(OFF,ON(VS),ON(VL),ON(BOTH)) OFF
LC After Cl Select after manual close (DISABLE, ENABLE) DISABLE
LC After Op Select after manual open (DISABLE, ENABLE) DISABLE
OT Both DL Open time on both dead Line (0.01 ~ 600.00 sec) 0.01 10.00
Auto Rest’ T Auto restoration Time (0.01 ~ 600.00 sec) 0.01 5.00
DL V Max(%) Dead Line maximum voltage (20.0 ~ 70.0 %) 0.1 50.0
LL V Min(%) Live Line minimum voltage (50.0 ~ 85.0 %) 0.1 70.0
DL Pickup T Dead Line Pickup time delay (0.01 ~ 600.00 sec) 0.01 50.00
LL Regain T Live Line Pickup time delay (0.01 ~ 600.00 sec) 0.01 10.00
DL Reset T Dead Line Reset time delay (0.01 ~ 600.00 sec) 0.01 5.00
NRT After LC Non Recloser Time after LC Action(0.00 ~ 600.00 sec) 0.01 10.00
3.PROTECTION 1.OPERATIONS Lockout-PHA Operations to lockout - phase (1-5) 1 4
Lockout-GND Operations to lockout - ground (1-5) 1 4
Lockout-SEF Operations to lockout - SEF (1-5) 1 4
Lockout-NEQ Operations to lockout - NEQ (1-5) 1 4
Fast Curve-PHA Operations - phase fast curve (0-5) 1 2
Fast Curve-GND Operations - ground fast curve (0-5) 1 2
Fast Curve-NEQ Operations - NEQ fast curve (0-5) 1 2
2.INTERVALS Reclose 1 Reclosing time 1 (0.50-600.00 sec) 0.01 0.60
Reclose 2 Reclosing time 2 (1.00-600.00 sec) 0.01 2.00
Reclose 3 Reclosing time 3 (1.00-600.00 sec) 0.01 15.00
Reclose 4 Reclosing time 4 (1.00-600.00 sec) 0.01 15.00
Reset T(AR) Reset time from autoreclose cycle (1.00-600.00 sec) 0.01 30.00
Reset T(LO) Reset time from lockout (1.00-600.00 sec) 0.01 10.00
C/P Wait Limit time to waiting closing power (1.00-600.00 sec) 0.01 60.00
APPENDIX http://www.entecene.co.kr
14 ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (6/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
3.PICKUP CURRENT Phase Pickup current - phase (0.00(OFF),0.04-3.20 xCT phase ratio) 0.01 0.50
Ground Pickup current - ground (0.00(OFF),0.02-3.20 xCT ground ratio) 0.01 0.25
S.E.F Pickup current - SEF (0.000(OFF),0.005-0.160 xCT SEF ratio) 0.001 OFF
NEG Seq Pickup current - NEQ (0.00(OFF),0.04-3.20 xCT phase ratio) 0.01 OFF
4.PHASE FAST Function Phase fast protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-STI
Time Dial Time dial (0.05-15.00) 0.01 0.50
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
5.PHASE DELAY Function Phase delay protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-VI
OPERATIONS CURVE
ANSI-MI ANSI-NI ANSI-VI ANSI-EI ANSI-STI ANSI-STVI
IEC-SI IEC-VI IEC-EI IEC-LTI IEC-STI ESB-SI
ESB-VI ESB-LTVI USER-1 USER-2 USER-3 USER-4
DEF-1S DEF-10S A(101) B(117) C(133) D(116)
E(132) F(163) H(122) J(164) KP(162) L(107)
M(118) N(104) P(115) R(105) T(161) V(137)
W(138) Y(120) Z(134) 1(102) 2(135) 3(140)
4(106) 5(114) 6(136) 7(152) 8(113) 8*(111)
9(131) 11(141) 13(142) 14(119) 15(112) 16(139)
17(103) 18(151) KG(165)
Time Dial Time dial (0.05-15.00) 0.01 3.00
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
6.GROUND FAST Function Ground fast protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-STI
Time Dial Time dial (0.05-15.00) 0.01 0.50
APPENDIX http://www.entecene.co.kr
15ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (7/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
7.GROUND DELAY Function Ground delay protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-VI
Time Dial Time dial (0.05-15.00) 0.01 3.00
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
8.SEF ELEMENT Function SEF protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Time Delay Time delay (0.00-10.00 sec) 0.01 1.00
9.NEG SEQ FAST Function Negative sequence fast protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-STI
Time Dial Time dial (0.05-15.00) 0.01 0.50
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
10.NEG SEQ DELAY Function Negative sequence delay protection function (TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Curve Operations curve (ANSI-MI,..,KG(165):total 57) ANSI-VI
Time Dial Time dial (0.05-15.00) 0.01 3.00
Time Adder Constant time adder (0.00-10.00 sec) 0.01 0.00
M.R.T Minimum response time (0.00-10.00 sec) 0.01 0.00
Reset Method Select reset method (INST,LINEAR) INST
11.H/C TRIP-PHA Function High current trip - phase function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - phase (0.10-20.00 xCT phase ratio) 0.01 4.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
12.H/C TRIP-GND Function High current trip - ground function (OFF,TRIP,TRIP&ALARM) OFF
APPENDIX http://www.entecene.co.kr
16 ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (8/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - ground (0.10-20.00 xCT phase ratio) 0.01 4.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
13.H/C TRIP-NEQ Function High current trip - NEQ function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current – NEQ (0.10-20.00 xCT phase ratio) 0.01 4.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active trip Active trip (OFF,1-5) OFF
14.H/C LOCKOUT-PHA Function High current lockout - phase function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - phase (0.10-20.00 xCT phase ratio) 0.01 8.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
15.H/C LOCKOUT-GND Function High current lockout - ground function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - ground (0.10-20.00 xCT phase ratio) 0.01 8.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
16.H/C LOCKOUT-NEQ Function High current lockout - NEQ function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xCT) Pickup current - NEQ (0.10-20.00 xCT phase ratio) 0.01 8.00
Time Delay Time delay (0.00-10.00 sec) 0.01 0.00
Active Trip Active trip (OFF,1-5) OFF
17.COLD LOAD PICKUP Function Cold load pickup function (OFF,TRIP,TRIP&ALARM) TRIP
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
PHA(xCT) Pickup current - phase (0.10-20.00 xCT phase ratio) 0.01 2.00
GND(xCT) Pickup current - ground (0.10-20.00 xCT ground ratio) 0.01 2.00
SEF(xCT) Pickup current - SEF (0.10-20.00 xCT SEF ratio) 0.01 2.00
NEQ(xCT) Pickup current - NEQ (0.10-20.00 xCT phase ratio) 0.01 2.00
Outage Time Outage time (0.00-600.00 sec) 0.01 10.00
RMT Time Restore minimum trip current time limit (0.00-600.00 sec) 0.01 5.00
RMT Func-PHA Restore minimum trip - phase (OFF,ON) ON
RMT Func-GND Restore minimum trip - ground (OFF,ON) ON
APPENDIX http://www.entecene.co.kr
17ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (9/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
RMT Func-SEF Restore minimum trip - SEF (OFF,ON) ON
RMT Func-NEQ Restore minimum trip - NEQ (OFF,ON) ON
Reset Time Cold load pickup function reset time (0.00-600.00 sec) 0.01 0.60
18.DIRECTION 1.PHASE DIRECTION
Type Direction of current flow - phase (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 300
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
2.GROUND DIRECTION
Type Direction of current flow - ground (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 135
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
3.SEF DIRECTION
Type Direction of current flow - SEF (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 135
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
4.NEQ DIRECTION
Type Direction of current flow - NEQ (OFF,FORWARD,REVERSE) OFF
M.T.A Maximum torque angle (0-359 deg) 1 135
M.P.V Minimum polarizing voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.20
BLOCK OC Block overcurrent under minimum polarizing voltage (NO,YES) NO
19.VOLTAGE 1.UNDER VOLTAGE 1
Function Under voltage 1 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.70
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
Min. V(xVT) Minimum voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.10
Pickup Type Under voltage 1 pickup type (1,2,3 phase) 1P
2.UNDER VOLTAGE 2
Function Under voltage 2 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.70
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
Min. V(xVT) Minimum voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.10
Pickup Type Under voltage 2 pickup type (1,2,3 phase) 1P
APPENDIX http://www.entecene.co.kr
18 ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (10/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
3.OVER VOLTAGE 1
Function Over voltage 1 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 1.20
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
Pickup Type Over voltage 1 pickup type (1,2,3 phase) 1P
4.OVER VOLTAGE 2
Function Over voltage 2 function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(xVT) Pickup voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 1.20
Time Delay Time delay (0.00-600.00 sec) 0.01 5.00
Pickup Type Over voltage 2 pickup type (1,2,3 phase) 1P
20.FREQUENCY 1.UNDER FREQUENCY
Function Under frequency function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Pickup(Hz) Pickup frequency (40.00-65.00 Hz) 0.01 55.00
Time Delay Time delay (0.00-600.00 sec) 0.01 2.00
Min. V(xVT) Minimum voltage (0.00-1.25 x VT 2nd norminal volt) 0.01 0.10
Min. I(xCT) Minimum current (0.01-3.20 x CT Phase ratio) 0.01 0.01
21.OTHER ELEMENT Seq' Coordi' Sequence coordination function (OFF,ON) OFF
L.O Priority Lockout priority (GROUND,PHASE) GND
F/I Reset Fault indicator reset method (AUTO,MANUAL) AUTO
D/T M-Close Manual close Time delay (0.00-600.00 sec) 0.01 0.00
22.USER CURVE SET 1.USER CURVE 1
Factor a User define curve 1 factor a (0.0000-150.9999) 0.0001 59.5000
Factor b User define curve 1 factor b (0.0200-150.9999) 0.0001 2.0000
Factor r User define curve 1 factor r (0.0000-150.9999) 0.0001 1.8000
Factor rt User define curve 1 factor rt (0.0000-150.9999) 0.0001 59.5000
2.USER CURVE 2
Factor a User define curve 2 factor a (0.0000-150.9999) 0.0001 39.8500
Factor b User define curve 2 factor b (0.0200-150.9999) 0.0001 2.0000
Factor r User define curve 2 factor r (0.0000-150.9999) 0.0001 0.9500
Factor rt User define curve 2 factor rt (0.0000-150.9999) 0.0001 39.8500
3.USER CURVE 3
Factor a User define curve 3 factor a (0.0000-150.9999) 0.0001 59.1000
Factor b User define curve 3 factor b (0.0200-150.9999) 0.0001 2.0000
APPENDIX http://www.entecene.co.kr
19ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (11/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
Factor r User define curve 3 factor r (0.0000-150.9999) 0.0001 0.3450
Factor rt User define curve 3 factor rt (0.0000-150.9999) 0.0001 59.1000
4.USER CURVE 4
Factor a User define curve 4 factor a (0.0000-150.9999) 0.0001 5.6700
Factor b User define curve 4 factor b (0.0200-150.9999) 0.0001 2.0000
Factor r User define curve 4 factor r (0.0000-150.9999) 0.0001 0.0352
Factor rt User define curve 4 factor rt (0.0000-150.9999) 0.0001 5.6700
4.MONITORING 1.DEMAND Function Monitoring demand function (OFF,TRIP,TRIP&ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Type Demand method (THERMAL,ROLLING) THM
Time
Constant(m) Time interval (5,10,15,20,30,60 minute) 5
PHA PU(xCT) Current demand pickup-phase (0.00(OFF),0.04-3.20xCT phase ratio) 0.01 0.60
GND PU(xCT) Current demand pickup-ground
(0.00(OFF),0.020-3.20xCTground ratio) 0.01 0.30
NEQ PU(xCT) Current demand pickup-NEQ (0.00(OFF),0.04-3.20 xCT phase ratio) 0.01 0.60
2.SYNCHROCHECK Function Synchrocheck function (OFF,ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
D.V.Max(xVT) Dead line maximum voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.50
L.V.Min(xVT) Live line minimum voltage (0.00-1.25 xVT 2nd norminal volt) 0.01 0.85
M.V.D(V) Maximum voltage difference (0.00-1.25 xVT 2nd norminal volt) 0.01 0.10
M.A.D(Deg) Maximum angle difference (0-100 deg) 1 15
M.F.D(Hz) Maximum frequency difference (0.00-5.00 Hz) 0.01 2.00
Sync Phase Synchrocheck phase (R(AB), S(CB) ,T phase) R(AB)
3.TRIP COUNTER Function Monitoring trip counter function (OFF,ALARM) OFF
Relays(0-8) Select the output relays (Any combination of the 0-8 AUX relays) 1 OFF
Limit Counter for ALARM (1-20000) 1 10000
Counter set Trip counter set when clearing mode (0-10000) 1 0
4.RECLOSER WEAR Function Recloser wear monitor function (OFF,ALARM) ALARM
Pickup(%) Pickup wear level (0.0-50.0 %) 0.1 20.0
Rated Volt(kV) Recloser rated voltage (15,27,38 kV) *NOTE (1
Interrupt Interrupt rating (5.0-50.0 kA) 0.1 12.5
No. Max I Number of operation under Maximum interrupt rating (1-999) 1 100
APPENDIX http://www.entecene.co.kr
20 ENHANCED TECHNOLOGY
Table E-1. MENU MESSAGE & HELP MESSAGE DESCRIPTION (12/12)
MANU NAME DESCRIPTION STEP FACTORY
DEFAULT
A Wear Set Recloser Wear set - A phase when clearing mode (0.00-100.00 %) 0.01 100.00
B Wear Set Recloser Wear set - B phase when clearing mode (0.00-100.00 %) 0.01 100.00
C Wear Set Recloser Wear set - C phase when clearing mode (0.00-100.00 %) 0.01 100.00
5.BATTERY TEST BT Time(day) Self battery test interval (0FF,1-7 day) 1 OFF
6.FAULT LOCATOR Function Fault Locator (OFF,ON) OFF
Length(km) Length of Feeder (0.1-99.9 km) 0.1 50.0
Z1(RES) Real impedance of the feeder positive sequence (0.1-6000.0 ohms) 0.1 10.0
Z1(IND) Imaginary impedance of the feeder positive sequence
(0.1-6000.0 ohms) 0.1 10.0
Z0(RES) Real impedance of the feeder zero sequence (0.1-6000.0 ohms) 0.1 10.0
Z0(IND) Imaginary impedance of the feeder zero sequence (0.1-6000.0 ohms) 0.1 10.0
NOTE
1) The rated voltage determines the Recloser type.
APPENDIX http://www.entecene.co.kr
21ENHANCED TECHNOLOGY
Appendix F. Ordering Guide
Choose from the following options. E V R C 2 A - M 2 - -
Example Model E V R C 2 A - M 2 - 2 2 0 C 2 7 5 - D 1 2 X X L X P
220Vac** 2 2 0 110Vac 1 1 0 Control Power
Other Voltage X X X CVD (Capacitor Voltage Divider)** C
Voltage Sensing Device VT (Voltage Transformer) V 15kV 1 5 27kV 2 7 Line Voltage Class
38kV 3 8 50Hz 5
Line Frequency 60Hz 6 Without** X Modbus M DNP D DNP & Modbus C DNP & Modbus & IEC60870-5-101 1 DNP & Modbus & IEC60870-5-103 3
Communication Protocol Unit
DNP & Modbus & IEC60870-5-104 4 12Vdc** 1 2 13Vdc 1 3 15Vdc 1 5
User Available DC Power Output
24Vdc 2 4 Without** X
125Vdc** S 12Vdc A 24Vdc B 48Vdc C
SCADA Input/Output Input Voltage
250Vdc D Without** X
Loop Automation Scheme Available L LCD (Liquid Crystal Display)** L
User Interface Panel Display VFD (Vacuum Fluorescent Display) VWithout** X
Cubicle Heater Available HWithout** X
Mount Accessory Plate Available P
NOTES 1. The directional controls element is available as an ordering VT (Voltage Transformer) 2. Operaing Temperature : LCD (-20℃~+70℃), VFD (-40℃~+85℃) 3. ** : EVRC2A Standard Type