05 SEP-602B RED670 1p1 Current Functions

download 05 SEP-602B RED670 1p1 Current Functions

of 31

Transcript of 05 SEP-602B RED670 1p1 Current Functions

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    1/31

    1

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    RED670 Line DifferentialProtection IED

    Current functions

    Substation Automation andProtection Training

    2

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Instantaneous phase overcurrent, IOC max

    2 instances

    Four step phase overcurrent, TOC, 1

    instance

    Instantaneous residual current, IEF, 1instance

    Four step residual overcurrent, TEF, max 1

    instance

    RED 670; Current functions

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    2/31

    3

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    RED 670; Current functions

    Breaker failure protection, BFP, max 2 instances

    Stub protection, STB, max 2 instances

    Thermal overload protection, THL, max 2 instances

    Pole Discordance, PD, max 2 instances

    4

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    IOC, TOC, THL, BFP and PD are standard in the pre-

    configured variants:

    A31 3ph 1 CB

    A32 1ph 1 CB B31 3ph 2 CB

    B32 1PH 2 CB

    RED 670; Current functions

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    3/31

    5

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Instantaneous Phase Overcurrent function (PIOC, 51)

    Set as instantaneous protectionwhere the fault current is limited todefined maximum values e.g. froma long power line or a transformerreactance.

    Low transient overreach to allowsetting close to the maximumthrough fault current level

    High speed to give fast faultclearance at heavy fault currents

    Can give phase information and beused with Distance protection as

    fast optional function also givingsingle phase tripping

    Current can be summated from two(or more) current input sets.

    IF

    3I>>

    6

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    OpMode = 1out of 3 or 2 out of 3

    IP>> = The setting threshold for the current function

    StVaMult = A multiplication factor for increase of IP>> by

    activating input ENMULT

    Instantaneous Phase Overcurrent function (PIOC, 51)

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    4/31

    7

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    PIOC,51; Calculation of settings

    Select IP>> = max(IfB,IfA)

    Consider also eventual transient overreach due to

    possible dc component of the fault current

    8

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Consider also the effect of parallel line when applicable

    PIOC,51; Calculation of settings

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    5/31

    9

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    PIOC, 51; Function block

    10

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Phase Overcurrent function (TOC, 51_67)

    Four stage Phase overcurrent.

    Each stage can be setDirectional or Non directional

    Each stage can be Definite- orInverse time delayed.

    19 IEC/ANSI curves

    Logaritmic invers

    Taylor made curve is available

    Each stage can be blocked fromsecond harmonic inrush currents.

    With directional memory

    Current can be summated from two(or more) current input sets.

    IF

    3I>

    4

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    6/31

    11

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    en05000740_ansi.vsd

    Direction

    Element

    4 step over currentelement

    One element for eachstep

    HarmonicRestraint

    Mode Selection

    dirPhAFlt

    dirPhBFlt

    dirPhCFlt

    harmRestrBlock

    enableDir

    enableStep1-4

    DirectionalMode1-4

    faultState

    Element

    faultState

    I3P

    V3P

    I3P

    PICKUP

    TRIP

    Phase Overcurrent function (PTOC, 51_67)

    12

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Phase Overcurrent function (PTOC, 51_67)

    The filtering principal can be

    selected to Discrete Fourier

    Filtering (DFT) or true RMS

    (RMS) by the setting

    parameter MeasType

    DFT filer out the fundamental

    component which is most

    common in normal line

    protection applications

    RMS gives a current which

    includes harmonics, which is

    usefull in shunt capacitor

    applications

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    7/31

    13

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Phase Overcurrent function (PTOC, 51_67), - Application

    Back-up selectivity with directionand different time grading in bothdirections

    IF

    3I>

    4

    G

    G67/51

    14

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    PTOC, 51_67; Direction

    Uref

    Idir

    RCAROA

    Forward

    ROA

    en05000745.vsd

    Reverse

    The direction is determined by

    checking the angle of U and I

    Voltage is the angle reference

    Lagging current is plus angle

    With directional memory

    Direction can be set

    Off/Non-directional

    Forward/Reverse

    RCA ~ 10-40

    ROA ~ 100-150

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    8/31

    15

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOC, 51_67; Reset possibilities

    3ANSI Reset

    (Inverse time)

    2IEC Reset

    (constant time)

    1Instantaneous

    Curve Index no.Curve name

    16

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    4-step Phase overcurrent protection (TOC)

    110-150

    10-40

    jX

    R

    Forward operation

    Reverse operation

    Forward operation

    Reverse operation

    The direction is determined by

    checking the angle of U and I

    Voltage is the angle reference

    Lagging current is plus angle

    With directional memory

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    9/31

    17

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOC, 51_67; Polarizing voltages

    Polarizing voltages at phase to phase fault

    L2-L1 UU=2L1LUref

    L3-L2 UU=3L2LUrefL1-L3 UU=1L3LUref

    L2-L1 II=2L1LIdir

    L3-L2 II=3L2LIdirL1-L3 II=1L3LIdir

    Polarizing voltages at phase to earth fault

    L1U=1LUref

    L2U=2LUref

    L3U=3LUref

    L1I=1LIdir

    L2I=2LIdir

    L3I=3LIdir

    18

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    OC4PTOC_51_67

    TOC1-

    I3P

    U3P

    BLOCK

    BLKTR

    BLKST1

    BLKST2

    BLKST3

    BLKST4

    ENMULT1

    ENMULT2

    ENMULT3

    ENMULT4

    TRIP

    TR1

    TR2

    TR3

    TR4

    TRL1

    TRL2

    TRL3

    TR1L1

    TR1L2

    TR1L3

    TR2L1

    TR2L2

    TR2L3

    TR3L1TR3L2

    TR3L3

    TR4L1

    TR4L2

    TR4L3

    START

    ST1

    ST2

    ST3

    ST4

    STL1

    STL2

    STL3

    ST1L1

    ST1L2

    ST1L3

    ST2L1

    ST2L2

    ST2L3

    ST3L1

    ST3L2

    ST3L3

    ST4L1

    ST4L2

    ST4L3

    2NDHARM

    DIRL1

    DIRL2

    DIRL3

    VisioDocument

    When activated, the current multiplier InMult

    (n=1 for step1 etc) is in use for step1, Step2,

    step3 and step4 for increasing the operate

    level

    TOC, 51_67; Function block inputs

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    10/31

    19

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    OC4PTOC_51_67

    TOC1-

    I3P

    U3P

    BLOCK

    BLKTR

    BLKST1

    BLKST2

    BLKST3

    BLKST4

    ENMULT1

    ENMULT2ENMULT3

    ENMULT4

    TRIP

    TR1

    TR2

    TR3

    TR4

    TRL1

    TRL2

    TRL3

    TR1L1

    TR1L2TR1L3

    TR2L1

    TR2L2

    TR2L3

    TR3L1

    TR3L2

    TR3L3

    TR4L1

    TR4L2

    TR4L3

    START

    ST1

    ST2

    ST3

    ST4

    STL1

    STL2

    STL3

    ST1L1

    ST1L2

    ST1L3

    ST2L1

    ST2L2

    ST2L3

    ST3L1

    ST3L2

    ST3L3

    ST4L1

    ST4L2

    ST4L3

    2NDHARM

    DIRL1

    DIRL2

    DIRL3

    TRIP step1, step2, step3 and step4

    TRIP phase L1, L2, and L3

    TRIP step1 phase L1, L2, L3TRIP step2 phase L1, L2, L3

    General TRIP

    TRIP step3 phase L1, L2, L3

    TRIP step4 phase L1, L2,L3

    General start

    START step1, step2, step3 and step4

    START L1, L2 and L3

    START step1 phase L1, L2 and L3

    START step2 phase L1, L2 and L3

    START step3 phase L1, L2 and L3

    START step4 phase L1,L2 and L3

    Second harmonic blockDirection phase L1, L2 and L3

    TOC, 51_67; Function block outputs

    20

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOC, 51_67; Setting calculation

    Select the max(IfB)

    Consider also eventual transientoverreach due to possible dccomponent of the fault current

    The set value for the high setunderreaching step can bederived as:

    The value 1.31 includes asecurity margin of 10% fortransient overreach and 20 %general security margin

    For directional underreaching step1

    IfB31.11I =>

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    11/31

    21

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOC, 51_67; Setting parameters

    22

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOC, 51_67; Setting parameters

    IminOpPhSel = Minimum current in % of Ibase for directionality

    Should be set lower than setting of the lowest step

    General setting parameters

    Basic settings

    Advanced

    settings

    StartPhSel = Number of phases needed for operation (1, 2 or 3 of 3)

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    12/31

    23

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Basic setting parameters for step1

    TOC, 51_67; Setting parameters

    K1 = Time multiplier for inverse time characteristic

    t1Min = Minimum operate time for inverse time characteristicI1Mult = Current multiplication factor for step1, activates

    if input ENMULT1 is high

    24

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOC, 51_67; Setting parameters

    Advanced setting parameters for step1

    ResetTypeCrv1 = Reset curve type for step1

    tReset1 = Reset time delay for IEC inverse curve for step1

    tPCrv1, tACrv1, tBCrv1, tCCrv1, tPRCrv1, tTRCrv1, tCRCrv1 = Parameter P, A, B,C , PR, TR and CR for customer programmable inverse time curve for step1

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    13/31

    25

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    IBase: Base current in primary A.

    Normally set to the primary current of the

    CT. Range 1-99999

    UBase: Base voltage in primary kV

    Normally set to the primary voltage of the

    VT (PT). Range 0.05-2000

    AngleRCA: Protection characteristic

    angle set in degrees.

    Default set to 55. Range 40-65

    AngleROA: Angle to define the angle

    sector of the directional function

    Default set to 80. Range 40-89

    PTOC, 51_67; Setting parameters

    26

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    IminOpPhSel: Minimum current for phase selection set in % ofIbase

    should be less than the lowest step setting. Default setting is 7%.

    StartPhSel: Number of phases, with high current, required for

    operation: 1 of 3, 2 of 3 or 3 of 3. Default setting is 1 of 3.

    DirMode1: Directional mode

    Default set to Non-Directional

    2ndHarmStab: Operate level of 2nd harmonic current restrain setin % of the fundamental current, range is 5-100% I steps of 1%.

    Default setting is 20%.

    HarmRestrain: Off/On, enables blocking from harmonic restrain.

    PTOC, 51_67; Setting parameters

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    14/31

    27

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    PTOC, 51_67; Setting parameters

    28

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Instantaneous Earth Overcurrent function (IEF)

    Set as instantaneous protection wherethe fault current is limited to definedmaximum values e.g. from a longpower line or a transformer reactance.

    Low transient overreach to allowsetting close to the maximum through

    fault current level High speed to give fast fault clearance

    at heavy fault currents

    Can give phase information and beused with Distance protection as fastoptional function also giving singlephase tripping

    Current can be summated from two (ormore) current input sets.

    Residual connection or separate inputscan be used.

    IF

    IN>>

    Irsd

    or

    3I0

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    15/31

    29

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    4-step Earth fault protection (TEF, 51N_67N)

    Earth fault protection of feeders in effectively earthed

    distribution and sub transmission systems Back-up earth fault protection of transmission lines

    Sensitive earth fault protection of transmission lines

    Back-up earth fault protection of power transformers

    Earth fault protection of different kinds of equipmentconnected to the power system

    such as shunt capacitor banks, shunt reactors andothers

    Application

    30

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Four stage Earth overcurrent.

    Each stage can be set Off, Non-directional, Forward or Reverse

    Each stage can be Definite- orInverse time delayed.

    Taylor made curve is available

    Each stage can be blocked fromsecond harmonic inrush currents.

    Directional polarizing from calculatedUL1+UL2+UL3 or by external Opendelta to a separate Analogue input.

    IF

    IN>

    4

    UL1+UL2+UL3

    4-step Earth fault protection (TEF)

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    16/31

    31

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    4-step Earth fault protection (TEF, 51N_67N)

    Directional element with communication and WEI

    Reverse

    operation

    Forward

    operation

    -Upol3Io

    Operation based on I*cos

    Polarising -3U0 > 1.0 %

    CVT filter against 3rd harm

    Characteristic angleAngleRCA = -180--180(default -65

    o)

    Current can be summatedfrom two current sets andthe measurement can befrom separate IN input orinternally calculated:3I0 = IL1+IL2+IL3

    3Io3Io(rev) = 0,6 x 3Io (forward)

    AngleRCA

    32

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TEF, 51N_67N; Polarizing alternatives

    Voltages polarization (-3U0)

    Current polarization (IN*ZN)

    Dual polarization

    Both voltage and current is

    allowed to polarize

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    17/31

    33

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Earth Overcurrent function (TEF) - Application

    Back-up selectivity with twodirections and different time gradingin both directions

    IF

    IN>

    4

    G

    G 67N/51N

    34

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    PEFM, 51N_67N; Functional overview

    en05000741.vsd

    DirectionElement

    4 step over currentelement

    One element for each

    step

    HarmonicRestraint

    ModeSelection

    earthFaultDirection

    harmRestrBlock

    enableDir

    enableStep1-4

    DirectionalMode1-4

    TRIP

    Element

    enableDir

    angleValid

    Directional Check

    operatingCurrent

    SwitchOnToFault

    start step 2, 3 and4

    signal tocommunication

    scheme

    TRIP

    3U0

    3I0

    Blocking at paralleltransformers

    1

    CBpos

    or cmd

    Element

    3I0

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    18/31

    35

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    The function are connected to pre-processing block by the following

    signals

    I3P, input for the function Operating Quantity

    U3P, input for the function Voltage Polarizing Quantity

    IP3P, input for the function Current Polarizing Quantity

    The function uses Residual Current (i.e. 3Io) for its operating

    quantity

    directly measured

    Internally calculated from three phase current input within IED 670

    (when the fourth analog input into the pre-processing block connected

    to TEF function Analog Input I3Pis not connected to a dedicated CT

    input of IED 670 in SMT tool).

    TEF, 51N_67N; Analogue inputs

    36

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    4-step earth fault protection (TEF)

    Step 1-3:

    Directional or Non- directional

    Definitive time

    Second harmonic restrained

    Step 4:

    Directional or Non- directional

    Normal inverse

    Very Inverse

    Extremely inverse -

    Logarithmic inverse

    Definitive time

    Second harmonic restrained

    t

    1sec

    20 ms

    min

    Set to match the distance protection reach

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    19/31

    37

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Directional

    Non-directional

    Independent or dependenttime delay

    Second harmonic restrained

    Settable minimum operate

    current and time delay

    Logarithmic inverse

    t

    tmin

    Imin

    Independent

    Normal inverse

    Very inverse

    Extremely inverse

    4-step earth fault protection (TEF)

    38

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    19 different IEC/ANSI Current

    dependent characteristic curves

    (New)

    Communication logic

    Blocking

    Permissive overreach (POR)

    Fault current reversal

    Weak-end infeed echo and trip

    100 1 .103

    1 .104

    1 .105

    0.1

    1

    1010

    0.1

    t1 i

    t2 i

    t3 i

    t4 i

    t5 i

    t6 i

    100000100 Sti

    4-step earth fault protection (TEF)

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    20/31

    39

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Inverse characteristic for time-current back-up

    Required for Back-up functions TOC, TEF

    Diagram or characteristic showing the operating times and correspondingactuating quantities or fault positions for the selective protection relays in the

    network

    Purpose

    Coordinate the relay settings so that

    Faulty equipment is tripped asfast as possible

    The least possible damage isobtained for the healthyequipment

    A Back-up protection is obtainedif the primary protectionfails to trip

    Directional

    40

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Earth fault protection (TEF) Application problem

    Energizing a transformer willalways mean inrush currents.

    Inrush has a high neutral contentin directly earthed systems

    A parallel transformer in service

    will also see the inrush. Theinrush will increase successively

    2nd harmonic will be in phaseopposition and the total contentwill after a while be reduced tosmall values.

    BlkParTrans set to ON and INover a set level (1-4) can be usedto maintain the blocking even ifthe harmonic contents is reduced

    and gives an advantage at paralleltransformers.

    Close

    IN> IN>

    IN>

    IN>

    51N 51N

    51N

    51N

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    21/31

    41

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    42

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    STUB protection (STB)

    Instantaneous overcurrentprotection of busbarconnection (STUB) when aline disconnector is open

    Required in Multi-breakerarrangements with CVT(VT) on line side of DS

    Z< (21) function cannotmeasure when linedisconnector is open andmust be blocked.

    open

    I STUB >&

    t

    Trip

    Line discon.

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    22/31

    43

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Pole discordance protection (PD)

    Pole discordance can occur atbreaker closing or opening whensingle pole operating devices areused.- Higher than 300 kV

    - Single phase trip breakers Contact based supervision of the

    poles

    I2 criteria to verify can be added asadditional criteria to increase security

    Can be blocked during 1-ph AR toallow shorter trip times.

    Note! Only remote b-u trip if localattempt does not remove asymmetry.

    Bus trip will mean a big disadvantagefor service.Trip rem end

    & t

    +

    1Ph AR in progr

    Trip

    t

    44

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Breaker failure protection (BFP)

    BFP is the Local back-up for breakerfailures. The failures can be due totrip coil, breaker drive or breakingcomponents failure.

    At an breaker failure the surroundingbreakers are used to clear the fault.

    Due to the big impact a breaker failuretrip will have on the power systemservice, the BFR function has veryhigh requirements on security againstunnecessary tripping.

    The BFR function is started at CBtripping and if current still flows within,about 150 ms the surroundingbreakers are tripped.

    G

    G

    G

    G

    Back-up breakers

    Failing

    breaker

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    23/31

    45

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Some setting parameters

    BFP

    I>

    t1

    t2

    Current level Iset 0,1 2 * IbaseRetrip of actual breaker -No retrip

    -With current check-Without current check

    Current check mode 1 out of 3 or 2 out of 4

    Retrip delay, one per phase t1 0.000 60.000 s

    Back up trip delay, one timerper phase t2 0.000 60.000 sBack-up trip 2 t3 0.000 60.000 s

    Trip pulse tp 150 ms (settable)

    Breaker failure protection (BFP)

    46

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    ASD output

    RMS output

    Pre-filter

    Post-filter0.5 *

    Stab zone

    Adaptive currentdetection ASD

    No false operation in

    case of saturated CT Maximum reset time

    approx 1/2 cycle toallow short back-uptripping times.

    Breaker failure protection (BFP)

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    24/31

    47

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    - 30 ms - 60 ms

    Fault occurs

    Normal clearing time

    Current detector

    dropout

    MarginBreaker

    interrupting time

    Protection

    time

    Start

    BFP

    BFP timer t2 BFP

    Trip

    Breaker time

    Back-up breaker

    Breaker failure total clearing time

    Breaker failure protection (BFP)

    48

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    3I>BF

    3I>BF

    Z

    Start L1

    Start L2Start L3

    Start L1

    Start L2Start L3

    Start from all protection relays

    tripping the Breaker. Also Bus and

    Breaker failure protection.

    Not manual opening of breaker!

    CB1

    CB3

    Trip Busbar

    Trip CB3

    Intertrip 1

    Trip CB1

    Trip CB2

    Intertrip1

    Intertrip2

    CB2

    Note! Multiple functions

    Breaker failure protection (BFP)

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    25/31

    49

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Energizing Check (SYN)

    The dead line and Live bus

    conditions are checked.

    Uhigh and Ulow are verified

    SC/VC

    27

    AB

    ILoad

    UA UB

    Ulow

    Uhigh

    Inductive and Capacitive

    charging of dead line

    50

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Synchronism Check (SYN)

    Paralleling (synchronismconditions are checked

    ,f, U and Uhigh are within

    set values

    SC/VC

    25

    AB

    ILoad

    UA UB

    UAL

    d

    dU

    Icap

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    26/31

    51

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Synchrocheck function (SYN)

    BLOCK

    U-LineU-Bus

    SYNC

    Linereferencevoltage

    Fuse fail

    U-Bus

    Energizing check

    High voltage U> 50-120% of Ub

    Low voltage U< 10- 80% of Ub

    Operate time 80 ms (typical)

    Paralleling (Synchronism) CheckFrequency difference f < 3-1000mHz

    Voltage difference U < 2 - 50 % of

    UbPhase difference < 5 - 90o

    Operate time 80 ms (typical)

    Accuracy of frequency measurement

    about 0,5 mHz!

    U

    52

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Synchrocheck (SYN) Function block

    Fuse fail on sel fuse

    Information that the voltage

    is included in the

    synchrocheck

    Information that the

    conditions for voltage, diff

    voltage phase angle diff etc

    are fulfilled

    Conditions for AR

    Conditions for Man close

    Test conditions fulfilledDS Bus 1 at DB arrangement

    DS Bus 2 at DB arrangement

    DS Line at 1 1/2 arrangement

    DS alt Line at 1 1/2 arrangement

    Bus1 VT Fuse fail alt. OK

    Bus2 VT Fuse fail alt. OK

    Line 1 VT Fuse fail alt. OK

    Line 2 VT Fuse fail alt. OK

    Block inputs

    Test mode inputs

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    27/31

    53

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Synchrocheck (SYN) Voltage selection

    SYN1

    SYN1 SYN2

    1 U

    1 U1 U

    IED

    3 U

    1 U

    3 U

    B2QB1Q

    UB1 UB2

    ULN1

    ULN1

    UB1 UB2

    LN1Q

    DB Volt sel

    No Volt sel

    54

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    SYN1

    IED 1

    SYN1

    IED 2

    SYN1

    IED 3

    1 U

    1 U3 U

    3 U

    SYN1

    IED

    SYN2

    3 U

    1 U

    1 U

    1 U

    1 U

    1 U

    1 U

    1 U

    B2Q

    UB1UB2

    ULN1

    LN1Q

    LN2Q

    ULN2 UB2

    B1Q

    No Volt sel1 CB Volt sel

    Synchrocheck (SYN) Voltage selection

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    28/31

    55

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    SYN1

    REC670

    SYN2

    SYN3

    3 U

    3 U

    1 U

    1 U

    No Volt sel

    Synchrocheck (SYN) Voltage selection

    56

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Auto Reclosing (AR)

    Single-/ Two-/ Three-phase reclosing programs

    3 phase

    --------

    3 phase

    --------

    1 phase

    2 phase3 phase

    1/2/3 phase6

    3 phase

    3 phase

    ----

    3 phase

    3 phase

    ----

    1 phase

    2 phase

    3 phase

    1/2/3 phase5

    3 phase

    ----

    3 phase

    ----

    1 phase

    2 phase

    1/2 phase

    (No 3 phase)

    4

    3 phase

    3 phase

    3 phase

    3 phase

    1 phase

    2 phase

    1/2 phase

    (No 3 phase)

    3

    3 phase

    3 phase

    3 phase

    3 phase

    3 phase

    3 phase

    1 phase

    2 phase

    3 phase

    1/2/3 phase2

    3 phase3 phase3 phase3 phase1

    3rd and 4st attempt2nd attempt1st attemptProgram

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    29/31

    57

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Start Quick AR without

    synchrocheck

    Auto-Reclosing (AR) new in REx670

    Put AR on hold e.g. waiting

    for Thermal relays to resetto have less sag before

    reclosing

    Skip a step and continue

    with next (at multiple shots)

    58

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Content

    Time Overvoltage protection function

    Time Undervoltage protection function

    Multipurpose general protection function

    Fuse failure supervision

    Instantaneous phase overcurrent Time delayed phase overcurrent

    Instantaneous earth overcurrent

    Time delayed earth overcurrent

    Stub protection

    Pole Discordance protection

    Breaker failure protection

    Synchrocheck function Auto Reclose function

    Frequency protection

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    30/31

    59

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOF/TUF/RVF(df/dt) Frequency Protection-Functionality

    Detection of over- or underfrequency

    Six stages of each function

    Measures Ph-Ph or Positive sequence voltage Undervoltage (Dead) blocking level

    Trip signal each step fully individually:

    Settable frequency and settable time delay

    High accuracy, short measuring time

    Df/dt with positive or negative setting

    Accuracy 2 mHz for three phase

    Accuracy 50 mHz for single phase

    Voltage dependent tripping time!

    60

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    TOF/TUF Frequency Protection - Application

    Load shedding system

    System restoration system

    Generation shedding

    Remedial Action schemes

  • 8/12/2019 05 SEP-602B RED670 1p1 Current Functions

    31/31

    61

    ABB

    AB,

    2007

    2008-01-30 Substation Automation and Protection Training

    Trip Circuit Supervision Application with 670 series

    Trip Circuit supervision can be arranged

    using Binary inputs or mA inputs.

    mA inputs shall be used if supervision is

    required from both sides i.e. at Lock-outtripping

    + -

    Trip Circuit fail3s