04 Transformer

download 04 Transformer

of 98

Transcript of 04 Transformer

  • 7/29/2019 04 Transformer

    1/98

    TRANSFORMER PROTECTION

    Slide 1Issue A

  • 7/29/2019 04 Transformer

    2/98

    Slide 2Issue A

    Causes of failure:

    Environment

    System

    Mal operation

    Wrong design

    Manufacture

    Material

    Maintenance

  • 7/29/2019 04 Transformer

    3/98

    Slide 3Issue A

    Transformer failures classification :

    1. Internal failureCauses:

    Winding & terminal faults

    Core faults

    Onload tap changer faults

    Overheating faults

  • 7/29/2019 04 Transformer

    4/98

    2. External failure

    Causes:

    Issue A Slide 4

    Abnormal operating condition

    sustained or unclear faults

    Transformer failures classification :

  • 7/29/2019 04 Transformer

    5/98

    Issue A Slide 5

    Vector Groups

    Phase displacement0

    Group 1

    Phase displacement180

    Group 2

    Lag phase displacement30

    Group 3

    Lead phase displacement30

    Group 4

    Yy0Dd0Zd0

    Yy6Dd6Dz6

    Yd1

    Dy1Yz1

    Yd11Dy11

    Yz11

  • 7/29/2019 04 Transformer

    6/98

    Slide 6Issue A

    Vector Configurations

    12

    11

    300

    1, DRAW PHASE-NEUTRAL VOLTAGE VECTORS

    300

  • 7/29/2019 04 Transformer

    7/98

    Slide 7Issue A

    2. Draw Delta Connection

    A

    C B

    a

    c

    b

    Vector Configurations

  • 7/29/2019 04 Transformer

    8/98

    Issue A Slide 8

    3. Draw A Phase Windings

    A

    C B

    a

    c

    b

    a2

    a1

    A2

    A1

    Vector Configurations

  • 7/29/2019 04 Transformer

    9/98

    Slide 9Issue A

    4. Complete Connections (a)

    A

    C B

    a

    c

    b

    a2

    a1

    A2

    A1

    C1

    C2

    B1

    B2

    b2b1c1

    c2

    Vector Configurations

  • 7/29/2019 04 Transformer

    10/98

    Slide 10Issue A

    Fault current distribution

    Earth fault on Transformer winding

    V2

    R

    T2 T1

    V 1

    X

    Fig.3 If

    Fig.N

  • 7/29/2019 04 Transformer

    11/98

  • 7/29/2019 04 Transformer

    12/98

    Slide 12Issue A

    Fault current distribution

    If Transformer star winding is solid earthed,

    fault current limited only by the leakage

    reactanceof the winding

    If asmultiple of

    IF.L.

    .1 .2 .3 .4 .5 .6 .7 .8 . 9 1.0 x p.u

    Delta side

    Star side

    Fig.Q

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

  • 7/29/2019 04 Transformer

    13/98

    Slide 13Issue A

    Differential

    Basic Protection

    Restricted Earthfault

    Overfluxing

    Overcurrent & Earthfault

  • 7/29/2019 04 Transformer

    14/98

    Slide 14Issue A

    Differential Protection

    Where protection co-ordination is difficult / notpossible using time delayed elements

    For fast fault clearance

    Applied

    Works on Merz-price current comparison principle

    Relays with bias characteristic should only be used

    For zone of protection

  • 7/29/2019 04 Transformer

    15/98

    Slide 15Issue A

    Differential Protection

    Consideration for applying differential

    protection

    Phase correction

    Filtering of zero sequence currents

    Ratio correction

    Magnetizing inrush during energisation

    Overfluxing

  • 7/29/2019 04 Transformer

    16/98

    Slide 16Issue A

    Differential Protection - Principle

    R I diff = 0

    Nominal current through the protected equipment

    I Diff = 0 : No tripping

  • 7/29/2019 04 Transformer

    17/98

    Slide 17Issue A

    Differential Protection - Principle

    Through fault current

    I Diff = 0 : No tripping

    R I diff = 0

  • 7/29/2019 04 Transformer

    18/98

    Slide 18Issue A

    Differential Protection - Principle

    Tripping

    Internal Fault

    I Diff = 0 :

    R I diff = 0

  • 7/29/2019 04 Transformer

    19/98

    Slide 19Issue A

    Biased differential protection

    Fast operation

    Adjustable characteristic

    High through fault stability

    CT ratio compensation

    Magnetising inrush restraint

    Overfluxing 5th harmonic restraint

  • 7/29/2019 04 Transformer

    20/98

    Slide 20Issue A

    Biased differential protection

    1 A

    100/50 KV100 / 1 200 / 1

    1 A

    0 A

    LOAD

    = 200 A

    Why bias characteristic ?

    OLTC Setting is at mid tap

    R

    I1I2

  • 7/29/2019 04 Transformer

    21/98

    Slide 21Issue A

    Biased differential protection100/50 KV100 / 1 200 / 1

    0.9 A 1 A

    0.1 A

    Relay pickup setting = O.2 A, So the Relay restrains

    LOAD= 200 A

    OLTC SETTING IS AT 10%

    Differential current = 0.1 A

    R

  • 7/29/2019 04 Transformer

    22/98

    Slide 22Issue A

    Biased differential protection

    100/50 KV100 / 1 200 / 1

    9 A10 A

    1 A

    Relay Pickup Setting is O.2 AOLTC SETTING IS AT 10%

    2000 A

    R

    OperatesSo the Relay

  • 7/29/2019 04 Transformer

    23/98

    Slide 23Issue A

    Role of Bias

    Setting range(0.1 - 0.5)

    Effective bias (x In) = I + I + I + I1 2 3 4

    2

    Differential current (x In)= I + I + I + I1 2 3 4

    0 1 2 3 4

    1

    2

    3

    Operate

    Restrain

    80%

    Slope

    20%Slope

  • 7/29/2019 04 Transformer

    24/98

    R RR

    Dy1(-30 )

    Yd11(+30 )

    Interposing CT provides

    Vector correction

    Ratio correction

    Zero sequencecompensation

    USE OF ICT

  • 7/29/2019 04 Transformer

    25/98

    Dy1(-30 )

    RR

    R

    PROTECTION TRANSFORMATEUR

    sur dfaut interne: Protection diffrentielle

    Yd11

    Vector Group Correction - Static Relays

    Vector and Ratio correction by interposing CT

    CURRENT DIFFERENTIAL PROTECTION

  • 7/29/2019 04 Transformer

    26/98

    RR

    R

    PROTECTION TRANSFORMATEUR

    sur dfaut interne: Protection diffrentielle

    Yd11

    Vector Group Correction - Static Relays

    Vector and Ratio correction by CT Connection

    CURRENT DIFFERENTIAL PROTECTION

  • 7/29/2019 04 Transformer

    27/98

    87

    Yy0 Yd11

    0 +30

    Yy0, Yd1, Yd5 , Yy6, Yd7, Yd11, Ydy0

    0 , -30 , -150 , 180,+150, +30 , 0

    Dy1 (-30 )

    VECTOR GROUP CORRECTION

  • 7/29/2019 04 Transformer

    28/98

    87

    Dy11 (+30 )

    Yy0

    0

    Yd1

    -30

    SELECTION OF SUITABLE

    VECTOR CORRECTION FACTOR

  • 7/29/2019 04 Transformer

    29/98

    0.875A

    87

    200/1

    1.31 Amps

    I = 175A I = 525A 400/1L L

    33kV : 11kV10 MVA

    1.14 0.76

    1A 1A

    CT RATIO MISMATCH CORRECTION

  • 7/29/2019 04 Transformer

    30/98

    +VE SEQUENCECURRENTSBALANCE

    REQUIRE ZEROSEQUENCE

    CURRENT

    TRAPS FORSTABILITY B CA

    ZERO SEQUENCE COMPENSATION

  • 7/29/2019 04 Transformer

    31/98

    Slide 24Issue A

    Based on Current operated relay with an external stabilisingresistor

    Requires matched current transformers of low reactance design,typically class X or equivalent

    Equal CT ratios

    Non-linear resistor may be required to limit voltage across relaycircuit during internal faults

    Suitable for zones up to 200 - 300 metres (typically)

    High Impedance Principle

  • 7/29/2019 04 Transformer

    32/98

    Slide 25Issue A

    High Impedance Principle

    TC satur

    M

    RCT

    ZM

    RCT2RL 2RL

    A

    M

    ZM

    RCT

    2RL

    2RL

    RCT

  • 7/29/2019 04 Transformer

    33/98

    Slide 26Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    M

    M

  • 7/29/2019 04 Transformer

    34/98

    Slide 27Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    TC satur

    A

    M

    M

  • 7/29/2019 04 Transformer

    35/98

    Slide 28Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    M

    M

  • 7/29/2019 04 Transformer

    36/98

    Slide 29Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    TC satur

    A

    M

    M

  • 7/29/2019 04 Transformer

    37/98

    Slide 30Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    M

    M

  • 7/29/2019 04 Transformer

    38/98

    Slide 31Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    TCsatur

    A

    M

    M

  • 7/29/2019 04 Transformer

    39/98

    Slide 32Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    TC satur

    RCT

    2RL

    2RL

    RCT

    A

    M

    MCT Saturation

    False tripping

  • 7/29/2019 04 Transformer

    40/98

    Slide 33Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    TC satur

    RCT

    2RL

    2RL

    RCT

    A

    RS

    M

    M

  • 7/29/2019 04 Transformer

    41/98

    Slide 34Issue A

    High Impedance Principle

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    TC satur

    RCT

    2RL

    2RL

    RCT

    A

    RS

    M

    M

    Stabilising resistor

  • 7/29/2019 04 Transformer

    42/98

    Slide 35Issue A

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    A

    RS

    M

    M

    RCT

    2RL

    2RL

    RCT Vset

    High Impedance Principle

  • 7/29/2019 04 Transformer

    43/98

    Slide 36Issue A

    RCT

    ZM

    RCT

    ZM=0

    2RL 2RL

    RCT

    2RL

    2RL

    RCT

    A

    RS

    M

    M

    ZM = 0

    (CT "shortcircuited" )

    Vset

    High Impedance Principle

  • 7/29/2019 04 Transformer

    44/98

    Slide 37Issue A

    A

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    2RL

    RCT

    2RL

    RCT

    RS

    M

    M

    Vset

    High Impedance Principle

  • 7/29/2019 04 Transformer

    45/98

    Slide 38Issue A

    High Impedance Principle

    2RL

    RCT

    2RL

    RCT

    M

    Vset

    A

    RCT

    ZM

    RCT

    ZM

    2RL 2RL

    RS

    M

  • 7/29/2019 04 Transformer

    46/98

    Slide 39Issue A

    High Impedance Principle

    M

    A

    RC

    T

    ZM

    RC

    T

    ZM

    2R

    L

    2R

    L

    RS

    M

    Vset

    Metrosil may be

    required for voltagelimitation

    2R

    L

    RC

    T 2R

    L

    RC

    T

    M

  • 7/29/2019 04 Transformer

    47/98

    Slide 40Issue A

    Restricted Earthfault Protection

    Increased sensitivity for earth faults

    REF elements for each transformer winding

    CTs may be shared with differential element

    Uses high impedance principle

    6464

    64

    Restricted Earthfault Protection

  • 7/29/2019 04 Transformer

    48/98

    Slide 41Issue A

    est cted a t au t otect o

    P1

    S1

    P2

    S2P1

    S1

    P2

    S2

    P1S1

    P2S2

    P1

    P2

    S1

    S2

    Stability level : usually maximum through fault level of transformerREF Case I : Normal Condition

    Under normal conditions no current flows thro Relay

    So, No Operation

    Restricted Earthfault Protection

  • 7/29/2019 04 Transformer

    49/98

    Slide 42Issue A

    Restricted Earthfault Protection

    REF Case II : External Earth Fault

    External earth fault - Current circulates between the phase & neutral CTs;

    no current thro the relay

    So, No Operation

    Restricted Earthfault Protection

  • 7/29/2019 04 Transformer

    50/98

    Issue ASlide 43

    Issue A

    Restricted Earthfault Protection

    REF Case III : Internal Earth Fault

    For an internal earth fault the unbalanced current flows thro the relay

    So, Relay Operates

    Restricted Earthfault Protection

  • 7/29/2019 04 Transformer

    51/98

    Slide 44Issue A

    Restricted Earthfault Protection

    Restricted Earth Fault ProtectionSetting

    1MVA(5%)

    11000V 415V

    1600/1

    RCT = 4.9

    80MVA

    RS1600/1

    RCT = 4.8MCAG14

    IS = 0.1 Amp

    2 Core 7/0.67mm (7.41/km)100m Long

    Setting will requirecalculation of :

    1) Setting stabilityvoltage (V

    S

    )

    2) Value of stabilisingresistor required

    3) Peak voltage

    developed by CTsfor internal fault

    Restricted Earthfault Protection

  • 7/29/2019 04 Transformer

    52/98

    Slide 45Issue A

    Restricted Earthfault Protection

    Example : Earth fault calculation :-

    Using 80MVA base

    Source impedance = 1 p.u.

    Transformer impedance = 0.05 x 80 = 4 p.u.1

    Total impedance = 14 p.u.

    I1 = 1 = 0.0714 p.u.14

    Base current = 80 x 106

    3 x 415

    = 111296 Amps IF = 3 x 0.0714 x 111296

    = 23840 Amps (primary)= 14.9 Amps (secondary)

    1 P.U.1 4

    I1

    4

    I2

    4

    I0

    1

    1

    Restricted Earthfault Protection

  • 7/29/2019 04 Transformer

    53/98

    Slide 46Issue A

    Restricted Earthfault Protection

    (1) Setting voltage

    VS = IF (RCT + 2RL)

    Assuming earth CT saturates,

    RCT = 4.8 ohms2RL = 2 x 100 x 7.41 x 10

    -3 = 1.482 ohms

    Setting voltage = 14.9 (4.8 + 1.482)

    = 93.6 Volts

    (2) Stabilising Resistor (RS)

    RS = VS - 1IS IS

    2 Where IS = relay current setting

    RS = 93.6 - 1 = 836 ohms

    0.1 0.22

    Restricted Earthfault Protection

  • 7/29/2019 04 Transformer

    54/98

    Slide 47Issue A

    Restricted Earthfault Protection

    3) Peak voltage = 22 VK (VF - VK)

    VF = 14.9 x VS = 14.9 x 936 = 13946 VoltsIS

    For Earth CT, VK = 1.4 x 236 = 330 Volts (from graph) VPEAK = 22 330 (13946 - 330)

    = 6kV

    Thus, metrosil voltage limiter will be required.

    Magnetising Inrush

  • 7/29/2019 04 Transformer

    55/98

    Slide 48Issue A

    Magnetising Inrush

    Transient condition - occurs when a

    transformer is energised

    Normal operating flux of a transformer is close to saturation

    level

    Residual flux can increase the mag-current

    In the case of three phase transformer, the point-on-wave at

    switch-on differs for each phase and hence, also the inrush

    currents

    Magnetising Inrush

  • 7/29/2019 04 Transformer

    56/98

    Slide 49Issue A

    Transformer Magnetising Characteristic

    TwiceNormal

    Flux

    Normal

    Flux

    NormalNo Load Current

    No Load Currentat Twice NormalFlux

    Magnetising Inrush

    Magnetising Inrush

  • 7/29/2019 04 Transformer

    57/98

    Slide 50Issue A

    Magnetising Inrush

    m+

    SWITCH ON AT VOLTAGE

    ZERO - NO RESIDUAL FLUX

    m-

    m2

    STEADY STATE

    V

    mI

    mI

    V

    Inrush Current

    Magnetising Inrush

  • 7/29/2019 04 Transformer

    58/98

    Slide 51Issue A

    Magnetising Inrush

    Magnetising Inrush

  • 7/29/2019 04 Transformer

    59/98

    Slide 52Issue A

    Magnetising Inrush

    Appears on one side of transformer only

    - Seen as fault by differential relay

    - Transient magnetising inrush could cause

    relay to operate

    Makes CT transient saturation- Can make mal-operation of Zero sequence

    relay at primary

    Effect of magnetising current

    Magnetising Inrush

  • 7/29/2019 04 Transformer

    60/98

    Slide 53Issue A

    P1

    S1

    P2

    S2P1

    S1

    P2

    S2P1

    S1

    P2

    S2

    IR

    IS

    IT

    IR + IS + IT = 3Io = 0

    Magnetising Inrush

    Magnetising Inrush

  • 7/29/2019 04 Transformer

    61/98

    Slide 54Issue A

    Effect of magnetising current

    Example of disurbance recordswith detail

    Magnetising Inrush

    Magnetising Inrush Restrain

  • 7/29/2019 04 Transformer

    62/98

    Slide 55Issue A

    2nd (and 5th) harmonic restraint

    Makes relay immune to magnetisinginrush

    Slow operation may result for genuine

    transformer faults if CT saturationoccurs

    Magnetising Inrush Restrain

    Magnetising Inrush Restrain

  • 7/29/2019 04 Transformer

    63/98

    Slide 56Issue A

    Biasdifferential

    threshold

    TripDifferential

    comparator

    T1 = 5ms T2 = 22ms

    Differential input

    Comparator output

    Trip

    T2 Reset

    T1

    Magnetising Inrush Restrain

    Overfluxing - Basic Theory

  • 7/29/2019 04 Transformer

    64/98

    Slide 57Issue A

    Overfluxing Basic Theory

    Low frequency

    High voltage

    Geomagnetic disturbances

    Causes

    Overfluxing = V/F

    Overfluxing - Basic Theory

  • 7/29/2019 04 Transformer

    65/98

    Slide 58Issue A

    Overfluxing Basic Theory

    Transient Overfluxing - Tripping of differential

    element Prolonged Overfluxing - Damage to transformers

    Effects

    m2

    Ie

    m

    V = kf

    Overfluxing - Condition

  • 7/29/2019 04 Transformer

    66/98

    Slide 59Issue A

    Ove u g Co d t o

    Differential element should be blockedfor transient overfluxing-+

    25% OVERVOLTAGE CONDITION

    43% 5TH HARMONIC CONTENT

    Overfluxing waveform

    contains very high 5th

    Harmonic content

    Overfluxing - Protection

  • 7/29/2019 04 Transformer

    67/98

    Slide 60Issue A

    V Kf

    Trip and alarm outputs for clearing prolonged overfluxing

    Alarm : Definite time characteristic to initiate correctiveaction

    Trip : IT or DT characteristic to clear overfluxing condition

    g

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    68/98

    Slide 60Issue A

    Oil conservator

    Bucholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    69/98

    Slide 60Issue A

    Buchholz Relay Installation

    5 x internal pipediameter (minimum)

    3 x internal pipediameter (minimum)

    Transformer

    76 mm typical

    To oil conservator

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    70/98

    Slide 60Issue A

    Buchholz Relay

    Petcock

    From

    transformer

    Deflector plate

    Trip bucket

    To oilconservator

    Mercury switch

    Alarm bucket

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    71/98

    Slide 60Issue A

    Accumulation of gazOil LeakageSevere winding faults

    Buccholz Protection Application

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    72/98

    Slide 60Issue A

    Interturn faults

    Winding faults to earth with low

    power (fault close to neutral forexample)

    Accumulation of Gaz

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    73/98

    Slide 60Issue A

    Inter-Turn Fault

    Nominal turns ratio

    Fault turns ratio

    Current ratio

    : 11,000 / 240

    : 11,000 / 1

    : 1 / 11,000

    Shortedturn

    Load

    Primary Secondary

    CTE

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    74/98

    Slide 60Issue A

    Nominal turns ratio

    Fault turns ratioCurrent ratio

    : 11,000 / 240

    : 11,000 / 1: 1 / 11,000

    CTE

    Shortedturn

    Primary Secondary

    Inter-Turn Fault

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    75/98

    Slide 60Issue A

    Interturn Fault Current / Numberof Turns Short Circuited

    5 10 15 20 25

    Turn short-circuited(percentage ofwinding)

    Primary current(multiples ofrated current)

    Fault current(multiples ofrated current)

    100

    80

    60

    40

    20

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    76/98

    Slide 60Issue A

    Interturn Fault Current / Numberof Turns Short Circuited

    5 10 15 20 25

    Primary current

    (multiples of

    rated current)

    Fault current

    (multiples of

    rated current)

    100

    80

    60

    40

    20

    Fault current very high

    Primary phase current very low

    Detected by Bucholz relay

    Not detected by current

    operated relays

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    77/98

    Slide 60Issue A

    Interturn faults

    Winding faults to earth with low

    power (fault close to neutral forexample)

    Accumulation of Gaz

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    78/98

    Slide 60Issue A

    Earth Fault Current / Number ofTurns Short Circuited

    5 10 15 20 25

    Turn short-circuited(percentage of

    winding)

    Primary current

    Fault current

    100

    80

    60

    40

    20

    multiples ofmax fault current

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    79/98

    Slide 60Issue A

    Operating principle

    Accumulation of Gaz

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    80/98

    Slide 60Issue A

    Buchholz Relay

    Accumulationof gaz

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    81/98

    Slide 60Issue A

    Accumulationof gaz

    Buchholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    82/98

    Slide 60Issue A

    Accumulationof gaz

    Buchholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    83/98

    Slide 60Issue A

    Color of gaz indicatesthe type of fault

    White or Yellow :Insulation burnt

    Grey :

    Dissociated oil

    Accumulationof gaz

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    84/98

    Slide 60Issue A

    Accumulation

    of gaz

    Gaz can be extractedfor detailled analysis

    Buchholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    85/98

    Slide 60Issue A

    After oil maintenance, false

    tripping may occur because Oil

    aeration

    Effects of Oil Maintenance

    Bucholz relay tripping inhibited duringsuitable period

    Need of electrical protection

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    86/98

    Slide 60Issue A

    Accumulation of gazOil LeakageSevere winding faults

    Bucholtz Protection Application

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    87/98

    Slide 60Issue A

    Oil LeakageBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    88/98

    Slide 60Issue A

    Oil LeakageBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    89/98

    Slide 60Issue A

    Oil LeakageBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    90/98

    Slide 60Issue A

    Oil LeakageBuchholz Relay

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    91/98

    Slide 60Issue A

    Accumulation of gazOil LeakageSevere winding faults

    Buccholz Protection Application

    B hh l R l

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    92/98

    Slide 60Issue A

    Severe winding faultBuchholz Relay

    B hh l R l

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    93/98

    Slide 60Issue A

    Severe winding faultBuchholz Relay

    B hh l R l

    BUCCHOLZ PROTECTION

  • 7/29/2019 04 Transformer

    94/98

    Slide 60Issue A

    Severe winding faultBuchholz Relay

    3 3kVScheme exemple Up to 1MVA

    CONCLUSION

  • 7/29/2019 04 Transformer

    95/98

    51

    3.3kV

    200/5 P1215051

    1MVA3.3/0.44kV1500/5

    1500/564

    P120

    MCAG14

    N50N

    51N

    Scheme exemple Up to 1MVA

    11kVScheme exemple 1 - 5MVA

    CONCLUSION

  • 7/29/2019 04 Transformer

    96/98

    11kV

    P1215051

    5MVA11/3.3kV1000/5

    1000/564

    P120

    MCAG14

    51N

    MCAG1464

    3.3kV

    33KV

    Scheme exemple Above 5MVACONCLUSION

  • 7/29/2019 04 Transformer

    97/98

    33KV

    P1415051

    200/5

    P120

    10MVA33/11KV 51

    N 87600/5P631

    MCAG1464

    600/5

    5/5A

    Three Winding Transformer25MVA63MVA

    CONCLUSION

  • 7/29/2019 04 Transformer

    98/98

    25MVA11KV

    63MVA132KV

    1600/5300/5

    50MVA

    33KV

    1000/5

    4.59

    2.88

    10.33

    2.88

    5.51

    5

    5

    All interposing C.T. ratios referto common MVA base (63MVA)