04 Transformer
-
Upload
taha-mohammed -
Category
Documents
-
view
217 -
download
0
Transcript of 04 Transformer
-
7/29/2019 04 Transformer
1/98
TRANSFORMER PROTECTION
Slide 1Issue A
-
7/29/2019 04 Transformer
2/98
Slide 2Issue A
Causes of failure:
Environment
System
Mal operation
Wrong design
Manufacture
Material
Maintenance
-
7/29/2019 04 Transformer
3/98
Slide 3Issue A
Transformer failures classification :
1. Internal failureCauses:
Winding & terminal faults
Core faults
Onload tap changer faults
Overheating faults
-
7/29/2019 04 Transformer
4/98
2. External failure
Causes:
Issue A Slide 4
Abnormal operating condition
sustained or unclear faults
Transformer failures classification :
-
7/29/2019 04 Transformer
5/98
Issue A Slide 5
Vector Groups
Phase displacement0
Group 1
Phase displacement180
Group 2
Lag phase displacement30
Group 3
Lead phase displacement30
Group 4
Yy0Dd0Zd0
Yy6Dd6Dz6
Yd1
Dy1Yz1
Yd11Dy11
Yz11
-
7/29/2019 04 Transformer
6/98
Slide 6Issue A
Vector Configurations
12
11
300
1, DRAW PHASE-NEUTRAL VOLTAGE VECTORS
300
-
7/29/2019 04 Transformer
7/98
Slide 7Issue A
2. Draw Delta Connection
A
C B
a
c
b
Vector Configurations
-
7/29/2019 04 Transformer
8/98
Issue A Slide 8
3. Draw A Phase Windings
A
C B
a
c
b
a2
a1
A2
A1
Vector Configurations
-
7/29/2019 04 Transformer
9/98
Slide 9Issue A
4. Complete Connections (a)
A
C B
a
c
b
a2
a1
A2
A1
C1
C2
B1
B2
b2b1c1
c2
Vector Configurations
-
7/29/2019 04 Transformer
10/98
Slide 10Issue A
Fault current distribution
Earth fault on Transformer winding
V2
R
T2 T1
V 1
X
Fig.3 If
Fig.N
-
7/29/2019 04 Transformer
11/98
-
7/29/2019 04 Transformer
12/98
Slide 12Issue A
Fault current distribution
If Transformer star winding is solid earthed,
fault current limited only by the leakage
reactanceof the winding
If asmultiple of
IF.L.
.1 .2 .3 .4 .5 .6 .7 .8 . 9 1.0 x p.u
Delta side
Star side
Fig.Q
10
9
8
7
6
5
4
3
2
1
-
7/29/2019 04 Transformer
13/98
Slide 13Issue A
Differential
Basic Protection
Restricted Earthfault
Overfluxing
Overcurrent & Earthfault
-
7/29/2019 04 Transformer
14/98
Slide 14Issue A
Differential Protection
Where protection co-ordination is difficult / notpossible using time delayed elements
For fast fault clearance
Applied
Works on Merz-price current comparison principle
Relays with bias characteristic should only be used
For zone of protection
-
7/29/2019 04 Transformer
15/98
Slide 15Issue A
Differential Protection
Consideration for applying differential
protection
Phase correction
Filtering of zero sequence currents
Ratio correction
Magnetizing inrush during energisation
Overfluxing
-
7/29/2019 04 Transformer
16/98
Slide 16Issue A
Differential Protection - Principle
R I diff = 0
Nominal current through the protected equipment
I Diff = 0 : No tripping
-
7/29/2019 04 Transformer
17/98
Slide 17Issue A
Differential Protection - Principle
Through fault current
I Diff = 0 : No tripping
R I diff = 0
-
7/29/2019 04 Transformer
18/98
Slide 18Issue A
Differential Protection - Principle
Tripping
Internal Fault
I Diff = 0 :
R I diff = 0
-
7/29/2019 04 Transformer
19/98
Slide 19Issue A
Biased differential protection
Fast operation
Adjustable characteristic
High through fault stability
CT ratio compensation
Magnetising inrush restraint
Overfluxing 5th harmonic restraint
-
7/29/2019 04 Transformer
20/98
Slide 20Issue A
Biased differential protection
1 A
100/50 KV100 / 1 200 / 1
1 A
0 A
LOAD
= 200 A
Why bias characteristic ?
OLTC Setting is at mid tap
R
I1I2
-
7/29/2019 04 Transformer
21/98
Slide 21Issue A
Biased differential protection100/50 KV100 / 1 200 / 1
0.9 A 1 A
0.1 A
Relay pickup setting = O.2 A, So the Relay restrains
LOAD= 200 A
OLTC SETTING IS AT 10%
Differential current = 0.1 A
R
-
7/29/2019 04 Transformer
22/98
Slide 22Issue A
Biased differential protection
100/50 KV100 / 1 200 / 1
9 A10 A
1 A
Relay Pickup Setting is O.2 AOLTC SETTING IS AT 10%
2000 A
R
OperatesSo the Relay
-
7/29/2019 04 Transformer
23/98
Slide 23Issue A
Role of Bias
Setting range(0.1 - 0.5)
Effective bias (x In) = I + I + I + I1 2 3 4
2
Differential current (x In)= I + I + I + I1 2 3 4
0 1 2 3 4
1
2
3
Operate
Restrain
80%
Slope
20%Slope
-
7/29/2019 04 Transformer
24/98
R RR
Dy1(-30 )
Yd11(+30 )
Interposing CT provides
Vector correction
Ratio correction
Zero sequencecompensation
USE OF ICT
-
7/29/2019 04 Transformer
25/98
Dy1(-30 )
RR
R
PROTECTION TRANSFORMATEUR
sur dfaut interne: Protection diffrentielle
Yd11
Vector Group Correction - Static Relays
Vector and Ratio correction by interposing CT
CURRENT DIFFERENTIAL PROTECTION
-
7/29/2019 04 Transformer
26/98
RR
R
PROTECTION TRANSFORMATEUR
sur dfaut interne: Protection diffrentielle
Yd11
Vector Group Correction - Static Relays
Vector and Ratio correction by CT Connection
CURRENT DIFFERENTIAL PROTECTION
-
7/29/2019 04 Transformer
27/98
87
Yy0 Yd11
0 +30
Yy0, Yd1, Yd5 , Yy6, Yd7, Yd11, Ydy0
0 , -30 , -150 , 180,+150, +30 , 0
Dy1 (-30 )
VECTOR GROUP CORRECTION
-
7/29/2019 04 Transformer
28/98
87
Dy11 (+30 )
Yy0
0
Yd1
-30
SELECTION OF SUITABLE
VECTOR CORRECTION FACTOR
-
7/29/2019 04 Transformer
29/98
0.875A
87
200/1
1.31 Amps
I = 175A I = 525A 400/1L L
33kV : 11kV10 MVA
1.14 0.76
1A 1A
CT RATIO MISMATCH CORRECTION
-
7/29/2019 04 Transformer
30/98
+VE SEQUENCECURRENTSBALANCE
REQUIRE ZEROSEQUENCE
CURRENT
TRAPS FORSTABILITY B CA
ZERO SEQUENCE COMPENSATION
-
7/29/2019 04 Transformer
31/98
Slide 24Issue A
Based on Current operated relay with an external stabilisingresistor
Requires matched current transformers of low reactance design,typically class X or equivalent
Equal CT ratios
Non-linear resistor may be required to limit voltage across relaycircuit during internal faults
Suitable for zones up to 200 - 300 metres (typically)
High Impedance Principle
-
7/29/2019 04 Transformer
32/98
Slide 25Issue A
High Impedance Principle
TC satur
M
RCT
ZM
RCT2RL 2RL
A
M
ZM
RCT
2RL
2RL
RCT
-
7/29/2019 04 Transformer
33/98
Slide 26Issue A
High Impedance Principle
RCT
ZM
RCT
ZM
2RL 2RL
A
M
M
-
7/29/2019 04 Transformer
34/98
Slide 27Issue A
High Impedance Principle
RCT
ZM
RCT
ZM
2RL 2RL
TC satur
A
M
M
-
7/29/2019 04 Transformer
35/98
Slide 28Issue A
High Impedance Principle
RCT
ZM
RCT
ZM
2RL 2RL
A
M
M
-
7/29/2019 04 Transformer
36/98
Slide 29Issue A
High Impedance Principle
RCT
ZM
RCT
ZM
2RL 2RL
TC satur
A
M
M
-
7/29/2019 04 Transformer
37/98
Slide 30Issue A
High Impedance Principle
RCT
ZM
RCT
ZM
2RL 2RL
A
M
M
-
7/29/2019 04 Transformer
38/98
Slide 31Issue A
High Impedance Principle
RCT
ZM
RCT
ZM
2RL 2RL
TCsatur
A
M
M
-
7/29/2019 04 Transformer
39/98
Slide 32Issue A
High Impedance Principle
RCT
ZM
RCT
ZM=0
2RL 2RL
TC satur
RCT
2RL
2RL
RCT
A
M
MCT Saturation
False tripping
-
7/29/2019 04 Transformer
40/98
Slide 33Issue A
High Impedance Principle
RCT
ZM
RCT
ZM=0
2RL 2RL
TC satur
RCT
2RL
2RL
RCT
A
RS
M
M
-
7/29/2019 04 Transformer
41/98
Slide 34Issue A
High Impedance Principle
RCT
ZM
RCT
ZM=0
2RL 2RL
TC satur
RCT
2RL
2RL
RCT
A
RS
M
M
Stabilising resistor
-
7/29/2019 04 Transformer
42/98
Slide 35Issue A
RCT
ZM
RCT
ZM
2RL 2RL
A
RS
M
M
RCT
2RL
2RL
RCT Vset
High Impedance Principle
-
7/29/2019 04 Transformer
43/98
Slide 36Issue A
RCT
ZM
RCT
ZM=0
2RL 2RL
RCT
2RL
2RL
RCT
A
RS
M
M
ZM = 0
(CT "shortcircuited" )
Vset
High Impedance Principle
-
7/29/2019 04 Transformer
44/98
Slide 37Issue A
A
RCT
ZM
RCT
ZM
2RL 2RL
2RL
RCT
2RL
RCT
RS
M
M
Vset
High Impedance Principle
-
7/29/2019 04 Transformer
45/98
Slide 38Issue A
High Impedance Principle
2RL
RCT
2RL
RCT
M
Vset
A
RCT
ZM
RCT
ZM
2RL 2RL
RS
M
-
7/29/2019 04 Transformer
46/98
Slide 39Issue A
High Impedance Principle
M
A
RC
T
ZM
RC
T
ZM
2R
L
2R
L
RS
M
Vset
Metrosil may be
required for voltagelimitation
2R
L
RC
T 2R
L
RC
T
M
-
7/29/2019 04 Transformer
47/98
Slide 40Issue A
Restricted Earthfault Protection
Increased sensitivity for earth faults
REF elements for each transformer winding
CTs may be shared with differential element
Uses high impedance principle
6464
64
Restricted Earthfault Protection
-
7/29/2019 04 Transformer
48/98
Slide 41Issue A
est cted a t au t otect o
P1
S1
P2
S2P1
S1
P2
S2
P1S1
P2S2
P1
P2
S1
S2
Stability level : usually maximum through fault level of transformerREF Case I : Normal Condition
Under normal conditions no current flows thro Relay
So, No Operation
Restricted Earthfault Protection
-
7/29/2019 04 Transformer
49/98
Slide 42Issue A
Restricted Earthfault Protection
REF Case II : External Earth Fault
External earth fault - Current circulates between the phase & neutral CTs;
no current thro the relay
So, No Operation
Restricted Earthfault Protection
-
7/29/2019 04 Transformer
50/98
Issue ASlide 43
Issue A
Restricted Earthfault Protection
REF Case III : Internal Earth Fault
For an internal earth fault the unbalanced current flows thro the relay
So, Relay Operates
Restricted Earthfault Protection
-
7/29/2019 04 Transformer
51/98
Slide 44Issue A
Restricted Earthfault Protection
Restricted Earth Fault ProtectionSetting
1MVA(5%)
11000V 415V
1600/1
RCT = 4.9
80MVA
RS1600/1
RCT = 4.8MCAG14
IS = 0.1 Amp
2 Core 7/0.67mm (7.41/km)100m Long
Setting will requirecalculation of :
1) Setting stabilityvoltage (V
S
)
2) Value of stabilisingresistor required
3) Peak voltage
developed by CTsfor internal fault
Restricted Earthfault Protection
-
7/29/2019 04 Transformer
52/98
Slide 45Issue A
Restricted Earthfault Protection
Example : Earth fault calculation :-
Using 80MVA base
Source impedance = 1 p.u.
Transformer impedance = 0.05 x 80 = 4 p.u.1
Total impedance = 14 p.u.
I1 = 1 = 0.0714 p.u.14
Base current = 80 x 106
3 x 415
= 111296 Amps IF = 3 x 0.0714 x 111296
= 23840 Amps (primary)= 14.9 Amps (secondary)
1 P.U.1 4
I1
4
I2
4
I0
1
1
Restricted Earthfault Protection
-
7/29/2019 04 Transformer
53/98
Slide 46Issue A
Restricted Earthfault Protection
(1) Setting voltage
VS = IF (RCT + 2RL)
Assuming earth CT saturates,
RCT = 4.8 ohms2RL = 2 x 100 x 7.41 x 10
-3 = 1.482 ohms
Setting voltage = 14.9 (4.8 + 1.482)
= 93.6 Volts
(2) Stabilising Resistor (RS)
RS = VS - 1IS IS
2 Where IS = relay current setting
RS = 93.6 - 1 = 836 ohms
0.1 0.22
Restricted Earthfault Protection
-
7/29/2019 04 Transformer
54/98
Slide 47Issue A
Restricted Earthfault Protection
3) Peak voltage = 22 VK (VF - VK)
VF = 14.9 x VS = 14.9 x 936 = 13946 VoltsIS
For Earth CT, VK = 1.4 x 236 = 330 Volts (from graph) VPEAK = 22 330 (13946 - 330)
= 6kV
Thus, metrosil voltage limiter will be required.
Magnetising Inrush
-
7/29/2019 04 Transformer
55/98
Slide 48Issue A
Magnetising Inrush
Transient condition - occurs when a
transformer is energised
Normal operating flux of a transformer is close to saturation
level
Residual flux can increase the mag-current
In the case of three phase transformer, the point-on-wave at
switch-on differs for each phase and hence, also the inrush
currents
Magnetising Inrush
-
7/29/2019 04 Transformer
56/98
Slide 49Issue A
Transformer Magnetising Characteristic
TwiceNormal
Flux
Normal
Flux
NormalNo Load Current
No Load Currentat Twice NormalFlux
Magnetising Inrush
Magnetising Inrush
-
7/29/2019 04 Transformer
57/98
Slide 50Issue A
Magnetising Inrush
m+
SWITCH ON AT VOLTAGE
ZERO - NO RESIDUAL FLUX
m-
m2
STEADY STATE
V
mI
mI
V
Inrush Current
Magnetising Inrush
-
7/29/2019 04 Transformer
58/98
Slide 51Issue A
Magnetising Inrush
Magnetising Inrush
-
7/29/2019 04 Transformer
59/98
Slide 52Issue A
Magnetising Inrush
Appears on one side of transformer only
- Seen as fault by differential relay
- Transient magnetising inrush could cause
relay to operate
Makes CT transient saturation- Can make mal-operation of Zero sequence
relay at primary
Effect of magnetising current
Magnetising Inrush
-
7/29/2019 04 Transformer
60/98
Slide 53Issue A
P1
S1
P2
S2P1
S1
P2
S2P1
S1
P2
S2
IR
IS
IT
IR + IS + IT = 3Io = 0
Magnetising Inrush
Magnetising Inrush
-
7/29/2019 04 Transformer
61/98
Slide 54Issue A
Effect of magnetising current
Example of disurbance recordswith detail
Magnetising Inrush
Magnetising Inrush Restrain
-
7/29/2019 04 Transformer
62/98
Slide 55Issue A
2nd (and 5th) harmonic restraint
Makes relay immune to magnetisinginrush
Slow operation may result for genuine
transformer faults if CT saturationoccurs
Magnetising Inrush Restrain
Magnetising Inrush Restrain
-
7/29/2019 04 Transformer
63/98
Slide 56Issue A
Biasdifferential
threshold
TripDifferential
comparator
T1 = 5ms T2 = 22ms
Differential input
Comparator output
Trip
T2 Reset
T1
Magnetising Inrush Restrain
Overfluxing - Basic Theory
-
7/29/2019 04 Transformer
64/98
Slide 57Issue A
Overfluxing Basic Theory
Low frequency
High voltage
Geomagnetic disturbances
Causes
Overfluxing = V/F
Overfluxing - Basic Theory
-
7/29/2019 04 Transformer
65/98
Slide 58Issue A
Overfluxing Basic Theory
Transient Overfluxing - Tripping of differential
element Prolonged Overfluxing - Damage to transformers
Effects
m2
Ie
m
V = kf
Overfluxing - Condition
-
7/29/2019 04 Transformer
66/98
Slide 59Issue A
Ove u g Co d t o
Differential element should be blockedfor transient overfluxing-+
25% OVERVOLTAGE CONDITION
43% 5TH HARMONIC CONTENT
Overfluxing waveform
contains very high 5th
Harmonic content
Overfluxing - Protection
-
7/29/2019 04 Transformer
67/98
Slide 60Issue A
V Kf
Trip and alarm outputs for clearing prolonged overfluxing
Alarm : Definite time characteristic to initiate correctiveaction
Trip : IT or DT characteristic to clear overfluxing condition
g
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
68/98
Slide 60Issue A
Oil conservator
Bucholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
69/98
Slide 60Issue A
Buchholz Relay Installation
5 x internal pipediameter (minimum)
3 x internal pipediameter (minimum)
Transformer
76 mm typical
To oil conservator
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
70/98
Slide 60Issue A
Buchholz Relay
Petcock
From
transformer
Deflector plate
Trip bucket
To oilconservator
Mercury switch
Alarm bucket
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
71/98
Slide 60Issue A
Accumulation of gazOil LeakageSevere winding faults
Buccholz Protection Application
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
72/98
Slide 60Issue A
Interturn faults
Winding faults to earth with low
power (fault close to neutral forexample)
Accumulation of Gaz
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
73/98
Slide 60Issue A
Inter-Turn Fault
Nominal turns ratio
Fault turns ratio
Current ratio
: 11,000 / 240
: 11,000 / 1
: 1 / 11,000
Shortedturn
Load
Primary Secondary
CTE
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
74/98
Slide 60Issue A
Nominal turns ratio
Fault turns ratioCurrent ratio
: 11,000 / 240
: 11,000 / 1: 1 / 11,000
CTE
Shortedturn
Primary Secondary
Inter-Turn Fault
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
75/98
Slide 60Issue A
Interturn Fault Current / Numberof Turns Short Circuited
5 10 15 20 25
Turn short-circuited(percentage ofwinding)
Primary current(multiples ofrated current)
Fault current(multiples ofrated current)
100
80
60
40
20
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
76/98
Slide 60Issue A
Interturn Fault Current / Numberof Turns Short Circuited
5 10 15 20 25
Primary current
(multiples of
rated current)
Fault current
(multiples of
rated current)
100
80
60
40
20
Fault current very high
Primary phase current very low
Detected by Bucholz relay
Not detected by current
operated relays
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
77/98
Slide 60Issue A
Interturn faults
Winding faults to earth with low
power (fault close to neutral forexample)
Accumulation of Gaz
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
78/98
Slide 60Issue A
Earth Fault Current / Number ofTurns Short Circuited
5 10 15 20 25
Turn short-circuited(percentage of
winding)
Primary current
Fault current
100
80
60
40
20
multiples ofmax fault current
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
79/98
Slide 60Issue A
Operating principle
Accumulation of Gaz
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
80/98
Slide 60Issue A
Buchholz Relay
Accumulationof gaz
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
81/98
Slide 60Issue A
Accumulationof gaz
Buchholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
82/98
Slide 60Issue A
Accumulationof gaz
Buchholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
83/98
Slide 60Issue A
Color of gaz indicatesthe type of fault
White or Yellow :Insulation burnt
Grey :
Dissociated oil
Accumulationof gaz
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
84/98
Slide 60Issue A
Accumulation
of gaz
Gaz can be extractedfor detailled analysis
Buchholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
85/98
Slide 60Issue A
After oil maintenance, false
tripping may occur because Oil
aeration
Effects of Oil Maintenance
Bucholz relay tripping inhibited duringsuitable period
Need of electrical protection
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
86/98
Slide 60Issue A
Accumulation of gazOil LeakageSevere winding faults
Bucholtz Protection Application
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
87/98
Slide 60Issue A
Oil LeakageBuchholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
88/98
Slide 60Issue A
Oil LeakageBuchholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
89/98
Slide 60Issue A
Oil LeakageBuchholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
90/98
Slide 60Issue A
Oil LeakageBuchholz Relay
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
91/98
Slide 60Issue A
Accumulation of gazOil LeakageSevere winding faults
Buccholz Protection Application
B hh l R l
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
92/98
Slide 60Issue A
Severe winding faultBuchholz Relay
B hh l R l
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
93/98
Slide 60Issue A
Severe winding faultBuchholz Relay
B hh l R l
BUCCHOLZ PROTECTION
-
7/29/2019 04 Transformer
94/98
Slide 60Issue A
Severe winding faultBuchholz Relay
3 3kVScheme exemple Up to 1MVA
CONCLUSION
-
7/29/2019 04 Transformer
95/98
51
3.3kV
200/5 P1215051
1MVA3.3/0.44kV1500/5
1500/564
P120
MCAG14
N50N
51N
Scheme exemple Up to 1MVA
11kVScheme exemple 1 - 5MVA
CONCLUSION
-
7/29/2019 04 Transformer
96/98
11kV
P1215051
5MVA11/3.3kV1000/5
1000/564
P120
MCAG14
51N
MCAG1464
3.3kV
33KV
Scheme exemple Above 5MVACONCLUSION
-
7/29/2019 04 Transformer
97/98
33KV
P1415051
200/5
P120
10MVA33/11KV 51
N 87600/5P631
MCAG1464
600/5
5/5A
Three Winding Transformer25MVA63MVA
CONCLUSION
-
7/29/2019 04 Transformer
98/98
25MVA11KV
63MVA132KV
1600/5300/5
50MVA
33KV
1000/5
4.59
2.88
10.33
2.88
5.51
5
5
All interposing C.T. ratios referto common MVA base (63MVA)