  • 8/11/2019 02.Fire Calculations

    1/2

    Project : SRTPL BCP.

    Owner : SRTPL.

    Fire Suppression Calculations

    CLIENT: SRTPL SHEET: of 2

    PROJECT SRTPL,BCP DATE: 21/7/2011

    PM PROJECT NO: IN20101004 ORIG: R.N

    CLIENT PROJECT NO: AUTH CHK:BMD

    Part of Document No./Description: IN20101004 46 CA - 0019

    Calculation No./Description: Fire Suppression System Calculations

    TAG No: DESCRIPTION: Fire Suppression System

    1 As per NBC Part 4 Life & Safety - Table 23, Page 39

    Under Group E Buisness Building, Sub division E2-Laboratories & Research Establishments

    Description Building Less than 10mts in

    height

    Building above 10

    Mts but not

    Exceeding 15mts in

    height

    Extinguisher Required Required

    Hose Reel Required Required

    Dry Riser Not Required Not Required

    Wet Riser Not Required Required

    Downcomer Required Not Required

    Yard hydrant Not Required Not Required

    Automatic Sprinkler

    System Required(See Note 1) Required(See Note1)Manualy Operated Fire

    Alarm System Required RequiredAutomaticDetection &

    Alarm System Not Required RequiredUnderground Static Water

    Storage Tank Not Required Not Required

    Terrace Tank 10,000ltrs 5,000ltrsPumps near U.G Sump Not Required See Note(2)

    O.H.T capacity 450LPM 450LPM

    Note :

    1. Required to be provided if the basement area exceed 200m2

    2. One Electric & one diesel pump of capacity 2280LPM & one electric pump capacity of 180LPM

    2 Pump Capacity

    Diesel Engine Pump 2280LPM @ 75mts

    Hydrant Pump 2280LPM @ 75mts

    SprinklerPump 2280LPM @ 75mts

    Jockey Pump 180LPM @ 75mts

    3 Booster Pump450 lpm @35mts

    4 OHT Capacity

    For Building less than 10mts 10,000 ltrs

    For Building above 10mts

    no exceeding 15mts 5,000 ltrs

    5 U.G.Sump Capacity

    Considering pump working

    for 1 hour 2280x60

    136800Litres

    Total U.G.Sump Capacity 1,40,000 litres

    Project Management Engineering

    Services(I) Pvt.Ltd.

    Last modified : 21.07.11

    Rev : RA 1 of 2

    Venkataramanana AssociatesProject Management Engineering Services (India) Pvt Ltd

  • 8/11/2019 02.Fire Calculations

    2/2

    Project : SRTPL BCP.

    Owner : SRTPL.

    6 Sprinkler pipe Schedule as per NFPA 13 table 22.5.3.4

    Pipe dia(in mm) Sprinklers(Nos.)

    25 2

    32 3

    40 5

    50 10

    65 20

    80 40100 100

    150 275

    7 Spacing between each Yard Hydrant is 45mts as per TAC under clause 7.6.11 page 51

    8 Number of Hydrant in 150mm dia pipe

    As per TAC Table 2 page 30

    Hydrant Exceeding 20 nos

    but not exceeding 55nos

    for 2280 Lpm

    9 Coverage Area of Sprinklers 9-12 Sq.mts as per standard Engineering practice

    10 Suction Header size

    Pump Discharge in LPM 2280Pump Discharge in m3/s 0.038

    Q=AV

    A= d2/4

    Q(cum/sec) 0.038

    V 2

    ( As per Standard

    Engineering practice

    the suction velocity

    shall be considered

    between 1.5 to 2)

    D(in mts) 0.155526

    D(in MM) 155.5263

    As per the calculation

    the Pipe dia(in MM) wehave got is 155 so the

    suction header size is

    200

    Last modified : 21.07.11

    Rev : RA 2 of 2

    Venkataramanana AssociatesProject Management Engineering Services (India) Pvt Ltd