Project : SRTPL BCP.
Owner : SRTPL.
Fire Suppression Calculations
CLIENT: SRTPL SHEET: of 2
PROJECT SRTPL,BCP DATE: 21/7/2011
PM PROJECT NO: IN20101004 ORIG: R.N
CLIENT PROJECT NO: AUTH CHK:BMD
Part of Document No./Description: IN20101004 46 CA - 0019
Calculation No./Description: Fire Suppression System Calculations
TAG No: DESCRIPTION: Fire Suppression System
1 As per NBC Part 4 Life & Safety - Table 23, Page 39
Under Group E Buisness Building, Sub division E2-Laboratories & Research Establishments
Description Building Less than 10mts in
height
Building above 10
Mts but not
Exceeding 15mts in
height
Extinguisher Required Required
Hose Reel Required Required
Dry Riser Not Required Not Required
Wet Riser Not Required Required
Downcomer Required Not Required
Yard hydrant Not Required Not Required
Automatic Sprinkler
System Required(See Note 1) Required(See Note1)Manualy Operated Fire
Alarm System Required RequiredAutomaticDetection &
Alarm System Not Required RequiredUnderground Static Water
Storage Tank Not Required Not Required
Terrace Tank 10,000ltrs 5,000ltrsPumps near U.G Sump Not Required See Note(2)
O.H.T capacity 450LPM 450LPM
Note :
1. Required to be provided if the basement area exceed 200m2
2. One Electric & one diesel pump of capacity 2280LPM & one electric pump capacity of 180LPM
2 Pump Capacity
Diesel Engine Pump 2280LPM @ 75mts
Hydrant Pump 2280LPM @ 75mts
SprinklerPump 2280LPM @ 75mts
Jockey Pump 180LPM @ 75mts
3 Booster Pump450 lpm @35mts
4 OHT Capacity
For Building less than 10mts 10,000 ltrs
For Building above 10mts
no exceeding 15mts 5,000 ltrs
5 U.G.Sump Capacity
Considering pump working
for 1 hour 2280x60
136800Litres
Total U.G.Sump Capacity 1,40,000 litres
Project Management Engineering
Services(I) Pvt.Ltd.
Last modified : 21.07.11
Rev : RA 1 of 2
Venkataramanana AssociatesProject Management Engineering Services (India) Pvt Ltd
-
8/11/2019 02.Fire Calculations
2/2
Project : SRTPL BCP.
Owner : SRTPL.
6 Sprinkler pipe Schedule as per NFPA 13 table 22.5.3.4
Pipe dia(in mm) Sprinklers(Nos.)
25 2
32 3
40 5
50 10
65 20
80 40100 100
150 275
7 Spacing between each Yard Hydrant is 45mts as per TAC under clause 7.6.11 page 51
8 Number of Hydrant in 150mm dia pipe
As per TAC Table 2 page 30
Hydrant Exceeding 20 nos
but not exceeding 55nos
for 2280 Lpm
9 Coverage Area of Sprinklers 9-12 Sq.mts as per standard Engineering practice
10 Suction Header size
Pump Discharge in LPM 2280Pump Discharge in m3/s 0.038
Q=AV
A= d2/4
Q(cum/sec) 0.038
V 2
( As per Standard
Engineering practice
the suction velocity
shall be considered
between 1.5 to 2)
D(in mts) 0.155526
D(in MM) 155.5263
As per the calculation
the Pipe dia(in MM) wehave got is 155 so the
suction header size is
200
Last modified : 21.07.11
Rev : RA 2 of 2