02b_SGF100_procent_ protection.pdf

download 02b_SGF100_procent_ protection.pdf

of 22

Transcript of 02b_SGF100_procent_ protection.pdf

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    1/22

    The year of Profitable Growth

    Global networkof innovation

    100% - Stator - Ground-

    Fault Protection

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    2/22

    Power Automation 2

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Presenter: Dr. Hans-Joachim Herrmann

    PTD PA13

    Phone +49 911 433 8266E-Mail: [email protected]

    Generator Protection

    100%-Stator-Ground-Fault

    Protection

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    3/22

    Power Automation 3

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Basic ProblemFaults Close to the Star Point

    V0Displacement voltage

    At faults close to the star point V0 goes to zero. Protection criteriadisplacement voltage and ground current do not work.

    Alternatives: Evaluation of 3rd harmonics in the zero sequence voltage Additional injection of low frequency voltage into the star

    point (20 Hz =Siemens principle)

    U0

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    4/22

    Power Automation 4

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Distribution of 3rd Harmonics in a Generator

    V0 3.Harm(V03H>)

    V0 3.Harm(V03H

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    5/22

    Power Automation 5

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Considered Notes at the Applicationof 3rd Harmonics

    ? The distribution of 3rd. harmonics can be different fromgenerator to generator - the application of this principle canbe sometimes determined only during a primary test

    ? The harmonics (e.g. measuring location at the star point)are detectable not before the nominal voltage is available

    ? The part of harmonics depends also from the operationcondition of the generators (Influence of active and reactivepower)

    - Application is not always possible

    - Application has a restricted operating range

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    6/22

    Power Automation 6

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Measurements on a Generator

    V0

    G

    7UM 61ILU0

    VLILV0

    1. Test device 7UM 61

    2. Test device 7UM 61

    6 MVA; Yd55,25/58,3 kV

    6 MVA5250 V

    400 Rpm

    45 VA5P20

    800/5 A

    606 Ohm5250 100 100

    ?3 ?3 3 V5250?3

    100 V60 kV

    5 %+-

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    7/22

    Power Automation 7

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Measurements on a GeneratorInfluence of the Active and Reactive Power

    Influence of theactive power isvisible

    Approx. 15 V measured

    without load

    Release of theprotection functionat a determinedactive power is

    recommended

    150-Hz-Voltage at the star point as a function of

    active power; Parameter reactive power

    0

    20

    40

    60

    80

    100

    120

    140

    0 1 2 3 4 5 6

    Active Power in MW

    150-Hz-voltagein

    V

    150 Hz at Q = - 2 MVar 150 Hz at Q = 0 MVar

    150 Hz at Q = 2 MVar 150 Hz at Q = 4 MVar

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    8/22

    Power Automation 8

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Comparison ofMeasuring Resultsbetween Star Pointand Terminals

    Reactive Power 2 MVar

    -150

    -100

    -50

    0

    50

    100

    150

    200

    250

    300

    0 2 4 6 8 10 12

    Stator (0= star point; 10= terminal)

    150-Hz-

    voltage

    in

    V

    P 2 MW P 3 MW

    P 4 MW P 5,6 MW

    Earth fault at 2 MVar and 4 MW

    During an ground fault onthe star point the dis-

    placement voltage on theterminal side was lowerthan the 3rd harmonics atfull load.A higher voltage wasexpected.

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    9/22

    Power Automation 9

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Fault RecordSwitching OFF of a Generators during Full Load

    Generator: 25 MVA, 6,3 kV

    iL3

    VL3

    VE

    3rd harmonicsdrops

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    10/22

    Power Automation 10

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    0 50 100 150 200 250 300 3500

    2

    4

    6

    8

    10

    Zeit in ms

    Spannung

    inV

    10

    0

    5.58

    9.3

    U03hi

    knU

    10 tan( )i

    312.633.344

    181

    tai

    Fault on a Transmission Line (Ph-E ?) -An increasing of3rd harmonics on a broken delta winding was observed.

    Pickup generatorovercurrentprotection

    Drop off overcurrentprotection

    Time in ms

    Calculated 3rd harmonicsfrom a fault record

    Secondarydisplacementvoltage(3rdharmonics

    )

    3rd harmonicsunder load

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    11/22

    Power Automation 11

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Logic Diagram

    PreferredConnection:Star point(V3.H

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    12/22

    Power Automation 12

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Injection of a 20-Hz-voltage into the Star Point

    Basic idea ? With the injection of a voltage into thestar point a electromotive force isavailable in case of an ground fault

    ? Also during an ground fault in the starpoint a fault current flows through thefault resistance.

    ? This measuring principle is independentfrom the operation conditions of thegenerator. A measuring during stand stillis possible.

    ? Following additional devices arenecessary:

    20-Hz-Generator,20-Hz-Band passCurrent CT

    20 Hz

    RE

    max.200 V

    I

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    13/22

    Power Automation 13

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    20-Hz-Measuring Principle is the Real100%-Stator Ground Fault Protection

    U0

    100 % protection range includes VTsand low side of unit transformer

    ? Measuring principle is independent from the operationconditions of the generator

    ? Measuring is possible during stand still of the generator

    ? High sensitivity (negative influence of capacitive currentwill be eliminated)

    ? Different and independent measuring principle againstthe displacement measuring method

    90 % protection range with displacement voltage measurement

    10 % -25 % Protection range of 3rd harmonic, with additional limits(see previous slides)

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    14/22

    Power Automation 14

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Basic Scheme - Unit ConnectionInjection via Grounding or Neutral Transformer

    Load resistor should be> 0,5 ?

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    15/22

    Power Automation 15

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Scheme DesignGas Turbine with Neutral Transformer

    Currenttransformer:Direct orderat RitzKS60-03 Size 315VA Cl.1 FS5

    UER13

    R14

    RL

    Neutral

    transformer

    J7

    J8

    TD3

    K18

    K17 +

    UErrExcitation

    TD1K14

    K13 +

    IEE1

    7XT33

    7XT34

    20-Hz-

    Generator20-Hz-

    Band pass

    4A3

    4A11B4

    1A1

    1A2

    1A3

    3A2

    3A1

    3A3

    1B1

    Wiring shielded

    400A

    5A

    max 200 V

    kl

    7KG6+ 31

    - 32

    + 12

    - 11 (Amplifier)

    max. 10 cm Wiring twisted and shielded

    Shunt:10 A/ 150 mV

    2A1

    2A3BE

    +UH-UH

    UL1UL2

    UL3

    Deviceready

    Auxi liary

    voltage

    DC AC

    external

    block

    KL

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    16/22

    Power Automation 16

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    100%-Stator Ground-Fault ProtectionNumerical Design

    Replica:

    ises

    ises Vses

    20HzRE RBCE

    RE = Fault resistance

    CE = Ground capacitance instator circuit

    Vses

    ises

    1) Filtering

    3) Impedance replica of fault 4) Calculation of fault resistor from 2) and 3)

    2) Calculation of the real part

    Yers CE RE Yers =1

    RE

    + j ? CE RE =V2r+ V

    2i

    Vr. Ir + Vi

    . Ii

    Re

    Vr. Ir+ Vi

    . Ii

    V2r+ V2

    i

    Fourierfilter

    (20Hz)

    V20 = Vr+ jVi

    I20 = Ir+ jIi=

    ???

    ???

    20

    20

    V

    I

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    17/22

    Power Automation 17

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Filter Coefficients of the 20-Hz-FIR Filter

    0 10 20 30 40 50 60 702

    0

    21.989

    1.733

    af1

    bf1

    630 f1

    af1

    cos 2 ?

    32

    f1 0.5( )? 1 cos 2 ? f1 0.5

    64

    ??

    bf1

    sin 2 ?

    32f1 0.5( )? 1 cos 2 ?

    f1 0.5

    64??

    Filter window: 4 cycles (64 filter coefficients)

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    18/22

    Power Automation 18

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Compensation of Sources of an Error

    ? Angle error of CT 400A/5A

    (measuring currents in mA - 20 Hz current can be max. 3A )

    ? Primary to secondary impedance of the grounding/ neutraltransformer

    ? Angle errors of relay transformers

    Compensation of the angle error via parameter(5309 PHI I SES Correction angle for I SGF)

    Primary to secondary resistance from grounding orneutral transformer can be set (that is New)(5311 SGF Rps Resistance Rps)

    Calibration is only for one point possible, e.g. Trip stage

    Final settings during the primary test

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    19/22

    Power Automation 19

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Fault Record during a Primary Test

    At the device

    inputs aresmallsecondaryvalues

    The capacitivecurrent is visible.This disturbance

    current will beeliminated by thealgorithm.

    Phase to groundvoltage

    Displacementvoltage

    Ground current

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    20/22

    Power Automation 20

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    100 % Stator Ground Fault Protectionwith Primary Load Resistor

    UER13

    R14

    RL

    J7

    J8 IEE1

    7XT337XT34

    20-Hz-Generator20-Hz-

    Bandpass

    4A3

    4A11B4

    1A1

    1A2

    1A3

    3A2

    3A1

    3A3

    1B1

    2A1

    2A3BI

    +UH-UH

    UL1UL2UL3

    Device

    ready

    Aux.

    voltage

    DC AC

    external

    Block

    1A4 1A3

    UN

    ?3500 V

    CT Ratio 1: 1

    Voltagetransformer

    7UM62

    1A1

    Voltage transformer:two pole isolated,until VN saturation freefor 20 Hz should be Rps< 1000?20s approx. 3 kVA

    Current transformer:5P10 or 5P15 (or 5FS10)1A secondaryCT Ratio: 1A/1A(max. Ampere windings)

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    21/22

    Power Automation 21

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Setting Sheet of the100% Stator Ground Fault Protection

    Two Stages

    Back-upovercurrent

    Supervision

    Calibration

  • 7/23/2019 02b_SGF100_procent_ protection.pdf

    22/22

    Power Automation 22

    Power Transmission and Distribution

    Power AutomationProgress. Itsthatsimple.

    Logic Diagram