Volume 6 Tab1 - KJ ELECTRIC SOFTSTARTER.pdf · Volume 6—Solid-State Motor Control...

Post on 02-May-2018

272 views 4 download

Transcript of Volume 6 Tab1 - KJ ELECTRIC SOFTSTARTER.pdf · Volume 6—Solid-State Motor Control...

V6-T1-84 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Type S811, Soft Starters with DIM ContentsDescription Page

Type S611, Solid-State Soft Starters . . . . . . . . . . . V6-T1-39Type S801, Soft Starters. . . . . . . . . . . . . . . . . . . . . V6-T1-56Type S811, Soft Starters with DIM

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V6-T1-86Features and Benefits . . . . . . . . . . . . . . . . . . . V6-T1-89Standards and Certifications . . . . . . . . . . . . . . V6-T1-92Instructional Leaflets . . . . . . . . . . . . . . . . . . . . V6-T1-92Catalog Number Selection . . . . . . . . . . . . . . . . V6-T1-92Product Selection . . . . . . . . . . . . . . . . . . . . . . . V6-T1-93Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . V6-T1-107Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V6-T1-108Technical Data and Specifications . . . . . . . . . . V6-T1-109Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . V6-T1-113Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . V6-T1-114

Type S811, Soft Starters with DIM Product DescriptionEaton’s S811 offers all the popular features of the S801, but adds enhanced functionality with the new DIM (Digital Interface Module), communications, metering, monitoring and diagnostics capabilities.

Eaton’s line of S811 reduced voltage soft starters is very compact, multi-functional, easy to install and easy to set operating parameters. Designed to control the acceleration and deceleration of three-phase motors up to 690V, the line is available from 11–1000A.

The S811 is designed to be a complete package combining the silicon controlled rectifiers (SCRs), bypass contactor and overload in one, very compact unit. The S811 is available as a component for panel mounting, in motor control centers or in enclosed control (NEMA Type 1, 3R, 4, 4X, 7/9 and 12).

Application DescriptionDesigned to control the acceleration and deceleration of three-phase motors, the S811 soft starter uses SCRs to control the voltage to soft start and soft stop the motor. After the motor is started, internal run bypass contactors close, resulting in the motor running directly across-the-line. The built-in solid-state overload protects the motor from overload conditions with sophisticated algorithms that model true motor heating, resulting in better motor protection and fewer nuisance trips. Advanced protective and diagnostic features reduce downtime.

A voltage ramp start or current limit start is available. Kick start is available in either starting mode. The soft stop option allows for a ramp stop time that is longer than the coast to stop time. The pump control option provides a smooth transition for starting and stopping a motor and eliminating the “water-hammer” effect that can damage pipes, valves and pumps.

The S811 offers an impressive array of advanced protective features. Not only are the protective features selectable, but many offer variable settings and adjustable time delays to ride through system discrepancies.

The S811 has an easy to use Digital Interface Module (DIM) that allows the user to configure the device and to read system parameters and monitor system values. The DIM includes an LCD display and keypad to scroll through the various menus. The DIM allows the user to modify control parameters, enable or disable protections, set communication variables, monitor system parameters such as line voltages and currents, and access the fault queue.

The DIM can be removed from the S811 and remote mounted. Kits are available to door mount the DIM, enabling users to safely configure, commission, monitor and troubleshoot the system at the electrical panel without opening the enclosure door. This will help eliminate the possibility of an arc flash incident.

Digital Interface Module (DIM)

ESC

ONLN SS OXFDO1 H STOP

Monitoring

PREV NEXT ENTER

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-85

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Communications

The S811 has built-in communication capabilities through Eaton’s QC (Quick Connect) Port. QCPort™ enables the soft starter to be connected to a variety of networks, including DeviceNet™, EtherNet/Modbus, EtherNet/IP and PROFIBUS. The advantage of QCPort is that multiple control components can be connected to one Eaton D77D gateway.

The gateway concentrates data from the devices into a single node. Configuration is simple—a single press of the gateway’s Auto Configuration button sets the system up for default operation. This automatically configures the I/O assemblies to the QCPort system devices. The data from these devices are then assembled into single input and output messages

Communications Reference

DescriptionPartNumber

DeviceNet network adapter D77D-DNA

EtherNet Modbus network adapter D77D-EMA

EtherNet/IP network adapter D77D-EIP

PROFIBUS network adapter D77D-PNA

Terminator and power tap D77E-QPLR

DIN rail communications backplane, 7-position D77E-BP7

DIN rail communications backplane, 12-position D77E-BP12

85–264 Vac input, 24 Vdc output PSG240E

360–575 Vac input, 24 Vdc output PSG240F

The S811 communication parameters can be configured with the DIM or through the Fieldbus using CH Studio Component Manager. Advanced communication configuration settings provide the system integrator with powerful tools to facilitate system optimization

S811 Connection

Fieldbus

DIM

NetworkAdapter

(Gateway)

Terminatorand

Power Tap

DIN RailCommunications

Backplane

24 VdcPowerSupply

+– 1 0

S811 Soft Starter

V6-T1-86 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Operation

Starting and Stopping ModesThe S811 has a variety of starting and stopping methods to provide superior performance in the most demanding applications. The motor can be started in either voltage ramp start or current limit start mode. Kick start and soft stop are available within both starting modes.

Voltage Ramp StartProvides a voltage ramp to the motor resulting in a constant torque increase. The most commonly used form of soft start, this start mode allows you to set the initial torque value and the duration of the ramp to full voltage conditions. Bypass contactors close after ramp time.

● Adjustable initial torque 0–85% of locked rotor torque

● Adjustable ramp time 0.5–180 seconds (can be extended with factory modification)

Starting Characteristics—Ramp Start

Current Limit StartLimits the maximum current available to the motor during the start phase. This mode of soft starting is used when it becomes necessary to limit the maximum starting current due to long start times or to protect the motor. This start

mode allows you to set the maximum starting current as a percentage of locked rotor current and the duration of the current limit. Bypass contactors close after current limit time.

● Maximum current of 0–85% locked rotor current

● Adjustable ramp time 0.5–180 seconds (can be extended with factory modification)

Starting Characteristics—Current Limit Start

Run (FLA)

100%

Lock

ed R

oto

r To

rqu

e

Time (Seconds)

InitialTorque

Run

Max.Allowed

100%FLA

Cu

rren

t

Time (Seconds)

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-87

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Kick StartSelectable feature in both voltage ramp start and current limit start modes. Provides a current and torque “kick” for 0 to 2.0 seconds. This provides greater initial current to develop additional torque to breakaway a high friction load.

● 0–85% of locked rotor torque

● 0–2.0 seconds duration

Starting Characteristics—Kick Start

Soft StopAllows for a controlled stopping of a load. Used when a stop-time that is greater than the coast-to-stop time is desired. Often used with high friction loads where a sudden stop may cause system or load damage.

● Stop time = 0–60 seconds

Starting Characteristics—Soft Stop

100%

Lock

ed R

oto

r To

rqu

e

Ramp

Time (Seconds)

KickStart

Run (FLA)

Ramp

Time (Seconds)

Run

V6-T1-88 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Edge and Level Sensing Control

Edge SensingEdge sensing requires +24 Vdc power be momentarily applied to Pin 1 (with terminal P at +24 Vdc) to initiate a start under all conditions. After a stop or fault occurs, the +24 Vdc must be removed, then reapplied to pin 1 before another start can occur. This control configuration should be used when restarting of the motor after a fault or stop must be supervised manually or as a part of a control scheme. The cycling of +24 Vdc power to Terminal 1 before starting is required regardless of the position of the auto reset switch on the DIM.

Level Sensing Level sensing will enable a motor to restart after a fault is cleared without cycling +24 Vdc power to Terminal 1 as long as:

● Terminal P is supplied with +24 Vdc (to start from Terminal Block, Input #3 must also be enabled)

● The auto reset switch on the DIM is set to enabled

● All faults have been reset

This control configuration should be used where it is desirable to restart a motor after a fault without additional manual or automatic control. An example of this condition would be on a remote pumping station where it is desirable to automatically restart a pump after a power outage without operator intervention.

Note: If the auto reset feature is used, CAUTION must be exercised to ensure that any restart occurs in a safe manner.

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-89

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Features and Benefits● Communication

capabilities with various protocols

● The DIM (Digital Interface Module) provides an intuitive, easy-to-use human interface with powerful configuration capabilities to maximize system performance

● Door or device mounted DIM enables users to safely configure, commission, monitor and troubleshoot the system at the electrical panel without opening the enclosure door, eliminating the possibility of an arc flash incident

● System operating parameters can be monitored enterprise-wide through a communications network. Increase uptime by providing data for process management and preventive diagnostics

● Run internal bypass mode greatly reduces internal heating created by the greater power dissipation in the SCRs. Bypass contactor directly connects the motor to the line and improves system efficiency by reducing internal power losses

● Internal solid-state overload protection provides accurate current measurement and trip settings. Sophisticated algorithms solve a series of differential equations that model true motor heating and cooling, resulting in superior motor overload protection while minimizing nuisance trips. Advanced selectable protective features safeguard the motor and system against a variety of system faults

● Internal run bypass contactors and overload protection eliminate the need for additional devices, reducing enclosure sizes, minimizing installation and wiring time, and reducing overall assembly size and cost

● Wide range of overload FLA settings (31–100% of rated current) and a selectable trip class (5–30) offers users the flexibility to fine tune the starter to match specific application requirements

● Variable ramp times and torque control settings provide unlimited starting configurations, allowing for maximum application flexibility

● Kick-start feature enables soft starting of high friction loads

● Soft stop control for applications where an abrupt stop of the load is not acceptable

● Pump control option with sophisticated pump algorithms on both starting and stopping that minimize the pressure surges that cause water hammer. The pump control option will maximize the life of the pump and piping systems while minimizing the downtime caused by system failure

● Six SCRs control all three motor phases, providing smooth acceleration and deceleration performance

● Soft acceleration and deceleration reduces wear on belts, gears, chains, clutches, shafts and bearings

● Reduce the peak inrush current’s stress on the power system

● Manage peak starting torque to diminish mechanical system wear and damage

● 24 Vdc control voltage enhances personnel and equipment safety

● Removable, lockable control terminal block reduces maintenance costs. Also provides the opportunity for OEMs to reduce assembly and test costs by utilizing pre-assembled wire harnesses

Protective FeaturesAll protective features can be configured, enabled or disabled with the DIM or through the communications network.

Motor OverloadThe S811 includes electronic overload protection as standard. The overload meets applicable requirements for a motor overload protective device. The overload protects the motor from over heat conditions with the use of sophisticated algorithms that model true motor heating, resulting in superior motor protection and fewer nuisance trips.

The S811 calculates a thermal memory value based on the heat energy introduced into the motor during the start process. A 100% value represents the maximum safe internal temperature of the motor.

When the thermal memory value reaches 100%, an overload trip will occur removing power to the motor. Upon trip, the S811 stores the calculated motor heating value and will not allow a motor re-start until the motor has a thermal memory value of less than 100%. This feature ensures the motor will not be damaged by repeated overload trip, reset and re-start cycles.

The thermal memory value can be monitored through the DIM or the communications network. The thermal memory value can be of great use in determining an impending overload trip condition.Alarms can be implemented in the

process monitoring system warning of an impending trip before a trip occurs halting the process. Costly system downtime can be avoided.

The trip current is adjusted to match the specific application requirements by entering the motor nameplate full load current rating and trip class. The FLA parameter is adjustable from 32% to 100% of the unit’s rated current. The overload trip class is adjustable from class 5 through class 30. The overload is ambient temperature compensated—meaning its trip characteristics will not vary with changes in ambient temperature. The overload protection can be enabled, disabled, or disabled on start.

Short CircuitThe use of a short-circuit protective device in coordination with the S811 is required in branch motor circuits by most electrical codes. Short-circuit coordination ratings with both fuses and Eaton molded case circuit breakers are available providing customers with design flexibility. The S811 has short-circuit coordination ratings as an open component, an enclosed starter, and in a motor control center.

V6-T1-90 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

JamExcessive current and torque up to locked rotor levels can occur in a jam condition. The condition can result in stress and damage to the motor, load, mechanical system, and the electrical distribution system. Jam protection prevents the stress and damage from a jam during normal run. After the motor is in bypass, a current greater than 300% FLA setting will cause the starter to trip on a jam fault.

StallExcessive current and torque up to locked rotor levels can occur in a stall condition. The condition can lead to an overload trip and result in stress and damage to the motor, load, mechanical system, and the electrical distribution system. Stall protection prevents stress and damage to a motor that has not come up to speed during the soft start time. The S811 will trip to protect the system in the event that the motor did not get to the rated speed in the defined soft start period. A current greater than 200% FLA at the end of the soft start period will cause the starter to trip on a stall fault.

Pole Over TemperatureHigh ambient temperatures, extended ramp times and high duty cycle conditions may cause the S811 power pole conductors to reach a temperature that exceeds their thermal rating. The S811 is equipped with sensors that monitor the temperature of the power poles. Over temperature protection occurs if the power pole’s thermal capacity is exceeded. The soft starter will trip in over temperature conditions, preventing device failure.

Each power pole temperature value can be monitored through the DIM or the communications network. This feature can be of use in determining an impending over temperature trip condition.

When using a communications network, alarms can be implemented in the process monitoring system warning of an impending trip before the trip occurs, halting the process.

Phase LossLoss of a phase can cause a significant increase in the current drawn in the remaining two phases. Phase loss can lead to motor damage before an eventual overload trip occurs. Phase loss is typically an indication of a failure in the electrical distribution system. The S811 will detect a phase loss and trip if any phase current drops below a preset value. The phase loss trip level is adjustable from 0% to 100% of the average of the other two phase levels with an adjustable trip delay of 0.1 to 60 seconds.

Phase ImbalancePhase current or voltage imbalance can cause a significant increase in the current drawn in the remaining two phases. Phase imbalance can lead to motor damage before an eventual overload trip. Phase imbalance is typically an indication of a failure in the electrical distribution system or the motor. The S811 will detect both current and voltage phase imbalances and trip if any phase becomes imbalanced as compared to the average of the other two phases.

The phase current imbalance trip level is adjustable from 0% to 100% of the average of the current in the other two phases with an adjustable trip delay of 0.1 to 60 seconds.

The phase voltage imbalance trip level is adjustable from 0% to 100% of the average of the voltage in the other two phases with an adjustable trip delay of 0.1 to 60 seconds.

Reset ModeThe S811 can be set up for automatic or manual reset on trip. The manual reset mode requires the operator to physically press the RESET button located on the Soft Starter. The trip can be manually reset through the DIM or through the communications network. The trip can also be electrically reset by energizing a 24 Vdc input on the control terminal block.

The automatic reset mode allows the Soft Starter to be automatically reset as soon as the trip condition is no longer present. With the automatic reset mode, after the fault is no longer present, the motor will be restarted as soon as a valid start signal is present.

Phase ReversalThe S811 can determine if the proper line phase sequence is present by default. The device will trip if the line phase sequence is something other than A-B-C. The S811 can be configured to operate under reversed phase conditions (A-C-B).

Shorted SCR DetectionThe S811 monitors the operation of the power poles and will trip under a shorted SCR condition.

Open SCR DetectionThe S811 monitors the operation of the power poles and will trip under an open SCR condition.

Low CurrentLow current conditions can be a result of a loss of load or a failure in the mechanical system. The S811 has low current protection that will trip if the average rms current falls below a preset value. The low current protection can be programmed as a percent of motor FLA from 0% to 100%.

Low VoltageLow voltage conditions can result from disturbances in the electrical power distribution system. Low voltage conditions can cause a malfunction and damage to electrical equipment. The S811 has low voltage protection that will trip if the average rms voltage falls below a preset value. The low voltage protection can be programmed as a percent of nominal voltage from 1% to 99% with a trip delay of 0.1 to 60 seconds to accommodate short temporary voltage drops during the start process.

High VoltageHigh voltage conditions can result from disturbances in the electrical power distribution system. High voltage conditions can cause malfunctions or failures of electrical equipment. The S811 has high voltage protection that will trip if the average rms voltage is greater than a preset value. The high voltage protection can be programmed as a percent of nominal voltage from 101% to 120% with a trip delay of 0.1 to 60 seconds.

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-91

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Monitoring CapabilitiesThe S811 has an impressive array of system monitoring capabilities that allows users to access real time process and diagnostic data. This data can be viewed at the device with the DIM or through a communications network. Data over a communications network can provide valuable insight into the condition of the equipment and processes. Maintenance and

production personnel can monitor critical operational and maintenance data from a central control station that can be located far away from the production facility. Process data can be monitored to determine system anomalies that may indicate a need for preventive maintenance or an impeding failure. Adjustments made through the communications

network can reduce costs by minimizing the time traveling to the location where the motor controls are located. When faults do occur, real time fault data can assist maintenance in trouble-shooting and planning repair resources. Remote reset signals can be given to tripped devices without the need for manual intervention by maintenance personnel.

Average Line CurrentProvides the average of the three-phase rms line currents in amps, accurate to within 2%. Current data can be used to indicate a need for maintenance. Increased currents in a fixed load application can indicate a reduction in system efficiencies and performance, signifying system maintenance is due.

Average Pole CurrentProvides the average of the three-phase rms pole currents in amps, accurate to within 2%. The pole current is the current through the Soft Starter. The line and pole current will be identical in inline applications, and will differ in inside-the-delta applications.

Average Line Current as a % FLAProvides the average rms line current as a percentage of the S811 FLA setting.

Three-Phase Line CurrentsProvides three rms phase line currents in amps, accurate to within 2%. Imbalances or changes in the relative phase current to one another can indicate anomalies in the motor or electrical distribution system.

Three-Phase Pole CurrentsProvides three rms phase pole currents in amps, accurate to within 2%. The pole current is the current through the soft starter. The line and pole current will be identical in in-line applications, and will differ in inside-the-delta applications.

Three-Phase Line VoltagesProvides the individual rms three-phase line voltages. Imbalances or changes in |the relative phase voltage to one another can indicate anomalies in the motor or electrical distribution system. Voltage can be used to monitor electrical distribution system performance. Warnings, alarms and system actions to low or high voltage conditions can be implemented.

Percent Thermal MemoryProvides the real time calculated thermal memory value. The S811 calculates thermal memory value. A 100% value represents the maximum safe internal temperature of the motor. When the thermal memory value reaches 100%, an overload trip will occur, removing power to the motor.

The thermal memory value can be of great use in determining an impending overload trip condition. When using a communications network, alarms can be implemented in the process monitoring system warning of an impending trip before the trip occurs, halting the process. Costly system downtime can be avoided.

DC Control VoltageMonitors level of the 24 Vdc control voltage. Fluctuations in control voltage can cause component malfunction and failure. System control voltage data can be used to implement warnings, alarms and system actions to low or high voltage conditions.

Pole TemperatureIncreases in power pole temperature are caused by increases in ambient temperature, start/stop times and start duty cycles. Changes in pole temperatures represent a change in system operating conditions. Identifying unexpected operating conditions or changes can prompt maintenance and aid in process evaluation activities.

PCB Device TemperatureAn increase in printed circuit board (device) temperature is a strong indication of an increase in ambient temperature. High ambient temperature operation can be identified with the device temperature data. Device temperature increases can be due to undersized enclosures, failure of cooling fans or blocked venting. High operating temperatures will reduce the life of all electrical equipment in the enclosure.

Start CountStart count data can be used to monitor system output, schedule preventative maintenance, identify system anomalies and identify changes in system operation.

V6-T1-92 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Diagnostics

Fault QueueCurrent fault and a fault queue containing the last nine system faults can be read through the DIM or communications network. Fault identification can minimize troubleshooting time and cost, and prevent arc flash incidents. The fault queue can be remotely accessed through a communications network to assist in planning maintenance resources. Thirty different faults can be identified by the S811.

Control StatusThe S811 provides data that represents system conditions that can be read through the DIM or the communications network. This data identifies the status of the system and the control commands the system is requesting of the S811. This can be used for advanced troubleshooting and system integration activities.

Breaker StatusThe S811 has provisions to read and display circuit breaker status. Eaton communicating cover control or other communicating protective device is required to take advantage of this feature.

Standards and Certifications ● IEC 60947-4-2● EN 60947-4-2● UL listed (NMFT-E202571)

Frame N37 to V85● UL recognized (NMFT2)–

Frame V10

● CE marked● CSA certified (3211 06)● CSA elevator (2411 01)

Instructional Leaflets● User manual MN03902002E● Inside-the-Delta user manual MN03902009E● Outline drawings:

● 65 mm, N-Frame: 10-8574● 110 mm, R-Frame: 10-8575● 200 mm, T-Frame: 10-8576● 200 mm, U-Frame: 10-8857● 290 mm, V-Frame: 10-8577

Catalog Number Selection

S811 Open Soft Starters 1

Notes1 All units require a 24 Vdc power supply found on catalog Page V6-T1-107, or equivalent.2 T-, U- and V-Frames require lug kits found on Page V6-T1-107.3 U-Frame 500A unit does not have IEC certification.4 Not available in U-Frame.

S 811 T 30 N 3 S

Frame Size 2

N = 65 mmR = 110 mmT = 200 mmU = 200 mmV = 290 mm

Ampere Rating37 = 37A66 = 66A10 = 105A13 = 135A18 = 180A

24 = 240A30 = 304A36 = 360A42 = 420A

50 = 500A 3

65 = 650A72 = 720A85 = 850A10 = 1000A

S = Standard soft starter (configurable for edge or level control)

D = Inside-the-deltaL = Extended ramp startW = Without DIM

Number of Poles3 = Three-pole device

OptionsN = No optionsP = Pump controlV = 690V option (Frame

T18 through V85) 4

S = Soft Starter

811 = Non-combination soft starter

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-93

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Product Selection

Standard Duty Ratings

Motor applications and customer needs come in many different varieties. With the standard and severe duty rating tables, we have attempted to provide

guidelines on what the soft starter is capable of. If the application falls under these categories, you can use these charts. For other applications, or when a

question arises, consult with your local Eaton representative or call our Technical Resource Center.

Standard Duty—15 Second Ramp, 4 Starts per Hour, 300% Current Limit at 40°C

Notes1 690V is available only from T18 thru V85. Not available on U-Frames.2 500A rating does not have IEC certification.3 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Starting MethodRamp Current % of FLA

Ramp Time Seconds Starts per Hour

Ambient Temperature

Soft start 300% 30 sec. 3 50°C

Full voltage 500% 10 sec. 3 50°C

Wye-delta 350% 20 sec. 3 50°C

80% RVAT 480% 20 sec. 2 50°C

65% RVAT 390% 20 sec. 3 50°C

50% RVAT 300% 20 sec. 4 50°C

Max.Current

Three-Phase Motors

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575–690V 1

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

37 10 18.5 18.5 10 10 10 10 25 20 30 30 S811N37N3S

66 18.5 30 37 20 15 20 20 50 40 60 50 S811N66N3S

Frame Size R

105 30 55 59 30 25 40 30 75 60 100 75 S811R10N3S

135 40 63 80 40 30 50 40 100 75 125 100 S811R13N3S

Frame Size T

180 51 90 110 60 50 60 60 150 125 150 150 S811T18N3S

240 75 110 147 75 60 75 75 200 150 200 200 S811T24N3S

304 90 160 185 100 75 100 100 250 200 300 250 S811T30N3S

Frame Size U

360 110 185 220 125 100 150 125 300 250 350 300 S811U36N3S

420 129 220 257 150 125 175 150 350 300 450 350 S811U42N3S

500 150 257 300 150 150 200 150 400 350 500 450 S811U50N3S 2

Frame Size V

360 110 185 220 125 100 150 125 300 250 350 300 S811V36N3S

420 129 220 257 150 125 175 150 350 300 450 350 S811V42N3S

500 150 257 300 150 150 200 150 400 350 500 450 S811V50N3S

650 200 355 425 250 200 250 200 500 450 600 500 S811V65N3S

720 220 400 450 — — 300 250 600 500 700 600 S811V72N3S

850 257 475 500 — — 350 300 700 600 900 700 S811V85N3S

1000 277 525 550 — — 400 350 800 700 900 800 S811V10N3S 3

For Pump Option, replace character 8 with “P” and also, see Page V6-T1-108.

S811

V6-T1-94 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Standard Duty—25 Second Ramp, 4 Starts per Hour, 300% Current Limit at 40°C

Notes1 690V is available only from T18 thru V85. Not available on U-Frames.2 500A rating does not have IEC certification.3 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.Current

Three-Phase Motors

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575–690V 1

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

34 9 15 18.5 10 7-1/2 10 10 25 20 30 25 S811N37N3S

63 15 30 33 20 15 20 20 40 40 60 50 S811N66N3S

Frame Size R

96 25 45 55 30 25 30 30 75 60 75 75 S811R10N3S

120 33 63 63 40 30 40 40 75 75 100 100 S811R13N3S

Frame Size T

150 45 80 90 50 40 50 50 100 100 150 125 S811T18N3S

215 63 110 132 60 60 75 60 150 150 200 150 S811T24N3S

278 80 147 160 75 75 100 75 200 200 250 250 S811T30N3S

Frame Size U

320 90 160 185 100 75 125 100 250 200 300 250 S811U36N3S

380 110 200 220 125 100 150 125 300 250 350 300 S811U42N3S

460 140 250 280 150 125 150 150 350 300 450 400 S811U50N3S 2

Frame Size V

320 90 160 185 100 75 125 100 250 200 300 250 S811V36N3S

380 110 200 220 125 100 150 125 300 250 350 300 S811V42N3S

460 140 250 280 150 125 150 150 350 300 450 400 S811V50N3S

610 185 315 375 250 150 200 200 500 450 600 500 S811V65N3S

680 200 375 445 — 200 250 200 600 500 700 600 S811V72N3S

810 250 450 500 — — 300 300 700 600 900 700 S811V85N3S

890 290 510 560 — — 400 350 700 600 900 700 S811V10N3S 3

For Pump Option, replace character 8 with “P” and also, see Page V6-T1-108.

S811

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-95

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Standard Duty—15 Second Ramp, 4 Starts per Hour, 300% Current Limit at 50°C

Notes1 690V is available only from T18 thru V85. Not available on U-Frames.2 500A rating does not have IEC certification.3 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.Current

Three-Phase Motors

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575–690V 1

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

34 9 15 18.5 10 7-1/2 10 10 25 20 30 25 S811N37N3S

63 15 30 33 20 15 20 20 40 40 60 50 S811N66N3S

Frame Size R

96 25 45 55 30 25 30 30 75 60 75 75 S811R10N3S

120 33 63 63 40 30 40 40 75 75 100 100 S811R13N3S

Frame Size T

150 45 80 90 50 40 50 50 100 100 150 125 S811T18N3S

215 63 110 132 60 60 75 60 150 150 200 150 S811T24N3S

278 80 147 160 75 75 100 75 200 200 250 250 S811T30N3S

Frame Size U

320 90 160 185 100 75 125 100 250 200 300 250 S811U36N3S

460 110 200 220 125 100 150 125 300 250 350 300 S811U42N3S

460 140 250 280 150 125 150 150 350 300 450 400 S811U50N3S 2

Frame Size V

320 90 160 185 100 75 125 100 250 200 300 250 S811V36N3S

380 110 200 220 125 100 150 125 300 250 350 300 S811V42N3S

460 140 250 280 150 125 150 150 350 300 450 400 S811V50N3S

610 185 315 375 250 150 200 200 500 450 600 500 S811V65N3S

680 200 375 445 — 200 250 200 600 500 700 600 S811V72N3S

830 257 450 500 — — 300 300 700 600 900 700 S811V85N3S

960 302 510 540 — — 350 300 800 700 900 800 S811V10N3S 3

For Pump Option, replace character 8 with “P” and also, see Page V6-T1-108.

S811

V6-T1-96 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Standard Duty—50 Second Ramp, 2 Starts per Hour, 300% Current Limit at 50°C

Notes1 690V is available only from T18 thru V85. Not available on U-Frames.2 500A rating does not have IEC certification.3 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.Current

Three-Phase Motors

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575–690V 1

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

21 5.5 10 11 5 5 5 5 15 10 15 15 S811N37N3S

42 11 18.5 22 10 10 15 10 30 25 40 30 S811N66N3S

Frame Size R

60 15 30 33 15 15 20 15 40 40 50 50 S811R10N3S

80 22 40 45 25 20 30 25 60 50 75 60 S811R13N3S

Frame Size T

115 33 59 63 30 30 40 30 75 75 100 100 S811T18N3S

150 45 80 90 50 40 50 50 100 100 150 125 S811T24N3S

192 55 100 110 60 50 60 60 150 125 200 150 S811T30N3S

Frame Size U

280 80 150 160 75 75 100 75 200 200 250 250 S811U36N3S

340 110 180 200 100 100 125 100 250 200 350 300 S811U42N3S

380 110 200 220 125 100 150 125 300 250 350 300 S811U50N3S 2

Frame Size V

280 80 150 160 75 75 100 75 200 200 250 250 S811V36N3S

340 110 180 200 100 100 125 100 250 200 350 300 S811V42N3S

380 110 200 220 125 100 150 125 300 250 350 300 S811V50N3S

420 129 220 257 150 125 150 150 350 300 450 350 S811V65N3S

480 147 257 295 150 150 200 150 400 350 500 450 S811V72N3S

590 180 315 375 200 150 200 200 500 400 600 500 S811V85N3S

650 205 370 415 250 200 250 200 500 450 600 500 S811V10N3S 3

For Pump Option, replace character 8 with “P” and also, see Page V6-T1-108.

S811

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-97

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Standard Duty—15 Second Ramp, 4 Starts per Hour, 450% Current Limit at 40°C

Notes1 690V is available only from T18 thru V85. Not available on U-Frames.2 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.Current

Three-Phase Motors

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575–690V 1

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

29 7.5 12.5 15 7-1/2 7-1/2 10 7-1/2 20 15 25 20 S811N37N3S

49 12.5 22 25 15 10 15 15 30 30 40 40 S811N66N3S

Frame Size R

73 18.5 37 40 20 20 25 20 50 40 60 60 S811R10N3S

94 25 45 55 30 25 30 30 60 60 75 75 S811R13N3S

Frame Size T

155 45 80 90 50 40 60 50 100 100 150 125 S811T18N3S

219 63 110 132 60 60 75 60 150 150 200 150 S811T24N3S

280 80 150 160 75 75 100 75 200 200 250 250 S811T30N3S

Frame Size U

345 100 185 200 100 100 125 100 250 200 350 300 S811U36N3S

405 110 200 250 125 100 150 125 300 250 400 350 S811U42N3S

Frame Size V

345 100 185 200 100 100 125 100 250 200 350 300 S811V36N3S

405 110 200 250 125 100 150 125 300 250 400 350 S811V42N3S

465 140 250 280 150 125 150 150 350 300 450 400 S811V50N3S

530 160 280 335 150 150 200 150 450 350 500 450 S811V65N3S

590 180 315 375 200 150 — 200 500 400 600 500 S811V72N3S

651 200 355 425 — — — — 600 450 700 600 S811V85N3S

754 220 400 465 — — — — 600 500 800 700 S811V10N3S 2

For Pump Option, replace character 8 with “P” and also, see Page V6-T1-108.

S811

V6-T1-98 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Standard Duty—30 Second Ramp, 4 Starts per Hour, 450% Current Limit at 40°C

Notes1 690V is available only from T18 thru V85. Not available on U-Frames.2 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.Current

Three-Phase Motors

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575–690V 1

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

21 5.5 10 12.5 5 5 5 5 15 10 15 15 S811N37N3S

40 11 18.5 22 10 10 10 10 30 25 30 30 S811N66N3S

Frame Size R

55 15 25 30 15 15 20 15 40 30 50 40 S811R10N3S

75 22 37 45 20 20 25 20 50 50 60 60 S811R13N3S

Frame Size T

151 45 80 90 50 40 50 50 100 100 150 125 S811T18N3S

215 63 110 132 60 60 75 60 150 150 200 150 S811T24N3S

264 80 140 160 75 75 100 75 200 150 250 200 S811T30N3S

Frame Size U

300 90 160 185 100 75 100 100 200 200 300 250 S811U36N3S

340 100 180 200 100 100 125 100 250 200 350 300 S811U42N3S

380 110 200 220 125 100 150 125 300 250 350 300 S811U50N3S

Frame Size V

300 90 160 185 100 75 100 100 200 200 300 250 S811V36N3S

340 100 180 200 100 100 125 100 250 200 350 300 S811V42N3S

380 110 200 220 125 100 150 125 300 250 350 300 S811V50N3S

420 129 220 257 150 125 150 150 350 300 450 350 S811V65N3S

460 140 250 280 150 125 150 150 350 300 450 400 S811V72N3S

500 150 257 300 150 150 200 150 400 350 500 450 S811V85N3S

560 160 277 325 200 150 250 200 500 400 600 500 S811V10N3S 2

For Pump Option, replace character 8 with “P” and also, see Page V6-T1-108.

S811

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-99

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Severe Duty

Severe Duty Ratings

Severe duty ratings are defined as any combination of parameters that exceed the standard duty ratings where

the ramp time is over 30 seconds, the number of starts per hour exceeds 4, or the current limit set is over

300%. Example: 35-second ramp, 5 starts per hour, 350% current limit at 40°C ambient.

Severe Duty—>30 Second Ramp, >4 Starts per Hour or >300% Current Limit

Notes1 690V is available only from T18 thru V85. Not available on U-Frames.2 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Starting MethodRamp Current % of FLA

Ramp Time Seconds Starts per Hour

Ambient Temperature

Soft start 450% 30 sec. 4 50°C

Full voltage 500% 10 sec. 10 50°C

Wye-delta 350% 65 sec. 3 50°C

80% RVAT 480% 25 sec. 4 50°C

65% RVAT 390% 40 sec. 4 50°C

50% RVAT 300% 60 sec. 4 50°C

Max.Current

Three-Phase Motors

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575–690V 1

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

22 5.5 10 11 5 5 7-1/2 5 15 10 20 15 S811N37N3S

42 11 18.5 22 10 10 15 10 30 25 40 30 S811N66N3S

Frame Size R

65 15 30 33 15 15 20 15 50 40 50 50 S811R10N3S

80 22 40 45 25 20 30 25 60 50 75 60 S811R13N3S

Frame Size T

115 33 59 63 30 30 40 30 75 75 100 100 S811T18N3S

150 45 80 90 50 40 50 50 100 100 150 125 S811T24N3S

192 55 100 110 60 50 75 60 150 125 200 150 S811T30N3S

Frame Size U

240 75 110 147 75 60 75 75 200 150 200 200 S811U36N3S

305 90 160 185 100 75 100 100 250 200 300 250 S811U42N3S

Frame Size V

240 75 110 147 75 60 75 75 200 150 200 200 S811V36N3S

305 90 160 185 100 75 100 100 250 200 300 250 S811V42N3S

365 110 185 220 125 100 150 125 300 250 350 300 S811V50N3S

420 129 220 257 150 125 150 150 350 300 450 350 S811V65N3S

480 147 257 295 150 150 200 150 400 350 500 450 S811V72N3S

525 160 280 335 150 150 200 150 450 350 500 450 S811V85N3S

575 172 303 370 200 150 250 200 500 450 600 500 S811V10N3S 2

S811

V6-T1-100 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Inside-the-Delta Standard Duty Ratings

Inside-the-Delta Standard Duty—15 Second Ramp, 4 Starts per Hour, 300% Current Limit at 40°C Ambient

Notes1 15 sec. start, 300% inrush, 40°C, 1 start every 15 minutes. If these start parameters are exceeded, please refer to 290 mm V-Frame, 865A inside-the-delta starter.2 U-Frame 500A unit does not have IEC certification. 3 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.ContinuousMotor LineCurrent

Three-Phase Motor

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V

200V 230V 460V 575V

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

65 10 18.5 18.5 15 15 15 15 40 30 50 50 S811N37N3D

114 18.5 30 37 30 25 30 30 75 60 100 75 S811N66N3D

Frame Size R

182 30 55 59 50 40 60 50 125 100 150 125 S811R10N3D

234 40 63 80 60 50 75 60 150 125 200 150 S811R13N3D

Frame Size T

311 51 90 110 100 75 100 100 250 200 250 250 S811T18N3D

415 75 110 147 125 100 125 125 300 250 300 300 S811T24N3D

526 90 160 185 150 125 150 150 400 300 400 400 S811T30N3D

Frame Size U

623 110 185 220 200 150 250 200 450 400 550 450 S811U36N3D

727 129 220 257 250 200 300 250 550 450 700 550 S811U42N3D

865 150 257 300 250 250 300 250 600 550 750 700 S811U50N3D 12

Frame Size V

623 110 185 220 200 150 250 200 450 400 550 450 S811V36N3D

727 129 220 257 250 200 300 250 550 450 700 550 S811V42N3D

865 150 257 300 250 250 300 250 600 550 750 700 S811V50N3D

1125 200 355 425 400 300 400 300 750 700 900 750 S811V65N3D

1246 — — — — — — — — — — — S811V72N3D

1471 — — — — — — — — — — — S811V85N3D

— — — — — — — — — — — — S811V10N3D 3

S811

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-101

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Inside-the-Delta Standard Duty—25 Second Ramp, 4 Starts per Hour, 300% Current Limit at 40°C Ambient

Notes1 15 sec. start, 300% inrush, 40°C, 1 start every 15 minutes. If these start parameters are exceeded, please refer to 290 mm V-Frame, 796A inside-the-delta starter.2 U-Frame 500A unit does not have IEC certification. 3 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.ContinuousMotor LineCurrent

Three-Phase Motor

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575V1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

58 9 15 18.5 15 10 15 15 40 30 50 40 S811N37N3D

108 15 30 33 30 25 30 30 60 60 100 75 S811N66N3D

Frame Size R

164 25 45 55 50 40 50 50 125 100 125 125 S811R10N3D

206 33 63 63 60 50 60 50 125 125 150 150 S811R13N3D

Frame Size T

257 45 80 90 75 60 75 60 150 150 250 200 S811T18N3D

365 63 110 132 100 100 125 100 250 250 300 250 S811T24N3D

477 80 147 160 125 125 150 125 300 300 400 400 S811T30N3D

Frame Size U

554 90 160 185 150 125 200 150 400 300 450 400 S811U36N3D

646 110 200 220 200 150 250 200 500 400 550 450 S811U42N3D

796 140 250 280 250 200 250 250 550 500 700 600 S811U50N3D 12

Frame Size V

554 90 160 185 150 125 200 150 400 300 450 400 S811V36N3D

646 110 200 220 200 150 250 200 500 400 550 450 S811V42N3D

796 140 250 280 250 200 250 250 550 500 700 600 S811V50N3D

1055 185 315 375 400 250 300 300 800 700 900 750 S811V65N3D

1176 200 375 445 — 300 400 300 900 800 900 900 S811V72N3D

1358 — — — — — — — — — — — S811V85N3D

— — — — — — — — — — — — S811V10N3D 3

S811

V6-T1-102 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Inside-the-Delta Standard Duty—15 Second Ramp, 4 Starts per Hour, 300% Current Limit at 50°C Ambient

Notes1 U-Frame 500A unit does not have IEC certification. 2 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.ContinuousMotor LineCurrent

Three-Phase Motor

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V200V 230V 460V 575V1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

58 9 15 18.5 15 10 15 15 40 30 50 40 S811N37N3D

108 15 30 33 30 25 30 30 60 60 100 75 S811N66N3D

Frame Size R

164 25 45 55 50 40 50 50 125 100 125 125 S811R10N3D

206 33 63 63 60 50 60 60 125 125 150 150 S811R13N3D

Frame Size T

257 45 80 90 75 60 75 75 150 150 250 200 S811T18N3D

365 63 110 132 100 100 125 100 250 250 300 250 S811T24N3D

477 80 147 160 125 125 150 125 300 300 400 400 S811T30N3D

Frame Size U

554 90 160 185 150 125 200 150 400 300 450 400 S811U36N3D

646 110 200 220 200 150 250 200 450 400 550 450 S811U42N3D

796 140 250 280 250 200 250 250 550 450 700 600 S811U50N3D 1

Frame Size V

554 90 160 185 150 125 200 150 400 300 450 400 S811V36N3D

646 110 200 220 200 150 250 200 450 400 550 450 S811V42N3D

796 140 250 280 250 200 250 250 550 450 700 600 S811V50N3D

1055 185 315 375 400 250 300 300 750 700 900 750 S811V65N3D

1176 200 375 445 — — — — — — — — S811V72N3D

1358 257 450 500 — — — — — — — — S811V85N3D

— — — — — — — — — — — — S811V10N3D 2

S811

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-103

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Inside-the-Delta Standard Duty—50 Second Ramp, 2 Starts per Hour, 300% Current Limit at 50°C Ambient

Notes1 U-Frame 500A unit does not have IEC certification. 2 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.ContinuousMotor LineCurrent

Three-Phase Motor

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V

200V 230V 460V 575V

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

36 5.5 10 11 7-1/2 7-1/2 7-1/2 7-1/2 25 15 25 25 S811N37N3D

73 11 18.5 22 15 15 25 15 50 40 60 50 S811N66N3D

Frame Size R

103 15 30 33 25 25 30 25 60 60 75 75 S811R10N3D

138 22 40 45 40 30 50 40 100 75 125 100 S811R13N3D

Frame Size T

199 33 59 63 50 50 60 50 125 125 150 150 S811T18N3D

257 45 80 90 75 60 75 75 150 150 250 200 S811T24N3D

324 55 100 110 100 75 100 100 250 200 300 250 S811T30N3D

Frame Size U

485 80 150 160 125 125 150 125 300 300 400 400 S811U36N3D

580 100 180 200 150 150 200 150 400 300 550 450 S811U42N3D

646 110 200 220 200 150 250 200 450 400 550 450 S811U50N3D 1

Frame Size V

485 80 150 160 125 125 150 125 300 300 400 400 S811V36N3D

580 100 180 200 150 150 200 150 400 300 550 450 S811V42N3D

646 110 200 220 200 150 250 200 450 400 550 450 S811V50N3D

727 129 220 257 250 200 250 250 550 500 700 550 S811V65N3D

816 147 257 295 250 250 300 250 600 550 750 700 S811V72N3D

1021 180 315 375 300 250 300 300 750 600 900 750 S811V85N3D

— — — — — — — — — — — — S811V10N3D 2

S811

V6-T1-104 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Inside-the-Delta Standard Duty—15 Second Ramp, 4 Starts per Hour, 450% Current Limit at 40°C Ambient

Note1 U-Frame 500A unit does not have IEC certification.

Max.ContinuousMotor LineCurrent

Three-Phase Motor

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V

200V 230V 460V 575V

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

47 7.5 12.5 15 10 10 15 10 30 25 40 30 S811N37N3D

83 12.5 22 25 25 15 25 25 50 50 60 60 S811N66N3D

Frame Size R

126 18.5 37 40 30 30 40 30 75 60 100 100 S811R10N3D

162 25 45 55 50 40 50 50 100 100 125 125 S811R13N3D

Frame Size T

266 45 80 90 75 60 100 75 150 150 250 200 S811T18N3D

379 63 110 132 100 100 125 100 250 250 300 250 S811T24N3D

485 80 150 160 125 125 150 125 300 300 400 400 S811T30N3D

Frame Size U

580 100 185 200 150 150 200 150 400 300 550 450 S811U36N3D

695 110 200 250 200 150 250 200 450 400 600 550 S811U42N3D

798 140 250 280 250 200 250 250 550 450 700 600 S811U50N3D 1

Frame Size V

580 100 185 200 150 150 200 150 400 300 550 450 S811V36N3D

695 110 200 250 200 150 250 200 450 400 600 550 S811V42N3D

798 140 250 280 250 200 250 250 550 450 700 600 S811V50N3D

908 160 280 335 250 250 300 250 700 550 750 700 S811V65N3D

1021 — — — — — — — — — — — S811V72N3D

1125 — — — — — — — — — — — S811V85N3D

S811

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-105

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Inside-the-Delta Standard Duty—30 Second Ramp, 4 Starts per Hour, 450% Current Limit at 40°C Ambient

Note1 U-Frame 500A unit does not have IEC certification.

Max.ContinuousMotor LineCurrent

Three-Phase Motor

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V

200V 230V 460V 575V

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

36 5.5 10 12.5 7-1/2 7-1/2 7-1/2 7-1/2 25 15 25 25 S811N37N3D

69 11 18.5 22 15 15 15 15 50 40 50 50 S811N66N3D

Frame Size R

96 15 25 30 25 25 30 25 60 50 75 60 S811R10N3D

130 22 37 45 30 30 40 30 75 75 100 100 S811R13N3D

Frame Size T

257 45 80 90 75 60 75 75 150 150 250 200 S811T18N3D

365 63 110 132 100 100 125 100 250 250 300 250 S811T24N3D

448 80 140 160 125 125 150 125 300 250 400 300 S811T30N3D

Frame Size U

503 90 160 185 150 125 150 150 300 300 450 400 S811U36N3D

580 100 180 200 150 150 200 150 400 300 550 450 S811U42N3D

646 110 200 220 200 150 250 200 450 400 550 450 S811U50N3D 1

Frame Size V

503 90 160 185 150 125 150 150 300 300 450 400 S811V36N3D

580 100 180 200 150 150 200 150 400 300 550 450 S811V42N3D

646 110 200 220 200 150 250 200 450 400 550 450 S811V50N3D

727 129 220 257 250 200 250 250 550 450 700 550 S811V65N3D

796 — — — — — — — — — — — S811V72N3D

865 — — — — — — — — — — — S811V85N3D

S811

V6-T1-106 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Inside-the-Delta Severe Duty RatingsSevere duty ratings are defined as any combination of parameters that exceed the standard duty ratings where the ramp time is over 30 seconds, the number of starts per hour exceeds 4, or the current limit set is over 300%.

Example: 35-second ramp, 5 starts per hour 350% current limit at 40°C ambient.

Inside-the-Delta Severe Duty

Notes1 U-Frame 500A unit does not have IEC certification. 2 For more information on optimum performance of the 1000A Frame Size V S811, see Appendix E of MN03902002E.

Max.ContinuousMotor LineCurrent

Three-Phase Motor

CatalogNumber

kW Rating (50 Hz) hp Rating (60 Hz)

230V 380–400V 440V

200V 230V 460V 575V

1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF 1.0SF 1.15SF

Frame Size N

39 5.5 10 11 7-1/2 7-1/2 10 7-1/2 25 15 30 25 S811N37N3D

73 11 18.5 22 15 15 25 15 50 40 60 50 S811N66N3D

Frame Size R

111 15 30 33 25 25 30 25 75 60 75 75 S811R10N3D

138 22 40 45 40 30 50 40 100 75 120 100 S811R13N3D

Frame Size T

199 33 59 63 50 50 60 50 125 125 150 150 S811T18N3D

257 45 80 90 75 60 75 75 150 150 250 200 S811T24N3D

324 55 100 110 100 75 100 100 250 200 300 250 S811T30N3D

Frame Size U

415 75 110 147 125 100 125 125 300 250 300 300 S811U36N3D

526 90 160 185 150 120 150 150 400 300 450 400 S811U42N3D

623 110 185 220 200 150 250 200 450 400 550 450 S811U50N3D 1

Frame Size V

415 75 110 147 125 100 125 125 300 250 300 300 S811V36N3D

526 90 160 185 150 120 150 150 400 300 450 400 S811V42N3D

623 110 185 220 200 150 250 200 450 400 550 450 S811V50N3D

727 129 220 257 250 200 250 250 550 450 700 550 S811V65N3D

816 147 257 295 250 250 300 250 600 550 750 700 S811V72N3D

908 160 280 335 250 250 300 250 700 550 750 700 S811V85N3D

— — — — — — — — — — — — S811V10N3D 2

S811

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-107

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Accessories

Lug Kits The T and U frame (200 mm) and V frame (290 mm) each have different lug options based on your wiring needs.

The T and U frame (200 mm) and V frame (290 mm) soft starters each have different lug options based on your wiring needs. Each lug kit contains three lugs that can be mounted on either the load or line side.

Lug Kits

Power Supplies24 Vdc power supply that can be used with the S811 SSRV or as a stand-alone device.

Power Supplies

Lug Cover Kits Replacement covers for the T- and V-Frame are availablein case of damage to the existing covers.

Lug Cover Kits

IP20 Kits

IP20 Kits

Surge SuppressorsThe surge suppressor can mount on either the line or load side of the soft starter. It is designed to clip the line voltage (or load side induced voltage).

Surge Suppressors

Notes1 The EML33 does not have a CSA listing. 2 T-Frame only.3 For more information, see Pub. 51719.

FrameSize

FrameDesignation Description

Catalog Number

200 mm SSRV

T, U 2 cable connections, 4 AWG to 1/0 cable EML22

1 cable connection, 4/0 to 500 kcmil cable EML23

2 cable connections, 4/0 to 500 kcmil cable EML24

1 cable connection, 2/0 to 300 kcmil cable EML25

2 cable connections, 2/0 to 300 kcmil cable EML26

290 mmSSRV

V 2 cable connections, 4/0 to 500 kcmil cable EML28

4 cable connections, 4/0 to 500 kcmil cable EML30

6 cable connections, 4/0 to 500 kcmil cable EML32

4 cable connections, 2/0 to 300 kcmil cable EML33 1

Lug Kit

DescriptionCatalogNumber

85–264 Vac input24 Vdc output

PSG240E

360–575 Vac input24 Vdc output

PSG240F

DescriptionCatalogNumber

Lug cover T-, U-Frame EML27

Lug cover V-Frame EML34

DescriptionCatalogNumber

N-Frame kit SS-IP20-N

R-Frame kit SS-IP20-R

T- and U-Frame kit SS-IP20-TU

V-Frame kit SS-IP20-V

DescriptionCatalogNumber

600V MOV for 200 mm and 290 mm units EMS39

690V MOV for 200 mm and 290 mm units 2 EMS41

Surge Suppressor

V6-T1-108 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Mounting PlatesThe mounting plates are designed to help make it easy to install or retrofit the soft starter into enclosures and MCCs. The soft starter can be mounted onto the plate prior to installation. The mounting plate is designed with tear drop mounting holes for easier installation.

Mounting Plates

Vibration PlatesThe vibration plates allow the soft starter to be applied in high shock and vibration applications. The vibration plate allows vibration up to 5g and shock in up to 40g. The soft starter is mounted onto the vibration plate prior to installation in the panel.

Vibration Plates

Adapter PlatesThe adapter plate allows customers to retrofit a V-Frame 290 mm soft starter with the U-Frame 200 mm soft starter.

Adapter Plates

Control Wire Connector

Control Wire Connector

Control Interface ModuleThe Control Interface Module (CIM) is available as a replacement part in two versions.

CIM

Options

Pump ControlFor pump control option, change the 8th digit in the catalog number to P.

Pump Control Option

Extended Ramp For a longer ramp acceleration time of 0.5–360 seconds, change the last digit in the catalog number from Page V6-T1-93 to L.

Extended Ramp Option

Extended Ramp and 690V Option690V ratings are available on the T- and V-Frames by changing the 8th digit in the 0.0 to V.

690V Option

Cooling Fan KitThe EMM18 cooling fan kit mounts on either side of any frame size S801 Soft Starter to provide additional printed circuit board cooling in high ambient operating temperatures.

Cooling Fan Kit

Notes1 U-Frame 500A unit does not have IEC certification. 2 For more information, see Pub 51719.

DescriptionCatalogNumber

Mounting Plate N-Frame EMM13N

Mounting Plate R-Frame EMM13R

Mounting Plate T-, U-Frame EMM13T

Mounting Plate V-Frame EMM13V

DescriptionCatalogNumber

Vibration plate N-Frame EMM14N

Vibration plate R-Frame EMM14R

Vibration plate T-, U-Frame EMM14T

Vibration plate V-Frame EMM14V

DescriptionCatalogNumber

Adapter plates 2 EMM13U

DescriptionCatalogNumber

12-pin, 5 mm pitch connector for control wiring

EMA75

DescriptionCatalogNumber

Blank cover (filler) EMA68

CIM for standard unit EMA71

CIM for pump control option EMA72

Panel mounting kit

3 ft cable EMA69A

5 ft cable EMA69B

8 ft cable EMA69C

10 ft cable EMA69D

Frame Size

Max. Current

Catalog Number

N 37 S811N37P3S

66 S811N66P3S

R 105 S811R10P3S

135 S811R13P3S

T 180 S811T18P3S

240 S811T24P3S

304 S811T30P3S

U 360 S811U36P3S

420 S811U42P3S

500 S811U50P3S 1

V 360 S811V36P3S

420 S811V42P3S

500 S811V50P3S

650 S811V65P3S

720 S811V72P3S

850 S811V85P3S

1000 S811V10P3S

Frame Size

Max. Current

Catalog Number

N 37 S811N37N3L

66 S811N66N3L

R 105 S811R10N3L

135 S811R13N3L

T 180 S811T18N3L

240 S811T24N3L

304 S811T30N3L

U 360 S811U36N3L

420 S811U42N3L

500 S811U50N3L 1

V 360 S811V36N3L

420 S811V42N3L

500 S811V50N3L

650 S811V65N3L

720 S811V72N3L

850 S811V85N3L

1000 S811V10N3L

Frame Size

Max. Current

Catalog Number

T 180 S811T18V3L

240 S811T24V3L

304 S811T30V3L

V 360 S811V36V3L

420 S811V42V3L

500 S811V50V3L

650 S811V65V3L

720 S811V72V3L

850 S811V85V3L

DescriptionCatalogNumber

Fan Kit EMM18

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-109

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Technical Data and Specifications

Soft Starters—S811

DescriptionS811 Soft Starter (Partial Catalog Number)S811N37 S811N66 S811R10 S811R13

Max. current capacity 37 66 105 135

FLA range 11–37 20–66 32–105 42–135

General Information

Bypass mechanical lifespan 10M 10M 10M 10M

Insulating voltage Ui 660V 660V 660V 660V

Ramp time range 0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds(0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

Resistance to vibration 3g 3g 3g 3g

Resistance to shock 15g 15g 15g 15g

Electrical Information

Operating voltage 200–600V 200–600V 200–600V 200–600V

Operating frequency 47–63 Hz 47–63 Hz 47–63 Hz 47–63 Hz

Overload setting 30–100% 30–100% 30–100% 30–100%

Trip class 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30

Cabling Capacity (IEC 947)

Number of conductors 1 1 1 1

Wire sizes 14–2 14–2 14–4/0 14–4/0

Type of connectors Box lug Box lug Box lug Box lug

Control Wiring (12-Pin)

Wire sizes in AWG 22–14 22–14 22–14 22–14

Number of conductors (stranded) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12)

Torque requirements in lb-in 3.5 3.5 3.5 3.5

Solid, stranded or flexible max. size in mm2 3.31 3.31 3.31 3.31

Control Power Requirements

Voltage range (24V ±10%) 21.6–26.4 21.6–26.4 21.6–26.4 21.6–26.4

Steady-state current amps 1.0 1.0 1.0 1.0

Inrush current amps 10 10 10 10

Ripple 1% 1% 1% 1%

Relays (1) Class A and C

Voltage AC—maximum 240 240 240 240

Voltage DC—maximum 120 120 120 120

Amps—maximum 3 3 3 3

Environment

Temperature—operating –30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

Temperature—storage –50 to 70°C –50 to 70°C –50 to 70°C –50 to 70°C

Altitude <2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

Humidity <95% noncondensing <95% noncondensing <95% noncondensing <95% noncondensing

Operating position Any Any Any Any

Pollution degree IEC947-1 3 3 3 3

Impulse withstand voltage IEC947-4-1 6000V 6000V 6000V 6000V

V6-T1-110 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Soft Starters—S811, continued

DescriptionS811 Soft Starter (Partial Catalog Number)S811T18 S811T24 S811T30 S811U36

Max. current capacity 180 240 304 360

FLA range 56–180 75–240 95–304 112–360

General Information

Bypass mechanical lifespan 10M 10M 10M 10M

Insulating voltage Ui 660V 660V 660V 660V

Ramp time range 0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds(0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

Resistance to vibration 3g 3g 3g 3g

Resistance to shock 15g 15g 15g 15g

Electrical Information

Operating voltage 200–600V 200–600V 200–600V 200–600V

Operating frequency 47–63 Hz 47–63 Hz 47–63 Hz 47–63 Hz

Overload setting 30–100% 30–100% 30–100% 30–100%

Trip class 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30

Cabling Capacity (IEC 947)

Number of conductors 1 or 2 1 or 2 1 or 2 1 or 2

Wire sizes 4 AWG to 500 kcmil 4 AWG to 500 kcmil 4 AWG to 500 kcmil 4 AWG to 500 kcmil

Type of connectors Add-on lug kit Add-on lug kit Add-on lug kit Add-on lug kit

Control Wiring (12-Pin)

Wire sizes in AWG 22–14 22–14 22–14 22–14

Number of conductors (stranded) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12)

Torque requirements in lb-in 3.5 3.5 3.5 3.5

Solid, stranded or flexible max. size in mm2 3.31 3.31 3.31 3.31

Control Power Requirements

Voltage range (24V ±10%) 21.6–26.4 21.6–26.4 21.6–26.4 21.6–26.4

Steady-state current amps 1.0 1.0 1.0 1.0

Inrush current amps 10 10 10 10

Ripple 1% 1% 1% 1%

Relays (1) Class A and C

Voltage AC—maximum 240 240 240 240

Voltage DC—maximum 120 120 120 120

Amps—maximum 3 3 3 3

Environment

Temperature—operating –30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

Temperature—storage –50 to 70°C –50 to 70°C –50 to 70°C –50 to 70°C

Altitude <2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

Humidity <95% noncondensing <95% noncondensing <95% noncondensing <95% noncondensing

Operating position Any Any Any Any

Pollution degree IEC947-1 3 3 3 3

Impulse withstand voltage IEC947-4-1 6000V 6000V 6000V 6000V

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-111

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Soft Starters—S811, continued

Note1 U-Frame 500A unit does not have IEC certification.

DescriptionS811 Soft Starter (Partial Catalog Number)S811U42 S811U50 1 S811V36 S811V42

Max. current capacity 420 500 360 420

FLA range 131–420 156–500 112–360 131–420

General Information

Bypass mechanical lifespan 10M 10M 10M 10M

Insulating voltage Ui 660V 660V 660V 660V

Ramp time range 0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

Resistance to vibration 3g 3g 3g 3g

Resistance to shock 15g 15g 15g 15g

Electrical Information

Operating voltage 200–600V 200–600V 200–600V 200–600V

Operating frequency 47–63 Hz 47–63 Hz 47–63 Hz 47–63 Hz

Overload setting 30–100% 30–100% 30–100% 30–100%

Trip class 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30

Cabling Capacity (IEC 947)

Number of conductors 1 or 2 1 or 2 2, 4 or 6 2, 4 or 6

Wire sizes 4 AWG to 500 kcmil 4 AWG to 500 kcmil 4 AWG to 500 kcmil 4 AWG to 500 kcmil

Type of connectors Add-on lug kit Add-on lug kit Add-on lug kit Add-on lug kit

Control Wiring (12-Pin)

Wire sizes in AWG 22–14 22–14 22–14 22–14

Number of conductors (stranded) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12)

Torque requirements in lb-in 3.5 3.5 3.5 3.5

Solid, stranded or flexible max. size in mm2 3.31 3.31 3.31 3.31

Control Power Requirements

Voltage range (24V ±10%) 21.6–26.4 21.6–26.4 21.6–26.4 21.6–26.4

Steady-state current amps 1.0 1.0 1.4 1.4

Inrush current amps 10 10 10 10

Ripple 1% 1% 1% 1%

Relays (1) Class A and C

Voltage AC—maximum 240 240 240 240

Voltage DC—maximum 120 120 120 120

Amps—maximum 3 3 3 3

Environment

Temperature—operating –30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

Temperature—storage –50 to 70°C –50 to 70°C –50 to 70°C –50 to 70°C

Altitude <2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

Humidity <95% noncondensing <95% noncondensing <95% noncondensing <95% noncondensing

Operating position Any Any Any Any

Pollution degree IEC947-1 3 3 3 3

Impulse withstand voltage IEC947-4-1 6000V 6000V 6000V 6000V

V6-T1-112 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Soft Starters—S811, continued

Note1 UR recognized product.

DescriptionS811 Soft Starter (Partial Catalog Number)S811V50 S811V65 S811V72 S811V85 S811V10 1

Max. current capacity 500 650 720 850 1000

FLA range 156–500 203–650 225–720 265–580 320–1000

General Information

Bypass mechanical lifespan 10M 10M 10M 10M 10M

Insulating voltage Ui 660V 660V 660V 660V 660V

Ramp time range 0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

0.5–180 seconds (0.5–360 seconds extended ramp)

Resistance to vibration 3g 3g 3g 3g 3g

Resistance to shock 15g 15g 15g 15g 15g

Electrical Information

Operating voltage 200–600V 200–600V 200–600V 200–600V 200–600V

Operating frequency 47–63 Hz 47–63 Hz 47–63 Hz 47–63 Hz 47–63 Hz

Overload setting 30–100% 30–100% 30–100% 30–100% 30–100%

Trip class 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30 5, 10, 20 and 30

Cabling Capacity (IEC 947)

Number of conductors 2, 4 or 6 2, 4 or 6 2, 4 or 6 2, 4 or 6 2, 4 or 6

Wire sizes 2/0 to 500 kcmil 2/0 to 500 kcmil 2/0 to 500 kcmil 2/0 to 500 kcmil 2/0 to 500 kcmil

Type of connectors Add-on lug kit Add-on lug kit Add-on lug kit Add-on lug kit Add-on lug kit

Control Wiring (12-Pin)

Wire sizes in AWG 22–14 22–14 22–14 22–14 22–14

Number of conductors (stranded) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12) 2 (or one AWG 12)

Torque requirements in lb-in 3.5 3.5 3.5 3.5 3.5

Solid, stranded or flexible max. size in mm2 3.31 3.31 3.31 3.31 3.31

Control Power Requirements

Voltage range (24V ±10%) 21.6–26.4 21.6–26.4 21.6–26.4 21.6–26.4 21.6–26.4

Steady-state current amps 1.4 1.4 1.4 1.4 1.4

Inrush current amps 10 10 10 10 10

Ripple 1% 1% 1% 1% 1%

Relays (1) Class A and C

Voltage AC—maximum 240 240 240 240 240

Voltage DC—maximum 120 120 120 120 120

Amps—maximum 3 3 3 3 3

Environment

Temperature—operating –30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

–30 to 50°C (no derating) consult factory for operation >50°C

Temperature—storage –50 to 70°C –50 to 70°C –50 to 70°C –50 to 70°C –50 to 70°C

Altitude <2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

<2000m—consult factory for operation >2000m

Humidity <95% noncondensing <95% noncondensing <95% noncondensing <95% noncondensing <95% noncondensing

Operating position Any Any Any Any Any

Pollution degree IEC947-1 3 3 3 3 3

Impulse withstand voltage IEC947-4-1 6000V 6000V 6000V 6000V 6000V

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-113

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Wiring Diagrams

Line Connected Soft Starter

Inside-the-Delta Connected Soft Starter for a 6-Lead Motor

Inside-the-Delta Connected Soft Starter for a 12-Lead Low Voltage Motor

Inside-the-Delta Connected Soft Starter for a 12-Lead High Voltage Motor

1 L1 3 L2

S811

5 L3

2 T1 4 T2 6 T3

M3˜

L1S L2SSupply

L3S

L31L1

3L2

5L3

T5 T4 T6

T3

T3

T3

T6

T4

T1T1

T2

T2

T2

T1

2T1

4T2

6T3

S811

T5

L1

L1

Motor

L3

L2L2

L1S L2SSupply

L3S

L3

L1

1L1

3L2

5L3

T11T5

T11T10T4

T12T6

T3T9

T3

T5

T3

T6T10

T7

T4

T1

T1

T12

T9

T2T8

T2T2

T1T7

2T1

4T2

6T3

T8

L1

Motor

L3

L2L2

12-LeadLow Voltage

S811

L1S L2SSupply 12-Lead

High VoltageL3S

L3

L1

1L1

3L2

5L3

T11

T11

T10 T12

T3

T3

T3

T6T10

T7T4

T1T1

T12

T9

T2

T2

T2

T1

2T1

4T2

6T3

T8T5

T5T8

T6T9

L1

T7T4

Motor

L3

L2L2

S811

V6-T1-114 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

DimensionsApproximate Dimensions in Inches (mm)

Soft Starters—S811

N-Frame (65 mm) S811

PartialCatalog Number W H D

Weightin Lbs (kg)

S811N37 2.66 (67.6) 7.38 (187.4) 6.47 (164.4) 5.8 (2.6)

S811N66 2.66 (67.6) 7.38 (187.4) 6.47 (164.4) 5.8 (2.6)

S811R10 4.38 (111.3) 7.92 (201.2) 6.66 (169.2) 10.5 (4.8)

S811R13 4.38 (111.3) 7.92 (201.2) 6.66 (169.2) 10.5 (4.8)

S811T18 7.67 (194.8) 12.71 (322.9) 6.39 (162.4) 48 (21.8) with lugs 41 (18.6) without lugs

S811T24 7.67 (194.8) 12.71 (322.9) 6.39 (162.4) 48 (21.8) with lugs 41 (18.6) without lugs

S811T30 7.67 (194.8) 12.71 (322.9) 6.39 (162.4) 48 (21.8) with lugs 41 (18.6) without lugs

S811U36 7.73 (196.3) 12.72 (323.1) 7.08 (179.9) 48 (21.8) with lugs 41 (18.6) without lugs

S811U42 7.73 (196.3) 12.72 (323.1) 7.08 (179.9) 48 (21.8) with lugs 41 (18.6) without lugs

S811U50 7.73 (196.3) 12.72 (323.1) 7.08 (179.9) 48 (21.8) with lugs 41 (18.6) without lugs

S811V36 11.05 (280.6) 16.57 (420.8) 7.35 (186.6) 103 (46.8) with lugs 91 (41.4) without lugs

S811V42 11.05 (280.6) 16.57 (420.8) 7.35 (186.6) 103 (46.8) with lugs 91 (41.4) without lugs

S811V50 11.05 (280.6) 16.57 (420.8) 7.35 (186.6) 103 (46.8) with lugs 91 (41.4) without lugs

S811V65 11.05 (280.6) 16.57 (420.8) 7.35 (186.6) 103 (46.8) with lugs 91 (41.4) without lugs

S811V72 11.05 (280.6) 16.57 (420.8) 7.35 (186.6) 103 (46.8) with lugs 91 (41.4) without lugs

S811V85 11.05 (280.6) 16.57 (420.8) 7.35 (186.6) 103 (46.8) with lugs 91 (41.4) without lugs

S811V10 11.05 (280.6) 16.57 (420.8) 7.35 (186.6) 103 (46.8) with lugs 91 (41.4) without lugs

Also refer to dimension drawings below and on Pages V6-T1-115 and V6-T1-116.

6.87(174.5)

1.97(50.0)

0.22 (5.5)Typ.

4 Places

2.66(67.6)

3.46(88.0)

5.35(135.9)

6.47(164.4)

7.38(187.4)

Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com V6-T1-115

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2Reduced Voltage Motor Starters

Solid-State Starters

Approximate Dimensions in Inches (mm)

R-Frame (110 mm) S811

T-Frame (200 mm) S811

3.49(88.5)

5.53(140.5)

6.66(169.2)

7.44(189.0)

3.54(90.0)

4.38(111.3)

7.92(201.2)

0.27 (6.8)Typ.

4 Places

5.40(137.2)

6.39(162.4)

7.67(194.8)

11.77(299.0)Slots

12.71(322.9)

2.95(75.0)Slots

0.28(7.1)

Slots Typ.6 Places

5.91 (150.0)Slots

V6-T1-116 Volume 6—Solid-State Motor Control CA08100007E—January 2012 www.eaton.com

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1.2 Reduced Voltage Motor Starters

Solid-State Starters

Approximate Dimensions in Inches (mm)

U-Frame (200 mm) S811

V-Frame (290 mm) S811

11.77 (299.0)Mounting

5.20 (132.0)Mounting

Mounting Slotsfor M6 (1/4) Screws(Up to 6 Quantity)

0.47(11.9)

7.08(179.9)

12.72(323.1)

7.73(196.3)

5.20 (132.0)Pole Centers

C L

C L

3.74(95.0)

0.26 (6.5) Dia.Typ.

4 Places

7.35(186.6)

15.16(385.0)Slots

15.63(397.0)

MountingHoles

16.57(420.8)

9.84(250.0)

11.05 (280.6)0.27 (6.8)Typ.

4 Places