Post on 29-May-2018
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Applications• Foruseinlocationswhere:
— Flammablegases,vaporsanddustsarepresent— Ahighdegreeofcorrosionresistanceisrequired— Protectionagainstdirt,waterandmoistureisnecessary
• Typicalapplicationsinclude:—Oilrefineries—Petrochemicalfacilities—Pulpandpapermills—Foodprocessingplants—Wasteandsewertreatment—Undergroundtunnels—Generalmanufacturingfacilities
Features• 60,000+hourLEDlifeforyearsofmaintenancefreeoperation.• Lightweightdesign,hingedcoverwithcaptivescrews,and
terminalblockwiringforeasyinstallationandmaintenance.• Standardscrew-typeterminalblockcanaccept1to6mm2 wire.• Contemporary,lowprofiledesignsuitablefortightspaces.• FieldreplaceableLEDdriverandlens.• Industry-leadingthermalmanagementforsafe,reliable
operationoverwidetemperaturerange.• Fullrangeoflumenoutputs,withlightdistributionequivalentto
Appleton’sFNSeriesfluorescentfixtures• EasytoretrofitinsamemountingfootprintasAppleton’sFE/FN
Seriesfluorescentfixtures. • M20plugorM25plugprovided.• Universal,highefficiency,driverscovervoltagerequirementsfor
120-277Vac,50/60Hz+/-10%.• Standard2KVsurgesuppression.
Options• Safetycableforfallsaferetention;addsuffix-Ctotheendof
thecatalognumber.
Standard Materials• Housing:copperfree(4/10of1%max.)aluminum• Lens:thermalshock-andimpact-resistantpolycarbonatelens• Gasket:siliconerubber,mechanicallysecured• Bolts:stainlesssteel• Closeupplugs:nickelplatedbrass
—Mountinghardware:Seeorderinginformation
Standard Finishes• Housing:grayRAL7038epoxy
Related Products• ForNEC/CECcertifiedproducts,refertoViamasterLEDSeries
LuminairesforNECandCECGovernedHazaardousLocations
ATEX/IECEx Certifications and Compliances• CertificationType:LLEDA
—Gas:Zone2–ConformingtoATEX94/9/EC: II3G–ProtectionLevel:EPLGc–TypeofProtection:ExnAIIC–TemperatureClass:See Technical Data table(T6toT3)–ECDeclarationofConformity:50309–ATEXCertificate:LCIE15ATEX1003X–IECExCertificate:IECExLCIE15.0010X
—Dust:Zones21and22–ConformingtoATEX94/9/EC: II2DandII3D–ProtectionLevel:EPLDbandDc–TypeofProtection:ExtbIIICandExtcIIIC–SurfaceTemperature:See Technical Data table
[+63°Cto+84°C(+145°Fto+183°F)]–ECDeclarationofConformity:50309–ATEXCertificate,Zone21:LCIE15ATEX3006X–ATEXCertificate,Zone22:LCIE15ATEX1003X–IECExCertificate,Zone21and22:IECExLCIE15.0010X
• AmbientTemperature:—LLEDAA2:-40°Cupto+65°C(-40°Fupto+149°F)—LLEDAA5/7:-40°Cupto+60°C(-40°Fupto+140°F)
• IndexofProtectionaccordingEN/IEC60529:IP66• ImpactResistance(shock):IK08• ExStandards:EN/IEC60079-0;60079-15;60079-31• ProductStandards:EN/IEC61347-1;EN/IEC61347-2-13;
60598-1• EMCStandards:EN/IEC61000.4.2;61000.4.3;61000.4.4;
61000.4.5;61000.4.6;61000.4.8;61000.4.11;EN/IEC55015;61547
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/
AREA
: NEC
/CEC
, ATE
X/IEC
Ex E
NCLO
SED
AND
GASK
ETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
60
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Orderusingcatalognumberingguidesbeloworselectcatalognumberfromtablesonfollowingpages.
Catalog Numbering Guide — ATEX/IECEx Certified Linear LED
LLEDA A 2 L 2 BU Z2 C
LLEDA-ATEX/IECExCertifiedLinearLEDSeries
SizeofCableEntries:2 - M203-M25
Lumens[LengthofFixture]:2-2KLumens,[0.61m(2ft)]5-5KLumens,[0.61m(2ft)]7-7KLumens,[1.22m(4ft)]
HazardousRating:Z2-Zone2and21-22
Housing:A-Aluminum
Termination/Wiring:L-LoopIn/Out(3entries,1at
oneendand2attheother)S-Standard(2entriesonthe
sameside)T-ThroughWired(2entries,
oneateachend)
Voltage:BU-UniversalVoltages
120-277Vac,50/60Hz
Options:C-SafetyCables
Lamp Comparison Chart
Catalog Number
Line Current Amps
Input Power
Power Factor THD
Lumens
CRIColor Temp
CCTLength m (ft)
Clear Polycarbonate
LLEDAA2S2BUZ2
.24@120V.15@277V 22 W >0.95
>0.87 <20% 2,200 70 5650K 0.61(2)
LLEDAA3S2BUZ2
LLEDAA2T2BUZ2
LLEDAA3T2BUZ2
LLEDAA2L2BUZ2
LLEDAA3L2BUZ2
LLEDAA2S5BUZ2
.51@120V.30@277V 45W >0.95 <20% 4,400 70 5650K 0.61(2)
LLEDAA3S5BUZ2
LLEDAA2T5BUZ2
LLEDAA3T5BUZ2
LLEDAA2L5BUZ2
LLEDAA3L5BUZ2
LLEDAA2S7BUZ2
.90@120V.53@277V 81W >0.95 <20% 7,800 70 5650K 1.22(4)
LLEDAA3S7BUZ2
LLEDAA2T7BUZ2
LLEDAA3T7BUZ2
LLEDAA2L7BUZ2
LLEDAA3L7BUZ2
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
61
“T” Numbers Represent the Maximum External Surface Temperature
“T” # T1 T2 T3 T4 T5 T6
Temp. Range ºC (●ºF)
301-450 201-300 136-200 101-135 86-100 85
(547-842) (394-572) (277-392) (214-275) (187-212) (185)
T codes provided in catalog pages are based on worst case data. Zone 2 (Gas) and 22 (Dust) locations as designated by the IEC.
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Technical Data
Lamp
Ambient Temperature °C (°F)
Supply Wire Temperature °C (°F)
Zone 2 - 22 Zone 21
LumenOutput Type
GasDust
SurfaceTemperature °C (°F)
DustSurface
Temperature °C (°F)Class of
Temperature °C (°F)
2,200lm LED
40(104) 75(167) T675(167) 54(129) 54(129)
55(131) 75(167) T590(203) 69(156) 69(156)
60(140) 75(167) T590(203) 74(165) 74(165)
65(149) 75(167) T5100(212) 79(174) 79(174)
4,400lm LED
40(104) 75(167) T4129(264) 64(147) 64(147)
55(131) 75(167) T3144(291) 79(174) 79(174)
60(140) 75(167) T3148(298) 84(183) 84(183)
7,800lm LED
40(104) 75(167) T4130(266) 64(147) 64(147)
55(131) 75(167) T3145(293) 79(174) 79(174)
60(140) 75(167) T3149(300) 84(183) 84(183)
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/
AREA
: NEC
/CEC
, ATE
X/IEC
Ex E
NCLO
SED
AND
GASK
ETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
62
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Conduit/Cable Entries Voltage
Ambient Temperature
Weight kg (lb)
Catalog Numbers
Clear Polycarbonate
2,200 Lumens — 0.61 m (2 ft)
M20Standard 120-277Vac,50/60Hz-40°Cupto+65°C (-40°Fupto+149°F)
6.21 (13.7)
LLEDAA2S2BUZ2
M25Standard 120-277Vac,50/60Hz LLEDAA3S2BUZ2
M20ThroughWired 120-277Vac,50/60Hz-40°Cupto+65°C (-40°Fupto+149°F)
6.21 (13.7)
LLEDAA2T2BUZ2
M25ThroughWired 120-277Vac,50/60Hz LLEDAA3T2BUZ2
M20LoopIn/LoopOut 120-277Vac,50/60Hz-40°Cupto+65°C (-40°Fupto+149°F)
6.21 (13.7)
LLEDAA2L2BUZ2
M25LoopIn/LoopOut 120-277Vac,50/60Hz LLEDAA3L2BUZ2
4,400 Lumens — 0.61 m (2 ft)
M20Standard 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)
6.35 (14.0)
LLEDAA2S5BUZ2
M25Standard 120-277Vac,50/60Hz LLEDAA3S5BUZ2
M20ThroughWired 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)
6.35 (14.0)
LLEDAA2T5BUZ2
M25ThroughWired 120-277Vac,50/60Hz LLEDAA3T5BUZ2
M20LoopIn/LoopOut 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)
6.35 (14.0)
LLEDAA2L5BUZ2
M25LoopIn/LoopOut 120-277Vac,50/60Hz LLEDAA3L5BUZ2
7,800 Lumens — 1.22 m (4 ft)
M20Standard 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)
8.69 (19.15)
LLEDAA2S7BUZ2
M25Standard 120-277Vac,50/60Hz LLEDAA3S7BUZ2
M20ThroughWired 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)
8.69 (19.15)
LLEDAA2T7BUZ2
M25ThroughWired 120-277Vac,50/60Hz LLEDAA3T7BUZ2
M20LoopIn/LoopOut 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)
8.69 (19.15)
LLEDAA2L7BUZ2
M25LoopIn/LoopOut 120-277Vac,50/60Hz LLEDAA3L7BUZ2
Standard cable entry provides 2 entries on the same side of the housing. Through wired cable entry provides 2 entries, one at each end of the housing. Loop In/Loop Out cable entry provides 3 entries, 1 at one and 2 at the other end of the housing. For optional safety cables, add suffix -C to the end of the catalog number.
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
63
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Accessories and Replacement Parts
Description Catalog Numbers
Mounting Brackets — Set of Two
8.5
9.0mm(0.35")
68m
m(2.68")
30mm(1.18")
49.0mm(1.93")
25.0mm(0.98")
8.5mm
(0.33")
Fixing Brackets for Surface Installation
Zincplatedsteel 316stainlesssteel
FEFBZFEFBS
14.59.5
232mm(9.13")
200mm(7.87")
38.0m
m(1.50")
13.0m
m(0.51")
9.5mm
(0.37")
14.5mm(0.57")
30.0mm(1.18")
Surface Mounting
Aluminum(graypainted)316stainlesssteel
FESBAFESBS
L NPE PEL N
N L PE
Version : L
Dual Loop In/Out - Through Wiring (Single phase)
3 entries, 1 at one end and 2 at the other
Version : S
Standard
2 entries on the same side
Version : T
Through Wiring (3 phases)
2 entries, one at each end
L NPE PEL N L1 NPE PEL1 NL2 L3
L1 N PEL2L3
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/
AREA
: NEC
/CEC
, ATE
X/IEC
Ex E
NCLO
SED
AND
GASK
ETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
64
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Accessories and Replacement Parts
Description Catalog Numbers
Mounting Brackets — Set of Two
Ø 8mm (0.31")
23mmx5.08mm
Ø 8mm (0.31")
Ø 5.08mm (0.20")
Ø 8mm (0.31")
25.4mm
(1.00")
104.9mm
(4.13")
60.5mm
(2.38")
241.3mm
(9.50")
23.9mm
(0.94")
209.6mm
(8.25")
Surface Mounting
14-gaugestainlesssteel FVSM
30°
90
30
60
900
30 60
30°
5.5mm(0.22”)
67.0mm
(2.63”)
41.0mm(1.61”)
82.0mm(3.23”)
13.0mm (0.51”)
M8x1.25mm(1.25")
9.5mm(0.37”)
100.0mm
(3.94”)
32.0mm(1.26”)
18.0mm(0.71”)
14.5mm(0.57”)
132mm(5.20”)
Hinged Brackets for Adjusting Luminaire
Aluminum FEHBA
Half Clamp Brackets for Pole Mounting
For42mmto49mmpole(1-1/4to1-1/2"tube)
Zincplatedsteel FEHC49Z
316stainlesssteel FEHC49S
For60mmpole(2"tube)
Zincplatedsteel FEHC60Z
316stainlesssteel FEHC60S
FVSM does not retrofit in same mounting footprint as Appleton’s FN/FE series.
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
65
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Accessories and Replacement Parts
Description Catalog Numbers
Mounting Brackets — Set of Two
Ø 12.7mm (0.50")
Ø 7.6mm
Ø 8.5mm
(0.30")
(0.34")
38.0mm (1.50")
90mm
196mm
31.8mm194mm
(3.55")
(7.72")
(1.25")(7.64")
Fixed 45˚ Wall Mount
11-gauge(1/8”)stainlesssteel FVWFM
M 8 x 1.25
36.0m
m(1.42")
15.0m
m(0.59")
20.0mm(0.80")
8.0mm(0.32")
M8x1.25mm(1.25")
M8 Ring Bolts
Zincplatedsteel—Forusewithoptionalsafetychain(notprovided) FERBM8Z
Retrofit Brackets — Set of Two
Adaptsmountingholesfor4footfixtureto700mmmountingcenters LLEDRB
Fall Prevention Kit
SafetyCables—Attachedtofixturestoguardagainstthemfallingwhentheprimarymethodofattachmentfails.
LLEDSC
Replacement Drivers
120-277Vacdriver LLEDBU2
Replacement Lenses
ClearPolycarbonatelenswithanintegralgasket LLEDCPL
FVWFM does not retrofit in same mounting footprint as Appleton’s FN/FE series.
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/
AREA
: NEC
/CEC
, ATE
X/IEC
Ex E
NCLO
SED
AND
GASK
ETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
66
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Mounting Options Dimensions in Millimeters (Inches)
FEFBS Ceiling/Surface Mount
30 (1.18)
172 (6.78)
178 (7.01)
● Ø 9(0.35)
68 (2.68)
610 (24.02)
400 (15.75)
(1.92)49
FESBA Aluminum (gray painted)
FESBS 316 stainless steel Ceiling/Surface Mount
30 (1.18)
● Ø 9(0.35)
178 (7.01)
142 (5.59)
38 (1.50)
232 (9.13)
200 (7.87)
610 (24.02)
400 (15.75)
FVSM Ceiling/Surface Mount
25(1.00)
27 (1.08)
● Ø 8(0.31)
131 (5.17)
178 (7.01)
178 (9.50)
210 (8.25)164
(6.46)
610 (24.02)
400 (15.75)
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
67
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Mounting Options Dimensions in Millimeters (Inches)
FEHBA Wall/Hinged Mount
FEHBA
610 (24.02)
102 (4.00)
193 (7.60)
89 (3.51)
132 (5.20)
172 (6.77)
178 (7.01)
MAX.WALL
MOUNT
WALL
Bracket Bolt
193 (7.60) 400
(15.75)
440 (17.32) 40.1
(1.58)
16 (0.63)
75°
FVWFM Wall/Fixed 45° Mount
400 (15.75)
● Ø 12.7(0.50)
38(1.50)
90 (3.54)245
(9.66)
610 (24.02)
196 (7.72)
194 (7.64)
178 (7.01)
244 (9.63)
FERBM8Z Ceiling/Chain Mount
610 (24.02)
400 (15.75)
36 (1.42)
400 (15.75)
178 (7.01)
● Ø 8(0.32) ● Ø 20
(0.80)
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/
AREA
: NEC
/CEC
, ATE
X/IEC
Ex E
NCLO
SED
AND
GASK
ETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
68
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Luminaire Dimensions in Millimeters (Inches)
178.4 mm (7.07”)
113.
0 m
m (4
.45”
)
End View — 0.61 m (2 ft) and 1.22 m (4 ft) Versions
610.0 mm (24.02”)
400.0 mm (15.75”)
530 mm (20.87”)
89.0
mm
(3.5
0”)
Mounting Hole Mounting Hole
C L
Conduit/CableEntry
Conduit/CableEntry
Side View — 0.61 m (2 ft) Versions
610.0 mm (24.02”)
400.0 mm (15.75”)
530 mm (20.87”)
89.0
mm
(3.5
0”)
Mounting Hole Mounting Hole
C L
Conduit/CableEntry
Conduit/CableEntry
Top (Mounting) View — 0.61 m (2 ft) Versions
610.0 mm (24.02”)
1220.0 mm (48.03”)
Conduit/CableEntry
Conduit/CableEntry
400.0 mm (15.75”)
89.0
mm
(3.5
0”)
C L
530 mm (20.87”)Mounting Hole Mounting Hole
Side View — 1.22 m (4 ft) Version
610.0 mm (24.02”)
1220.0 mm (48.03”)
Conduit/CableEntry
Conduit/CableEntry
400.0 mm (15.75”)
89.0
mm
(3.5
0”)
C L
530 mm (20.87”)Mounting Hole Mounting Hole
Top (Mounting) View — 1.22 m (4 ft) Version
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
69
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Photometric Data — DATA SHOWN IS ABSOLUTE
LLEDAA(XY)2BUZ2 with Clear Polycarbonate Lens X = cable entry size, Y = style of termination
Polar Candela Distribution Isoillumination Plot
180° 170° 160° 150° 140°
130°
120°
110°
100°
90°
80°
70°
60°
475
570
380
285
100
200
300
400
500
600
95
0
50°
40°30°20°10°0°
-0° H -22.5° H-45° H-67.5° H
-90° H
2.5 fc 0.5 fc0.2 fc0.1 fc
1 fc
3
2
2
1
1
0
0
1
1
2
2
3
Distance in units of mount height (10ft)
Zonal Lumens and Percentages at 25°CZone Lumens % Luminaire Zone Lumens % Luminaire0-30 424.1 20.2 0-10 46.7 2.20-40 741.2 35.4 10-20 140.9 6.70-60 1521 72.6 20-30 236.4 11.360-90 573.3 27.4 30-40 317.2 15.10-90 2094 100.0 40-50 378.4 18.1
90-180 0.3 0.0 50-60 401.5 19.20-180 2095 100.0 60-70 324.6 15.5
70-80 209.6 10.080-90 39.1 1.990-100 0.3 0.0
LLEDAA(XY)5BUZ2 with Clear Polycarbonate Lens X = cable entry size, Y = style of termination
Polar Candela Distribution Isoillumination Plot
180° 170° 160° 150° 140°
130°
120°
110°
100°
90°
80°
70°
60°
1,400
1,400
1,167
1,167
933
933
700
700
467
467
233
233
0
50°
40°30°20°10°0°
-0° H -22.5° H-45° H-67.5° H
-90° H
10 fc
2.5 fc
2 fc0.5 fc0.2 fc0.1 fc
5 fc
5
3
4
4
2
1
3
0
2
1
1
2
3
4
5
0 1 2 3 4
Distance in units of mount height (10ft)
Zonal Lumens and Percentages at 25°CZone Lumens % Luminaire Zone Lumens % Luminaire0-30 912.8 20.3 0-10 100.4 2.20-40 1593 35.5 10-20 303.6 6.80-60 3282 73.0 20-30 508.8 11.360-90 1206 26.8 30-40 680.0 15.10-90 4488 99.9 40-50 822.5 18.3
90-180 4.5 0.1 50-60 866.3 19.30-180 4492 100.0 60-70 682.0 15.2
70-80 438.3 9.880-90 85.9 1.990-100 4.2 0.1
100-110 0.3 0.0
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/
AREA
: NEC
/CEC
, ATE
X/IEC
Ex E
NCLO
SED
AND
GASK
ETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016
70
Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations
Photometric Data — DATA SHOWN IS ABSOLUTE
LLEDAA(XY)7BUZ2 with Clear Polycarbonate Lens X = cable entry size, Y = style of termination
Polar Candela Distribution Isoillumination Plot
180° 170° 160° 150° 140°
130°
120°
110°
100°
90°
80°
70°
60°
2,300
2,300
1,917
1,917
1,533
1,533
1,150
1,150
767
767
383
383
0
50°
40°30°20°10°0°
-0° H -22.5° H-45° H-67.5° H
-90° H
10 fc
2.5 fc
2 fc0.5 fc0.2 fc0.1 fc
5 fc
5
3
4
4
2
1
3
0
2
1
1
2
3
4
5
0 1 2 3 4
Distance in units of mount height (10ft)
Zonal Lumens and Percentages at 25°CZone Lumens % Luminaire Zone Lumens % Luminaire0-30 1560 20.0 0-10 170.7 2.20-40 2728 34.9 10-20 518.4 6.60-60 5631 72.1 20-30 870.5 11.260-90 2171 27.8 30-40 1168 15.00-90 7802 100.0 40-50 1406 18.0
90-180 2.8 0.0 50-60 1497 19.20-180 7805 100.0 60-70 1229 15.7
70-80 785.7 10.180-90 156.6 2.090-100 2.7 0.0
ATEX/IECEx: Zones 2 and 22
II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08
ATEX/IECEx: Zone 21
II 2 D EPL Db Ex tb IIIC IP66/IK08
LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED
Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016