Viamaster LED Series Luminaires For ATEX and IECEx ... · For ATEX and IECEx Governed Hazardous...

12
Viamaster LED Series Luminaires For ATEX and IECEx Governed Hazardous Locations Applications For use in locations where: Flammable gases, vapors and dusts are present A high degree of corrosion resistance is required Protection against dirt, water and moisture is necessary Typical applications include: — Oil refineries — Petrochemical facilities — Pulp and paper mills — Food processing plants — Waste and sewer treatment — Underground tunnels — General manufacturing facilities Features 60,000+ hour LED life for years of maintenance free operation. Lightweight design, hinged cover with captive screws, and terminal block wiring for easy installation and maintenance. Standard screw-type terminal block can accept 1 to 6 mm 2 wire. Contemporary, low profile design suitable for tight spaces. Field replaceable LED driver and lens. Industry-leading thermal management for safe, reliable operation over wide temperature range. Full range of lumen outputs, with light distribution equivalent to Appleton’s FN Series fluorescent fixtures Easy to retrofit in same mounting footprint as Appleton’s FE/FN Series fluorescent fixtures. M20 plug or M25 plug provided. Universal, high efficiency, drivers cover voltage requirements for 120-277 Vac, 50/60 Hz +/- 10%. Standard 2KV surge suppression. Options Safety cable for fall safe retention; add suffix -C to the end of the catalog number. Standard Materials Housing: copperfree (4/10 of 1% max.) aluminum Lens: thermal shock- and impact-resistant polycarbonate lens Gasket: silicone rubber, mechanically secured Bolts: stainless steel Close up plugs: nickel plated brass — Mounting hardware: See ordering information Standard Finishes Housing: gray RAL 7038 epoxy Related Products For NEC/CEC certified products, refer to Viamaster LED Series Luminaires for NEC and CEC Governed Hazaardous Locations ATEX/IECEx Certifications and Compliances Certification Type: LLEDA — Gas: Zone 2 – Conforming to ATEX 94/9/EC: II 3 G – Protection Level: EPL Gc – Type of Protection: Ex nA IIC – Temperature Class: See Technical Data table (T6 to T3) – EC Declaration of Conformity: 50309 – ATEX Certificate: LCIE 15 ATEX 1003X – IECEx Certificate: IECEx LCIE 15.0010X — Dust: Zones 21 and 22 – Conforming to ATEX 94/9/EC: II 2 D and II 3 D – Protection Level: EPL Db and Dc – Type of Protection: Ex tb IIIC and Ex tc IIIC – Surface Temperature: See Technical Data table [+63 °C to +84 °C (+145 °F to +183 °F)] – EC Declaration of Conformity: 50309 – ATEX Certificate, Zone 21: LCIE 15 ATEX 3006X – ATEX Certificate, Zone 22: LCIE 15 ATEX 1003X – IECEx Certificate, Zone 21 and 22: IECEx LCIE 15.0010X Ambient Temperature: — LLEDAA2: -40 °C up to +65 °C (-40 °F up to +149 °F) — LLEDAA5/7: -40 °C up to +60 °C (-40 °F up to +140 °F) Index of Protection according EN/IEC 60529: IP66 Impact Resistance (shock): IK08 Ex Standards: EN/IEC 60079-0; 60079-15; 60079-31 Product Standards: EN/IEC 61347-1; EN/IEC 61347-2-13; 60598-1 EMC Standards: EN/IEC 61000.4.2; 61000.4.3; 61000.4.4; 61000.4.5; 61000.4.6; 61000.4.8; 61000.4.11; EN/IEC 55015; 61547 ATEX/IECEx: Zones 2 and 22 II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08 ATEX/IECEx: Zone 21 II 2 D EPL Db Ex tb IIIC IP66/IK08 LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016 60

Transcript of Viamaster LED Series Luminaires For ATEX and IECEx ... · For ATEX and IECEx Governed Hazardous...

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Applications• Foruseinlocationswhere:

— Flammablegases,vaporsanddustsarepresent— Ahighdegreeofcorrosionresistanceisrequired— Protectionagainstdirt,waterandmoistureisnecessary

• Typicalapplicationsinclude:—Oilrefineries—Petrochemicalfacilities—Pulpandpapermills—Foodprocessingplants—Wasteandsewertreatment—Undergroundtunnels—Generalmanufacturingfacilities

Features• 60,000+hourLEDlifeforyearsofmaintenancefreeoperation.• Lightweightdesign,hingedcoverwithcaptivescrews,and

terminalblockwiringforeasyinstallationandmaintenance.• Standardscrew-typeterminalblockcanaccept1to6mm2 wire.• Contemporary,lowprofiledesignsuitablefortightspaces.• FieldreplaceableLEDdriverandlens.• Industry-leadingthermalmanagementforsafe,reliable

operationoverwidetemperaturerange.• Fullrangeoflumenoutputs,withlightdistributionequivalentto

Appleton’sFNSeriesfluorescentfixtures• EasytoretrofitinsamemountingfootprintasAppleton’sFE/FN

Seriesfluorescentfixtures. • M20plugorM25plugprovided.• Universal,highefficiency,driverscovervoltagerequirementsfor

120-277Vac,50/60Hz+/-10%.• Standard2KVsurgesuppression.

Options• Safetycableforfallsaferetention;addsuffix-Ctotheendof

thecatalognumber.

Standard Materials• Housing:copperfree(4/10of1%max.)aluminum• Lens:thermalshock-andimpact-resistantpolycarbonatelens• Gasket:siliconerubber,mechanicallysecured• Bolts:stainlesssteel• Closeupplugs:nickelplatedbrass

—Mountinghardware:Seeorderinginformation

Standard Finishes• Housing:grayRAL7038epoxy

Related Products• ForNEC/CECcertifiedproducts,refertoViamasterLEDSeries

LuminairesforNECandCECGovernedHazaardousLocations

ATEX/IECEx Certifications and Compliances• CertificationType:LLEDA

—Gas:Zone2–ConformingtoATEX94/9/EC: II3G–ProtectionLevel:EPLGc–TypeofProtection:ExnAIIC–TemperatureClass:See Technical Data table(T6toT3)–ECDeclarationofConformity:50309–ATEXCertificate:LCIE15ATEX1003X–IECExCertificate:IECExLCIE15.0010X

—Dust:Zones21and22–ConformingtoATEX94/9/EC: II2DandII3D–ProtectionLevel:EPLDbandDc–TypeofProtection:ExtbIIICandExtcIIIC–SurfaceTemperature:See Technical Data table

[+63°Cto+84°C(+145°Fto+183°F)]–ECDeclarationofConformity:50309–ATEXCertificate,Zone21:LCIE15ATEX3006X–ATEXCertificate,Zone22:LCIE15ATEX1003X–IECExCertificate,Zone21and22:IECExLCIE15.0010X

• AmbientTemperature:—LLEDAA2:-40°Cupto+65°C(-40°Fupto+149°F)—LLEDAA5/7:-40°Cupto+60°C(-40°Fupto+140°F)

• IndexofProtectionaccordingEN/IEC60529:IP66• ImpactResistance(shock):IK08• ExStandards:EN/IEC60079-0;60079-15;60079-31• ProductStandards:EN/IEC61347-1;EN/IEC61347-2-13;

60598-1• EMCStandards:EN/IEC61000.4.2;61000.4.3;61000.4.4;

61000.4.5;61000.4.6;61000.4.8;61000.4.11;EN/IEC55015;61547

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/

AREA

: NEC

/CEC

, ATE

X/IEC

Ex E

NCLO

SED

AND

GASK

ETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

60

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Orderusingcatalognumberingguidesbeloworselectcatalognumberfromtablesonfollowingpages.

Catalog Numbering Guide — ATEX/IECEx Certified Linear LED

LLEDA A 2 L 2 BU Z2 C

LLEDA-ATEX/IECExCertifiedLinearLEDSeries

SizeofCableEntries:2 - M203-M25

Lumens[LengthofFixture]:2-2KLumens,[0.61m(2ft)]5-5KLumens,[0.61m(2ft)]7-7KLumens,[1.22m(4ft)]

HazardousRating:Z2-Zone2and21-22

Housing:A-Aluminum

Termination/Wiring:L-LoopIn/Out(3entries,1at

oneendand2attheother)S-Standard(2entriesonthe

sameside)T-ThroughWired(2entries,

oneateachend)

Voltage:BU-UniversalVoltages

120-277Vac,50/60Hz

Options:C-SafetyCables

Lamp Comparison Chart

Catalog Number

Line Current Amps

Input Power

Power Factor THD

Lumens

CRIColor Temp

CCTLength m (ft)

Clear Polycarbonate

LLEDAA2S2BUZ2

[email protected]@277V 22 W >0.95

>0.87 <20% 2,200 70 5650K 0.61(2)

LLEDAA3S2BUZ2

LLEDAA2T2BUZ2

LLEDAA3T2BUZ2

LLEDAA2L2BUZ2

LLEDAA3L2BUZ2

LLEDAA2S5BUZ2

[email protected]@277V 45W >0.95 <20% 4,400 70 5650K 0.61(2)

LLEDAA3S5BUZ2

LLEDAA2T5BUZ2

LLEDAA3T5BUZ2

LLEDAA2L5BUZ2

LLEDAA3L5BUZ2

LLEDAA2S7BUZ2

[email protected]@277V 81W >0.95 <20% 7,800 70 5650K 1.22(4)

LLEDAA3S7BUZ2

LLEDAA2T7BUZ2

LLEDAA3T7BUZ2

LLEDAA2L7BUZ2

LLEDAA3L7BUZ2

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

61

“T” Numbers Represent the Maximum External Surface Temperature

“T” # T1 T2 T3 T4 T5 T6

Temp. Range ºC (●ºF)

301-450 201-300 136-200 101-135 86-100 85

(547-842) (394-572) (277-392) (214-275) (187-212) (185)

T codes provided in catalog pages are based on worst case data. Zone 2 (Gas) and 22 (Dust) locations as designated by the IEC.

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Technical Data

Lamp

Ambient Temperature °C (°F)

Supply Wire Temperature °C (°F)

Zone 2 - 22 Zone 21

LumenOutput Type

GasDust

SurfaceTemperature °C (°F)

DustSurface

Temperature °C (°F)Class of

Temperature °C (°F)

2,200lm LED

40(104) 75(167) T675(167) 54(129) 54(129)

55(131) 75(167) T590(203) 69(156) 69(156)

60(140) 75(167) T590(203) 74(165) 74(165)

65(149) 75(167) T5100(212) 79(174) 79(174)

4,400lm LED

40(104) 75(167) T4129(264) 64(147) 64(147)

55(131) 75(167) T3144(291) 79(174) 79(174)

60(140) 75(167) T3148(298) 84(183) 84(183)

7,800lm LED

40(104) 75(167) T4130(266) 64(147) 64(147)

55(131) 75(167) T3145(293) 79(174) 79(174)

60(140) 75(167) T3149(300) 84(183) 84(183)

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/

AREA

: NEC

/CEC

, ATE

X/IEC

Ex E

NCLO

SED

AND

GASK

ETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

62

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Conduit/Cable Entries Voltage

Ambient Temperature

Weight kg (lb)

Catalog Numbers

Clear Polycarbonate

2,200 Lumens — 0.61 m (2 ft)

M20Standard 120-277Vac,50/60Hz-40°Cupto+65°C (-40°Fupto+149°F)

6.21 (13.7)

LLEDAA2S2BUZ2

M25Standard 120-277Vac,50/60Hz LLEDAA3S2BUZ2

M20ThroughWired 120-277Vac,50/60Hz-40°Cupto+65°C (-40°Fupto+149°F)

6.21 (13.7)

LLEDAA2T2BUZ2

M25ThroughWired 120-277Vac,50/60Hz LLEDAA3T2BUZ2

M20LoopIn/LoopOut 120-277Vac,50/60Hz-40°Cupto+65°C (-40°Fupto+149°F)

6.21 (13.7)

LLEDAA2L2BUZ2

M25LoopIn/LoopOut 120-277Vac,50/60Hz LLEDAA3L2BUZ2

4,400 Lumens — 0.61 m (2 ft)

M20Standard 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)

6.35 (14.0)

LLEDAA2S5BUZ2

M25Standard 120-277Vac,50/60Hz LLEDAA3S5BUZ2

M20ThroughWired 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)

6.35 (14.0)

LLEDAA2T5BUZ2

M25ThroughWired 120-277Vac,50/60Hz LLEDAA3T5BUZ2

M20LoopIn/LoopOut 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)

6.35 (14.0)

LLEDAA2L5BUZ2

M25LoopIn/LoopOut 120-277Vac,50/60Hz LLEDAA3L5BUZ2

7,800 Lumens — 1.22 m (4 ft)

M20Standard 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)

8.69 (19.15)

LLEDAA2S7BUZ2

M25Standard 120-277Vac,50/60Hz LLEDAA3S7BUZ2

M20ThroughWired 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)

8.69 (19.15)

LLEDAA2T7BUZ2

M25ThroughWired 120-277Vac,50/60Hz LLEDAA3T7BUZ2

M20LoopIn/LoopOut 120-277Vac,50/60Hz-40°Cupto+60°C (-40°Fupto+140°F)

8.69 (19.15)

LLEDAA2L7BUZ2

M25LoopIn/LoopOut 120-277Vac,50/60Hz LLEDAA3L7BUZ2

Standard cable entry provides 2 entries on the same side of the housing. Through wired cable entry provides 2 entries, one at each end of the housing. Loop In/Loop Out cable entry provides 3 entries, 1 at one and 2 at the other end of the housing. For optional safety cables, add suffix -C to the end of the catalog number.

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

63

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Accessories and Replacement Parts

Description Catalog Numbers

Mounting Brackets — Set of Two

8.5

9.0mm(0.35")

68m

m(2.68")

30mm(1.18")

49.0mm(1.93")

25.0mm(0.98")

8.5mm

(0.33")

Fixing Brackets for Surface Installation

Zincplatedsteel 316stainlesssteel

FEFBZFEFBS

14.59.5

232mm(9.13")

200mm(7.87")

38.0m

m(1.50")

13.0m

m(0.51")

9.5mm

(0.37")

14.5mm(0.57")

30.0mm(1.18")

Surface Mounting

Aluminum(graypainted)316stainlesssteel

FESBAFESBS

L NPE PEL N

N L PE

Version : L

Dual Loop In/Out - Through Wiring (Single phase)

3 entries, 1 at one end and 2 at the other

Version : S

Standard

2 entries on the same side

Version : T

Through Wiring (3 phases)

2 entries, one at each end

L NPE PEL N L1 NPE PEL1 NL2 L3

L1 N PEL2L3

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/

AREA

: NEC

/CEC

, ATE

X/IEC

Ex E

NCLO

SED

AND

GASK

ETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

64

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Accessories and Replacement Parts

Description Catalog Numbers

Mounting Brackets — Set of Two

Ø 8mm (0.31")

23mmx5.08mm

Ø 8mm (0.31")

Ø 5.08mm (0.20")

Ø 8mm (0.31")

25.4mm

(1.00")

104.9mm

(4.13")

60.5mm

(2.38")

241.3mm

(9.50")

23.9mm

(0.94")

209.6mm

(8.25")

Surface Mounting

14-gaugestainlesssteel FVSM

30°

90

30

60

900

30 60

30°

5.5mm(0.22”)

67.0mm

(2.63”)

41.0mm(1.61”)

82.0mm(3.23”)

13.0mm (0.51”)

M8x1.25mm(1.25")

9.5mm(0.37”)

100.0mm

(3.94”)

32.0mm(1.26”)

18.0mm(0.71”)

14.5mm(0.57”)

132mm(5.20”)

Hinged Brackets for Adjusting Luminaire

Aluminum FEHBA

Half Clamp Brackets for Pole Mounting

For42mmto49mmpole(1-1/4to1-1/2"tube)

Zincplatedsteel FEHC49Z

316stainlesssteel FEHC49S

For60mmpole(2"tube)

Zincplatedsteel FEHC60Z

316stainlesssteel FEHC60S

FVSM does not retrofit in same mounting footprint as Appleton’s FN/FE series.

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

65

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Accessories and Replacement Parts

Description Catalog Numbers

Mounting Brackets — Set of Two

Ø 12.7mm (0.50")

Ø 7.6mm

Ø 8.5mm

(0.30")

(0.34")

38.0mm (1.50")

90mm

196mm

31.8mm194mm

(3.55")

(7.72")

(1.25")(7.64")

Fixed 45˚ Wall Mount

11-gauge(1/8”)stainlesssteel FVWFM

M 8 x 1.25

36.0m

m(1.42")

15.0m

m(0.59")

20.0mm(0.80")

8.0mm(0.32")

M8x1.25mm(1.25")

M8 Ring Bolts

Zincplatedsteel—Forusewithoptionalsafetychain(notprovided) FERBM8Z

Retrofit Brackets — Set of Two

Adaptsmountingholesfor4footfixtureto700mmmountingcenters LLEDRB

Fall Prevention Kit

SafetyCables—Attachedtofixturestoguardagainstthemfallingwhentheprimarymethodofattachmentfails.

LLEDSC

Replacement Drivers

120-277Vacdriver LLEDBU2

Replacement Lenses

ClearPolycarbonatelenswithanintegralgasket LLEDCPL

FVWFM does not retrofit in same mounting footprint as Appleton’s FN/FE series.

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/

AREA

: NEC

/CEC

, ATE

X/IEC

Ex E

NCLO

SED

AND

GASK

ETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

66

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Mounting Options Dimensions in Millimeters (Inches)

FEFBS Ceiling/Surface Mount

30 (1.18)

172 (6.78)

178 (7.01)

● Ø 9(0.35)

68 (2.68)

610 (24.02)

400 (15.75)

(1.92)49

FESBA Aluminum (gray painted)

FESBS 316 stainless steel Ceiling/Surface Mount

30 (1.18)

● Ø 9(0.35)

178 (7.01)

142 (5.59)

38 (1.50)

232 (9.13)

200 (7.87)

610 (24.02)

400 (15.75)

FVSM Ceiling/Surface Mount

25(1.00)

27 (1.08)

● Ø 8(0.31)

131 (5.17)

178 (7.01)

178 (9.50)

210 (8.25)164

(6.46)

610 (24.02)

400 (15.75)

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

67

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Mounting Options Dimensions in Millimeters (Inches)

FEHBA Wall/Hinged Mount

FEHBA

610 (24.02)

102 (4.00)

193 (7.60)

89 (3.51)

132 (5.20)

172 (6.77)

178 (7.01)

MAX.WALL

MOUNT

WALL

Bracket Bolt

193 (7.60) 400

(15.75)

440 (17.32) 40.1

(1.58)

16 (0.63)

75°

FVWFM Wall/Fixed 45° Mount

400 (15.75)

● Ø 12.7(0.50)

38(1.50)

90 (3.54)245

(9.66)

610 (24.02)

196 (7.72)

194 (7.64)

178 (7.01)

244 (9.63)

FERBM8Z Ceiling/Chain Mount

610 (24.02)

400 (15.75)

36 (1.42)

400 (15.75)

178 (7.01)

● Ø 8(0.32) ● Ø 20

(0.80)

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/

AREA

: NEC

/CEC

, ATE

X/IEC

Ex E

NCLO

SED

AND

GASK

ETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

68

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Luminaire Dimensions in Millimeters (Inches)

178.4 mm (7.07”)

113.

0 m

m (4

.45”

)

End View — 0.61 m (2 ft) and 1.22 m (4 ft) Versions

610.0 mm (24.02”)

400.0 mm (15.75”)

530 mm (20.87”)

89.0

mm

(3.5

0”)

Mounting Hole Mounting Hole

C L

Conduit/CableEntry

Conduit/CableEntry

Side View — 0.61 m (2 ft) Versions

610.0 mm (24.02”)

400.0 mm (15.75”)

530 mm (20.87”)

89.0

mm

(3.5

0”)

Mounting Hole Mounting Hole

C L

Conduit/CableEntry

Conduit/CableEntry

Top (Mounting) View — 0.61 m (2 ft) Versions

610.0 mm (24.02”)

1220.0 mm (48.03”)

Conduit/CableEntry

Conduit/CableEntry

400.0 mm (15.75”)

89.0

mm

(3.5

0”)

C L

530 mm (20.87”)Mounting Hole Mounting Hole

Side View — 1.22 m (4 ft) Version

610.0 mm (24.02”)

1220.0 mm (48.03”)

Conduit/CableEntry

Conduit/CableEntry

400.0 mm (15.75”)

89.0

mm

(3.5

0”)

C L

530 mm (20.87”)Mounting Hole Mounting Hole

Top (Mounting) View — 1.22 m (4 ft) Version

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

69

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Photometric Data — DATA SHOWN IS ABSOLUTE

LLEDAA(XY)2BUZ2 with Clear Polycarbonate Lens X = cable entry size, Y = style of termination

Polar Candela Distribution Isoillumination Plot

180° 170° 160° 150° 140°

130°

120°

110°

100°

90°

80°

70°

60°

475

570

380

285

100

200

300

400

500

600

95

0

50°

40°30°20°10°0°

-0° H -22.5° H-45° H-67.5° H

-90° H

2.5 fc 0.5 fc0.2 fc0.1 fc

1 fc

3

2

2

1

1

0

0

1

1

2

2

3

Distance in units of mount height (10ft)

Zonal Lumens and Percentages at 25°CZone Lumens % Luminaire Zone Lumens % Luminaire0-30 424.1 20.2 0-10 46.7 2.20-40 741.2 35.4 10-20 140.9 6.70-60 1521 72.6 20-30 236.4 11.360-90 573.3 27.4 30-40 317.2 15.10-90 2094 100.0 40-50 378.4 18.1

90-180 0.3 0.0 50-60 401.5 19.20-180 2095 100.0 60-70 324.6 15.5

70-80 209.6 10.080-90 39.1 1.990-100 0.3 0.0

LLEDAA(XY)5BUZ2 with Clear Polycarbonate Lens X = cable entry size, Y = style of termination

Polar Candela Distribution Isoillumination Plot

180° 170° 160° 150° 140°

130°

120°

110°

100°

90°

80°

70°

60°

1,400

1,400

1,167

1,167

933

933

700

700

467

467

233

233

0

50°

40°30°20°10°0°

-0° H -22.5° H-45° H-67.5° H

-90° H

10 fc

2.5 fc

2 fc0.5 fc0.2 fc0.1 fc

5 fc

5

3

4

4

2

1

3

0

2

1

1

2

3

4

5

0 1 2 3 4

Distance in units of mount height (10ft)

Zonal Lumens and Percentages at 25°CZone Lumens % Luminaire Zone Lumens % Luminaire0-30 912.8 20.3 0-10 100.4 2.20-40 1593 35.5 10-20 303.6 6.80-60 3282 73.0 20-30 508.8 11.360-90 1206 26.8 30-40 680.0 15.10-90 4488 99.9 40-50 822.5 18.3

90-180 4.5 0.1 50-60 866.3 19.30-180 4492 100.0 60-70 682.0 15.2

70-80 438.3 9.880-90 85.9 1.990-100 4.2 0.1

100-110 0.3 0.0

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/

AREA

: NEC

/CEC

, ATE

X/IEC

Ex E

NCLO

SED

AND

GASK

ETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

70

Viamaster™ LED Series LuminairesFor ATEX and IECEx Governed Hazardous Locations

Photometric Data — DATA SHOWN IS ABSOLUTE

LLEDAA(XY)7BUZ2 with Clear Polycarbonate Lens X = cable entry size, Y = style of termination

Polar Candela Distribution Isoillumination Plot

180° 170° 160° 150° 140°

130°

120°

110°

100°

90°

80°

70°

60°

2,300

2,300

1,917

1,917

1,533

1,533

1,150

1,150

767

767

383

383

0

50°

40°30°20°10°0°

-0° H -22.5° H-45° H-67.5° H

-90° H

10 fc

2.5 fc

2 fc0.5 fc0.2 fc0.1 fc

5 fc

5

3

4

4

2

1

3

0

2

1

1

2

3

4

5

0 1 2 3 4

Distance in units of mount height (10ft)

Zonal Lumens and Percentages at 25°CZone Lumens % Luminaire Zone Lumens % Luminaire0-30 1560 20.0 0-10 170.7 2.20-40 2728 34.9 10-20 518.4 6.60-60 5631 72.1 20-30 870.5 11.260-90 2171 27.8 30-40 1168 15.00-90 7802 100.0 40-50 1406 18.0

90-180 2.8 0.0 50-60 1497 19.20-180 7805 100.0 60-70 1229 15.7

70-80 785.7 10.180-90 156.6 2.090-100 2.7 0.0

ATEX/IECEx: Zones 2 and 22

II 3 GD EPL Gc and Dc Ex nA IIC; Ex tc IIIC IP66/IK08

ATEX/IECEx: Zone 21

II 2 D EPL Db Ex tb IIIC IP66/IK08

LED/AREA: NEC/CEC, ATEX/IECEx ENCLOSED AND GASKETED

Visit our website at www.emerson.com or contact us at (800) 621-1506. © May 2016

71