GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1
18.12.2017
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
2 / 20 EKM 20170103 Revision: 1
Original User Manual
Copyright © 2015 RITZ Instrument Transformers GmbH
All rights reserved. This document may only be partially or completely copied or reproduced with explicit
consent of our company.
This document does not refer to patents, trademarks or other proprietary rights that may be linked to certain
terms or entries. The absence of these entries, however, does not indicate that the corresponding terms or
entries are free of these rights.
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 3 / 20
1 Introduction .............................................................................................. 4
1.1 Liability and Damage ......................................................................... 4
1.2 Product Identification ......................................................................... 5
1.3 Using the User Manual ...................................................................... 5
1.3.1 Validity .................................................................................. 5
1.3.2 Highlighting in the Text ......................................................... 5
2 Safety ....................................................................................................... 7
2.1 Proper Use ........................................................................................ 7
2.2 User Obligations ................................................................................ 7
2.3 Training and Qualification .................................................................. 8
2.4 Safety Instructions ............................................................................. 8
2.5 Other Requirements ........................................................................ 10
2.6 Information and Warning Signs ....................................................... 11
3 Description of the Transformer ............................................................... 11
3.1 Safety Labels ................................................................................... 11
3.2 Technical Data................................................................................. 12
3.3 Ambient Conditions ......................................................................... 12
3.4 Function for revenue metering purposes ......................................... 13
4 Installation .............................................................................................. 13
5 Start-up .................................................................................................. 18
6 Shutdown ............................................................................................... 18
7 Maintenance ........................................................................................... 18
8 Spare parts ............................................................................................. 18
9 Repairs ................................................................................................... 18
10 Disassembly ........................................................................................... 19
11 Disposal ................................................................................................. 19
12 Trouble Shooting .................................................................................... 19
13 Service/Contact ...................................................................................... 20
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
4 / 20 EKM 20170103 Revision: 1
1 Introduction
Keep the user manual as well as all the documents that are in force with
care so that they are:
− always available at the product’s place of usage
− maintained during the entire life time of the product
− available for every user or future owner
Read this user manual carefully prior to start-up of the product and follow
all regulations and instructions so that personal injury and property
damage can be avoided.
All people involved in the operation and maintenance of the product must
be qualified appropriately. They must read and adhere to these
instructions completely.
1.1 Liability and Damage
The manufacturer assumes no liability whatsoever for direct or
consequential damage resulting from improper operation or maintenance.
The product may only be operated by people who are familiar with the
instructions, the product as well as with the national laws, regulations and
requirements concerning work, safety and accident prevention.
The manufacturer is not responsible for any personal injury or property
damage caused by unskilled people or by ignoring the regulations on
work, safety and accident prevention.
No claims for changes to products already delivered can be made from the
data, illustrations and descriptions in this user manual.
The following shall be carried out immediately upon receipt of delivery:
► Check the delivery for transport damage and completeness
► Document defects and damage immediately
► Photograph damaged components
► Send a written report of the damage
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 5 / 20
1.2 Product Identification
For inquiries at the manufacturer the specification of the type classification
and the serial number are necessary.
This information can be found on the rating plate. The rating plate is
usually mounted above the secondary terminals.
1.3 Using the User Manual
1.3.1 Validity
This user manual contains information that is necessary for the operation
of the product.
In addition to the description of the special equipment, the user manual
also contains some abstractions and exemplary images. Therefore, the
equipment of the product may differ from the descriptions and illustrations.
1.3.2 Highlighting in the Text
In order to simplify legibility and overview, different paragraphs or
information are highlighted.
These symbols have the following meaning:
► Carry out the instructions one by one in the order described
Outcome of the action
Measure to avoid consequences of a hazard warning
− List without fixed order
MA* Tightening torque for dry mounting without additional lubricants
(Coefficient of friction μ = 0.14)
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
6 / 20 EKM 20170103 Revision: 1
DANGE
This signal word with danger sign warns of an extremely dangerous
situation in which failure to observe the hazard warning will lead to death
or serious irreversible injury.
WARNING
This signal word with danger sign warns of a dangerous situation in which
failure to observe the hazard warning can lead to death or serious
irreversible injury.
CAUTION
This signal word with danger sign warns of a dangerous situation in which
failure to observe the hazard warning can lead to a slight reversible injury.
NOTICE
This signal word warns of a harmful situation in which failure to observe
the warning can lead to damage to the product or to something in the
surrounding.
This warning sign warns of hazardous electrical voltage, which will result
in death or serious irreversible injury if the hazard warning is not observed.
This mandatory action symbol refers to the requirement to start-up a
grounded product only. Failure to observe this order will result in death or
serious irreversible injury.
This mandatory action symbol refers to the order to carry out works on a
disconnected product only. Failure to observe this order will result in death
or serious irreversible injury.
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 7 / 20
2 Safety
2.1 Proper Use
The product is a shock hazard protected voltage transformer
(subsequently referred to in this manual as transformer only). It serves to
transform a medium voltage into a lower voltage
Operate the transformer only with the values described in chapter
"Description of the Transformer" in section “Technical Data”.
Operate the transformer only in undamaged condition.
The transformer may only be operated by people who fulfil the
requirements. The requirements for personnel are described in chapter
“Safety“ in section “Training and Qualification“.
The user manual is part of the transformer. The transformer is intended to
be used within the scope of this user manual only. The usage of the
transformer not described in this user manual may result in severe
personal injury or death, or in property damage.
Any other or additional use or deviation from the permissible operating
values is considered to be contrary to the intended use of the product.
2.2 User Obligations
The user is responsible for the determination of responsibility,
accountability and supervision of the personnel.
The user must
− ensure that every person operating this transformer has read and
understood these instructions
− inform every person working on the transformer about the enforced
regulations of work, safety and accident prevention
− supply every person working on the transformer with the required
personal protective equipment and instruct these people that
wearing the PPE is mandatory
− train all people working on the transformer periodically and inform
them about the dangers
− ensure that the transformer is operated in safe condition only
− inform him/herself about the hazards arising from auxiliary agents
− only qualified personnel for handling the auxiliary agents shall be
employed
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
8 / 20 EKM 20170103 Revision: 1
2.3 Training and Qualification
Failure to operate the transformer properly or working on the transformer
improperly may result in serious personal injury or death.
In order to avoid accidents, every person working on the transformer must
meet the following minimum requirements:
− be a qualified electrician or a trained person under the supervision
of a qualified electrician
− can carry out works on the transformer safely and within the scope
of this user manual
− understood the user manual and can implement the user manual
accordingly
2.4 Safety Instructions
High Voltage in the Working Area
The transformer is under high voltage when in operation. The transformer
can be under high voltage when in the connected state and not grounded
on the high voltage side. This can cause serious personal injury or death.
Switch off the high voltage source and secure against restarting
prior to any works on the transformer, such as installation,
maintenance and rectification of malfunctions. See chapter
“Installation” in section “Working in a Voltage-free Condition“.
Constructional Modifications
Constructional modifications can affect the functionality and operational
safety of the transformer. This can cause serious personal injury or death.
Adjacent equipment can be damaged as well.
Never perform constructional modifications on the transformer
Deviating Conditions in Operation
Deviating operational conditions can impair the functionality and
operational safety of the transformer. This can cause serious personal
injury or death.
Operate only with the data stated in chapter “Description of the
Transformer" in sections "Technical Data" and "Ambient Conditions”
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 9 / 20
Transport and Assembly
Loads can swivel and fall during lifting operations. Likewise, insufficiently
supported and fixed transformers can fall or tilt, especially at assembly on
a ceiling and/or wall. This can cause serious personal injury or death.
Carry out the transport properly. See chapter “Installation“ in
section “Transport of the Transformer“
Always fixate the transformer. See chapter "Installation“ in section
"Mounting of the Transformer“
Incorrect Connection with the high voltage terminal
Not suitable cable plugs and non-elastic connection with the high voltage
terminal can impair the functionality and operational safety of the
transformer. This can cause severe personal injury or death.
Never apply incorrect forces on the primary terminal, this applies
also in the event of switching and thermal expansion
Always use elastic connection and support the connector cable
Only use matching plugs. See chapter „Installation“ in section „High
Voltage Connection“
Short circuit at Secondary Terminals
Short circuited secondary terminals overload the windings thermally and
the transformer will be destroyed within a short time. This can cause
serious personal injury or death.
Never short circuit secondary terminals. See chapter “Installation“
in section “Secondary Connection“ and “Secondary Connector of
the Earth-fault Winding (Optional)“
High Voltage on the Earthed Terminal of the Primary Winding
The non-grounded earthed terminal of the primary winding is under high
voltage.
Never remove the connection between earthed terminal of the
primary winding and the base plate. See chapter “Installation” in
section “Ground-sided Terminal of the Primary Winding“.
Always ground the earthed terminal of the primary winding.
Always ground the base plate or the housing
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
10 / 20 EKM 20170103 Revision: 1
Damage on the Transformer
Damage can impair the functionality and operational safety of the
transformer. This can cause severe personal injury or death.
Take damaged transformers out of service immediately.
Contact the manufacturer if necessary (see chapter
“Service/Contact“)
Improper Auxiliary Agents
Auxiliary agents that do not meet the requirements of the manufacturer
may impair the operational safety of the transformer and can cause
accidents. This can cause serious personal injury or death.
Use auxiliary agents only that meet the requirements
Safe Handling of Auxiliary Agents
Depending on the chemical composition, the used auxiliary agents can
pose hazards. This may cause personal injury.
Adhere to the safety data sheets of the auxiliary agents. Observe
all information and regulations given in the safety data sheet
Operation only after proper Start-up
Without proper start-up in accordance with this manual, the operational
safety of the transformer is not guaranteed. This can cause accidents and
may result in serious personal injury or death.
► Use transformer only after proper start-up. See chapter “Start-up“
Technically Faultless Condition of the Transformer
Improper handling or maintenance can affect the operational safety of the
transformer. This can cause accidents and may result in serious personal
injury or death.
Carry out works on the transformer only according to the
instructions
2.5 Other Requirements
In addition to this user manual, the applicable national laws, regulations
and requirements as amended must be adhered to.
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 11 / 20
2.6 Information and Warning Signs
Keep Safety Labels visible
Safety labels on the transformers warn against dangers at hazardous
locations and are an important part of the safety equipment of the
transformer. Missing safety labels increase the risk of severe or deadly
personal injuries.
Clean dirty safety labels.
Renew damaged or unrecognizable labels immediately.
For safety labels see chapter “Description of the Transformer“ in
section “Safety Labels“
3 Description of the Transformer
Metal-clad voltage transformers with cast resin insulation for indoor use.
The transformer is single-poled insulated. The primary connection
complies with EN 50181 for the connection of a fully insulated high voltage
cable. Housing and base plate are conductively connected to one another.
3.1 Safety Labels
The following symbols and information signs are located on the
transformer.
Always ground housing
Never loosen connection between
earthed primary terminal and base plate
Never short-circuit secondary windings
Work on voltage-free device only
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
12 / 20 EKM 20170103 Revision: 1
3.2 Technical Data
Dimensions: Width Height Length
GBEAN 12/0…24/0 148 275 310
GBEA 36 Gr. 1 235 299 419
Weight: See rating plate
Electrical Data See rating plate
Standard See rating plate
High-voltage Connection External cone for connection of an internal
cone plug according to EN 50181, connecting
type see information sign
Earth-side primary winding
end
Connected to base plate
Secondary Connection Terminal Block 0,5…10 mm² (8…22 AWG)
3.3 Ambient Conditions
For deviating ambient conditions see data sheet and rating plate.
Use in interior only.
Never use in explosive areas.
Installation height up to 1,000 meters
Protection class EN 60529 IP20
Nominal operation
conditions
Temperature -5°Celcius to +40°Celcius
Relative humidity 5% to 90%
Storage and transport
conditions
Temperature -5°C to +40°Celcius
Relative humidity 5% to 95% without condensation
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 13 / 20
3.4 Function for revenue metering purposes
The sensor consists of the primary side the transformer and the
processing of the measured data takes place on the measurement chain
consisted of the transformer and an authorized meter for electricity.
On transformers with several secondary windings the secondary windings
for revenue metering are marked with a “Z” on the rating plate.
4 Installation
Working in a Voltage-free Condition
DANGER
High voltage in conductive components
Danger to life due to electrical shock
► Switch off high voltage source
► Secure against restart
► Ensure there is no voltage
► Grounding
► Cover or block neighbouring parts that are under voltage
Transport of the Transformer
WARNING
Danger to life due to hovering loads
Loads can swing and fall during lifting operations. This can cause serious
personal injury or death.
Never step underneath or in the swivel range of hovering loads.
Move loads only under supervision.
Use only admitted lifting gear and slings with sufficient load-bearing
capacity.
Use only lifting gear in faultless condition
► Lift and transport transformers by an appropriate lifting gear on the
lifting eye bolts
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
14 / 20 EKM 20170103 Revision: 1
Mounting of the Transformer
WARNING
Danger of injury due to falling or tilting transformer
Insufficiently supported and fixated transformers, especially for wall and
ceiling mounting, can fall or tilt. This can cause severe personal injury or
death
► Support and fixate the transformer
NOTICE
Damage due to uneven mounting surface
Base plate may be damaged by uneven mounting surfaces
► Level out uneven surfaces
► Set down transformer on even mounting surface
► Tighten base plate
o GBEAN 12/0…24/0 screw fitting with M8
o GBEA 36 Gr. 1 screw fitting with M12
► Release lifting gear from transport device
Establish Touch Protection and Grounding Terminal
DANGER
High voltage on non-grounded housing
Danger to life by non-grounded base plate and housing
► Connect base plate by means of screw fitting electrically
conductive with grounding point of the equipment
► GBEA 36 Gr. 1: Connect alternative grounding connector on
housing (M10, MA* = 30 Nm) electrically conductive to grounding
point of the equipment
Prepare Terminal Area
Establish access to the terminal area for the electrical connection
► Release and remove terminal box lid.
► Feed the cable through the cable bushings
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 15 / 20
Secondary Connector of the Earth-fault Winding (Optional)
Connect the secondary terminals of the transformer’s earth-fault winding
to the secondary connectors
WARNING
Danger to life due to short-circuited secondary winding
Bursting of the transformer due to thermally overloaded secondary
windings within a very short time
Never short-circuit secondary windings.
Ground the earth-connecting windings connected in the open
triangle only on one of the three transformers
► Insert stripped ends (11 mm) of the cables in the respective
terminal block and screw tightly (MA* = 0,8 Nm)
► Connect a maximum of one terminal per secondary winding in the
middle of the terminal block to the base plate via the attached
screw (MA* = 0,8 Nm)
Secondary Connection
Connect the secondary terminals of the transformer to the secondary
cables
WARNING
Danger to life due to short-circuited secondary winding
Bursting of the transformer due to thermally overloaded secondary
windings within a very short time
Never short-circuit secondary windings
► Insert stripped ends (11 mm) of the cables in the respective
terminal block and screw tightly (MA* = 0,8 Nm)
► Connect a maximum of one terminal per secondary in the middle of
the terminal block winding to the base plate via the attached screw
(MA* = 0,8 Nm)
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
16 / 20 EKM 20170103 Revision: 1
Ground-sided Terminal of the Primary Winding
DANGER
High voltage on earth-sided terminal of primary winding
Danger to life due to non-grounded earth-sided terminal of the primary
winding
Never open a factory-fitted ground connection of the earth-sided
terminal of the primary winding.
Always ground the earth-sided terminal of the primary winding
Cover Terminal Area
Establish operating status of the terminal area
► Screw terminal box lid tightly (MA* = 2,5 Nm)
High Voltage Connection
Connect primary connection of the transformer to the high voltage cable
WARNING
Risk of injury due to improper handling of auxiliary agents
Improper handling of auxiliary agents may endanger people. This can
cause personal injury
Consider the safety data sheets of the auxiliary agents
NOTICE
Damage due to wrong connection type of cable plug
Improper cable plugs may damage the transformer
Use only cable plugs stated on the information sign of the
transformer
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 17 / 20
NOTICE
Damage due to improper auxiliary agents
Improper auxiliary agents can damage the surface
Use only auxiliary agents approved by the manufacturer
► Remove transport protection.
► Clean surface of outer cone on primary connection (recommended
detergent: cleaning benzine, Acetone)
► Thinly rub the surface of the outer cone with silicone grease
(recommended silicone grease: Pfisterer MV-Special grease)
► Clean the surface of the isolation part on the plug (recommended
detergent: cleaning benzine, Acetone).
► Thinly rub the surface of the isolation part with silicone grease
(recommended silicone grease: Pfisterer MV-Special grease)
Connecting type A / Connecting type B:
► Place plastic cords on the cone surface of the outer
cone (ø2 mm, e.g. from nylon)
► Plug the high voltage cable to the outer cone until the
flange of the cable is shortly before the housing
► Remove plastic cords
► Pull up the high voltage cable to the housing by using
a suitable mounting device and screw tightly
► Fasten and ground the high voltage cable according
the manufacturer recommendation
Connecting type C
► Plug the high voltage cable to the outer cone
► Screw the plug to the primary terminal by the screwed
contact of the plug
► Tighten sealing plug on the rear side of the screwed
contact
► Press end cap on the screwed contact and the rear
side of the plug
► Fasten and ground the high voltage cable according
the manufacturer recommendation
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
18 / 20 EKM 20170103 Revision: 1
5 Start-up
Pre-Condition
The transformer is installed and connected according to this manual. The
high voltage cable has been connected to the transformer for at least one
hour.
► Switch on the voltage supply
6 Shutdown
► Switch off the voltage at the transformer and in the work
environment. See chapter “Installation“ in section “Working in a
Voltage-free Condition“
7 Maintenance
The transformer is free of maintenance
8 Spare parts
None
9 Repairs
On-site repairs are not possible. Contact the manufacturer if necessary
(see chapter “Service/Contact“).
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
EKM 20170103 Revision: 1 19 / 20
10 Disassembly
► Switch off the voltage at the transformer and in the working area.
See chapter “Installation“ in section “Working in a Voltage-free
Condition“
► Loosen screws on the flange of the high voltage cable.
► Remove high voltage cable.
► Loosen and remove terminal box lid.
► Loosen secondary cables and pull out from terminal block.
► Re-screw terminal box lid tightly.
► Loosen possible separate ground connection if necessary.
► Loosen screw connection of fastening angle.
► Transport the transformer to its new location. See chapter
“Installation“ in section “Transport of the Transformer“
11 Disposal
− Dispose of packaging materials properly.
− Dispose of demounted plastic and metal parts separately and
properly.
− Dispose of cast resin body including metal housing according to
national, regional and local waste management regulations
12 Trouble Shooting
Work in a Voltage-free Condition
DANGER
High voltage in conducting components
Danger to life due to electrical shock
► Switch off voltage of high voltage source.
► Secure against restart.
► Ensure there is no voltage.
► Grounding.
► Cover or block neighbouring parts that are under voltage
User manual
GBEAN 12/0...24/0; GBEA 36 Gr. 1
20 / 20 EKM 20170103 Revision: 1
Please contact the manufacturer if the measures below do not correct the
malfunction or if other malfunctions not listed here occur (see chapter
“Service/Contact “)
Malfunction Possible Cause Remedy
No measurement
signal
Loose connection
cable
Check secondary terminals, see
chapter “Installation“ in section
“Secondary Connection”
Transformer
damaged
Check transformer and replace
if necessary
Faulty measurement
signal
Deviating electrical
burden
Operation according to nominal
data on rating plate
Connections wrongly
poled
Match connecting cables
correctly
Transformer
damaged
Check transformer and replace
if necessary
Voltaged Housing Housing not
grounded
Check grounding connection,
see chapter “Installation“ in
section “Establish Touch
Protection and Grounding
Terminal”