F, V, W SeriesElectromagnetic flowmeterFull-bore flow sensors
The perfect fit for all water industry applications
Introduction
ABB’s full-bore FEF, FEV and FEW electromagnetic flowmeter sensors are available with either an AquaMaster 3 or a WaterMaster transmitter.
AquaMaster 3 and WaterMaster are a range of high performance electromagnetic flowmeters for the measurement of electrically conductive fluids and are supplied as factory-configured and calibrated systems.
This User Guide provides end-user details for installation and connection.
This User Guide should be used in conjunction with the following publications:
– AquaMaster 3 FET200 electromagnetic flowmeter transmitter User Guide (OI/FET200–EN)
– WaterMaster FET100 electromagnetic flowmeter transmitter User Guide (OI/FET100–EN)
The CompanyWe are an established world force in the design and manufacture of instrumentation for industrial process control, flow measurement, gas and liquid analysis and environmental applications.
As a part of ABB, a world leader in process automation technology, we offer customers application expertise, service and support worldwide.
We are committed to teamwork, high quality manufacturing, advanced technology and unrivalled service and support.
The quality, accuracy and performance of the Company’s products result from over 100 years experience, combined with a continuous program of innovative design and development to incorporate the latest technology.
Quality Control
The UKAS Calibration Laboratory No. 0255 is just one of the ten flow calibration plants operated by the Company and is indicative of our dedication to quality and accuracy.
UKAS Calibration Laboratory No. 0255
����
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors
OI/FEF/FEV/FEW–EN 1
1 Safety ............................................................................................................................................... 21.1 Electrical Safety ............................................................................................................................................. 21.2 Symbols ........................................................................................................................................................ 21.3 Health & Safety ............................................................................................................................................. 3
2 Mechanical Installation .................................................................................................................... 42.1 Unpacking .................................................................................................................................................... 42.2 Installation Conditions ................................................................................................................................... 4
3 Electrical Installation ....................................................................................................................... 83.1 Grounding ..................................................................................................................................................... 83.2 Cable Preparation (Remote Transmitter Only) .............................................................................................. 11
3.2.1 Sensor Cable Connections (Remote WaterMaster Transmitter Only) ............................................. 113.2.2 Sensor Cable Connections (Remote AquaMaster 3 Transmitter Only) ........................................... 12
3.3 Environmental Protection ............................................................................................................................ 13
4 Specification .................................................................................................................................. 14
5 Sensor dimensions ........................................................................................................................ 21
Notes .................................................................................................................................................... 26
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 1 Safety
1 SafetyInformation in this manual is intended only to assist our customers in the efficient operation of ourequipment. Use of this manual for any other purpose is specifically prohibited and its contents are not to bereproduced in full or part without prior approval of the Technical Publications Department.
1.1 Electrical SafetyThis equipment complies with the requirements of CEI/IEC 61010-1:2001-2 'Safety Requirements forElectrical Equipment for Measurement, Control and Laboratory Use' and complies with NIST and OSHA.
If the equipment is used in a manner NOT specified by the Company, the protection provided by theequipment may be impaired.
1.2 SymbolsOne or more of the following symbols may appear on the equipment labelling:
Warning – Refer to the manual for instructions Direct current supply only
Caution – Risk of electric shock Alternating current supply only
Protective earth (ground) terminal Both direct and alternating current supply
Earth (ground) terminal The equipment is protected through double insulation
2 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 1 Safety
1.3 Health & Safety
Health and Safety
To ensure that our products are safe and without risk to health, the following points must be noted:
The safety requirements of this equipment, any associated equipment and the local environment must be taken into consideration during installation.
Install and use this equipment and any associated equipment in accordance with the relevant national and local standards.
The relevant sections of these instructions must be read carefully before proceeding.
Warning labels on containers and packages must be observed.
Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with the information given.
Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating in conditions of high pressure and / or temperature.
Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling procedures must be used.
When disposing of chemicals ensure that no two chemicals are mixed.
Product liability – advice and assistance provided without charge is given in good faith but without liability.
Safety advice concerning the use of the equipment described in this manual or any relevant hazard data sheets (where applicable) may be obtained from the Company address on the back cover, together with servicing and spares information.
Warning.
System configuration must be carried out only by users or personnel with approved access rights(user privileges).
Read all relevant sections of this guide before configuring the system or modifying systemparameters.
Install and use associated equipment in accordance with the relevant national and localstandards.
OI/FEF/FEV/FEW–EN 3
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 2 Mechanical Installation
2 Mechanical Installation
2.1 Unpacking
2.2 Installation Conditions
Fig. 2.1 Unpacking
Caution. Visually inspect equipment for damage before installing. Do not install damaged or faultyequipment.
Caution. Do NOT exceed the maximum working pressure marked on the equipment.
Fig. 2.2 Spillage
Fig. 2.3 Vibration
4 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 2 Mechanical Installation
Fig. 2.4 Localized Heat
Fig. 2.5 Siting
Fig. 2.6 Within Temperature Limits
Fig. 2.7 Straight Pipe Requirements
Allow room to read display or data plate
70 °C (158 °F) Max.
– 20 °C(– 4 °F)
Min.
Min.Min.
>5 Pipe Diameters0 Pipe Diameter
Flow Direction
OI/FEF/FEV/FEW–EN 5
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 2 Mechanical Installation
Fig. 2.8 Fluid Level
Fig. 2.9 Above Ground
Fig. 2.10 Temperature Difference
Fig. 2.11 Within Environmental Rating
Supports
IP68 (NEMA 6)
Sensor Submersion: Continuous
6 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 2 Mechanical Installation
Fig. 2.12 Underground
Note. For further details when burying flow sensors contact the ABB Service Organization.
Fig. 2.13 Cable Routing
Fig. 2.14 Gasket Fitting
Fig. 2.15 Separation of Sensors
Protection Plate Recommended
Backfill
Fit Gaskets
Gaskets Same Size as Pipe
0.7 m (2.3 ft) Min.
OI/FEF/FEV/FEW–EN 7
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 3 Electrical Installation
3 Electrical Installation
3.1 Grounding
Caution. For safety reasons and optimum performance, the flowmeter, pipelines and medium must becorrectly bonded and grounded according to regulations.
Do not ground cathodically-protected pipelines to an external earth.
Note.
The flow sensor must not be connected to a ground spike.
For bonding connections use 4mm2 (< 10AWG) cable.
Fig. 3.1 Cross Bonding – All Flanged Pipes
Arrangement Number of Fluid Contact Rings
AquaMaster 3 Transmitter 2
WaterMaster Transmitter 1 minimum
Insulating Pipe 2
Table 3.1 Fluid Contact Rings
Fluid Contact Rings
To Transmitter
8 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 3 Electrical Installation
Fig. 3.2 Cross Bonding – Flange Adapter
Fig. 3.3 AquaMaster 3 Transmitter Mounted in a Chamber (Battery Version Shown)
OI/FEF/FEV/FEW–EN 9
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 3 Electrical Installation
Fig. 3.4 AquaMaster 3 Transmitter Mounted in a Cabinet (Battery Version Shown)
Fig. 3.5 WaterMaster Remote Transmitter Mounted in a Roadside Cabinet
Power Supply
10 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 3 Electrical Installation
3.2 Cable Preparation (Remote Transmitter Only)
To prepare the cable for connection at the transmitter and sensor terminal blocks:
1. Remove the outer cable insulation and Mylar® wrap.
2. Ensure the drain wire is sleeved.
3. Cut the cable connection wires to the lengths shown.
3.2.1 Sensor Cable Connections (Remote WaterMaster Transmitter Only)
Caution. Maintain Environmental Protection at all times – See Section 3.3, page 13.
Caution.
Make connections only as shown.
Twist the screen wire of D1 / TFE + D2 with the outer screen drain wire and sleeve them green / yellow.
Ensure the seal and mating surfaces are clean to maintain environmental rating.
Conduit connections must provide cable entry sealing.
Ensure cable glands are tightened after wiring. Do not overtighten the plastic cable glands to avoid destroying their sealing properties. Initially, tighten finger-tight, then a further 1/2 to 3/4 turn using a suitable spanner or wrench.
Fig. 3.6 Sensor Cable Connections – WaterMaster Transmitter
Screen to
Internal Earthfor NPT Variants
*Inner Wire**For Cathodically Protected Systems connect the drain wire to terminal PE.
**Drain Wire (Twisted with Screen Wire from D1/TFE – Orange and D2 – Yellow)for M20 Versions connect to PE
S1 Violet (Screen)
Cut cables to 60 mm (2.35 in)
E1 Violet (*Signal)
E2 Blue (*Signal)
S2 Blue (Screen)
3 Green (Sleeve)
D2 Yellow
D1/TFE Orange PE (Screen)
M2 Red
M1 Brown
OI/FEF/FEV/FEW–EN 11
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 3 Electrical Installation
3.2.2 Sensor Cable Connections (Remote AquaMaster 3 Transmitter Only)
Caution.
Twist the three screen wires together and sleeve them.
Keep cable pairs twisted.
Make connections only as shown.
Maintain Environmental Protection at all times.
Conduit connections must provide cable entry sealing.
Fig. 3.7 Sensor Cable Connections – AquaMaster 3 Transmitter
Drain / Screen
to Internal Earthfor NPT Gland
Cut cables to 60 mm (2.35 in)
7 Violet
6 Blue
5 Green
4 Yellow
3 Orange
2 Red
1 Brown
Drain / Screen Wire for M20 Gland
12 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 3 Electrical Installation
3.3 Environmental Protection
Fig. 3.8 Potting the Sensor Terminal Box
Warning.
Potting materials are toxic. Read the manufacturers' instructions carefully before preparing thepotting material and use suitable safety precautions.
Power up and check all connections before potting.
The remote sensor terminal box connections must be potted immediately on completion toprevent the ingress of moisture.
Do not overfill or allow the potting material to come into contact with 'O' rings or grooves.
Do not let potting material enter conduit (if used).
OI/FEF/FEV/FEW–EN 13
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 4 Specification
4 Specification
WaterMaster FEV1, FEF1 and FEW1 Flow Performance – m3/h
Standard Calibration0.4 % Class 2
High Accuracy Calibration0.2 % Class 1
Q4 Q3 Q0.4% Q2 Q1 Q0.2% Q2 Q1
DN (m3/h) (m3/h) (m3/h) (m3/h) (m3/h) (m3/h) (m3/h) (m3/h)
10 3.1 2.5 0.167 0.013 0.008 0.31 0.02 0.012
15 7.88 6.3 0.42 0.032 0.02 0.79 0.05 0.03
20 12.5 10 0.67 0.05 0.032 1.25 0.08 0.05
25 20 16 1.1 0.08 0.05 2 0.13 0.08
32 31.25 25 1.67 0.13 0.08 3 0.20 0.13
40* 50 40 4.2 0.2 0.13 6 0.32 0.2
50* 79 63 4.2 0.32 0.20 7.9 0.5 0.32
65* 125 100 6.7 0.5 0.32 12.5 0.8 0.5
80* 200 160 10.7 0.81 0.51 16 1.3 0.8
100* 313 250 16.7 1.3 0.79 25 2 1.25
125* 313 250 16.7 1.3 0.79 25 2 1.25
150* 788 630 42 3.2 2.0 63 5 3.2
200* 1,250 1,000 67 5.1 3.2 100 8 5
250 2,000 1,600 107 8.1 5.1 160 13 8
300 3,125 2,500 167 12.7 7.9 250 20 12.5
350 5,000 4,000 267 20.3 12.7 400 32 20
400 5,000 4,000 267 20.3 12.7 400 32 20
450 7,875 6,300 420 32 20 630 50 32
500 7,875 6,300 420 32 20 630 50 32
600 12,500 10,000 667 51 32 1000 80 50
700 20,000 16,000 1600 102 64 1600 160 100
30 in 20,000 16,000 1600 102 64 1600 160 100
800 20,000 16,000 1600 102 64 1600 160 100
900 31,250 25,000 2500 160 100 2500 250 156
1000 31,250 25,000 2500 160 100 2500 250 156
42 in 31,250 25,000 2500 160 100 2500 250 156
1200 50,000 40,000 4000 256 160 4000 400 250
1400 78,750 63,000 6300 403 252 6300 630 394
60 in 78,750 63,000 6300 403 252 6300 630 394
1600 78,750 63,000 6300 403 252 6300 630 394
1800 125,000 100,000 10000 640 400 10000 1000 625
2000 125,000 100,000 10000 640 400 10000 1000 625
2200 200,000 160,000 16000 1024 640 16000 1600 1000
* OIML R49 Certificate of Conformance to Class 1 and Class 2, with OIML R49 and M10 versions available.
Note. OIML R49–1 allows Class 1 only for meters with Q3 ³ 100 m3/h. Meters outside this range have been tested and conform to Class 1.
14 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 4 Specification
WaterMaster FEV1, FEF1 and FEW1 Flow Performance – gal/min
Standard Calibration0.4 % Class 2
High Accuracy Calibration0.2 % Class 1
Q4 Q3 Q0.4% Q2 Q1 Q0.2% Q2 Q1
NPS/NB (DN) (gal/min) (gal/min) (gal/min) (gal/min) (gal/min) (gal/min) (gal/min) (gal/min)3/8 (10) 13.8 11 0.73 0.06 0.035 1.38 0.09 0.0531/2 (15) 34.7 27.7 1.85 0.14 0.09 3.48 0.22 0.143/4 (20) 55 44 2.94 0.22 0.14 5.5 0.35 0.22
1 (25) 88 70.4 4.7 0.35 0.22 8.8 0.57 0.35
1 1/4 (32) 137.6 110 7.3 0.57 0.35 13.2 0.88 0.57
1 1/2 (40) 220 176 18.5 0.89 0.56 26.4 1.41 0.88
2 (50) 347 277 18.5 1.41 0.88 34.7 2.22 1.39
2 1/2* (65*) 550 440 29.4 2.24 1.40 55.0 3.52 2.20
3 (80) 881 704 47.0 3.58 2.24 70.4 5.64 3.52
4 (100) 1,376 1,101 73.4 5.59 3.49 110 8.81 5.50
5* (125*) 1,376 1,101 73.4 5.59 3.49 110 8.81 5.50
6 (150) 3,467 2,774 185 14.1 8.81 277 22.2 13.9
8 (200) 5,504 4,403 294 22.4 14.0 440 35.2 22.0
10 (250) 8,806 7,045 470 35.8 22.4 704 56.4 35.2
12 (300) 13,759 11,007 734 55.9 34.9 1,101 88.1 55.0
14 (350) 22,014 17,611 1,174 89.5 55.9 1,761 141 88.1
16 (400) 22,014 17,611 1,174 89.5 55.9 1,761 141 88.1
18 (450) 34,673 27,738 1,849 141 88.1 2,774 222 139
20 (500) 34,673 27,738 1,849 141 88.1 2,774 222 139
24 (600) 55,036 44,029 2,935 224 140 4,403 352 220
27/28** (700) 88,057 70,446 7,045 451 282 7,045 704 440
30 (760) 88,057 70,446 7,045 451 282 7,045 704 440
32 (800) 88,057 70,446 7,045 451 282 7,045 704 440
36 (900) 137,590 110,072 11,007 704 440 11,007 1,100 688
39/40** (1000) 137,590 110,072 11,007 704 440 11,007 1,100 688
42 (1050) 137,590 110,072 11,007 704 440 11,007 1,100 688
48 (1200) 220,143 176,115 17,611 1,127 704 17,611 1,761 1,101
54 (1400) 346,726 277,381 27,738 1,775 1,110 27,738 2,773 1,733
60 (1500) 346,726 277,381 27,738 1,775 1,110 27,738 2,773 1,733
66 (1600) 346,726 277,381 27,738 1,775 1,110 27,738 2,773 1,733
72 (1800) 550,358 440,287 44,029 2,818 1,761 44,029 4,403 2,752
78 (2000) 550,358 440,287 44,029 2,818 1,761 44,029 4,403 2,752
84 (2200) 880,573 704,459 70,446 4,509 2,818 70,446 7,045 4,403
*Future option**Size is dependent on flange specification
OI/FEF/FEV/FEW–EN 15
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 4 Specification
AquaMaster 3 FEV2, FEF2 AC-powered Full-bore Sensors – Flow Performance
Class 2 specification Class 1 specification
Size Q4 Q3 Q(0.5%) Q2 Q1 R Q2 Q1
Rmm in. m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)
40 11/2 50 (220)
40 (176)
4 (18)
0.20 (0.88)
0.13 (0.57) 315 0.32
(1.40)0.20 (0.88) 200
50 2 79 (247)
63 (277)
6.3 (28)
0.32 (1.41)
0.20 (0.88) 315 0.50
(2.20)0.32 (1.41) 200
65 21/2125 (550)
100 (440)
10 (44)
0.50 (2.20)
0.32 (1.41) 315 0.80
(3.52)0.50 (2.20) 200
80 3 200 (880)
160 (700)
16 (70)
0.81 (3.56)
0.51 (2.24) 315 1.30
(5.72)0.8
(3.52) 200
100 4 313 (1377)
250 (1100)
25 (110)
1.3 (5.72)
0.79 (3.47) 315 2.00
(8.80)1.25 (5.5) 200
125 5 313 (1377)
250 (1100)
25 (110)
1.3 (5.72)
0.79 (3.47) 315 2.00
(8.80)1.25 (5.5) 200
150 6 788 (3470)
630 (2770)
63 (277)
3.2 (14.08)
2.00 (8.80) 315 5.00
(22.00)3.2
(14.08) 200
200 8 1250 (5500)
1000 (4400)
100 (440)
5.1 (22.44)
3.2 (14.08) 315 8.0
(35.20)5.0
(22.00) 200
250 10 2000 (8800)
1600 (7040)
160 (700)
8.1 (35.64)
5.1 (22.44) 315 13.0
(57.20)8.0
(35.20) 200
300 12 3125 (13750)
2500 (11007)
250 (1100)
12.7 (55.88)
7.9 (34.76) 315 20.0
(88.00)12.5
(55.00) 200
350 14 5000 (22000)
4000 (17610)
400 (1760)
20.3 (89.32)
12.7 (55.88) 315 32.0
(14.08)20.0
(88.00) 200
400 16 5000 (22000)
4000 (17610)
400 (1760)
20.3 (89.32)
12.7 (55.88) 315 32.0
(14.08)20.0
(88.00) 200
450 18 7875 (34760)
6300 (27740)
630 (2770)
32.0 (140.8)
20.0 (88.00) 315 50.0
(220.00)32.0
(140.8) 200
500 20 7875 (34650)
6300 (27740)
630 (2770)
32.0 (140.8)
20.0 (88.00) 315 50.0
(220.00)32.0
(140.8) 200
600 24 12500 (55000)
10000 (44000)
1000 (4400)
51.0 (224.4)
32.0 (140.8) 315 80.0
(352.0)50.0
(220.0) 200
16 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 4 Specification
AquaMaster 3 FEV2, FEF2 Battery / Renewable Energy Full-bore Sensors – Flow Performance
Class 2 specification Class 1 specification
Size Q4 Q3 Q(0.25%) Q2 Q1 R Q2 Q1
Rmm in. m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)m3 / h
(Ugal / min)
40 11/2 50 (220)
40 (176)
2.7 (11.8)
0.4 (1.8)
0.25 (1.1) 160 0.64
(2.8)0.4 (1.8) 100
50 2 79 (247)
63 (277)
4.2 (18.5)
0.63 (2.8)
0.39 (1.71) 160 1.0
(4.4)0.63 (2.8) 100
65 21/2125 (550)
100 (440)
6.7 (29.5)
1.0 (4.4)
0.6 (1.41) 160 1.6
(7.0)1.0 (4.4) 100
80 3 200 (880)
160 (700)
10.7 (47.0)
1.6 (7.0)
1.0 (4.4) 160 2.6
(11.4)1.6 (7.0) 100
100 4 313 (1377)
250 (1100)
16.7 (73.5)
2.5 (11.0)
1.6 (7.0) 160 4.0
(17.6)2.5
(11.0) 100
125 5 313 (1377)
250 (1100)
16.7 (73.5)
2.5 (11.0)
1.6 (7.0) 160 4.0
(17.6)2.5
(11.0) 100
150 6 788 (3470)
630 (2770)
42.0 (184.8)
6.3 (27.7)
3.9 (17.1) 160 10.0
(44.0)6.3
(27.7) 100
200 8 1250 (5500)
1000 (4400)
67.0 (294.8)
10.0 (44.0)
6.0 (26.4) 160 16.0
(70.0)10.0 (44.0) 100
250 10 2000 (8800)
1600 (7040)
107.0 (470.8)
16.0 (70.0)
10.0 (44.0) 160 26.0
(110.4)16.0 (70.0) 100
300 12 3125 (13750)
2500 (11007)
167.0 (734.8)
25.0 (110.0)
15.6 (68.6) 160 40.0
(176.0)25.0
(110.0) 100
350 14 5000 (22000)
4000 (17610)
267.0 (1174.8)
40.0 (176.0)
25.0 (110.0) 160 64.0
(281.6)40.0
(176.0) 100
400 16 5000 (22000)
4000 (17610)
267.0 (1174.8)
40.0 (176.0)
25.0 (110.0) 160 64.0
(281.6)40.0
(176.0) 100
450 18 7875 (34760)
6300 (27740)
420.0 (184.8)
63.0 (277.0)
39.0 (171.6) 160 101.0
(444.4)63.0
(277.0) 100
500 20 7875 (34650)
6300 (27740)
420.0 (184.8)
63.0 (277.0)
39.0 (171.6) 160 101.0
(444.4)63.0
(277.0) 100
600 24 12500 (55000)
10000 (44000)
667.0 (2934.8)
100.0 (440.0)
63.0 (277.0) 160 160.0
(704.0)100.0 (440.0) 100
OI/FEF/FEV/FEW–EN 17
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 4 Specification
Functional Specification
Pressure limitationsAs per flange rating – non approved PN16 for OIML R49/MID Approved
Temperature limitations
Environmental protectionRating:
IP68 (NEMA 6) to 10m (33 ft) depth (not DN10 to DN32)
IP67 (NEMA 4X) – DN10 to DN32
Buriable (sensor only)FEW No
FEV, FEF to 5 m (16 ft) Yes
Conductivity>5µS cm–1 (WaterMaster Transmitter)
>50µS cm–1 (AquaMaster 3 Transmitter)
Transmitter mountingIntegral (close coupled for AquaMaster 3 Transmitter) or remote
Electrical connections20 mm glands1/2 in NPT (WaterMaster Transmitter)20 mm armored glands (WaterMaster Transmitter)
Sensor cableABB cable available in two forms – standard and armored (WaterMaster Transmitter only)Maximum length 200 m (660 ft)
Ambient temperatureRemote transmitter
Integral transmitter
–20 to 70 °C (–4 to 158 °F)
–20 to 60 °C (–4 to 140 °F)
Process temperature –6 to 70 °C (21 to 158 °F) – non approved0.1 to 50 °C (32.2 to 122 °F) – OIML R49/MID T50 Approved
18 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 4 Specification
Physical Specification
Wetted parts
Lining material / potable water approvals
Electrode materialStainless steel 316 L, super-austentic steel
Hastelloy® C-22 (Hastelloy C4 on DN10 to DN32)(Other electrode materials available on request)
Potential equalizing ringsAquaMaster 3 Transmitter – 2 off
WaterMaster Transmitter – 1 off (minimum)
Lining protection platesNot required
Installation conditions (recommended)Upstream 5D
Downstream 0D (FEV, FEF and FEW [DN10 to 32])
Downstream 3 (FEW [DN250 to 600])
Pressure loss
Potable Water Approvals
Product Code Size Range Liner WRAS ACS NSF-61 AZ/NZS4020
FEV DN40 – 200 Polypropylene Approved Meter
FEF DN250 – 2200 Elastomer Approved Meter
FEF DN250 – 2200 Neoprene
FEF DN250 – 600 Polyurethane
FEF DN250 –600 Linatex
FEW DN10 – 32 PTFE
FEW DN250 – 600 Elastomer *
*Made to NSF-61 approved design
<0.25 bar at Q3 (DN40 to 200 [11/2 to 8 NB])
Negligible at Q3 (DN10 to 32 [3/8 to 11/4 NB], DN250 to 2200 [10 to 84 NB])
OI/FEF/FEV/FEW–EN 19
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 4 Specification
Non-wetted parts
Flange material
Housing material
Terminal box materialPolycarbonate (except close coupled AquaMaster 3 Transmitter)
Aluminium (close coupled AquaMaster 3 Transmitter)
DS/FEV1XX/FEW1XX–ENDS/FER200/FEF200/FEV200–EN Rev E
Carbon steel (DN20 to DN2200 [3/4 to 84 NB])
Stainless steel (DN10 to DN15 [3/8 to 1/2 NB])
Carbon steel FEV and FEF (DN40 to 200 [11/2 to 8 NB]and DN700 to 2200 [28 to 84 NB])FEW (DN450 to DN600 [18 to 24 NB])
Plastic FEF (DN250 to 600 [10 to 24 NB])
Aluminium FEW (DN10 to DN32 [3/8 to 11/4 NB])(FEW (DN250 to DN400 [10 to 16 NB])
20 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 5 Sensor dimensions
5 Sensor dimensions
Fig. 5.1 DN10 to 32 (3/8 to 11/4 NB) full-bore (FEW)
Meter Size Dimensions mm (in) Approximate Weight
DN NPS/NB A* B kg lb
10 3/8 93 (3.7) 200 (7.9) 6 13.2
15 1/2 95 (3.7) 200 (7.9) 7 15.4
20 3/4 111 (4.4) 200 (7.9) 7 15.4
25 1 120 (4.7) 200 (7.9) 8 17.6
32 11/4 137 (5.4) 200 (7.9) 10 22
*Dimensions are approximate and vary depending on flange type
Table 5.1 DN10 to 32 (3/8 to 11/4 NB) full-bore (FEW)
�
�
OI/FEF/FEV/FEW–EN 21
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 5 Sensor dimensions
Fig. 5.2 DN40 to 200 (11/2 to 8 NB) full-bore (FEV)
Meter Size Dimensions mm (in) Approximate Weight
DN NPS/NB A* B kg lb
40 11/2 150 (5.9) 200 (7.9) 11 24
50 2 165 (6.5) 200 (7.9) 12 27
65 21/2 185 (7.2) 200 (7.9) 14 31
80 3 200 (7.9) 200 (7.9) 15 33
100 4 230 (9.1) 250 (9.8) 18 40
125 5 230 (9.1) 250 (9.8) 20 44
150 6 280 (11.0) 300 (11.8) 31 68
200 8 345 (13.6) 350 (13.8) 48 106
*Dimensions are approximate and vary depending on flange type
Table 5.2 DN40 to 200 (11/2 to 8 NB) full-bore (FEV)
��
Max. Max.
22 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 5 Sensor dimensions
Fig. 5.3 DN250 to 600 (10 to 24 NB) full-bore (FEF)
Fig. 5.4 DN700 to 2200 (28 to 84 NB) full-bore (FEF)
� �
Max. Max.
� �
Max. Max.
OI/FEF/FEV/FEW–EN 23
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 5 Sensor dimensions
Meter Size Dimensions in mm (in) Approximate Weight
DN NPS/NB AB
(<PN25)
B (PN25, PN40, ASME, CL300) kg lb
250 10 405 (15.9) 450 (17.7)** 488 (19.2) 88 194
300 12 460 (18.1) 500 (19.7)** 538 (21.2) 128 282
350 14 535 (21.1) 550 (21.7)** 568 (22.3) 100 220
400 16 600 (23.6) 600 (23.6)** 618 (24.3) 115 253
450 18 640 (25.2) 698 (27.5)** 698 (27.5) 160 352
500 20 715 (28.1) 768 (30.2)** 768 (30.2) 217 455
600 24 840 (33.1) 918 (36.1)** 918 (36.1) 315 693
700 27/28* 927 (36.5) 700 (27.6)*** – 430 945
760 30 985 (38.8) 762 (30)*** – 430 945
800 32 1060 (41.7) 800 (31.5)*** – 430 945
900 36 1170 (46.1) 900 (35.4)*** – 540 1190
1000 39/40* 1290 (50.8) 1000 (39.4)*** – 720 1585
1050 42 1405 (55.3) 1067 (42)*** – 880 1930
1100 44 1405 (55.3) 1067 (42)*** – 880 1930
1200 48 1511 (59.5) 1200 (47.2)*** – 1000 2160
1400 54 1745 (68.7) 1400 (55.1)*** – 1450 3190
1500 60 1855 (73.0) 1524 (59)*** – 1370 3000
1600 66 2032 (80.0) 1600 (63)*** – 2000 4400
1800 72 2197 (86.5) 2250 (88.6)*** – 2400 5280
2000 78 2362 (93.0) 2500 (98.4)*** – 3200 7040
2200 84 2534 (100.0) 2750 (110)*** – 4200 9300* Size is dependent on flange specification
Typical tolerances: ** +0/–10 mm (0.40 in) *** +0/–20 mm (1.0 in)
Table 5.3 DN250 to 2200 (10 to 84 NB) full-bore (FEF)
24 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors 5 Sensor dimensions
Fig. 5.5 DN250 to 600 (10 to 24 NB) FM – approved version (FEW)
Meter Size Dimensions in mm (in)* Approximate Weight**
DN NPS/NB A B kg lb
250 10 405 (15.9) 450 (17.7) 63 139
300 12 460 (18.1) 500 (19.7) 78 172
350 14 585 (23.0) 550 (21.7) 145 319
400 16 690 (27.2) 600 (23.6) 179 394
450 18 711 (28.0) 686 (27.0) 189 417
500 20 775 (30.5) 762 (30.0) 195 430
600 24 914 (36.0) 914 (36.0) 275 606
* Sizes are approximate and dependent on flange specification
**Approximate weight for Class 150 flanges
Table 5.4 DN250 to 600 (10 to 24 NB) FM – approved version (FEW)
� �
� �
Max. Max.
Max. Max.
DN350 and DN400
DN450 to DN600
OI/FEF/FEV/FEW–EN 25
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors Notes
Notes
26 OI/FEF/FEV/FEW–EN
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors Notes
OI/FEF/FEV/FEW–EN 27
F, V, W SeriesElectromagnetic flowmeters | Full-bore flow sensors Notes
28 OI/FEF/FEV/FEW–EN
Products and customer support
Automation SystemsFor the following industries:— Chemical & Pharmaceutical— Food & Beverage— Manufacturing— Metals and Minerals— Oil, Gas & Petrochemical— Pulp and Paper
Drives and Motors— AC and 6 Drives, AC and DC Machines, AC Motors to
1kV— Drive Systems— Force Measurement— Servo Drives
Controllers & Recorders— Single and Multi-loop Controllers— Circular Chart and Strip Chart Recorders— Paperless Recorders— Process Indicators
Flexible Automation— Industrial Robots and Robot Systems
Flow Measurement— Electromagnetic Flowmeters— Mass Flowmeters— Turbine Flowmeters— Wedge Flow Elements
Marine Systems & Turbochargers— Electrical Systems— Marine Equipment— Offshore Retrofit and Refurbishment
Process Analytics— Process Gas Analysis— Systems Integration
Transmitters— Pressure— Temperature— Level— Interface Modules
Valves, Actuators and Positioners— Control Valves— Actuators— Positioners
Water, Gas & Industrial Analytics Instrumentation— pH, Conductivity and Dissolved Oxygen Transmitters
and Sensors— Ammonia, Nitrate, Phosphate, Silica, Sodium,
Chloride, Fluoride, Dissolved Oxygen and Hydrazine Analyzers
— Zirconia Oxygen Analyzers, Katharometers, Hydrogen Purity and Purge-gas Monitors, Thermal Conductivity
Customer supportWe provide a comprehensive after sales service via a Worldwide Service Organization. Contact one of the following offices for details on your nearest Service and Repair Centre.
UKABB LimitedTel: +44 (0)1453 826661Fax: +44 (0)1453 829671
USAABB Inc.Tel: +1 215 674 6000Fax: +1 215 674 7183
Client WarrantyPrior to installation, the equipment referred to in this manual must be stored in a clean, dry environment, in accordance with the Company's published specification.Periodic checks must be made on the equipment's condition. In the event of a failure under warranty, the following documentation must be provided as substantiation:— A listing evidencing process operation and alarm
logs at time of failure.— Copies of all storage, installation, operating and
maintenance records relating to the alleged faulty unit.
Contact us
OI/F
EF/
FEV
/FE
W–E
N02
.201
2
ABB LimitedProcess AutomationOldends LaneStonehouseGloucestershire GL10 3TAUKTel: +44 1453 826 661Fax: +44 1453 829 671ABB Inc.Process Automation125 E. County Line RoadWarminsterPA 18974USATel: +1 215 674 6000Fax: +1 215 674 7183
ABB Engineering (Shanghai) Ltd.Process AutomationNo. 5, Lane 369, Chuangye Road201319, Shanghai, P.R. ChinaPhone: +86 (0) 21 6105 6666Fax: +86 (0) 21 6105 6992Mail: china.instrumentation@cn.abb.com
www.abb.com
NoteWe reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB.
Copyright© 2012 ABBAll rights reserved
3KXF210001R4201