Post on 14-Apr-2020
Temtrol, Inc.Phone - 405-263-7286 Fax - 405-263-4924
SSUUBBMMIITTTTAALL SSTTAATTUUSS
Date: July 20, 2012
Project: MIAMI UNIVERSITY SHRIVER CENTER
Temtrol Serial Number: T11291
� PENDING APPROVAL: Formal approval is required before units will be scheduled for production.
Provide timer for lights. Coordinate Access doors for AHU-11. see notes on drawing. Coordinate damper locations to make sure proper mixing occurs. Provide quick disconnects for the wiring.
� APPROVED � FURNISH AS CORRECTED
� REJECTED � REVISE AND RESUBMIT
� SUBMIT SPECIFIED ITEM
This review was performed only for general conformance with the design concept of the project and general compliance with the information given in the Contract Documents. Modifications or comments made on the shop drawings during this review do not relieve the contractor from compliance with the requirements of the plans and specifications. Approval of a specific item does not include approval of the assembly of which the item is a component. Contractor is responsible for the confirmation and correction of all dimensions at the job site. Information that pertains solely to the fabrication processes or to the means, methods, techniques, sequences, and procedures of construction; coordination of the work of all trades; and for the performing of all work in a safe and satisfactory manner.
Prater Engineering Associates, Inc��
Date: By: EMB
X
08/01/12
Temtrol, LLCPhone - 405-263-7286 Fax - 405-263-4924
JOB:
TEMTROL REP:
ORDER NUMBER:
MIAMI UNVERSITY SHRIVER CENTER
WRP ASSOCIATES, LLC.
T011291
GENERAL:
Factory fabricated (ITF) indoor air handling unit. (One piece construction unless noted by a demount on unit drawing). All units (single and multi-sectioned) ship fully assembled and sealed unless they exceed maximum shipping capacities. Multi-sectioned units, shipped in one piece, will require field disassembly by the installing contractor. All unit openings will be sealed for “shipping”. Units will ship on an open flat bed trailer and require off loading within three (3) hours of arrival at the jobsite or be subjected to demurrage fees. Upon arrival, units shall be cleaned (if necessary) and inspected by the contractor. Damaged or missing components must be noted on the bill of lading. Units should be properly stored indoors per Temtrol Operation and Maintenance manual. If units are stored for an extended period of time, routine maintenance is required.
Multi-sectioned units with factory furnished lights or electrical conduit will be furnished with flex connections at each demount. Electrical connections will be re-connected by installing contractor after the unit is reassembled and set in place.
Right and left determined by facing in the direction of air flow with air hitting the back of your neck.
All dimensions in inches.
The Air Handling Unit schedule indicates total static pressure only. All internal losses and available external static pressure are shown on the static pressure summary sheet in this submittal. Written verification of external static pressure is required by the engineer prior to release for production to prevent improper fan selection.
Loose parts requiring field assembly and or mounting, spare components (belts, sheaves, bearings, filters, etc.) if required (noted in this submittal) will ship with the unit (see bill of lading). Contractor shall verify before signing bill of lading.
CERTIFICATION:
ETL LISTED
UNIT BASE / FLOOR / FRAMEWORK:
T011291MIAMI UNVERSITY SHRIVER CENTER
Unit shall be knockdown type to allowinstallation.
Temtrol, LLCPhone - 405-263-7286 Fax - 405-263-4924
Unit base frame manufactured with heavy gauge rectangular structural tubing and coated with an air dried (phenolic) corrosion inhibitive finish. Perimeter base rails are fitted with lifting lugs at the unit or section (if demounted) corners. "Double Bottom" floor includes heavy gauge C-Channel and structural angle support members. The floor cavity is insulated with closed cell spray foam insulation and sealed for airtight / watertight application. Foam is 0-, 0-, (Non VOC) UL 94HF1 rated. Upper perimeter support "mechanical frame" is gasketed (thermal break) prior to attachment of the unit panels.See unit data sheet for specified floor and / or frame construction.
EXTERIOR PANEL (Painted):
Exterior panels are mill coated on both sides with a Polyceram 3200 coating system including polyester resin for long term corrosion resistance which meets or exceeds the following standards. (ASTM B-117) Salt Spray Resistance 5% salt fog at 95 degrees F. Passes 1,000 hrs. (ASTM D-2247) Humidity Resistance 100% salt fog at 95 degrees F. Passes 1,000 hrs. The complete exterior is painted with a finish coat of industrial air-dried (alkyd) enamel. Unless otherwise indicated on unit data sheet, exterior color will be Sandstone.
Panels are fabricated using state of the art, robotic manufacturing cells to guarantee an air tight precision fit. Formed heavy gauge panels are insulated and encased with an internal liner then fastened to the gasketed (thermal break) upper "mechanical frame" assembly. All panels are completely removable from the exterior. See unit drawings for total wall thickness, material and applicable inner liner.
INSULATION / LINERS ( DOUBLE WALL CONSTRUCTION):
Unit panels and liners are filled with a dual density fiberglass (R4.2 per inch thick). The insulation has an effective thermal conductivity (C) of .24 (BTU in./sq.ft. F°) and a noise reduction coefficient (NRC) of 0.70 per one inch thick (based on a type "A" mounting).Coefficients meet or exceed a 3.0 P.C.F. density material rating. Insulation meets erosion requirements of UL 181 facing the air stream and fire hazard classification of 25/50 (per ASTM-84 and UL 723). See unit drawing for total wall thickness and internal double wall liners are as indicated on unit drawings.
ACCESS DOORS:
Access door panels are double wall construction with dual full perimeter gasket. The extruded aluminum, foam injected door frame features built in thermal break design. Door hinges are completely (3 way) adjustable, die cast stainless steel. Door handles are operable from inside and outside the access door. Optional windows, if specified and shown on the unit drawing, are 10x10 dual thermal panes, UV rated safety glass. See unit drawing and data sheet for mechanical safety requirements.
FANWALL® / FANS:
T011291MIAMI UNVERSITY SHRIVER CENTER
Temtrol, LLCPhone - 405-263-7286 Fax - 405-263-4924
The multiple fan array systems include multiple, direct driven, arrangement 4 plenum fans constructed per AMCA requirements for the duty specified class III as required. Fans are rated in accordance with and certified by AMCA for performance. All fans are selected to deliver the specified airflow quantity at the specified operating Total Static Pressure and specified fan/motor speed. The fan array is selected to operate at a system Total Static Pressure that does not exceed 90% of the specified fan’s peak static pressure producing capability at the specified fan/motor speed. Each fan/motor cube or cell includes a minimum 10 gauge, G 90 Galvanized steel intake wall, .100 aluminum spun fan inlet funnel, and a 7 gauge steel motor support plate rail and structure. Each fan/motor assembly is dynamically balanced to meet AMCA standard 204-96, exceeding category BV-5, to meet or exceed an equivalent Grade G.55, producing a maximum rotational imbalance of .03” per second peak, filter in (.55mm per second peak, filter in) For optional fan construction see unit data sheet. NOTE: After units are set in place and prior to startup, fan wheels should be hand rotated to check for clearance between wheel and fan inlet cone. If adjustment is required; installing contractor should refer to the Temtrol Operation and Maintenance manual provided.
FANWALL® / MOTORS:
FANWALL motors are TEAO premium efficiency and selected at the specified operating voltage and rpm as indicated on the fan performance curves. Motors are (NEMA MG-1 Part 30 and 31, section 4.4.2.rated) manufactured by Baldor (or as indicated on unit data sheets) for use in multiple fan arrays that operate at varying synchronous speeds as driven by an approved VFD. All motors include permanently sealed minimum L10-300,000 hr bearings and AEGIS™ shaft grounding to protect the motor bearings from electrical discharge machining due to stray shaft currents. Motors have a 1.15 service factor, Class H rated wire, Class H rated varnish and Class F insulation. Motors are rated for 120 Hz continuous operation.
FANWALL® Flow Cone (Air monitoring device):
FANWALL® Flow Cone provided as indicated on unit data sheet. The flow measuring system consists of a flow measuring station with two static pressure taps located at the throat of the fan inlet cone. Optional accessories are indicated on unit data sheet.
ELECTRICAL:
Unless indicated on the unit data sheet, all electrical and automatic control devices are to be furnished and installed in the field by OTHERS. See unit data sheet for specified electrical requirements.
COILS:
T011291MIAMI UNVERSITY SHRIVER CENTER
Temtrol, LLCPhone - 405-263-7286 Fax - 405-263-4924
All coil assemblies are leak tested under water at 315 PSIG. PERFORMANCE is CERTIFIED under AHRI Standard 410. Coils exceeding the range of AHRI standard rating conditions will be as noted on the coil computer printout. Coils are constructed of seamless copper tubing mechanically expanded into fin collars. Fins are die formed plate type. Headers are seamless copper with die formed tube holes. Intermediate tube supports supplied on coils over 44" fin length with an additional support every 42" multiple thereafter. See unit data sheet (coil performance physical data) for options as specified.
Type SS (standard steam) - Connections are male pipe thread (MPT) Schedule 40 Red Brass. Steam pressure above 50 PSIG will have opposite end connections. Maximum fin length of 120" with same end connections
NOTE: If EAT is 32°F or less, a minimum of 5 psig is recommended. Modulating valves should not be used on any coil subject to freezing.
Type 9NF (non-freeze) - Connections are male pipe thread (MPT) Schedule 40 Red Brass. The 5/8" o.d. inner steam distributing tubes are centered in the outer condensing tube (11/8" o.d.). Inner tube has proportionally spaced directional steam jet orifice, which direct condensate flow to the outlet. Coils exceeding 144" fin length require two coils with connections right and left. Coils casing pitched for drainage.
NOTE: If EAT is 32°F or less, a minimum of 5 psig is recommended. Modulating valves should not be used on any coil subject to freezing.
CONDENSATE PAN:
The entire condensate pan / coil support assembly is fabricated from 16 gauge 304 stainless steel. The pan, recessed into the foam insulated-double bottom base is completely sealed. All pans are "Double Bottom" construction with welded corners. Note: Drain connections are standard 1-1/4” MPT connection unless noted on unit data sheet.Unless indicated on the unit drawing, pan is pitched towards a single drain connection as indicated on the unit drawing. Note: Units in excess of 160 inches in width may require drain connections on both sides of the unit or staggered connections on the same side. See unit drawings for drain locations.
FILTERS / FILTER GAGE:
See unit data sheet for specific Filtration / Filter gage requirements.
DAMPERS:
Temtrol TD6:Low leakage dampers have extruded aluminum airfoil blades, stainless steel square shafting, heavy duty non corrosive nylon shaft bearings, santoprene rubber edge seals, UVC rated jamb seals, a 16 ga galvanized steel frame and concealed linkage. Actuators are both furnished and mounted by OTHERS. (See attached damper cut sheet)
T011291MIAMI UNVERSITY SHRIVER CENTER
Page 1 of 5Unit Data Sheet
www.temtrol.com
ITF-DHRE26Model Number:Serial Number:
7/20/2012Report Created: 9:53:25AM
Unit Tag:T011291-001-00
AHU-11 / J28567
Submittal 01
Rep. Firm:Rep. Contact:
WDWTemtrol Eng.:
MIAMI UNVERSITY SHRIVER CENTERUnit Weight:
Job Name:11235 Lbs.
JIM PATTERSON @ 513-831-4199WRP ASSOCIATES, LLC.
Unit Type: INDOOR
Unit NotesUnit is knock-down construction.Unit to ship in two pieces, in bags.
Sub Floor Material:Floor Material:
20ga. Galvanized16 ga. G-90 Galvanized16 ga. G-90 Galvanized - PaintedExterior Casing:
Unit Details
Base Size: 6 in.
7 7 07Access Doors: Windows T.O.S.L. P.K.S.Quantity Louvers
0
Static Pressure SummarySupply
Description StaticHEATING 5SS - 2 - 31.5 X 63 X 2 - 6 AL 0.12COOLING 5WC - 8 - 31.5 X 63 X 8 - 10 AL 0.992" PLEATED FLAT 30% 0.5012" CARTRIDGE 65% 1.00DAMPERS 0.10CABINET 0.10
Total Supply Static Pressure
Internal Static PressureAvailable External Static Pressure
2.813.696.50
Comment:
StaticDescriptionReturn
DAMPERS 0.10
Total Return Static PressureAvailable External Static PressureInternal Static Pressure 0.10
1.401.50
Electrical 208/3/60VAC/PH/HZ:
Unless otherwise noted below all electrical and automatic control devices are furnished and installed by others in the field.Guarded vapor-proof light fixture(s) with 25W compact fluorescent light bulb(s). Fixture locations shown on unit drawings are approximate.All lights controlled by a single 0 to 60 minute light timer switch. One outlet provided.120 volt power for lighting and/or GFI outlets shall be provided by OthersMotor Overload Panel with aux. contacts.Single feed Overload Panel.Single fan air monitoring with transducer.
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
wire for two VFDs
Page 2 of 5Unit Data Sheet
www.temtrol.com
ITF-DHRE26Model Number:Serial Number:
7/20/2012Report Created: 9:53:25AM
Unit Tag:T011291-001-00
AHU-11 / J28567
Submittal 01
TSP:CFM per fan:
Fan RPM:
PHYSICAL OPERATION
Connected BHP:Operating Hz:BHP per fan:
Cone Constant Pp
Cone TypeBack draft dampers / Qty
Airflow Monitor / QTYArray: Row x Column (QTY)
Total Hp
Total CFM:
Motor / Frame / QtyVAC/PH/HZ - RPM / Encl
2 x 2 (4)MAGNESENSE @ 3 (1 Qty)1910(Pp)^0.5FBD-8 (4 Qty)Curved1.5 hp / 145T / 4208/3/60 - 1750/TEAO6 hp
11700 cfm2925.00 cfm1.50 in. Wg.1395 rpm
1.02 hp48.6 Hz4.08 hp
FWT-18-105 [RETURN FAN] - QTY 4100%
Active Cells: 4
SOUND OCTAVE BANDInlet / Discharge
63hz 125hz 250hz 500hz 1000hz 2000hz 4000hz 8000hz A-Weighted84 / 73 82 / 76 79 / 82 76 / 66 73 / 67 73 / 64 66 / 59 62 / 47 80 / 76
Comment:-
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
Page 3 of 5Unit Data Sheet
www.temtrol.com
ITF-DHRE26Model Number:Serial Number:
7/20/2012Report Created: 9:53:25AM
Unit Tag:T011291-001-00
AHU-11 / J28567
Submittal 01
TSP:CFM per fan:
Fan RPM:
PHYSICAL OPERATION
Connected BHP:Operating Hz:BHP per fan:
Cone Constant Pp
Cone TypeBack draft dampers / Qty
Airflow Monitor / QTYArray: Row x Column (QTY)
Total Hp
Total CFM:
Motor / Frame / QtyVAC/PH/HZ - RPM / Encl
2 x 2 (4)MAGNESENSE @ 5 (1 Qty)1910(Pp)^0.5FBD-8 (4 Qty)Curved5 hp / 184T / 4208/3/60 - 1750/TEAO20 hp
13000 cfm3250.00 cfm6.50 in. Wg.2793 rpm
4.68 hp95.8 Hz18.72 hp
FWT-18-60 [SUPPLY FAN] - QTY 4100%
Active Cells: 4
SOUND OCTAVE BANDInlet / Discharge
63hz 125hz 250hz 500hz 1000hz 2000hz 4000hz 8000hz A-Weighted97 / 83 92 / 81 88 / 91 93 / 84 85 / 78 82 / 77 82 / 75 76 / 69 93 / 87
Comment:-
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
Page 4 of 5Unit Data Sheet
www.temtrol.com
ITF-DHRE26Model Number:Serial Number:
7/20/2012Report Created: 9:53:25AM
Unit Tag:T011291-001-00
AHU-11 / J28567
Submittal 01
5/8" / 0.025"Tube O.D. / Wall:
Sup.Conn - Qty / Size:Ret.Conn - Qty / Size:
2Rows - FPI:0.00Serpentine:
13,000 / 13,510 - Sea LevelACFM / SCFM - Alt.:Total Face Area / FV :EDB :LDB :6
924,393 Btu/HrSensible Heat:
0.12APD:
7.0Steam Press:
31.50 X 63.00Coil FH x FL:
0.008" / ALFin Thickness / Matl:
Tube Material: CUCase Thickness / Matl: CT: 1" CB: 1" / 16 GA GALV.
(1) 1-1/2" MPT SCH40 Red Brass Per Coil(1) 1-1/2" MPT SCH40 Red Brass Per Coil
in. Wg.
-
27.6 / 471.750 °F113.1 °F
965.2 lbs/hr.Condensate:psig
Coating: NONE
OPERATIONPHYSICAL[ Coil # 1 ] Steam Heating Coil - (Qty. 2) 5SS - 2 - 31.5 x 63 x 2 - 6 AL
Hand: RIGHT
Comment:1. AHRI CERTIFIED 'Rated in Accordance with AHRI Standard 410'2. If EDB is less than or equal to 32°F, Temtrol recommends 5 psig minimum and NO modulating steam valve.
5/8" / 0.025"Tube O.D. / Wall:
Sup.Conn - Qty / Size:Ret.Conn - Qty / Size:
8Rows - FPI:1.00Serpentine:
13,000 / 12,534 - Sea LevelACFM / SCFM - Alt.:Total Face Area / FV :
10588,355 Btu/HrTotal Heat:394,686 Btu/HrSensible Heat:
0.99APD:6.01FPD:
WaterFluid - %:
97.76GPM:EFT / LFT:
31.50 X 63.00Coil FH x FL:
0.008" / ALFin Thickness / Matl:
Tube Material: CUCase Thickness / Matl: CT: 1" CB: 1" / 16 GA 304 SS
Fluid Velocity: 2.67(1) 2" MPT SCH40 Red Brass Per Coil(1) 2" MPT SCH40 Red Brass Per Coil
ft/s
in. Wg.
-
27.6 / 471.780 / 67 °F51.4 / 51.3 °F
45 / 57 °F
ft
EDB / EWB:LDB / LWB:
Coating: NONE
OPERATIONPHYSICAL[ Coil # 2 ] Chilled Water Coil - (Qty. 2) 5WC - 8 - 31.5 x 63 x 8 - 10 AL
Hand: RIGHTDrain Pan - 73W x 40L 16 GA 304 SS RIGHT HAND Comment:1. AHRI CERTIFIED 'Rated in Accordance with AHRI Standard 410'
(Qty) Size:Type:
(3)12x24 & (6)24x24Flat
[ Filter Bank # 1 ] Pre - 2" Pleated Flat - 30% / Final - 12" Cartridge - 65%Up Stream / Face LoadGalvanizedFrames:
Bank Size: 60 H x 72 WFace Area (ft²) / FV (fpm): 30.0 / 433
Location / Service:
Filter Bank Gauge: Dwyer Model 2003Clips:2 SetsSupplied Sets:IIClass:Media - Pre Filter APD: 0.50
Media - Final Filter Class: Supplied Sets: Clips:II 2 SetsAPD: 1.00Filter frames, media and holding clips are furnished by Factory.-
Comment:
OpeningsFVCFMLocationSize (A x B)Description
R/A 73 x 24 Top 11700 961S/A 73 x 24 Top 13000 1,068
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
Page 5 of 5Unit Data Sheet
www.temtrol.com
ITF-DHRE26Model Number:Serial Number:
7/20/2012Report Created: 9:53:25AM
Unit Tag:T011291-001-00
AHU-11 / J28567
Submittal 01
DampersDescription Location Model # / ActionFVCFMBank Size (AxB)R/A 11700Int - Vertical 1355 TD6 / Opposed60 x 24O/A 13000Top 1231 TD6 / Opposed73 x 24E/A 11700Top 1108 TD6 / Opposed73 x 24
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
Actual rotation of the unit has changed. ALL ACCESS DOORS TO BE ON THE OPPOSITE SIDE OF WHAT IS CURRENTLY SHOWN
Controller to be setup up to allow two (2) fans to be controlled from one VFD. The contractor will be supplying (2) VFDs for the S.A. and R.A. fan system.
Slide dampers around tomove mixed air up for bettermixing.
provide timer for lights
Page 1 of 4Unit Data Sheet
www.temtrol.com
ITF-DH5Model Number:Serial Number:
7/20/2012Report Created: 9:55:41AM
Unit Tag:T011291-002-00
AHU-12 / J28568
Submittal 01
Rep. Firm:Rep. Contact:
WDWTemtrol Eng.:
MIAMI UNVERSITY SHRIVER CENTERUnit Weight:
Job Name:3860 Lbs.
JIM PATTERSON @ 513-831-4199WRP ASSOCIATES, LLC.
Unit Type: INDOOR
Unit NotesUnit is knock-down construction.Unit to ship in two pieces, in bags.
Sub Floor Material:Floor Material:
20ga. Galvanized16 ga. G-90 Galvanized16 ga. G-90 Galvanized - PaintedExterior Casing:
Unit Details
Base Size: 5 in.
5 5 05Access Doors: Windows T.O.S.L. P.K.S.Quantity Louvers
0
Static Pressure SummarySupply
Description StaticCOOLING 5WC - 10 - 24 X 40 X 8 - 10 AL 0.73HEATING 9NS - 24 X 40 X 1 - 11 AL 0.122" PLEATED FLAT 30% 0.5012" CARTRIDGE 65% 1.00CABINET 0.10
Total Supply Static Pressure
Internal Static PressureAvailable External Static Pressure
2.452.555.00
Comment:
Electrical 208/3/60VAC/PH/HZ:
Unless otherwise noted below all electrical and automatic control devices are furnished and installed by others in the field.Guarded vapor-proof light fixture(s) with 25W compact fluorescent light bulb(s). Fixture locations shown on unit drawings are approximate.All lights controlled by a single 0 to 60 minute light timer switch. One outlet provided.120 volt power for lighting and/or GFI outlets shall be provided by OthersMotor Overload Panel with aux. contacts.Single feed Overload Panel.Single fan air monitoring with transducer.
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
Page 2 of 4Unit Data Sheet
www.temtrol.com
ITF-DH5Model Number:Serial Number:
7/20/2012Report Created: 9:55:41AM
Unit Tag:T011291-002-00
AHU-12 / J28568
Submittal 01
TSP:CFM per fan:
Fan RPM:
PHYSICAL OPERATION
Connected BHP:Operating Hz:BHP per fan:
Cone Constant Pp
Cone TypeBack draft dampers / Qty
Airflow Monitor / QTYArray: Row x Column (QTY)
Total Hp
Total CFM:
Motor / Frame / QtyVAC/PH/HZ - RPM / Encl
1 x 2 (2)MAGNESENSE @ 3 (1 Qty)910(Pp)^0.5FBD-6 (2 Qty)Curved2 hp / 145T / 2208/3/60 - 3500/TEAO4 hp
2500 cfm1250.00 cfm5.00 in. Wg.3605 rpm
1.37 hp62.7 Hz2.74 hp
FWT-12-60 [SUPPLY FAN] - QTY 2100%
Active Cells: 2
SOUND OCTAVE BANDInlet / Discharge
63hz 125hz 250hz 500hz 1000hz 2000hz 4000hz 8000hz A-Weighted84 / 77 79 / 74 77 / 78 84 / 72 80 / 72 79 / 69 79 / 68 75 / 64 86 / 77
Comment:-
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
Page 3 of 4Unit Data Sheet
www.temtrol.com
ITF-DH5Model Number:Serial Number:
7/20/2012Report Created: 9:55:41AM
Unit Tag:T011291-002-00
AHU-12 / J28568
Submittal 01
1-1/8" / 0.035"Tube O.D. / Wall:
Sup.Conn - Qty / Size:Ret.Conn - Qty / Size:
1Rows - FPI:0.00Serpentine:
2,500 / 2,881 - Sea LevelACFM / SCFM - Alt.:Total Face Area / FV :EDB :LDB :11
314,673 Btu/HrSensible Heat:
0.12APD:
7.0Steam Press:
24.00 X 40.00Coil FH x FL:
0.010" / ALFin Thickness / Matl:
Tube Material: CUCase Thickness / Matl: CT: 1" CB: 1" / 16 GA GALV.
(1) 1-1/2" MPT SCH40 Red Brass Per Coil(1) 1-1/2" MPT SCH40 Red Brass Per Coil
in. Wg.
-
6.7 / 375.00 °F100.7 °F
328.6 lbs/hr.Condensate:psig
Coating: NONE
OPERATIONPHYSICAL[ Coil # 1 ] Steam Heating Coil - (Qty. 1) 9NS - 24 x 40 x 1 - 11 AL
Hand: RIGHT
Comment:1. AHRI CERTIFIED 'Rated in Accordance with AHRI Standard 410'2. If EDB is less than or equal to 32°F, Temtrol recommends 5 psig minimum and NO modulating steam valve.
5/8" / 0.025"Tube O.D. / Wall:
Sup.Conn - Qty / Size:Ret.Conn - Qty / Size:
8Rows - FPI:0.80Serpentine:
2,500 / 2,335 - Sea LevelACFM / SCFM - Alt.:Total Face Area / FV :
10184,179 Btu/HrTotal Heat:113,804 Btu/HrSensible Heat:
0.73APD:5.76FPD:
WaterFluid - %:
30.55GPM:EFT / LFT:
24.00 X 40.00Coil FH x FL:
0.008" / ALFin Thickness / Matl:
Tube Material: CUCase Thickness / Matl: CT: 1" CB: 1" / 16 GA 304 SS
Fluid Velocity: 2.69(1) 1-1/2" MPT SCH40 Red Brass Per Coil(1) 1-1/2" MPT SCH40 Red Brass Per Coil
ft/s
in. Wg.
-
6.7 / 375.095 / 75 °F50.9 / 50.9 °F
45 / 57 °F
ft
EDB / EWB:LDB / LWB:
Coating: NONE
OPERATIONPHYSICAL[ Coil # 2 ] Chilled Water Coil - (Qty. 1) 5WC - 10 - 24 x 40 x 8 - 10 AL
Hand: RIGHTDrain Pan - 54W x 40L 16 GA 304 SS RIGHT HAND Comment:1. (FH<=30 or FL<=60 & Odd tubes) falls outside the range of Standard Rating Conditions specified in 'AHRI Standard 410'.2. Rated in Compliance with AHRI Standard 410
(Qty) Size:Type:
(2)24x24Flat
[ Filter Bank # 1 ] Pre - 2" Pleated Flat - 30% / Final - 12" Cartridge - 65%Up Stream / Face LoadGalvanizedFrames:
Bank Size: 24 H x 48 WFace Area (ft²) / FV (fpm): 8.0 / 313
Location / Service:
Filter Bank Gauge: Dwyer Model 2003Clips:2 SetsSupplied Sets:IIClass:Media - Pre Filter APD: 0.50
Media - Final Filter Class: Supplied Sets: Clips:II 2 SetsAPD: 1.00Filter frames, media and holding clips are furnished by Factory.-
Comment:
OpeningsFVCFMLocationSize (A x B)Description
O/A 26 x 14 Top 2500 989S/A 24 x 15 Top 2500 1,000
Temtrol, LLC 106 N. Industrial Blvd, Okarche, OK 73762 Phone: 405-263-7286 Fax: 405-263-4924
provide timer for lights
GE6000 Series 3" Tool Locking Latch Parts List (DRHW0283)
DESCRIPTIONGE #TEMTROL PART #QTYITEM
Handle, Latch HalfGE6150DRHW030021
Handle, 3" Link ShaftGE6175DRHW033012
Handle, Non-LockingGE6110DRHW027023
10-25 x 3/4" Square Socket ScrewNoneNone24
Handle, Roller PawGE6160DRHW031025
Handle, Tool LockingGE6120DRHW028017
GE6000 Series 2" Tool Locking Latch Parts List (DRHW0282)
DESCRIPTIONGE #TEMTROL PART #QTYITEM
Handle, Latch HalfGE6150DRHW030021
Handle, Non-LockingGE6110DRHW027023
10-25 x 3/4" Square Socket ScrewNoneNone24
Handle, Roller PawGE6160DRHW031025
Handle, Tool LockingGE6120DRHW028017
Handle, 2" Link ShaftGE6170DRHW032016REV Description
Page:
APPR
15 EAST OKLAHOMA AVENUE OKARCHE, OK 73762PH: (405) 263-7286 FAX: (405) 263-4924
Drawing By:
Date
Project #:2 of 5
Temtrolwww.temtrol.com
Drawing #:
Joshua McBride CAX-DRHW0281-01 GE6000 Series Latch
Tool Locking Latch(GE6000 Series)
1 Initial Drawing 8-15-11
File Saved: 2:36pm 01-04-2012
1
2
5
7
4
3
6 Both Roller Adjusted to Bottom of Travel
5
1
4
Torque = 15 ftlbs (5mm Hex)
Torque = 10 ftlbs (5mm Hex)
Torque = 8 ftlbs (#2 Square Drive)
Utilizes 1/4" Hex Tool to lock and unlock
� � � � � � � �
�
Motors�for�FAN
WALL®
�system
s�are�wire
d�to�a�factory�furnish
ed�m
anual�starter�overlo
ad�panel�as�a
�standard�fo
r�ind
ividual�m
otor�overlo
ad�protection�
�Pan
el is
pro
vide
d w
ith
carb
on s
teel
hin
ges,
fo
amed
in p
lace
gas
ket
and
zinc
pla
ted
back
pla
te.
Mot
or O
verl
oad
Pan
el w
ith
Aux
Con
tact
s �
Pow
er b
lock
for V
FD o
utpu
t wiri
ng.
Aux
iliar
y co
ntac
ts w
ired
in s
erie
s fo
r opt
iona
l fie
ld w
iring
to a
rem
ote
pow
ered
pilo
t lig
ht o
r al
arm
. (Te
rmin
als
51 &
52)
IEC
C m
anua
l sta
rters
with
rota
ry
type
op
erat
or.
NE
MA
4, U
L lis
ted
encl
osur
e is
con
stru
cted
of c
old
rolle
d 16
gau
ge
stee
l (14
gau
ge if
36”
H x
30”
W o
r lar
ger)
that
is d
ip-c
oate
d pr
imed
an
d po
wde
r coa
ted.