Recent Developments in Clean Fire Suppression Agents

Mark L. Robin, Ph.D.DuPont Chemicals & Fluoroproducts

NFPA Conference & ExpoJune 12, 2013Chicago, IL

2

2

2

04/2009

2

-DuPont Confidential-

Learning Objectives

1. What Are Clean Agents?2. The History of Clean Agents3. The Halon Clean Agents4. Halon Replacements

Desired PropertiesCurrent Commercial Clean Agents

5. DuPont Clean Agent ProgramTotal Flood CandidateStreaming Candidates

3

3

3

04/2009

3

-DuPont Confidential-

I. Clean Agents: What are they?

4

4

4

04/2009

4

-DuPont Confidential-

What is a Clean Agent?NFPA 2001 Standard on Clean Agent Fire

Extinguishing Systems (2012 edition)

3.3.6 Clean Agent. Electrically nonconducting, volatile, or gaseous fire extinguishing agent that does not leave a residue upon evaporation

No residueNo cleanupNo downtime

5

5

5

04/2009

5

-DuPont Confidential-

Which Fire Extinguishing Agents are NOT Clean? Water Foam Powder

ResidueCleanupDowntimeNon-fire damage to assets

6

6

6

04/2009

6

-DuPont Confidential-

Comparison Testing of Preaction Sprinkler and FM-200® Systems

• In-cabinet fire• Clean Agent System

FM-200® system designed and installed in accordance with NFPA 2001

• Preaction Sprinkler SystemDesigned and installed in accordance with NFPA 13

• Detection/Alarm SystemsDesigned and installed in accordance with NFPA 72

7

7

7

04/2009

7

-DuPont Confidential-

Clean Agent vs Sprinklers

In-cabinet fire

NFPA Compliant FM-200® and pre-action sprinkler systems

8

8

8

04/2009

8

-DuPont Confidential-

Before…..

DuPont FM-200® Clean Agent System

9

9

9

04/2009

9

-DuPont Confidential-

After…..

DuPont FM-200® Clean Agent System

10

10

10

04/2009

10

-DuPont Confidential-

Automatic Sprinkler System

Before…..

11

11

11

04/2009

11

-DuPont Confidential-

Automatic Sprinkler System

12

12

12

04/2009

12

-DuPont Confidential-

Automatic Sprinkler System

13

13

13

04/2009

13

-DuPont Confidential-

After…..

Automatic Sprinkler System

14

14

14

04/2009

14

-DuPont Confidential-

Automatic Sprinkler System

After…..

15

15

15

04/2009

15

-DuPont Confidential-

Suppression agent

Sprinkler Systems Clean Agent System Water Gas

Design Objective

Fire Control: Confine fire Control ceiling T

Fire Extinguishment

Design Objective Protect structure Protect contents Activation

Sprinkler head T 135 oF

Automatic activation following detection (air sampling, smoke detectors)

Fire size at activation

Can be 100's of kW Low as 0.1 kW with air aspirating detection system

Total Flooding

No. Water not three dimensional, will not fill entire enclosure

Yes. Agent distributed uniformly throughout enclosure

Cleanliness

No. Water damage, smoke damage

Yes. No residues to clean up following extinguishment

Comparison of Sprinkler and Clean Agent Systems

16

16

16

04/2009

16

-DuPont Confidential-

Foam System Discharge

17

17

17

04/2009

17

-DuPont Confidential-

Dry Chemical System Discharge

18

18

18

04/2009

18

-DuPont Confidential-

II. History of Clean Agents

19

19

19

04/2009

19

-DuPont Confidential-

The History of Clean Agent Fire Suppression

“Why should we look to the past in order to prepare for the future? Because there is

nowhere else to look.”

– James Burke

20

20

20

04/2009

20

-DuPont Confidential-

Halogenated Compounds as Fire Suppression Agents

1870 to 1910• CCl4 extinguishers introduced• Handhelds• Fire Grenades

21

21

21

04/2009

21

-DuPont Confidential-

Halogenated Compounds as Fire Suppression Agents

Late 1920s : Methyl Bromide (CH3Br)• More effective than CCl4• British – aircraft applications• WWII - German military aircraft, marine

Late 1930s: Bromochloromethane (CH2BrCl)• German Luftwaffe• US Air Force in late 1940s

22

22

22

04/2009

22

-DuPont Confidential-

Halogenated Compounds as Fire Suppression Agents

Late 1940s US Army sought agent as effective as

CH3Br or CH2BrCl, but with lower toxicity Over 60 agents evaluated: Purdue University

Four selected for further studyHalon 1301 CF3Br Halon 1211 CF2BrClHalon 1202 CF2Br2Halon 2402 BrCF2CF2Br

Br reacts chemically with key flame species

23

23

23

04/2009

23

-DuPont Confidential-

The Halon Era: 1960s to 1994Halon 1301: CF3Br

Total flooding applications

Prefer a Gaseous Agent

24

24

24

04/2009

24

-DuPont Confidential-

The Halon Era: 1960s to 1994Halon 1211: CF2BrCl

Portable applications

Prefer a Liquid Agent

25

25

25

04/2009

25

-DuPont Confidential-

24

26

26

26

04/2009

26

-DuPont Confidential-

25

27

27

27

04/2009

27

-DuPont Confidential-

26

28

28

28

04/2009

28

-DuPont Confidential-

III. The Halons were near ideal…– What Happened?

29

29

29

04/2009

29

-DuPont Confidential-

28

30

30

30

04/2009

30

-DuPont Confidential-

29

31

31

31

04/2009

31

-DuPont Confidential-

IV. Halon to be Phased Out- Now What?

32

32

32

04/2009

32

-DuPont Confidential-

The Search for “Son of Halon” mid-1980s to Present

33

33

33

04/2009

33

-DuPont Confidential-

32

34

34

34

04/2009

34

-DuPont Confidential-

33

35

35

35

04/2009

35

-DuPont Confidential-

34

36

36

36

04/2009

36

-DuPont Confidential-

35

37

37

37

04/2009

37

-DuPont Confidential-

36

38

38

38

04/2009

38

-DuPont Confidential-

37

39

39

39

04/2009

39

-DuPont Confidential-

38

40

40

40

04/2009

40

-DuPont Confidential-

The Search for Halon Replacements:Mid 1980s to today

AcademiaNMERI / CGET

Government/MilitaryNISTArmy, Navy, Air ForceFAA

IndustrialDuPontICIGreat Lakes Chemical Corporation3MAmerican PacificAnsul

41

41

41

04/2009

41

-DuPont Confidential-

Chemical Agents Extinguish fire by interfering with the flame chemistry

React with and remove key flame species Chain carriers H, O and HO radicals removed Very efficient

Physical Agents Extinguish fire via physical mechanisms

Heat removal O2 dilution Separation of fuel and oxidant

Search for Halon Replacements

Fire Tetrahedron

42

42

42

04/2009

42

-DuPont Confidential-

Chemical AgentsBromine or iodine containing molecules• Great Lakes Chemical Corporation

FM-100TM ; CF2HBr Performance = Halon 1301 ODP too high; toxicity too high

• ICI CF3CHFBr “Fluothane” Good performance Inhalation Anesthetic, ODP too high

• CF3I “Purple Haze” Good performance High toxicity Chemically reactive, corrosive High manufacturing cost

43

43

43

04/2009

43

-DuPont Confidential-

Chemical Agents• Advanced Agent Working Group (AAWG)• Roots in CF3I working group• Goal: Halon 1301 replacement• North Slope Operators, U.S. military, EPA, NASA,

Kidde International, Kidde-Fenwal Combustion Research, QinetiQ, UK MOD, American Pacific Corporation, NMERI, NIST, 3M, Great Lakes, DuPont, HARC

Bromine-containing alkenes, alcohols, ethers, amines, carbonyl compounds, and aromatics

Selection: bromine-containing alkenes

44

44

44

04/2009

44

-DuPont Confidential-

Chemical Agents• Advanced Agent Working Group (AAWG)• Bromine-containing alkenes

CF2BrCH=CH2CF2BrCF2CH=CH2CF3CH=CHBrCF3CBr=CH2CF2BrCF2CH=CH2CF3CF2CBr=CH2

“Tropodegradable” – short lifetime due to rxn with hydroxyl radical

Too reactive = high toxicityShort atmospheric lifetime = high toxicity

All too toxic for total flooding in occupied areas

45

45

45

04/2009

45

-DuPont Confidential-

Physical Agents• Chlorine-containing Agents: Safety Hi-Tech

NAF-S-III: HCFC-22/HCFC-123/HCFC-124/d-limonene Nonzero ODP; slated for phaseout

• Perfluorocarbons: 3M C3F8 PFC-2-1-8 n-C4F10 PFC-3-1-10 Extremely long atmospheric life, extremely high GWP Permanent effect on climate change

• Ethers C-O linkage leads to more rapid rxn with HO

• Only true for -OCH2-, -OCHF-, -OCH2F, -OCH3 groups

• AminesRfNH2, RfR’f’NH, RfRfRfNDifficult synthesis; toxic

46

46

46

04/2009

46

-DuPont Confidential-

Physical Agents• Inert Gases: Ansul

Inergen: N2/Ar/CO2

• Hydrofluorocarbons Great Lakes: CF3CHFCF3 FM-200®

DuPont: CF3H (FE-13TM); CF3CF2H (FE-25TM)

• Perfluoroketones: 3MCF3CF2C(O)CF(CF3)2 NovecTM 1230 ; NovecTM 649

47

47

47

04/2009

47

-DuPont Confidential-

Why Fluorine?

VolatilityStabilityLow ToxicityFlame Suppression

-C-H - C-F

48

48

48

04/2009

48

-DuPont Confidential-

V. Halon Replacements- Commercialized Agents

100s of Researchers1000s of Compounds Screened Later……..

49

49

49

04/2009

49

-DuPont Confidential-

Commercialized Halon 1301 Replacements

• Hydrofluorocarbons (HFCs) HFC-227ea: DuPont FM-200® CF3CHFCF3 HFC-125: DuPont FE-25TM CF3CF2H HFC-23: DuPont FE-13TM CF3H

• Hydrochlorofluorocarbons (HCFCs)HCFC Blend A: NAF-S-III

• HCFC-22/HCFC-123/HCFC-124/d-limonene• Inert Gases

IG-541: InergenTM Ar/N2/CO2 IG-55: ArgoniteTM Ar/N2

• Perfluorinated Ketones FK-5-1-12: NovecTM 1230 CF3CF2C(O)CF(CF3)2

Subject to Phase-out

50

50

50

04/2009

50

-DuPont Confidential-

Commercialized Halon 1211 Replacements

• Hydrofluorocarbons (HFCs) HFC-236fa: DuPont FE-36TM CF3CH2CF3

• Hydrochlorofluorocarbons (HCFCs) Halotron® I: HCFC-123 + Ar + CF4

51

51

51

04/2009

51

-DuPont Confidential-

Ideal Halon 1301 Replacement Halon 1301 HFCs Inert Gases PerfluoroketonesHigh weight efficiency XX X Gas at ambient temperature X X XLow chemical reactivity X X XElectrically nonconducting X X X XLow toxicity X X XLack of metabolism X X XLow agent cost X X XLow system cost X X XLow number agent cylinders X X XLow storage volume X X XLow system footprint X X XLow cylinder pressure rating X X XLow manifold pressure rating X X XLow negative pressures during discharge X X XLow positive pressures during discharge X X XSlow stratification X X XZero ODP (ozone depletion potential) X X XZero GWP (global warming potential) XVOC exempt (no contribution to smog) X X X

Comparison of Halon ReplacementsX = provides desired property

HFCs offer the best overall combination of the properties desirable in a Halon replacement

52

52

52

04/2009

52

-DuPont Confidential-

Worldwide Clean Agent MarketNumber of Installed Systems

HFCs (70%)

Inert Gases (20%)

Other (10%)

HFCs are the most widely employed Halon 1301 alternatives

70% FM-200®

20% FE-25TM

10% NovecTM 1230

90% Inergen®

10% Argonite®

53

53

53

04/2009

53

-DuPont Confidential-

VI. Recent Developments in Clean AgentsDuPont’s Clean Agent Program

54

54

54

04/2009

54

-DuPont Confidential-

DuPont Clean Agent History• 1947 Halon 1301 identified (U.S. Army Engineering Development

Research Lab, DuPont, and Purdue Research Foundation)

• 1960s Halon 1301 - manufactured and marketed by DuPont

• 1995 DuPont launches FE-13™ (HFC-23)

• 1997 DuPont launches FE-36™ (HFC-236fa) for portable extinguishers

• 2001 DuPont launches HFC-227ea as FE-227™

• 2002 DuPont launches FE-25™ (HFC-125)

• 2008 DuPont acquires FC business of GLCC- FM-200® becomes DuPont trade name

55

55

55

04/2009

55

-DuPont Confidential-

Goal: Discover and commercialize a range of new clean fire extinguishing agents to extend our current portfolio and

satisfy the safety, environmental and performancerequirements of clean agent users around the world

DuPont Clean Agent Program

56

56

56

04/2009

56

-DuPont Confidential-

Clean Agent DevelopmentTotal Flooding Agents

• High mass efficiency• Chemically inert

• No reaction with water, common solvents• Long term storage stability

• High volatility• bp -70 to + 40 oC

• Electrically non-conducting• Low toxicity

• MDC < CS NOAEL• MDC < 4h LC50

• Cost effective

57

57

57

04/2009

57

-DuPont Confidential-

Toxicological Requirements = BIG Challenge

Tox Requirements

• 4h LC50 > MDC• Cardiac NOAEL > MDC• Cardiac LOAEL > MDC

Much higher bar compared to refrigeration, foam blowing, propellant, & solvent tox requirements

58

58

58

04/2009

58

-DuPont Confidential-

Toxicological TestingNo Qualitative Structure Activity Relationships

(QSAR) available for 4h LC50 or cardiac sensitization tests

Agent screening: 1h LC50• 200 - 300 g material = $$• $10,0000

4 h LC50 and Cardiac Sensitization Tests• 50 – 60 kg material = $$$$• $150,000 for tox tests

59

59

59

04/2009

59

-DuPont Confidential-

Fire Suppression Testing Class B

Cup Burner TestingTotal Flood Tests

Class APlastic Rod TestTotal Flood Tests

60

60

60

04/2009

60

-DuPont Confidential-

Total Flooding AgentsFire Suppression Testing

• Class B (liquid, gaseous) FuelsCup burner apparatus• Standardized apparatus (NFPA 2001/ISO 14520)

61

61

61

04/2009

61

-DuPont Confidential-

235 mm

90 mm

535 mm

85 mm

fuel inletair/agent inlet

heater/TC

Cup Burner: Assembled View

62

62

62

04/2009

62

-DuPont Confidential-

Total Flooding AgentsFire Suppression Testing

• Class A (solid) Fuels• UL 2166 Full-scale Tests

• Plastic Sheets (PMMA, ABS, PP)• Wood crib• 100 m3 enclosure; 50 kg per single test run

95% of clean agent applications

are Class A/Class C hazard protection

63

63

63

04/2009

63

-DuPont Confidential-

DuPont-developed rod tests• Modification of cup burner apparatus• Plastic rod – special design• Laboratory scale : 300 g requirement• Excellent agreement with UL 2166 results

FM-200, FE-25, Novec 1230

Class A PerformanceLab Scale Method Developed

64

64

64

04/2009

64

-DuPont Confidential-

Small Scale Total Flooding Tests

• 0.6 m3 Lexan test enclosure• Class B “pan” fire tests• Class A tests

plastic pieces (PMMA, PP, ABS)“mini wood crib”

65

65

65

04/2009

65

-DuPont Confidential-

Toxicology• 4h LC50 > 231,000 ppm (> 23.1% v/v)• CS NOAEL = 100,000 ppm (10% v/v)• CS LOAEL = 125,000 ppm (12.5% v/v)

Fire Suppression• Class A MDC = 5.6% v/v• Class B MDC = 6.9% v/v a• Class C MDC = 6.3% v/v

Total Flooding Candidate

95% of applications

bp = 31 oC

a n-heptane

66

66

66

04/2009

66

-DuPont Confidential-

Total Flooding Candidate• Stability

High thermal and chemical stabilityStable to water

• Material compatibilityCompatible with common metals, plastics, elastomers

• Environmental PropertiesODP = 0GWP < 20 (estimate; determination in

progress)

67

67

67

04/2009

67

-DuPont Confidential-

Total Flooding Candidate• Inert gas solubility

• N2, Ar, CO2• Isotherms measured isotherms -10, 20, 50 oC

• Henry’s Law constants generated for -40 to 80 oC

• Thermodynamic and Transport Properties• PVT data• Fit to various equations of state

68

68

68

04/2009

68

-DuPont Confidential-

Total Flooding Candidate

• Current Activity• Process scale-up to produce 1000 kg • Intermediate-scale fire testing• Additional material of construction

testing• GWP determination in progress

69

69

69

04/2009

69

-DuPont Confidential-

Clean Agent DevelopmentStreaming Agents

• High mass efficiency• Chemically inert

• No reaction with water, common solvents• Long term storage stability

• Liquid or high bp gas• bp -10 to + 40 oC

• Electrically non-conducting• Toxicity

• Equal to or better than Halon 1211 or HCFC-123• Cost effective

70

70

70

04/2009

70

-DuPont Confidential-

Portables Development Complex interaction of variables affecting

performance• Fill density• Superpressure level• Application rate• Agent droplet size• Agent quality (% mass in vapor)• Valve, nozzle, horn design• Operator technique

Design of Experiment (DOE) not applicable Brute force empirical approach to

optimization

71

71

71

04/2009

71

-DuPont Confidential-

72

72

72

04/2009

72

-DuPont Confidential-

Portable Fire Extinguisher Design

73

73

73

04/2009

73

-DuPont Confidential-Source: NFPA 12B (1990)

74

74

74

04/2009

74

-DuPont Confidential-

• Fill density = kg agent per volume of unit• As the fill density increases, a more rapid

decrease in the application rate and throw distance during discharge occurs

• As the fill density decreases, the application rate and throw remain more constant throughout the discharge

Portable Fire Extinguisher DesignFill Density

Low fill densities not economical; balance between economics and performance required

75

75

75

04/2009

75

-DuPont Confidential-

76

76

76

04/2009

76

-DuPont Confidential-

77

77

77

04/2009

77

-DuPont Confidential-

Portables Development• No reliable small-scale test available

• Pan fire tests according to UL 711

• Wood crib tests according to UL 711

78

78

78

04/2009

78

-DuPont Confidential-

Flow Visualization : PLIFConcentration, temperature, and velocity maps

Qualitative droplet size infoDischarge shapeDischarge throw

79

79

79

04/2009

79

-DuPont Confidential-

Small droplet size:150 psig61 lb/ft3

1530 nozzle2 kg

“atomizing nozzle”

Droplets too small and light

– buoyed away from flame

80

80

80

04/2009

80

-DuPont Confidential-

Large droplet size150 psig23 lb/ft3

2 kgH nozzle

Droplets too big- Poor fire

performance

81

81

81

04/2009

81

-DuPont Confidential-

Sweet spot:150 psig43 lb/ft3H nozzle

2 kg

82

82

82

04/2009

82

-DuPont Confidential-

Toxicology• 4h LC50 > 102,900 ppm (> 10.3% v/v)• CS NOAEL = 12,500 ppm (1.25 % v/v)• CS LOAEL = 25,000 ppm (2.5% v/v)

Fire Suppression• Class A MEC = 4.7% v/v• Class B MEC = 5.3% v/v a

Streaming Candidate 1bp = 31 oC

a n-heptane

83

83

83

04/2009

83

-DuPont Confidential-

Toxicology• 4h LC50 = 120,000 ppm (12% v/v)• CS LOAEL = 25,000 ppm (2.5% v/v)

Fire Suppression• Class A MEC = 3.7% v/v• Class B MEC = 4.8 % v/v a

Streaming Candidate 2bp = 18 oC

a n-heptane

Efficiency on mass basis ~ Halon 1301

84

84

84

04/2009

84

-DuPont Confidential-

Recent Developments in Clean Agents: Summary

• Total flooding: occupied areasDevelopment of a promising candidate based on toxicological testing and small-scale fire testing

• Suitable for use in normally occupied areas• Zero ODP• Low GWP• Low chemical reactivity

Further evaluation in progress

85

85

85

04/2009

85

-DuPont Confidential-

Recent Developments in Clean Agents: Summary

• Streaming or Non-occupied AreasDevelopment of several promising candidates based on toxicological testing and small-scale fire testing• High mass efficiency; Candidate #2 close to Halon 1301 in

mass efficiency• Zero ODP• Low GWP• Low chemical reactivity

Further evaluation in progress