Transcript of HIGH PRESSURE DUCT - Tata Caldaie
HIGH PRESSURE DUCT
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 1 of 20
ISO 9001 QUALITY World Leading Design and Technology
Every product is manufactured to meet the stringent requirements of
the internationally recognized ISO 9001 standard for quality
assurance in design, development and production.
Equipped with the latest air-conditioning test rooms and
manufacturing technology, we produce over 50,000 fan coil units
each year, all conforming to the highest international standards of
quality and safety.
CE SAFETY STANDARDS The Highest Standards of Manufacturing
All products conform to the Certificate Europe directives
(Machinery Safety, Electromagnetic Compatibility and Low Voltage),
as required throughout the European Community, to guarantee correct
standards of safety.
In order to guarantee the very highest standards and performance,
we manage every stage in the manufacturing of our products.
Throughout the production process we maintain strict control,
starting with our extensive resources in research and development
through to the design and manufacture of almost every individual
component, from molded plastics to the assembly of units and
controllers.
WEEE MARK Quality Controlled from Start to Finish
All products conform to the “WEEE” directive to guarantee correct
standards of environmental solutions.
Our highly trained staff and strict quality control methods enable
us to produce products with an exceptional reputation for
reliability and efficiency, maintained over many years. As well as
full CE certification and ISO 9001, several products have UL/ ETL
safety approval in the USA and Canada, Eurovent performance and
sound certification as well as ROHS compliance for Europe, giving
you the confidence of knowing our company is the right choice when
selecting fan coil units.
ALWAYS MAKE SURE THIS MANUAL REMAINS WITH THE UNIT. READ THIS
MANUAL BEFORE PERFORMING ANY OPERATION ON THE UNIT.
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 2 of 20
B.4. Insulation
..........................................................................................................................................................................
12
B.6. Pipe Connection
................................................................................................................................................................
12
B.7. Electrical Connection
.........................................................................................................................................................
12
F. Accessories
.......................................................................................................................................................................
16
F.1. Filters
.................................................................................................................................................................................
16 F.1.1. Merv 8 (G4) Filter
.......................................................................................................................................................
16 F.1.2. Merv 14 (F8) Filter
.....................................................................................................................................................
16
F.2. Valve
..................................................................................................................................................................................
17 F.2.1. On/Off Ball Valve
.......................................................................................................................................................
17 F.2.2. Modulating Valve
.......................................................................................................................................................
17
F.3. Electric Heater Module
......................................................................................................................................................
18
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 3 of 20
Unit Sizes. See General Specification Section A for cooling and
heating capacities
510
TS Terminal Strip
FDBD Horizontal Air Handling Unit
4R 2 pipes 4 rows
6R 2 pipes 6 rows
4+2R 4 pipes with 4 rows cooling and 2 rows heating
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 4 of 20
A. Technical Data A.1. General Description FDBD unit is an ideal
air handling terminal unit for suspended ceiling installation and
suitable for ducted air distribution. It is constructed of sandwich
panels to achieve low noise level during operation. FDBD air
handling unit is shipped completely assembled and motor wiring is
introduced into the control box to reduce on-site installation time
and manpower. Every unit is thoroughly inspected and tested to
clear up potential problems during startup. The unit contains side
panels that provide easy access to fans, motors and filters.
FRAMEWORK A frameless structure is used. The panel is integrated
folding steel structure and tested to ensure that there is no air
leakage.
CASING Casing is double skinned and basically consists of two
panels with internal insulation. Each panel is 1” thick. The inner
and outer panels are made of plane galvanized steel and pre-coated
galvanized steel. The insulation consists of a high-pressure PU
foam sandwiched in between to reinforce the panel.
FILTER Filter is washable, double-layer acrylic nylon with aluminum
frame. G4 (Merv 8) or F8 (Merv 14) filter is optional.
COOLING COIL The Cooling Coil is standard Cu/Al 3/8” OD. The
manifolds are made of steel with threaded connections. The Cooling
Coil is provided with manual Air-Vent valve. The aluminum fins are
pre-coated for protection by hydrophilic blue fin process. Coils
are tested at 30 bar (435 PSI) and recommended operating at no more
than 16 bar (232 PSI).
DRAIN PAN Drain pan is made of single wall painting steel with
3/16" insulation on outer wall. The drain pan extends the full
length and width of the coil and is sloped for positive drainage
and includes 3/4” male pipe threaded galvanized drain
connector.
FAN SECTION Fans are mainly constructed of housing, impeller,
mounting feet, and AC motor. The housing is made of hot-dip
galvanized steel. The side panel includes inlet cones whose inlet
conditions are designed for optimum aerodynamics. The scroll is
fixed on the side panel by spot welding. The wheel is made of
hot-dip galvanized steel. The forward curved blades feature an
advanced aerodynamic design for maximum efficiency and minimum
noise level. The impeller is fixed on the center plate and on the
end ring with riveting compression. The impeller is designed for
maximum strength and can withstand continuous operation with
maximum power. All impellers and motor are fully balanced according
to ANSI/AMCA-204 standard. The mounting feet are made of galvanized
steel sheet with unique technical to ensure adequate
strength.
TERMINAL STRIP (T TYPE) A 230Vac relay is used to drive 1-speed AC
motor. 40VA (24Vac) transformer is optional which supplies power to
thermostat and modulating valve.
ACCESSORIES Optional accessories can be selected: G4 (Merv 8)
filter module, Mixing and recirculating chamber, 0~10V Modulating
2-way valve kit, On/Off 2-way valve kit, On/Off 3-way valve kit,
Electrical heating module, AC/EC thermostat, AQI control PCB-S5,
Complete function PCB-S6, Wired wall pad, Differential pressure
transducer.
Mixing and recirculating chamber Filter Coil Electric Heater
Module
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 5 of 20
A.2. General Specifications A.2.1. 2-pipe systems
FDBD(4R)-AC 4-row coil 2-pipe with AC motor(s) FDBD(4R)-[Size] 300
510 680 950 1200
Unit configuration
Power supply (V/Ph/Hz) 380~415/3/50 or 60Hz
Control Type ~T: Terminal Strips
P er
fo rm
an ce
D at
ESP Pa 150
Maximum sensible capacity 14.7 24.2 32.2 41.3 52.3
Heating Maximum capacity
Maximum EH 6 9 12 18 24
Sound Sound Pressure
Sound Power 73.2 79.2 82.7 83.2 87.7
Electrical Fan Motor Power W 1108 2059 3100 4118 6200
Current A 1.68 3.12 4.7 6.24 9.4
Hydraulic
Cooling water flow rate L/h 3545 5838 7790 9601 12218
Cooling water pressure drop kPa 13.5 36.1 48.2 11.9 19.8
Heating water flow rate L/h Same to cooling mode
Heating water pressure drop kPa 11.1 30.1 40.4 9.9 16.4
Water content L 9.12 10.9 13.7 16.7 18.7
Construction and Packing Data
W 1070 1070 1200 1200 1200
H 640 640 715 715 715
FDBD(6R)-AC 6-row coil 2-pipe with AC motor(s) FDBD(6R)-[Size] 300
510 680 950 1200
Unit configuration
Power supply (V/Ph/Hz) 380~415/3/50 or 60Hz
Control Type ~T: Terminal Strips
P er
fo rm
an ce
D at
ESP Pa 120
Maximum sensible capacity 16.1 25.5 34.1 47.1 59.8
Heating Maximum capacity kW 28.3 46 61.3 84.1 106
Sound Sound Pressure
Sound Power 73.2 79.2 82.7 83.2 87.7
Electrical Fan Motor Power W 1108 2059 3100 4118 6200
Current A 1.68 3.12 4.7 6.24 9.4
Hydraulic
Cooling water flow rate L/h 4053 6239 8351 11616 14755
Cooling water pressure drop kPa 25.7 9.1 12.1 25 41.3
Heating water flow rate L/h Same to cooling mode
Heating water pressure drop kPa 17.7 6.23 8.37 17.3 28.8
Water content L 13.7 16.3 20.5 25.1 28.1
Construction and Packing Data
W 1070 1070 1200 1200 1200
H 640 640 715 715 715
Test Conditions: a. Cooling mode: b. Heating mode: - Return air
temperature: 27C DB/ 19C WB. - Return air temperature: 20C. -
Inlet/ outlet water temperature: 7C/ 12C. - Inlet water
temperature: 50C.
- Water flow same to cooling model Sound Power in compliance with
EN9614-2.
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 6 of 20
A.2.2. 4-pipe Systems FDBD(4+2R)-4T 4-row cooling coil and 2-row
heating coil 4-pipe with AC motor(s)
FDBD(4+2R)-[Size]-4T 300 510 680 950 1200
Unit configuration
Power supply (V/Ph/Hz) 380~415/3/50 or 60Hz
Control Type ~T: Terminal Strips
P er
fo rm
an ce
D at
ESP Pa 120
Maximum sensible capacity 14.7 24.2 32.2 41.3 52.3
Heating Maximum capacity kW 32.1 50.6 65.3 88.7 111
Sound Sound Pressure
Sound Power 73.2 79.2 82.7 83.2 87.7
Electrical Fan Motor Power W 1108 2059 3100 4118 6200
Current A 1.68 3.12 4.7 6.24 9.4
Hydraulic
Cooling water flow rate L/h 2499 3545 4753 6890 9025
Cooling water pressure drop kPa 19.7 13.5 25.2 54.7 44.5
Cooling water content L 9.12 10.9 13.7 16.7 18.7
Heating water flow rate L/h 2756 4348 5610 7627 9519
Heating water pressure drop kPa 22.8 25.9 10.6 21.1 34.3
Heating water content L 4.56 5.43 6.84 8.36 9.37
Construction and Packing Data
Cooling In/out
W 1070 1070 1200 1200 1200
H 640 640 715 715 715
Test Conditions: a. Cooling mode: b. Heating mode: - Return air
temperature: 27C DB/ 19C WB. - Return air temperature: 20C. -
Inlet/ outlet water temperature: 7C/ 12C. - Water inlet/outlet
temperature:70 /60C Sound Power in compliance with EN9614-2.
A.3. Coil Data 2-Pipe System 4-Row Coil
Model Fin height
(mm) Fin Length
(mm) Fins per
Model Fin height
(mm) Fin Length
(mm) Fins per
Sound Power dB(A) 73.2 79.2 82.7 83.2 87.7
So u
n d
P o
w er
in 1
/3 O
ct av
e -b
an d
s u
n d
er E
SP :1
5 0
P a
(d B
25.0 Hz 29.3 26.7 32.4 30.7 37.4
31.5 Hz 36.2 27.9 39.4 31.9 44.4
40.0 Hz 40.6 39.7 42.2 43.7 47.2
50.0 Hz 44.0 42.3 51.5 46.3 56.5
63.0 Hz 54.0 47.0 60.3 51 65.3
80.0 Hz 57.4 51.5 67.6 55.5 72.6
100.0 Hz 57.6 57.7 66.3 61.7 71.3
125.0 Hz 55.3 57.1 68.9 61.1 73.9
160.0 Hz 56.2 61.8 67.2 65.8 72.2
200.0 Hz 55.9 61.7 64.9 65.7 69.9
250.0 Hz 52.1 61.4 63.8 65.4 68.8
315.0 Hz 58.6 58.2 66.4 62.2 71.4
400.0 Hz 58.8 63.3 69.0 67.3 74
500.0 Hz 59.4 65.0 68.8 69 73.8
630.0 Hz 64.7 66.5 74.2 70.5 79.2
800.0 Hz 63.8 68.7 73.4 72.7 78.4
1000Hz 66.6 71.5 73.5 75.5 78.5
1250 Hz 62.0 71.4 72.5 75.4 77.5
1600 Hz 59.5 69.5 70.3 73.5 75.3
2000 Hz 56.5 67.9 68.9 71.9 73.9
2500 Hz 55.2 67.8 67.9 71.8 72.9
3150 Hz 53.0 67.3 66.8 71.3 71.8
4000 Hz 49.7 64.6 64.9 68.6 69.9
5000 Hz 45.1 61.3 60.1 65.3 65.1
6300 Hz 42.3 59.0 56.7 63 61.7
8000 Hz 38.6 55.4 52.6 59.4 57.6
10000 Hz 33.9 50.2 46.5 54.2 51.5
12500 Hz 28.6 43.1 40.0 47.1 45
16000 Hz 21.8 33.8 30.9 37.8 35.9
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 8 of 20
A.5. Dimension Drawings FDBD-300/510/680 2-Pipe
Model A B C D E F G M W W1 H H1 I
FDBD-300 1285 563 1485 1225 305 700 780 1415 950 890 610 250
385
FDBD-510 1485 704 1685 1425 350 850 930 1615 950 890 610 250
385
FDBD-680 1585 704 1785 1525 380 950 1030 1715 1080 1020 685 326
418
All dimensions are in mm. FDBD-950/1200 2-Pipe
Model A B C D E F G H I
FDBD-950 1885 918 2085 1825 455 1420 1500 2015 385
FDBD-1200 2085 918 2285 2025 505 1570 1650 2215 418
All dimensions are in mm.
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 9 of 20
FDBD-300/510/680 4-Pipe
Model A B C D E F G M W W1 H H1 I
FDBD-300-4T 1285 563 1485 1225 305 700 780 1415 950 890 610 250
385
FDBD-510-4T 1485 704 1685 1425 350 850 930 1615 950 890 610 250
385
FDBD-680-4T 1585 704 1785 1525 380 950 1030 1715 1080 1020 685 326
418
All dimensions are in mm. FDBD-950/1200 4-pipe
Model A B C D E F G H I
FDBD-950-4T 1885 918 2085 1825 455 1420 1500 2015 385
FDBD-1200-4T 2085 918 2285 2025 505 1570 1650 2215 418
All dimensions are in mm.
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 10 of 20
B. Installation B.1. Safety Precautions When installing, performing
maintenance or servicing Daitsu fan coil units observe the
precautions stated in this manual
as well as those stated on the labels attached to the unit. Ensure
all local and national safety codes, laws, regulations, as well as
general electrical and mechanical safety guidelines
are followed for installation, maintenance and service. The
appliance is for indoor use only. Ensure the correct power supply
is provided. If the power supply cord is damaged, it must be
replaced by qualified personnel. Installing and servicing fan coil
unit should be performed by qualified service personnel only. This
appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental
capabilities, or persons lacking in experience and knowledge of the
appliance, unless they have been given supervision or instruction
concerning it.
User of this appliance is responsible for his/her own safety.
Warranty shall be voided if installation instructions and safety
precaution stated in this manual are not observed. The unit should
only be switched off by using the ON-OFF button on the control
interface.
B.2. Location Before installing and running the unit, please check
the following: 1. There must be enough space for the unit
installation and maintenance. Please refer to the below figures for
the unit's
outlines and dimensions and for the minimum distance between the
unit and the obstacle/ any obstructions/ its surroundings.
2. Please ensure there is enough space for piping connections and
electrical wiring. 3. Check whether the hanging rods can support
the weight of the unit (see specification table for weight of the
unit). 4. The unit must be installed horizontally to ensure proper
operation and condensate draining. 5. The external static pressure
of the ducting must be within the unit’s static pressure range. 6.
Confirm that the unit has been switched OFF before installing or
servicing the unit.
B >200mm -
CAUTIONS
Before any service or maintenance operations turn off the mains
electrical supply.
DO NOT turn OFF the main power supply when the unit is operating.
Turn off the unit BEFORE turning off the main power
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 11 of 20
B.3. Concealed Ceiling Installation The unit is designed to be
installed in a concealed ceiling. Installation and maintenance
should be performed by qualified personnel who are familiar with
local codes and regulations and are experienced with this type of
appliance.
Ceiling
CAUTION
Make sure the top of the unit is level after installation. The
drain pan is designed with a slight gradient to facilitate
drainage.
CAUTIONS
Dimension M and N are determined by air duct design. Air duct
should be fire-proof. Please refer to concerned country national
and local regulation. Circulatory air pressure drop should be
approximately equal to the External Static Pressure.
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 12 of 20
B.4. Insulation 1. The insulation design and materials should be
complying with local and national codes and regulations. 2. Chilled
water pipes and all parts on the pipes should be insulated. 3. It
is also necessary to insulate the air duct.
B.5. Air Duct Connection 1. Circulatory air pressure drop should be
within External Static Pressure. 2. Galvanized steel air ducts are
suitable. 3. Make sure there is no leak of air. 4. Air duct should
be fire-proof, refer to concerned national and local
regulations.
B.6. Pipe Connection 1. Using suitable fittings as water pipe
connections with reference to the outline and dimensions. 2. The
water inlet is on the bottom while outlet on top. 3. The connection
must be concealed with rubberized fabric to avoid leakage. 4. Drain
pipe can be PVC or steel. 5. Tightening torque should not be too
high when connecting water pipes, in order to avoid brass
deformation or water-
leakage by torsion split. 6. The suggested slope of the drain pipe
is at least 1:50.
B.7. Electrical Connection Standard Terminal Block
CAUTION
When connecting pipe to fan coil unit, do not bend or reposition
the coil header for alignment purposes. This could cause a tubing
fracture resulting in a water leak when water pressure is applied
to the system.
FDBD-TS
C. Maintenance
C.1. General Maintenance 1. Installation and maintenance should be
performed by qualified personnel who are familiar with local
codes and regulations and experienced with this type of appliance.
2. Confirm that the unit has been switched OFF before installing or
servicing the unit. 3. A good general maintenance plan will prevent
damage to and unexpected shutting down of the equipment. 4. Dirty
filters reduce air flow as well as unit performance. Therefore,
changing or cleaning the filters is very
important. Check the cleanliness of the filter and replace or clean
as required monthly. 5. Coils should be cleaned with compressed air
or water to remove dust, dirt or lint. They can be brushed
with a soft brush or vacuumed with a vacuum cleaner. 6. If the
water coil is not being used during the winter season it should be
drained, or an anti-freezing
solution should be added to the water circuit to avoid
freezing.
C.2. Regular Maintenance 1. Inspect and clean the condensate drain
pan to avoid any clogging of the drain by dirt, dust, etc.
Inspect
drainage piping to ensure the proper condensate flow. 2. Check and
clean the coil. Clean the coils with a low-pressure water jet or
low-pressure air. 3. Clean and tighten all the wiring connections.
4. Drain out the water system and check for buildup of residue
deposits.
C.3. Filter Cleaning 1. Remove the filter from the rear or bottom.
2. Clean the filter with a brush, or with water. 3. Reinstall the
filter by sliding it back into the groove.
C.4. Fan Replacement 1. Loosen the screws from front panel. 2.
Remove the fixing nuts of fan blower. 3. Replace the fan. 4.
Reinstall the front panel with screws.
SK 2019 GLOBAL FDBD-AC-TS-001_1
Page 14 of 20
No voltage
Faulty room control
- Check fuse on board
- Check the room control
- Remove obstacles
- Check the water source
- Check the air vent
Contact between metal parts
F. Accessories F.1. Filters
F.1.1. Merv 8 (G4) Filter Filter efficiency: Merv 8 / G4; Initial
pressure drop: 30 Pa @2m/s; HAF filter efficiency: initial
efficiency is tested under air velocity 0.1m/s
Remark: HAF filter efficiency will be down. The rate of diminishing
efficiency is based on using conditions.
F.1.2. Merv 14 (F8) Filter Filter efficiency: Merv 14 /F8 Initial
pressure drop: 80 Pa @2m/s
Filter weight: g/m2 70
Air velocity: m/s 0.51
F.2. Valve F.2.1. On/Off Ball Valve
Models 1. 3-way ball valve with 1” connectors and on/off motorized
actuator 2. 2-way ball valve with 1” connectors and on/off
motorized actuator 3. 3-way ball valve with 1-1/4” connectors and
on/off motorized actuator 4. 2-way ball valve with 1-1/4”
connectors and on/off motorized actuator Specifications Medium:
Cool/Hot water or 60% glycol Structure: Two way or Three way
Operating Mode: On/Off Power Supply: 230VAC Power Consumption: 6W
(during valve position change) Running Times: 15 sec. Pipe Fitting:
NPT internal thread
Body: Forged brass, nickel plated Ball: Chrome plated brass Stem:
Brass Seats: Fiberglass reinforced Teflon PTFE Seal: 2 EPDM
O-rings, lubricated Pressure Rating: 2MPa Media Temp. Range: 34°F
to 203°F (1°C to 95°C) Max. Differential Pressure: 1MPa Protection
Grade: IP65
Dimensions and Cv Values
2-way Valve 3-way Valve
1 1/4” (DN32) 25.97 100 50 48
All dimensions are in mm.
F.2.2. Modulating Valve
Models 2-way modulating valve with 1” connectors and 24VAC actuator
with 0-10VDC input control signal 2-way modulating valve with
1-1/4” connectors and 24VAC actuator with 0-10VDC input control
signal Specifications 24V AC power supply 0~10VDC control signal
Bi-directional modulating proportional control Working media:
cool/hot water or with 60% glycol
Media Temp. Range: 34°F to 203°F (1°C to 95°C) Rating pressure:
2.0MPa Max. Differential Pressure: 0.3MPa Opening or closing time:
50 sec. (50Hz) 40 sec. (60Hz) Connection: NPT internal thread
Dimensions & Kv Values
1-1/4(DN32) 2-way 131 73 67 105 90 10
All dimensions are in mm.
Page 18 of 20
SK 2019 GLOBAL FDBD-AC-TS-001_1 S
F.3. Electric Heater Module The electric heater module is supplied
for winter heating as an alternative to the auxiliary hot water
coil or a booster to the 2- pipe unit. The module must be installed
downstream of the basic unit at air outlet side. The PTC heaters
are mounted on a removable frame independent of the module. The
heaters feature ON-OFF operation.
FDBD-AC 300 510 680 950 1200
Max. EH capacity kW 6 7.5 7.5 9 9
Note: Make sure that the airflow is not less than the minimum value
when electric heater is turned on. It is recommended to add an air
flow switch or ESP transducer.
Eurofred S.A. Marqués de Sentmenat 97 08029 Barcelona
www.eurofred.es