FM APPROVAL ANNOUNCEMENT

Telephone: 13000 ASKINEmail: contact@askin.net.au

www.askin.net.au

ASKIN’s world beating XFLAM cored steel laminated insulated panel recently achieved a best in class by complying with the requirements of a Class One material under the test regime dictated by standard FM4880 and FM4881.

FM4880: Parallel Panel Test

The 16 foot test establishes the expected reaction of a specific product specimen to a standardized fire directed through a sand box at the base of two opposing walls, mounted to a steel frame with the following dimensions:

• Width: 1.1m

• Height: 4.9m

• Gap: 0.5m

A gas fired burner at 360kW is applied for fifteen minutes at the base of the two walls.

ASKIN’S XFLAM cored panels achieved a best in class performance without the use of joint stitching rivets.

• FM4880 unlimited height Class 1 Group A approval.

• Max heat output of 355 kW much less than the 850 kW threshold and significantly less than 550 kW generally achieved for other fire resistant insulated panels.

• Smoke generated 195 grams/15 minute test much less than 300 grams allowed for smoke sensitive construction, required for all food and drug manufacture.

In principle, the parallel panel test determines the following:

• The potential for fire spread up the wall, determined by height of char inside the panel.

• The potential for spread of fire through the wall, determined by measuring the depth of char and the remaining untouched material after the test.

• The potential for fire spread through a building is evaluated by the measurement of

the total rate of heat release of the fire, determining the material contribution to the fire.

• The hazard of reduced visibility is estimated by weighing of light-obscuring smoke.

APRIL 2015

ASKIN XFLAM PANEL ACHIEVED A CLASS ONE FIRE PERFORMANCE TO STANDARDS FM4880 AND FM4881 WITHOUT SLIP JOINT STITCHING RIVETS