248 I/O •6 HSC - w5.siemens.com · PLC Master Master Master Master Slave Slave Slave Slave Slave...
Transcript of 248 I/O •6 HSC - w5.siemens.com · PLC Master Master Master Master Slave Slave Slave Slave Slave...
Global network of innovation
Sacchi Leonardo A&D XASA
Simatic S7-200comunicazioni
Sacchi Leonardo A&D XASA
SIMATIC S7-200
• 5 cpu• Max 24 kb prog• 248 I/O• 6 HSC• Text Display programmabili
con Microwin• Wizard (programmazione
semplificata)• 8 PID
Sacchi Leonardo A&D XASA
Moduli di ampliamento…molte possibilita’
Digitali
Analogici
Posi
zion
amen
to
8 In DC
8 In AC, 120/230 VAC
16 In DC
8 In / 8 Out DC-DC
8 Out DC - 0.75 A
4 Out DC – 5A
4 Out Relay - 10 A
8 Out Relay - 2 A
8 In / 8 Out DC-Relay
16 In / 16 Out DC-DC
4 In / 4 Out DC-Rele’
4 In / 4 Out DC-DC
8 Out AC -120/230 VAC, 0.5 A
16 In / 16 Out DC-Relay
Mis
uraz
ione
tem
pera
tura
Position2 In RTD
4 In T/C
4 In
4 In / 1 Out
2 Out IT Communication
AS-i Master
Ethernet
PROFIBUS DP Slave
Modem
Com
unic
azio
ne
SIWAREX
Sacchi Leonardo A&D XASA
Telefonica
+ HTML
+ FTP
S7-200 Possibilita’ di comunicazione
S7-22x CP243-2
EM 277
CP243-1
EM 241
CP243-1 IT
Ethernet
PROFIBUS
AS Interface Field Bus
PPI/MPI Network
ASCII Protocol (FreePort)
Selfor Lodi 9/6/06
Global network of innovation
Sacchi Leonardo A&D XASA
Tecniche di comunicazione
Simatic S7-200
Sacchi Leonardo A&D XASA
Modulo Modem (EM 241)
Permette:Interfaccia per ogni tipo di linea internazioanaleModem programmabile con STEP7 Micro/WIN Password di protezioneRichiamata di sicurezzaPlug&Play
Supporta:Il protocollo Modbus RTUPaging sia numerico che testualeTrasferimento dati CPU-CPU o CPU-Modbus
Programmazione semplificata con Micro/WIN Wizard
Sacchi Leonardo A&D XASA
Modulo Slave PROFIBUS DP (EM 277)
Permette di collegare l’S7-200
come slave sulla rete PROFIBUS DP
Permette:Velocita’ di connessione da 9.6 KBit/sfino a 12 Mbit/s (con rilevazioneautomatica velocita’ massimapossibile) Protocollo PPI-Advanced, MPI e PROFIBUS DPIndicatore di stato a quattro LEDIndirizzo stazione selezionabile con switch a rotazione (0..99)
Supporta:99 periferiche sul Bus (Indirizzi da 0 a 99)Lunghezza massima rete 1200 m (a 93.75 KBit/s)
Sacchi Leonardo A&D XASA
Modulo As-I master (CP 243-2)
Permette:2 tasti sul modulo per selezionareDisplay & Operation ModeLED per indicare Slave Status, Errors e Bus Status
Supporta:128 Slave AS-Interface
Due modalita’ di funzionamento:
Standard (accesso ad I/O degli slave)Extended (Parametrizzazione or Interrogazionedati diagnostici)
Programmazione semplificata
con Wizard
Sacchi Leonardo A&D XASA
Flessibilità della struttura di rete
PLC
Master Master Master Master
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
Slave
SlaveSlave
stella lineare albero mista
PLC PLC PLC
Sacchi Leonardo A&D XASA
Modulo Ethernet (CP 243-1)
Semplice..ConnessioneAnalisi di datiAmministrazione semplice della reteFacile rimozione e sostituzione moduli
FornisceConnessione Ethernet via RJ45Collegamento a PC-Access Programmazione diagnostica e configurazioneremotaComunicazione simultanea fino ad un massimodi 8 S7
Facilita una flessibile e distribuitastruttura di automazione
Programmazione semplificata con Wizard
Global network of innovation
Sacchi Leonardo A&D XASA
Teleservice per S7-200
Teleassistenza
Sacchi Leonardo A&D XASA
Teleservice e Telecontrollo
TELEASSISTENZA TELECONTROLLO
WINCCFlex OPC CPU
5 POSSIBILITA’
Sacchi Leonardo A&D XASA
Teleservice PC+Modem+EM241
EM241Linea analogica
PG/PC
Modem qualsiasi
Step7 Microwin
Linea Analogica
Sacchi Leonardo A&D XASA
Teleservice con Modem analogico esterno
PG/PC
Modem qualsiasi
Step7 Microwin
Linea Analogica
+ +
Modem analogico PC/PPI RS232 CPU
VANTAGGI: Funzionamento anche in paesi non codificati
Sacchi Leonardo A&D XASA
Teleservice con Modem GSM
PG/PC
Modem qualsiasi
Step7 Microwin
Linea Analogica
+ +
Modem MC45t PC/PPI RS232 CPU
VANTAGGI: Funzionamento anche in paesi non codificatiGSM
MAX 9600 bps
Sacchi Leonardo A&D XASA
Teleservice VIA INTERNET / Intranet
PG/PC
Qualsiasi collegamento a Internet
Step7 Microwin
VPN Client
+
CP 243-1CP 243-1/IT
CPU
VANTAGGI: Scala geografica
Sacchi Leonardo A&D XASA
Teleservice VIA INTERNET
+
SCALANCE S ROUTER + IP statico
SCALANCE S = Firewall + VPN Server
Router NON SIEMENS
IP STATICO
Sacchi Leonardo A&D XASA
Quando con Ts adapter 2
+ +
Ts Adapter 2 CPUEM277
Se esiste una rete Mista S7-200 S7-300
E’ necessaria una EM277 per Profibus
Profibus DP 12 Mbit
MPI (anche senza Em277 se rete MPI)
Global network of innovation
Sacchi Leonardo A&D XASA
Telecontrollovia GPRS con S7-200
Sacchi Leonardo A&D XASA
Micro AutomationSINAUT MICRO - Concept
Sacchi Leonardo A&D XASA
Copertura GSM / GPRS
Sacchi Leonardo A&D XASA
Storia GPRS
INTERNETRequest
HTML-Page
ResponsePort #80
Basic idea of Micro Automation
Remote Station
Mobile
DataData
Central Station
INTERNET
Sacchi Leonardo A&D XASA
Funzionamento Routing
INTERNET
SINAUT MICRO SC
Communicationmanagment
OPC Server +Routing +
Communication management
OPC Client
GGSN*1
GSM Provider
Remote Station
Central Station
Remote Station
APN *2
Remote Station
Sacchi Leonardo A&D XASA
Interfacciamento OPC Client
VB100VB101VB102VB103 Establish and monitor connection
OPC - Server
WinCC flexible (OPC – Client)
MSC:[RS01]DB1,Real100
On Change
INTERNET
Remote StationCentral StationSINAUT MICRO SC
Sacchi Leonardo A&D XASA
Nuovo concetto
RS1 sends data to RS2
RS1 asks RS2 for data
RS2
Central Station
Central Station
�
�
RS1 sends data to CS
RS1 Central Station
�
RS1 asks CS for data
RS1 Central Station
CS sends Data to RS1
RS1 Central Station
�
CS asks RS1 for data
Central Station
Sample: Archive process data cyclic
Sample: Control Remote Station
Sample: Synchronization with Remote Station
Possible but not useful because data will be sent on change anyway
RS1
RS2
RS1 RS1
HMI
HMI HMI
HMI
Sacchi Leonardo A&D XASA
SMS e Teleservice
Sending a SMS
TeleserviceRemote Station Service Station
CSD CSD
Phone: 0911...
MicroWinDial 0911...
INTERNET
Remote StationCentral StationSINAUT MICRO SC
SMS
GPRS
GPRS
Global network of innovation
Sacchi Leonardo A&D XASA
Comunicazione PC Access
Sacchi Leonardo A&D XASA
Comunicazione Pc Acces : cosa serve
• OPC Server• Rende disponibile al sistema operativo variabili provenienti da PLC
Comunicazione PC Access
Sacchi Leonardo A&D XASA
Comunicazione Pc Acces : configurazione
• Definire interfaccia comunicazione
• Aggiungere un PLC
Comunicazione PC Access
Sacchi Leonardo A&D XASA
Comunicazione Pc Acces : Leggere il valore in tempo reale in Excel
• Anche excel può essere un OPC clientComunicazione PC Access
Sacchi Leonardo A&D XASA
Comunicazione Pc Acces : Highlights
• Connessione simultanea fino a 8 PLC
• Nessun limite sul numero di variabili
• Si possono collegare più PC ad uno stesso PLC (3 per ciascuna porta + 5 su ciascuna EM277 + 8 su ciascuna CP ethernet)
• Importazione simbolici da progetto PLC
• Possibilità integrata di interrogare via modem dei PLC remoti
Comunicazione PC Access
Sacchi Leonardo A&D XASA
Comunicazione Pc Acces : Interrogazione via modem
• Configurazione di un modem standard per PCComunicazione PC Access
Sacchi Leonardo A&D XASA
Comunicazione Pc Acces : Interrogazione via modem
• Inserire un PLC e un item come prima • Collegamento via modem
Comunicazione PC Access
Sacchi Leonardo A&D XASA
SIMATIC S7-200 Soluzioni semplici
Comunicazioni in rete semplificate da wizard
Comunicazione PPI, TCP/IP, AS-I, ASCII
Programmazione remota
Data Logging anche via modem o GSM
Integrazione in sistemi più complessi
Comunicazione GPRS