Universal Electronic Aquastat®L7224U1002
Training Module
Includes Honeywell’s AquaReset® Outdoor Reset Solution
2
What you will learn
• L7224U Product Overview• Key Features• Installation• Set Up• Troubleshooting• Product Cross Reference• L7224U Advantages
3
L7224U Universal Electronic Aquastat®
• What is the L7224U1002?
- Universal electronic Aquastat that provides circulator, burner and boiler temperature control with electronic temperature sensing in an oil fired hydronic heating appliance.
- Provides status and diagnostic information through an LED display to enhance the diagnostic process.
One part number:
L7224U1002
4
Aquastat® Key Features
Electronic Aquastat®
L7224U1002
• Triple Aquastat (High, Low, Circulator Control)
• Outdoor reset ready
• EnviraCOM™ communications enabled
• Electronic configuration
• Diagnostic updates through LED Display
• Provides multizone control
• Horizontal or vertical flange mounting
5
L7224U Universal Electronic Aquastat
• Why choose the Honeywell L7224U1002?
• Universal Compatibility• Replaces over 40 existing Honeywell controls
• Easy Installation• Redesigned to simplify wiring• Direct or remote mount
• Superior Performance and Accuracy• +/- 2 degree accuracy
• Multi-Function LED Display• Speeds installation and troubleshooting • Push button product set up & configuration• Get set point, temperature and diagnostic info
• EnviraCOMTM communications enabled• Easily add outdoor reset with 3 wires• Remote diagnostics• OnWatch Diagnotic compatible
6
Additional L7224U features
•Remote 48” sensors available
•One Amp slow-blow fuse
• Improved terminal layout and multiple knockouts
•Vertical, Horizontal, and Flush-Mounting - configurable for single-function use
•Low Limit can be disabled (cold start boiler applications)
•Outdoor reset functionality enabled when combined with W8735S1000 AquaReset® kit
7
L7224U Features
ThermostatTerminals
Digital Display
Capacitor
Keyed SensorConnector
Transformer
Fuse
Relays
Flush MountingTabs (2)
Line VoltageTerminals
PushButtons – Configuration& Access Diagnostic Information
EnviraCOM Data port
Multiple Sensor Holes
Enviracom™Terminals
8
Ranges and Ratings
• Setting Ranges +/-2 Degree Accuracy- High Limit: 130 – 240°F - High Limit Differential (new feature): 5 – 20°F- Low Limit: 110 – 220°F- Low Limit Differential: 10 – 25°F
• Electrical Ratings- Voltage: 120 VAC 60 HZ- Burner: 7.4 Amps- Circulator: 7.4 Amps- Zone Controller (ZC): 7.4 Amps
• Environmental Ratings- Temperature: -30 °F to 150 °F- Humidity: 0 to 95% relative humidity
Installation
10
Wiring of the L7224U
Keyed sensor connector plugs into circuit board
Well mounting PN 50001464-001 12 in.Included in the box
Flush mountingPN 50001464-005 48 in.
11
Wiring of the L7224U -- Thermostat
ThermostatTerminals
3
2
1
T
T
Enviracom™Terminals
Connect AquaReset® and otherEnviracom devices
12
Wiring of the L7224U – Line Voltage
Line VoltageTerminals
ZR Power from zone relayto burner
L1 Power hot
L2 Power neutral
C2 Circulator common
B2 Burner common
C1 Circulator hot
B1 Burner hot
ZC Power to zone
circulator relay
13
Connecting AquaReset®
ThermostatTerminals
3
2
1
T
T
Enviracom™Terminals
Wire 1,2,3 terminals on Aquastat to 1,2,3 terminalsto the Outdoor Reset Module
14
Connecting AquaReset®
Outdoor SensorTerminals
Wire 1,2,3 terminals on Aquastat to 1,2,3 terminalsto the Outdoor Reset Module. Mount outdoor sensor
Outside and connect wires to the OT terminals
Enviracom™Terminals
1 2 3 OTOT
Set Up
16
Set Up of the L7224U
• To adjust the settings- Press the UP, DOWN, and I buttons simultaneously for three
seconds- Press the I button until the desired feature is displayed- Then press UP and/or DOWN to move the set points to desired
values- After 60 seconds without any buttons pressed, the control
automatically goes back to READ mode
• Display- In RUN mode the Aquastat will flash boiler temp (bt) followed by the
temperature- To read settings press the I key to scroll thought the functions
I
Increase valueof setting
Decrease valueof setting
Cycles through Settings & conditions
17
Set Point Adjustments
I
Increase valueof setting
Decrease valueof setting
Cycles through Settings & conditions
18
L7224U Electronic Aquastats® (LED LIGHTS)
ThermostatCalling
EnviraCOMNetwork Active
Power toZone Circulator
Interrupted
CirculatorPowered
BurnerEnergized
19
Digital Readout of System Conditions
Run mode – display shows boiler temperature
Push “I” buttonto see other values
LED display
DisplayText Description Shows
bt Boiler Temperature
HL High Limit
LL Low Limit
Hdf High Limit Differential
Ldf Low Limit Differential
tt Local Thermostat Status
tte Enviracom Thermostat Status
brn Burner Status
cir Circulator Status
Zc Zone Control
Zr Zone Request
err Error Code
°f Degrees Fahrenheit
°c Degrees Celsius
20
DisplayText Description Shows
duu ZR configured as Domestic
Hot Water Request
ASC Anti Short-Cycle timeout
bSP Boiler Setpoint
dhc DHW module connected
ot Outdoor temperature
otL Outdoor temperature low
otH Outdoor temperature high
btL Boiler temperature low
bP Boost Period
bS Boost step
UUS Warm weather shutdown
temperature
Digital Readout of System Outdoor Reset Functions
Push “I” buttonto see other values
LED display
The following messages are only available when connected to a W8735S1000 outdoor reset kit and/or W8735S1008 domestic hot water priority kit
21
L7224U Electronic Aquastats® (Digital Readout of System Conditions)
Push “I” buttonto see other values
LED display
Run mode – display shows boiler temperature
Technicians Quick
Reference Guide #69-1957
Troubleshooting
23
• Is there an error code on the display?
ErrorCode Cause/Action• Err 1 Sensor fault; check sensor• Err 2 ECOM fault; check EnviraCOM™ wiring• Err 3 Hardware fault; replace control• Err 4 B1 fault; check B1 wiring/voltage• Err 5 Low line voltage; check L1-L2 110 Vac• Err 6 Fuse; check ECOM wires, replace fuse• Err 7 EEPROM, HL, LL, Hdf, Ldf; Reset to
default values. Restore desired settings.• Err 8 Repeated B1 fault (voltage present at B1 when output is turned off); check B1 wiring/voltage
Troubleshooting: L7224U Electronic Aquastats® (Error Codes)
24
• Is there an error code on the display?
ErrorCode Cause/Action• Err 9 Outdoor reset system failure, check wiring• Err 10 Boost Failure, check outdoor reset curve settings• Err 11 Domestic Hot Water module failure, check wiring
• Error codes 9, 10 and 11 only apply when AquaReset and/or Domestic Hot Water priority modules connected to Aquastat
Troubleshooting: L7224U Electronic Aquastats® (AquaReset Error codes)
25
Troubleshooting: L7224U Electronic Aquastats®
• For Honeywell EnviraCOM™ enabled equipment
- Read EnviraCOM™ Error Codes
- Line Voltage
- Aquastat Well Temperature- The QuickLookTM 72 is available through www.onwatchinc.com
On Watch QuickLookTM 72
Product Cross Reference
27
Product Cross Reference
• Where do I find Honeywell universal electronic aquastat cross reference information?
- www.customer.honeywell.com
- Honeywell Application Selection and Cross
Reference Guide – Form 63-9575
- Honeywell Laminated Truck Visor – Form 63-9581O
- Honeywell Residential Technical Support: 1-800-468-1502
63-9581O 63-9575
28
Aquastat® Cross Reference Table
This chart can be found in the Residential Combustion Application Guide: Form #63-9575
29
www.customer.honeywell.com
• See Cross Reference Search box in right column.
30
L7224U Advantages
• When promoting the Honeywell L7224U1002 keep these advantages in mind:
• This Universal control replaces over 40 existing Honeywell controls. • Save time searching for the exact replacement parts• Stock less parts on the shelf and in the truck
• Installation is easy with this redesigned control.• Wiring has been simplified• Mounting choices - control can be direct or remote mount
• Performance and accuracy are superior to past controls.• +/- 2 degree accuracy
• The multi-function LED display means less time spent on installation and troubleshooting.
• Push button product set up & configuration
• EnviraCOMTM communications enabled is an added advantage providing remote diagnostic capabilities.
31
L7224U Universal Electronic Aquastat Knowledge Test
• Now that you completed this training module, take the short quiz to test your knowledge.
32
Test
1. The L7224U provides temperature control of circulators, burners and boilers with electronic temperature sensing? T of F
2. The L7224U is considered a single function aquastat which provides high limit and low limit control? T or F
3. The L7224U is accurate within +/- 2 degrees? T or F
4. A 48” sensor is available to accommodate application requirements? T or F
5. Setpoints are easily adjusted with the up and down push buttons? T or F
33
Test
6. The “I” button cycles through settings and conditions? T or F
7. Error codes can be read only through the LED display? T or F
8. The low limit can be disabled for a cold start boiler application? T or F
9. Honeywell provides cross reference information for replacing over 40 existing controls? T or F
10.The L7224U has a LED light that shows whether the burner is energized? T or F
34
Answer Key
1. T2. F3. T4. T5. T6. T7. F8. T9. T10.T