STULZ IT Cooling Solutions and Services 11
Mission Energy:
Energy Efficient Cooling
Developing CAPEX efficient free cooling strategies and evaluating their
impact on OPEX and TCO
STULZ IT Cooling Solutions and Services 22
The tasks of cooling a data centreWhat is a direct and an indirect free cooling system?
TCO calculations for your investment in the futureThe air conditioning systems of the futureSTULZ – your partner for coolnig solutions
The new dimension of free cooling !
STULZ IT Cooling Solutions and Services 33
The tasks of cooling a data centre
The new dimension of free cooling !
STULZ IT Cooling Solutions and Services 4
Goals today: Cold aisle – hot aisle concept, but…
seperate the cold and the hot air
STULZ IT Cooling Solutions and Services 5
…„straight rows of racks are mixing with „other“ IT equipment
STULZ IT Cooling Solutions and Services 6
The target of the air conditioning: cold air in front of the 19” level
and a clear horizontal air path through the rack
Source: INTEL Source: HP
STULZ IT Cooling Solutions and Services 77
Energy flow through the Data CentrePower Usage Efficiency Finally all leaves as Waste Heat
Source: The Green Grid
STULZ IT Cooling Solutions and Services 8
FREE COOLING Room conditions
Ambient air
Raised floor height
Water temperatures
Part load behaviour
Coil dimensioning
Filter surface
Fan technology
Unit sizing
Refrigerant
Pipework dimensions
Pump technology
Unit options
parameters
Filter condition
Amount of refrigerant
Air path
Some criteria that have an influence on the energy efficiancy of your data centre
Stand-by concept
setpoints
Sensor adjustment
STULZ IT Cooling Solutions and Services 99
What is a direct and an indirect free cooling system?
The new dimension of free cooling !
STULZ IT Cooling Solutions and Services 10
…free cooling is not a new technology- at least not in this region!
Indirect free coolingindirect: water/glycol will be used as a medium between the inside and outside
Direct free coolingdirecf: a huge part of the ambient air will be deliveredinside the data centre
Cooling the room without compressor operation: FREE COOLING
Free cooling for IT-rooms
STULZ IT Cooling Solutions and Services 11
Indirect free coolingindirect: water/glycol will be used as a medium between the inside and outside
Direct free coolingdirecf: a huge part of the ambient air will be deliveredinside the data centre
Cooling the room without compressor operation: FREE COOLING
Free cooling for IT-rooms
⇒ pedal conneted to the back wheel with a chain will be used for the transmission of force ⇒ pedal directly
at the wheel
STULZ IT Cooling Solutions and Services 12
Function of the indirect free cooling system
STULZ IT Cooling Solutions and Services 13
Indirect free coolingCRAC units with integrated free cooling function
Room air will be seperated from the ambient air by a water/glycol system
STULZ IT Cooling Solutions and Services 14
Indirect free coolingchillers with integrsted free cooling function
Room air will be seperated from the ambient air by a water/glycol system
STULZ IT Cooling Solutions and Services 1515
TCO calculations for your investment in the future
The new dimension of free cooling !
STULZ IT Cooling Solutions and Services 16
System without freecooling vs. System with free cooling
TCO calculation for future investments
STULZ IT Cooling Solutions and Services 1717
CAPEX+32%
OPEX-56%PER
YEAR
Example1: Traditional Air cooled vs. Stulz DFC
STULZ IT Cooling Solutions and Services 1818
Example1: Traditional Air-cooled vs. Stulz DFC
€ 220.000.-Cost reduction
STULZ IT Cooling Solutions and Services 1919
Example1: Traditional Air-cooled vs. Stulz DFC
STULZ IT Cooling Solutions and Services 2020
Example 2: Chilled Water vs. DFC (300kW)
CAPEX:+70%
OPEX:-60%
10 yearSavings=€570.000
STULZ IT Cooling Solutions and Services 2121
Example 2 : Chilled Water vs. DFC (300kW)
STULZ IT Cooling Solutions and Services 22
Energy use
DX
Com
pressoroperation
FCFree cooling
EFCExtendedFree cooling
MIX
Com
pressor andFree cooling
Indoor
OutdoorC
ontrol
data
Dynamic Free Cooling,Control of all componentsIn the system to assure The minimum powerconsumption
Further potential of saving energy with an indirect free cooling system
variable control of all components Stand-by management Maximum energy eficiancy approx. 30% energy saving againstOther free cooling systems
STULZ IT Cooling Solutions and Services 2323
The air conditioning systems of the future
The new dimension of free cooling !
STULZ IT Cooling Solutions and Services 24
NEW CONCEPTS: STULZ Direct Free Coolung!
ASHRAE TC 9.9 - 2004
ASHRAE TC 9.9 - 2008
Different requirements allow for new concepts!
or
Tight tolerances will still require Indirect free cooling systems!
STULZ IT Cooling Solutions and Services 25
NEW CONCEPTS: STULZ Direct Free Cooling!
Ber
lin
Bre
mer
have
n
Ess
en
Fra
nkfu
rt
Ham
burg
Man
nhei
m
Mün
chen
Nür
nber
g
Stu
ttgar
t
% Anteil 87,6 94,1 91,2 86,8 92,6 85,7 90,0 88,9 90,7
Stunden 7.672 8.239 7.992 7.601 8.111 7.508 7.883 7.787 7.942
Stunden = Jahrestemperaturstunden bis einschließlich 18°C
WETTERDATEN
Mittlere jährliche Stundenanzahl, gemäß DIN 4710 Januar 2003
% Anteil = Prozentualer Anteil der Jahrestemperaturstunden bis einschließlich 18°C
In Germany for example more the 85% of the time the temperatures are ≤ 18°CHere the results will be even BETTER!!!!
STULZ IT Cooling Solutions and Services 26
NEW CONCEPTS: STULZ Direct Free Cooling with optimised coil placement
STULZ IT Cooling Solutions and Services 27
NEW CONCEPTS: STULZ Direct Free Cooling!
Advantages:
High energy efficiancy by using direct free cooling technology –no losses by additional heat exchangers
High scalibility of the system „Build as you grow!“ –no hydraulics (pipework, pumps, valves) at day 1 needed for the final stage
Lower CAPEX compared with indirect free cooling systems
Lower OPEX (energy consumption) the on all other systems
STULZ IT Cooling Solutions and Services 28
NEW CONCEPTS: STULZ Direct Free Cooling!Conditions:
Accepted room humidity level at approx. 20%- 80% r.H.
Ambient conditions need to be observed (dust) while selecting the site (not close to highways, harvest or in the city centres)
Acceptance of possible ourside influences(e. g. smoke, gas, etc.)
Compromising the building safety
Structural conditions:
Free in the construction of the building
short distances of the air intake and extract (pressure losses)
Air intake on the shadow side of the building
STULZ IT Cooling Solutions and Services 2929
STULZ – your partner for coolnig solutions
The new dimension of free cooling !
STULZ IT Cooling Solutions and Services 30
STULZ International Production Sites
STULZ Air Technology Systems,Frederick/MD, USA
STULZ S.p.A.Valeggio sul Mincio(VR),Italy
STULZ GmbHHamburg, Germany
STULZAir Technology Systems(Shanghai), China
STULZ CHSPL (India) Pvt. Ltd., India
STULZ IT Cooling Solutions and Services 3131
Find STULZ ...
Italy
Germany
China
USA
Headquarter
… and its qualified and professional partners –worldwide.
Production Sites
India
Germany
STULZ IT Cooling Solutions and Services 32
STULZ Group of Companies
A/C Technology Plastics Technology
Plastics Technology € ≥ 400 MioA/C Technology € ≥ 300 Mio
Total € ≥ 700 Mio
EmployeesPlastics Technology ≥ 2.400A/C Technology ≥ 1.600Total ≥ 4.000
Manufacturer and Distributor of Air Conditioning Products, SystemsEngineering, Service and Object Management.
STULZ GmbH, Germany (P)STULZ Pty Ltd., AustraliaSTULZ-ATS (Shanghai), China (P)STULZ France S.A.R.L., FranceSTULZ UK Ltd., Great BritainSTULZ CHSPL Pvt. Ltd., India (P)STULZ SpA, Italy (P)STULZ Groep B.V., NetherlandsSTULZ Ltd., New ZealandSTULZ Polska Sp. z o.o., PolandSTULZ España S.A., SpainSTULZ-ATS Inc., USA (P)Stulz South Africa Pty. Ltd. (P): Production Site
Development and Production of Technical Plastic Components for automotive industry.
Montaplast GmbH, Germany
Montaplast of North America, Inc.,USAMontaplast (SIP) Co.,Ltd., China
STULZ IT Cooling Solutions and Services 33
STULZ PRODUCTS – Reliable just everywherePrecision air conditioning for small telecom and IT applications Rechenzentrum
Chillers for precision air conditioning units and water-cooled racks
Chillers from 5kW – 1,5MW
Precision A/C units from 4kW – 200kW
Telecom air conditioners from 200W– 20kW
STULZ IT Cooling Solutions and Services 34
STULZ PRODUCTS – innovative and efficiant !
Introduction of the energy efficiant EC fan technology as STANDARD for all CyberAir units already in 2004 – today as option seen on nearly all other manufacturers
STULZ System Cost Calculation tool is delivering world-wide TCO calculations for operators all around the world since 2006
STULZ Stand-by Management as an integrated control function on all CW- units was introduced 2006 to save energy
Improvement of the indirect free cooling system by Stulz with the introduction of the Dynamic Free Cooling in May 2007
Optimisation / extension of the chilled water range in November 2008 CyberAir CWund CWE – Target: Max. energy efficiancy
New STULZ concepts for direct free cooling
STULZ IT Cooling Solutions and Services 3535
Stulz GmbHThomas SteinbergHolsteiner Chaussee 28322457 Hamburg, Germany
Thank you..
Ph: +49 – 40 – 5585 526 Email: [email protected] Web: www.stulz.com