SCHOOL OF ELECTRICAL AND ELECTRONICS ENGINEERING
LAB REPORT
THREE PHASE INDUCTION MOTOR
SUBJECT
CONTROL AND ELECTRICAL SYSTEMS
YEAR
2011
2
EXPERIMENT 1
STUDY OF CHARACTERISTICS OF THREE PHASE INDUCTION MOTOR
Aim
To study the no load characteristics of three phase induction motor
Objectives
i) To investigate the no load characteristic of a three phase induction motor.
ii) To study the relation between the current and the voltage of three phase induction
motor in both star and delta connection.
iii) To modify the sense of rotation.
Name plate details
3 phase induction motor
Rated voltage = 41.5 V.AC
Rated power = 50 W
Rated current = 1.4 A
Rated speed = 1320 RPM
3
Introduction
Induction motor is a rotating electrical machine. Induction motor can be operated by one
phase alternating voltage source and by three phase alternating voltage source. The
induction motor consists of ‘Stator’ and ‘Rotor’, stationary part and rotational part,
respectively. The rotor consists of cylindrical iron that laminated with copper strips. The
stator consists of a three phase windings that are placed on the slots of laminated core,
these windings apart by 120 degrees. These windings can be connected be configured in a
star connection or in delta connection.
4
i) Star connection
Circuit diagram
Figure 1.0: Star connection diagram
Procedure
Connections were mad as shown in (Figure 1.0).
The AC supply voltage adjusted to minimum and the maximum rated voltage of
the motor is noted.
The AC supply is turned on and the voltage increased to the maximum voltage
rated for the motor which is 41.5 volts. I been ware to not exceed the limit.
The no load current of the maximum rated voltage for the motor is tabulated.
The voltage is decreased gradually by 5 volts and the no loads current is tabulated
and repeat by decreasing the voltage and tabulate the no load current and voltage.
When all readings are tabulated I decreased the AC supply voltage to 0 volts and
off the supply.
The no load characteristics of the induction motor is sketched.
5
Experimental results of star connection
SI
No.
Star connection
Voltage Current
1 41.5 0.4
2 35 0.35
3 30 0.3
4 25 0.25
5 20 0.2
6 15 0.15
7 10 0.1
Star connection IV characteristics graph
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0 10 20 30 40 50
Cu
rre
nt
(A)
Voltage (V)
Figure 1.1: Star connection I versus V graph
Table 1.0: Star connection IV table
6
ii) Delta connection
Circuit diagram
Figure 1.2: Delta connection diagram
Procedure
Connections were mad as shown in (Figure 1.2).
The AC supply voltage adjusted to minimum and the maximum rated voltage of
the motor is noted.
The AC supply is turned on and the voltage increased to the maximum voltage
rated for the motor which is 41.5 volts. I been ware to not exceed the limit.
The no load current of the maximum rated voltage for the motor is tabulated.
The voltage is decreased gradually by 5 volts and the no loads current is tabulated
and repeat by decreasing the voltage and tabulate the no load current and voltage.
When all readings are tabulated the AC supply voltage is decreased to 0 volt and
off the supply.
The no load characteristics of the induction motor is sketched.
7
Experimental results of delta connection:
SI
No.
Star connection
Voltage Current
1 41.5 1.4
2 30 0.9
3 25 0.7
4 20 0.6
5 15 0.5
6 10 0.4
7 5 0.3
. Delta connection IV characteristics graph
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
0 5 10 15 20 25 30 35 40 45
Cu
rre
nt
(A)
Voltage (V)
Figure 1.2: Delta connection I versus V graph
Figure 1.2: Delta connection IV table
8
Analysis
1. Difference in phase and line current in star and delta connections.
Figure 1.3: Star connection
(Figure 1.3) shows that for a star connected loads the potential difference across
any load is the potential difference between the phase line connected to it and the
neutral, however the line voltage will be greater than this because it is the
potential difference between two phase lines. The current through the load will be
the same as the line current. Thus for balanced star connected loads:-
ELine = √3EPhase
And
ILine = IPhase
IP = IL
9
Figure 1.4: Delta connection
(Figure 1.4) shows that for delta connected systems of loads the phase voltage is
equal to the difference between two lines. The phase current for each load is
coming from two lines (because each load is connected to two lines) and will be
more than the line current. Thus for delta connected loads:-
ELine = EPhase
And
ILine = √3 IPhase
2. Reasons for the motor to change the rotation direction.
When exchanging two phases the motor rotation direction changes due to the
change in flux direction produced by the windings in the motor.
√3 IP = IL
10
3. Explanation on how rotating magnetic field is produced in the stator of a
three phase induction motor.
The premise for motor operation is that if you can create a rotating magnetic field
in the stator of the motor, it will induce a voltage in the armature that will have
magnetic properties causing it to 'chase' the field in the stator. This premise
applies to AC motors that employ a squirrel cage rotor, and it is probably the most
simple and basic of all motor designs. The three phase motor is widely used in
industry because of its low maintenance characteristics. Due to the nature of three
phase power, creating a rotating magnetic field in the stator of this motor is simple
and straight forward.
The stator windings are arranged on the stator poles in a way that results in
magnetic flux lines that seem to rotate where , the number of pole pairs must be
the same as or a multiple of the number of phases in the applied voltage. The
poles must then be displaced from each other by an angle equal to the phase angle
between the individual phases of the applied voltage and the strength of the
magnetic field changes, as the current flow in the coils of wire around the stator
poles change. Just as the current in the field windings rise and fall 120 electrical
degrees apart, so does the resulting magnetic field on the pole.
11
4. Safety requirements when dealing with high power rated three phase
induction motor.
Safety is needed at a time of installation, after the installation and at the time of
servicing.
Safety requirement at time of installation:-
Check for any damage which may have been incurred in handling.
The motor shaft should turn freely by hand. Repair or replace any loose or
broken parts before attempting to use the motor.
Check to be sure that motor has not been exposed to dirt, grit, or excessive
moisture in shipment or storage before installation.
Measure insulation resistance.
Clean and dry the windings as required. Never start a motor which has
been wet without having it thoroughly dried.
Safety requirement after installation:-
Ensure that safety guards are in use.
Keep hands and clothing away from moving parts.
Never attempt to measure the temperature rise of a motor by touch.
Temperature rise must be measured by thermometer, resistance, imbedded
detector, or thermocouple.
12
Safety requirement at time of maintenance:-
All power sources to the motor and to the accessory devices should be de-
energized and disconnected and all rotating parts should be at standstill.
Suitable protection must be used when working near machinery with high
noise levels.
Safeguard or protective devices must not be by-passed or rendered
inoperative.
The frame of this machine must be grounded in accordance with the
National Electric Code and applicable local codes.
A suitable enclosure should be provided to prevent access to the motor by
other than authorized personnel. Extra caution should be observed around
motors that are automatically or have automatic re-setting relays as they
may restart unexpectedly.
Shaft key must be fully captive or removed before motor is started.
Provide proper safeguards for personnel against possible failure of motor-
mounted brake, particularly on applications involving overhauling loads.
13
Conclusion
All in all, the three phase synchronous induction machine consist of winding
either connected in delta configuration or Star configuration but for each
configuration the relation between the phase and line in voltage and current varies.
And the rotating direction depends on the flux produced by the windings.
14
References
i. Donald G. Beaty, H. Wayne Fink, (1978). Standard Handbook for Electrical
Engineers. 11th Edition. The Kingsport Press.
ii. Galileo Ferraris, (1885). Electromagnetic rotation with an alternating current,
Electrican, Vol 36. p 360-75.
iii. Benjamin Franklin Bailey, (1911). The induction motor. McGraw-Hill.
15
EXPERIMENT 2
LOAD TEST ON THREE PHASE INDUCTION MOTOR
Aim
The load test on 3-phase induction motor is performed to obtain its various characteristics
including efficiency.
Objectives
i) To investigate the performance characteristics of three phase Induction motor by
applying eddy current load
ii) To determine the efficiency of a three phase Induction motor
Name plate
3 phase induction motor
Rated voltage = 41.5 V.AC
Rated power = 50 W
Rated current = 1.9 A
Rated speed = 1320 RPM
16
Circuit Diagram
3 phase squirrel cage induction
motor
Eddy current load
Stator star connected
3-phase winding
Eddy
current
load
3 phase
41.5V 50Hz
AC supply
Figure 2.0: Motor to Eddy current load connection
17
Procedure
Connections were mad as shown in (Figure 2.0).
The AC supply voltage adjusted to minimum and the maximum rated voltage of
the motor is noted.
The AC supply is turned on and the voltage increased to the maximum voltage
rated for the motor which is 41.5 volts. I been ware to not exceed the limit.
The no load current, power factor, power and torque of the maximum rated
voltage for the motor are tabulated.
Eddy current load was connected to the induction motor and supplied by a DC supply.
The Eddy current load is increased gradually by increasing the DC supply.
The load current, power factor, power and torque are tabulated for the resultant
until the load current reaches the maximum rated current.
When all readings are tabulated the AC and DC supplies are decreased to 0 volt
and off the supplies.
The load characteristic of the induction motor is sketched.
Experimental results
V1 V2 I1 I2 P.F1 P.F2 T N
41.3 V 41.5 V 0.5 A 0.5 A 0.995 0.82 0 1412.5
40.6 V 40.8 V 0.6 A 0.5 A 0.995 0.81 0.114 1389
38.8 V 39.1 V 0.7 A 0.6 A 0.995 0.78 0.1444 1332.4
35.9 v 36.2 V 0.8 A 0.8 A 0.998 0.74 0.2052 1223.1
35.5 V 35.8 V 0.9 A 0.8 A 0.999 0.72 0.2584 1191.1
34.4 V 34.7 V 1 A 0.9 A 0.999 0.69 0.3192 1082.3
Table 2.0: Tabulated experimental results
18
Analysis
1. Determine the input power, output power and efficiency.
i. For V1 = 41.3, I1 = 0.5 and Cos1 = 0.995
W1 = V1 x I1 x Cos1
= (41.3) (0.5) (0.995)
= 20.55W
For V2 = 41.5, I2 = 0.5 and Cos2 = 0.82
W2 = V2 x I2 x Cos2
= (41.5) (0.5) (0.82)
= 17.02W
Power Input = W1 + W2
= 20.55 + 17.02
= 37.57W
Power output = T
= 0
= 0 W
Efficiency% =
x 100
19
=
x 100
= 0 %
Synchronous speed (Ns) =
=
= 1500rpm
Thus, slip =
=
= 0.06
ii. For V1 = 40.6, I1 = 0.6 And Cos1 = 0.995
W1 = V1 x I1 x Cos1
= (40.6) (0.6) (0.995)
= 24.24W
For V2 = 40.8, I2 = 0.5 and Cos2 = 0.81
W2 = V2 x I2 x Cos2
= (40.8) (0.5) (0.81)
= 16.52W
Power Input = W1 + W2
= 24.24 + 16.52
= 40W
20
Power output = T
= 0.0114
= 16.58W
Efficiency% =
x 100
=
x 100
= 40.68%
Slip =
=
= 0.074
iii. For V1 = 38.8, I1 = 0.7 and Cos1 = 0.995
W1 = V1 x I1 x Cos1
= (38.8) (0.7) (0.995)
= 27.02W
For V2 = 39.1, I2 = 0.6 and Cos2 = 0.78
W2 = V2 x I2 x Cos2
= (39.1) (0.6) (0.78)
= 18.3W
21
Power Input = W1 + W2
= 27.02 + 18.3
= 45.32W
Power output = T
= 0.1444
= 20.15W
Efficiency% =
x 100
=
x 100
= 44.46%
slip =
=
= 0.112
iv. For V1 = 35.9, I1 = 0.8 and Cos1 = 0.998
W1 = V1 x I1 x Cos1
= (35.9) (0.8) (0.998)
= 28.66W
For V2 = 36.2, I2 = 0.8and Cos2 = 0.74
22
W2 = V2 x I2 x Cos2
= (36.2) (0.8) (0.74)
= 21.43W
Power Input = W1 + W2
= 28.66 + 21.43
= 50.09W
Power output = T
= 0.2052
= 26.3W
Efficiency% =
x 100
=
x 100
= 52.5%
Slip =
=
= 0.184
23
v. For V1 = 35.5, I1 = 0.9 and Cos1 = 0.999
W1 = V1 x I1 x Cos1
= (35.5) (0.9) (0.999)
= 31.79W
For V2 = 35.8, I2 = 0.8 & Cos2 = 0.72
W2 = V2 x I2 x Cos2
= (35.8) (0.8) (0.72)
= 20.62W
Power Input = W1 + W2
= 31.79 + 20.62
= 52.41W
Power output = T
= 0.2548
= 32.23W
Efficiency% =
x 100
=
x 100
= 61.5%
Slip =
=
= 0.206
vi. For V1 = 34.4, I1 = 1 and Cos1 = 0.999
24
W1 = V1 x I1 x Cos1
= (34.4) (1) (0.999)
= 34.37W
For V2 = 34.7, I2 = 0.9 and Cos2 = 0.69
W2 = V2 x I2 x Cos2
= (34.7) (0.9) (0.69)
= 21.55W
Power Input = W1 + W2
= 34.37 + 21.55
= 55.92W
Power output = T
= 0.3192
= 36.18W
Efficiency% =
x 100
=
x 100
= 64.7%
Slip =
=
= 0.28
25
The calculated input power, output power and efficiency are tabulated as shown in
(Table 1.1).
W1 W2 Efficiency
20.55w 17.02w 37.57 0 14.9%
24.24w 16.52w 40.76 16.58 40.68%
27.02w 18.30w 45.32 20.15 44.46%
28.66w 21.43w 50.09 26.3 52.5%
31.79w 20.62w 52.41 32.23 61.5%
34.37w 21.55w 55.92 36.18 64.7%
1. Can the speed of the induction motor be equal to synchronous speed?
At idle the rotor almost reaches the synchronous speed of the rotary field,
since only a small counter-torque (no-load losses) is present. If it were to turn
exactly synchronously, voltage would no longer be induced, current would
cease to flow, and there would no longer be any torque. During operation the
speed of the rotor drops to the load speed n. The difference between the
synchronous speed and the load speed is called slip s. Based on this load-
dependent slip s, the voltage induced in the rotor winding changes, which in
turn changes the rotor current and also the torque T. As slip s increases, the
rotor current and the torque rise. And that resultant drops in speed.
Table 2.1: Input power, output power and efficiency
26
3) Construction of squirrel cage rotor and slip ring rotor.
The squirrel cage rotor consists of a slotted cylindrical rotor core sheet package
with aluminium bars which are joined at the front by rings to form a closed cage. The
rotor of three-phase induction motors sometimes is also referred to as an anchor. The
reason for this name is the anchor shape of the rotors used in very early electrical
devices. In electrical equipment the anchor's winding would be induced by the
magnetic field, whereas the rotor takes this role in three-phase induction motors as
shown in (Figure 2.1).
Figure 2.1: Squirrel cage rotor
27
The slip ring induction motor rotor has similar construction as the squirrel cage
rotor, unless it consists of slip rings and it has three carbon brushes connected
externally to a 3-phase start connected rheostat as shown in (Figure 2.2). Thus
these slip ring and external slip rings rheostat makes the slip ring induction motors
possible to add external resistance to the rotor circuit, thus enabling them to have
a higher resistance during starting and thus higher starting torque. When running
during normal condition, the slip rings are automatically short-circuited by means
of a metal collar, which is pushed along the shaft, thus making the three rings
touching each other. Also, the brushes are automatically lifted from the slip-rings
to avoid frictional losses, wear and tear. Hence, under normal running conditions,
the wound rotor is acting as same as the squirrel cage rotor.
Rotor windings
Slip rings
Carbon brushes
Rheostat
Figure 2.2: Slip ring rotor
28
4) Sketching torque, speed and slip characteristics of the induction motor
Figure 2.3: Slip and Speed versus torque graph
29
5) Sketching torque, speed and slip characteristics of the induction motor
by using MATLAB software.
MATLAB commands is as shown in (Figure 2.4):-
The plotted slip versus torque graph is shown in (Figure 2.5) and the speed
versus torque graph is as shown in (Figure 2.6).
Figure 2.4: MATLAB commands
30
Figure 2.5: Slip vs torque graph by using MATLAB
Figure 2.6: Speed vs torque graph by using MATLAB
31
Conclusion
According to the plotted graphs we observe that the slip having a proportional
relation with the torque as the torque is increasing the slip is increasing as well,
while the relation between the torque and speed is non-proportional as the speed is
increasing the torque is decreasing.
32
References
i. B.L. Theraja, (2008). Textbook of Electrical Technology. Chand (S.) & Co
Ltd ,India.
ii. Edward Hughes, (2001). Electrical & Electronic Technology. 8th
Edition.
Longman Group United Kingdom.
iii. William D Stevenson, (1975). Elements of power system analysis
(McGraw-Hill electrical and electronic engineering series). 3rd
Edition.
McGraw-Hill.