Section
Selection Guide.................................. F-2
Din Rail Snap/Surface-Mount Sockets
• SU Series . . . . . . . . . . . . . . . . . . . F-6• SR Series . . . . . . . . . . . . . . . . . . . F-9• SH Series . . . . . . . . . . . . . . . . . . . F-12• SY Series . . . . . . . . . . . . . . . . . . . F-16• SM Series . . . . . . . . . . . . . . . . . . . F-18
Through Panel Mount Sockets
• SR Series . . . . . . . . . . . . . . . . . . . F-19• SH Series . . . . . . . . . . . . . . . . . . . F-20• SY Series . . . . . . . . . . . . . . . . . . . F-22
PCB Mount Sockets
• SH Series . . . . . . . . . . . . . . . . . . . F-23• SY Series . . . . . . . . . . . . . . . . . . . F-24
Surface Mount Sockets
• SH Series . . . . . . . . . . . . . . . . . . . F-26
Panel Mounted Sockets for Timers
• SR Series . . . . . . . . . . . . . . . . . . . F-26
Accessories ....................................... F-27
Dimensions....................................... F-29
F
Sockets
Selection Guide
Sockets
F-2
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
S
ockets
Relay and Timer Socket
Mounting Series Page Part No. No. ofPoles Receptacle Terminal Compatible
IDEC Relay and Timer
DIN Rail Snap/Surface-MountSU F-6
SU2S-11L 2 8-BladeSpring Clamp Terminals
RU2, RM2
SU4S-11L 4 14-Blade RU4, RU42, RY4, RY42
SR F-9
SR2P-05SR2P-05CSR2P-06
2 8-Pin
M3.5 Screw
RR2P, GT5P,RTE-P1, GT3 (8-pin)
SR3P-05SR3P-05CSR3P-06
3 11-Pin RR3PA, RR2KP, RTE-P2GT3 (11-pin)
SR3B-05 3 11-Blade RR1BA, RR2BA, RR3B, RTE-B
SH F-12
SH1B-05SH1B-05C 1 5-Blade M3.5 Screw
Coil Terminal: M3 RH1B
SH2B-05SH2B-05C 2 8-Blade
M3.5 Screw
RH2B
SH3B-05SH3B-05C 3 11-Blade RH3B, RH2LB
SH4B-05SH4B-05C 4 14-Blade RH4B
SY F-16
SY2S-05SY2S-05C 2 8-Blade
M3 ScrewRY2S, RY22S
SY4S-05SY4S-05C 4 14-Blade RU4S, RU42S, RY4S, RY42S, RY2KS, RY2LS,
RM2S, GT5Y
SM F-18 SM2S-05SM2S-05C RU2S, RM2S
Through Panel MountSR F-19
SR2P-51 2 8-Pin
Solder
RR2P, GT5P, RTE-P1, GT3 (8-pin)
SR3P-51 3 11-Pin RR3PA, RR2KP, RTE-P2, GT3 (11-pin)
SR3B-51 3 11-Blade RR1BA, RR2BA, RR3B
SH F-20
SH1B-51 1 5-Blade RH1B
SH2B-51 2 8-Blade RH2B
SH3B-51 3 11-Blade RH3B, RH2LB
SH4B-51 4 14-Blade RH4B
SY F-22SY2S-51 2 8-Blade RY2S, RY22S
SY4S-51 4 14-Blade RY4S, RY42S, RU4S, RU42S, RY2KS, RY2LS, RM2S, GT5Y
PCB Mount
SH F3-23
SH1B-62 1 5-Blade
PC Board
RH1BSH2B-62 2 8-Blade RH2BSH3B-62 3 11-Blade RH3B, RH2LBSH4B-62 4 14-Blade RH4B
SY F3-24
SY2S-61 2 8-Blade RY2S, RY22S
SY4S-61 4 14-Blade RY4S, RY42S, RU4S, RU42S, RY2KS, RY2LS, RM2S, GT5Y
SY4S-62 4 14-Blade RY4S, RY42S, RU4S, RU42S, RY2KS, RY2LS, RM2S, GT5Y
Surface Mount
SH F-26 SH2B-02 2 8-Blade M3.5 Screw RH2B
For Panel Mounted Timers
SR F-26SR6P-M08G
28-pin
M3.5 ScrewGE1A; RTE-P1; GT3 (8-pin);
SR6P-M11G 11-pin RTE-P2; GT3 (11-pin)
Relay and Timer Socket Selection Guide
For relay mounting accessories, see page F-27.
Sockets
Selection Guide
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-3
F
S
ockets
Relay socket part numbers are composed of 5 part number codes. When ordering a relay socket, select one code from each category.Example: SR2P-05C
Part Numbers: Relay Sockets
2. For hold-down springs and clips for DIN rail snap-mount, panel mount, and PC board mount, see page F-4.3. For socket accessories, see page F-27.
Spec
ifica
tions
Rated Insulation Voltage
300V; except SH1B, SU and SY4S-62: 250V
Rated Current
SU2/SR/SH/SM: 10A, SY: 7A, SU4: 6A with RU4, SU4: 10A with RU2 (SH1B coil terminal 7A)
Insulation Resistance
100M
Ω
minimum
Dielectric Strength
2,000V AC, 1 minute
Material Grade
UL94V-0
Terminal Torque
3.5mm Screws, 9-11.5 in•lbs3mm screws, 5.5-9 in•lbs
Description Part Number Code Remarks
➀
Socket Series
SU SU For use with RU, RY4, RM2 relays
SR SR For use with RR series relays
SH SH For use with RH series relays
SY SY For use with RY, RU4 series relays
SM SM For use with RU2, RM2 series relays
➁
No. of Poles
1-pole 1 SH series
2-pole 2 SR, SH, SM, and SY series
3-pole 3 SR, and SH series
4-pole 4 SH series
➂
Termination
Tubular pin P SR series
Blade (0.187”) B SH series
Solder/blade (0.110”) S SY and SM series
➃
Mounting Styles
DIN rail snap-mount (with spring clamp terminals) 11L Available for SU socket only
DIN rail snap-mount (with screw terminals)
05 To decide between configuration 05 and 06, see pictures and schematics beginning on page F-9
Model 05 is available as 05C with a fingersafe option; see
below06
Panel mount 51
PC board mount61
62
Fingersafe Option
With finger-protection terminals CAvailable only on SR, SH, SM, and SY series snap-mount sockets
Without finger-protection terminals Leave blank
1. * Applicable to DIN rail sockets only.
CSA CertifiedFile No.LR35144
UL RecognizedFile No. E62437
File No. BL950813332307
Relay Socket Part Numbering Guide
➀ Socket Series ➁ No. of Poles
P 05SR 2
➂ Termination
➃ Mounting Style Fingersafe Option
C
Selection Guide
Sockets
F-4
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
S
ockets
DIN Rail Snap/Surface-Mount Sockets
Socket Part No. Applicable Relays, Timer Hold-Down Pullover Spring Hold-Down Clip(side latch)
Hold-Down Clip(top latch)
SU2S-11LSU4S-11L
RM2S, RU2, GT5Y-2 SY4S-51F1 SFA-202 SFA-101
RY4S, RY42S, RU4, RU42, GT5Y, RY2LS, RM2S SY4S-51F1 SFA-202 SFA-101
SR2P-05SR2P-05C
RR2P SR2B-02F1 SFA-203 —
RTE-P1, GT3, GT5P — SFA-203 —
SR2P-06RR2P SR2B-02F1 SFA-202 —
GT3 (8-pin), RTE-P1, GT5P — SFA-202 —
SR3P-05SR3P-05C
RR3PA SR3B-02F1 SFA-203 —
RR2KP SR3P-06F3 SFA-203 —
RTE-P2, GT3 (11-pin) — SFA-203 —
SR3P-06
RR3PA SR3B-02F1 SFA-202 —
RR2KP SR3P-06F3 SFA-202 —
RTE-P2, GT3 (11-pin) — SFA-202 —
SR3B-05 RR1BA, RR2BA, RR3B, RTE-B SR3B-02F1 SFA-202 —
SH1B-05SH1B-05C RH1B SY2S-02F1 SFA-202 SFA-101
SH2B-05SH2B-05C RH2B SY4S-02F1 SFA-202 SFA-101
SH3B-05SH3B-05C RH3B, RH2LB SH3B-05F1 SFA-202 SFA-101
SH4B-05SH4B-05C RH4B SH4B-02F1 SFA-202 SFA-101
SY2S-05SY2S-05C RY2S, RY22S SY2S-02F1 SFA-202 SFA-101
SY4S-05SY4S-05C
RY4S, RY42S, RU4, RU42RY2LS, RM2S SY4S-51F1 SFA-202 SFA-101
RY2KS, GT5Y (SY4S-51F3) SFA-202
SM2S RM2S, RU2 SY4S-51F1 SFA-202 SFA-101
1. Hold-down springs work in conjunction with hold-down spring anchors included with DIN rail sockets.2. When mounting relays with a check button onto panel mount or PC board mount sockets, use the hold-down
spring shown in parenthesis. Hold-down springs for relays with check buttons are not available for SR2P-51.3. For close mounting of panel mount or PC mount sockets, use hold-down clips rather than hold-down springs.4. SFA-101, SFA-202 and SFA-302 come in pairs.
SR2B-02F1 SR3B-02F1 SY4S-02F1 SH3B-05F1 SH4B-02F1
SY4S-51F1 SY4S-51F3 SR3P-01F1 SR3P-06F3 SY2S-02F1
Hold-Down Springs and Clips Selection Guide
Sockets
Selection Guide
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-5
F
S
ockets
SFA-101
SFA-202SFA-302
SFA-402SFA-203SFA-301
Panel and PC Board Mount Sockets
* Does not accept hold down clips
Socket Part No. Applicable Relays, Timer Hold-Down Pullover Spring Hold-Down Clip(side latch)
Hold-Down Clip (top latch)
SR2P-51RR2P SR3P-01F1 — —
GT3 (8-pin), RTE-P1 — SFA-402 —
SR3P-51
RR3PA SR3P-01F1—
—
RR2KP SR3P-51F3 —
GT3 (11-pin), RTE-P2 — SFA-402 —
SR3B-51 RR1BA, RR2BA, RR3B, RTE-B SR3B-02F1 — —
SH1B-51SH1B-62 RH1B SY4S-51F1 — SFA-301
SFA-302
SH2B-51 RH2B SY4S-51F1(SY4S-02F1) — SFA-301
SFA-302
SH2B-62 RH2B SY4S-51F1(SY4S-02F1) — —
SH3B-51SH3B-62 RH3B, RH2LB SY4S-51F1
(SY4S-02F1) — SFA-301SFA-302
SH4B-51SH4B-62 RH4B SY4S-51F1
(SH4B-02F1) — SFA-301SFA-302
SY2S-51SY2S-61 RY2S, RY22S SY4S-51F1 — SFA-301
SFA-302
SY4S-51SY4S-61
RY4S, RY42S, RY2LS SY4S-51F1(SY4S-02F1) — SFA-301
SFA-302
RY2KS SY4S-51F1(SY4S-02F3) SFA-302 —
GT5Y — SFA-302 —
SY4S-62 *RY4S, RY42S, RY2LS, RM2S SY4S-51F1
(SY4S-02F1) — —
RY2KS SY4S-51F1(SY4S-02F3) — —
SU Series: DIN Rail Snap-Mount
Sockets
F-6
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
S
ockets
Center of Relay-mounting area
Inside the Cable Ports
SU Series: DIN Rail Snap-Mount Sockets
28.8
80
31
4.4
32
37.5
35.3
24
Spring slots for SFA-202:
Spring slots for SFA-101:
Marking Plate
Clamp➀ ➁ ➂➂
➃ ➄ ➅
➀➁➄➅
➁➂➃➄
Screwdriver Ports
CTerminal
NOTerminal
NCTerminal
CoilTerminal
Wire Ports
Wire Ports
WirePorts
WirePorts
SU2S-11L SU4S-11L
Terminal Arrangement (top view) Dimensions
Style 8-blade DIN-mount/surface mount Style 14-blade DIN-mount/surface mount
Terminal Spring clamp terminals Terminal Spring clamp terminals
Wire Size 24-16 AWG Wire Size 24-16 AWG
Electrical Rating 10A Electrical Rating 6A (using RU4), 10A (using RU2)
Compatible Relay RU2, RM2 Compatible Relay RY4S, RY42S, RU4, RU42S, RY2LS, RM2S
Compatible Timer GT5Y-2 Compatible Timer GT5Y
Hold-Down Clip SFA-101 (top latch), SFA-202 (side latch) Hold-Down Clip SFA-101 (top latch), SFA-202 (side latch)
Inside the Cable Ports1. On the SU2S, wires or ferrules cannot be connected to terminals 2, 3, 6, 7, 10 or 11 because neither springs nor conductive brackets are installed in these terminals.
2. For socket mounting accessories, see page F-27.
SU2S-11L
14 13
1234
8 7 6 5
9101112 12 11 10 9
5678
4 3 2 1
1314
SU4S-11L
Panel Cutout for Surface Mounting
Parts
All measurements are in mm.
Sockets
SU Series: DIN Rail Snap-Mount
www.idec.com
USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-7
F
S
ockets
SU Series: General Instructions
Applicable Wires
Applicable Ferrules
Marking Instructions
Write markings on the SU sockets using an oil-based marker, or glue printed mylar on the marking surface. The size of the printed mylar can be 8 x 9mm maximum.
Wiring Instructions
1. Insert the optional screwdriver (BC1S-SDO) or an applicable screwdriver into the square-shaped port as shown on the right, until the screwdriver tip touches the bottom of the spring.
2. Push in the screwdriver until it touches the bottom of the port. The wire port is now open, and the screwdriver is held in place. The screwdriver will not come off even if you release your hand.
3. While the screwdriver is retained in the port, insert the wire or ferrule into the round-shaped wire port. Each wire port can accommodate one wire or ferrule. When connecting two wires to one terminal, use the adjoining port of the same terminal.
4. Pull out the screwdriver. The connection is now complete.
Safety Precautions
Installing the Marking Plate
Because of its removable structure, the marking plate may have fallen from the socket or become loose in delivery. Make sure that the marking plate is securely installed before starting operation. The marking plate protects the conductive portion of the socket, located under the marking plate, by prevent-ing metal fragments or pieces of wire from dropping inside. Should any such fragments enter the socket, they may cause fire hazard, damage, or malfunc-tion.
Inserting Screwdriver into the Wire Ports
Wire Size
Stranded wire 0.2 to 1.25 mm2 or AWG24 to 16
Solid wire 0.2 to 1.5 mm2 or AWG24 to 16
Wire insulation diameter ø3.15mm maximum
Applicable Wire (stranded)Type Manufacturer
mm2 AWG
0.2 24 A10.25-12BU Phoenix Contact
_ 22 A10.34-8TQ Phoenix Contact
0.5 20
A10.5-8WHPhoenix Contact
A10.5-10WH
TE0.5 Nichifu Co. Ltd
1. Strip the wire insulation 9 to 10mm from the end.2. In applications using ferrules for stranded wires, choose
the ferrule listed in table below. Make sure that an insula-tion sheath is applied when using the ferrules. When using stranded wires without ferrules, make sure that the core wires have not been loosened.
3. Two cable ports are provided for each terminal.
9 to 10mm
7to
13
7t
º
ø2.
50.4
2.5
(Dimensions in mm)
For wiring, use the optional screwdriver (BC1S-SDO) or the following applicable screwdriver.
8.0
9.0
8.0
Marking Plate
Position of printedmylar on the markingsurface
Maximum size ofprinted mylar
Marking Surface
Direction of Screwdriver Tip
Wire Ports for Terminal 9Wire Ports for Terminal 10
Stopper
Wire Port
Note: Two cable ports are provided for each terminal.
A
B
A - B secScrewdriver Ports
CorrectIncorrect
IncorrectIncorrect
(on both sides)
Marking Plate
Note: For installation of optional jumper, see the instruction sheet provided
p j p see the instruction sheet provided
p j p
with the jumper. with the jumper.
plate ribs
r JumperInstalled securelyLoose fittingNo marking plate
Jumper Ports
SU Series: DIN Rail Snap-Mount
Sockets
F-8 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SU Series: SU9Z-J5 Jumper Installation Instructions
SU9Z-J5 Jumper for SU2S-11L and SU4S-11L
The SU9Z-J5 is used to install five sockets. When installing less than five sockets cut the jumper according to the instructions listed to the right.
The SU9Z-J5 jumper is for coil terminals only.
Installation
Loosen the marking plate on the socket.
Alignment
Making sure that the SU9Z-J5 jumper is correctly aligned, insert the blades into the ports in the groove of the SU sockets.
Install Jumper Securely
Press down the marking plate to secure the jumper. The jumper installation is now complete.
Installing Two, Three or Four SU Sockets on the SU9Z-J5 Jumper
As shown below, slide the jumper in the sheath so that the jumper aligns with the center of the sheath.
With the sheath properly installed on the jumper, cut the sheath and jumper at the points shown below, using cutting pliers. Referring to the drawing on the right, make sure that the sheath and jumper are cut within the cutting area. Dispose of unused portions according to local waste disposal requirements.
After cutting the jumper and sheath, slide the jumper as shown below, so that the ends of the jumper ar e not exposed.
Jumper Wiring to Six or More SU Sockets
To jumper wire six or more SU sockets, connect five sockets using whole jumpers and the remaining sockets using a cut jumper. Then connect the two terminals on adjoining sockets using an applicable wire (see table below).
Safety Precautions
Turn off the power to the SU9Z-J5 jumper before starting installation, removal, wiring, maintenance, or inspection of the jumper. Failure to turn power off may cause an electrical shock or fire hazard.
To avoid a short circuit due to incorrect wiring, confirm which terminals are connected to the jumper before beginning wiring.
SU9Z-95 Jumper
Rated Current 3A
MaterialConductor Nickel-plated brass
Sheath ABS resin
B: Installed securelyA: Loose fitting
Ribs
(on both sides)Grooves for marking plate ribs
CorrectIncorrect
Insertion Direction
Jumper Groove Jumper
Blade
Jumper portfor terminal 13
Jumper portfor terminal 14
Qty Cutting Area Discard
2 Sockets 2 A, C Y
2 Sockets1 A, B X
3 Sockets
4 Sockets 1 D Z
Wire Size
Stranded wire 0.2 to 1.25 mm2
Solid wire 0.2 to 1.5 mm2
AWG 24 to 16
Jumper on centerJumper off center
Cutting Area C
Cutting Area in Detail
Cutting Area D
SheaJump
SheaZ
X
Y
DCBA
Proper wire
1. Use a wire with cable insulation diameter of ø3.15mm maximum.
2. Strip the cable insulation 9 to 10mm from the end.
Sockets SR Series: DIN Rail Snap-Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-9
F
So
ckets
SR Series: DIN Rail Snap-Mount Sockets
SR2P Sockets
2-ø4.2 Mounting Hole(M4 screw hole)
7.9max.
ø3.6min.
M3.5
ø4.2
TerminalArrangement
(TOP VIEW)
6
5 4
3
7
8
2
1
16.5
20
28.5
33 523
ø25
29
4.4max. 5min.
8
523
36
29Mounting Hole
Screw
32 when using BAA
DIN Rail (BAA)SR2P-05
Style 8-pin octal, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RR2P
Compatible Timer RTE-P1, GT3 (8-pin), GT5P, GE1A
Hold-Down Spring SR2B-02F1 (for RR2P)
Hold-Down Clip SFA-203 (for timers only, except GE1A)
8
7
6
5 4
3
2
1
5
21.5
4.2
2.2
58
30
29
736
(TOP VIEW)
6
5 4
3
7
8
2
1
29
TerminalArrangement
DIN Rail (BAA)
2-ø4.2 Mounting Hole(M4 screw hole)
33.5 when using BAA
(cannot use ring terminal)
SR2P-05C Fingersafe
Style 8-pin octal, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp, fingersafe (9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RR2P
Compatible Timer RTE-P1, GT3 (8-pin), GT5P, GE1A
Hold-Down Spring SR2B-02F1 (for RR2P)
Hold-Down Clip SFA-203 (for timers only, except GE1A)
ø3.6min.
7.9max.
ø4.2(TOP VIEW)
6 5 4 3
2187
840
160
33 18
22
33
4.9max. 5min.
ø25
M3.5 Screw
Mounting Hole
25.5 when using BAA DIN Rail (BAA)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
SR2P-06
Style 8-pin octal, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RR2P
Compatible Timer RTE-P1, GT3 (8-pin), GT5P, GE1A
Hold-Down Spring SR2B-02F1 (for RR2P)
Hold-Down Clip SFA-202 (for timers only, except GE1A)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
SR Series: DIN Rail Snap-Mount Sockets
F-10 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SR3P Sockets
ø3.6min.
7.9max.
ø4.2 (TOP VIEW)
8
7 6 5
4
9
1110 1 2
334
4.4max. 5min.
16.5
20
28.5
ø2733
8
42
34
523
M3.5 Screw
32 when using BAA
DIN Rail (BAA) TerminalArrangement
2-ø4.2 Mounting Hole(M4 screw hole)
Mounting Hole
SR3P-05
Style 11-pin octal, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RR3PA, RR2KP
Compatible Timer GT3 (11-pin), RTE-P2
Hold-Down Spring SR3B-02F1 for RR3P; SR3P-06F3 for RR2KP
Hold-Down Clip SFA-203 (Timers)
4
3
211
01
1
8
7 6 5
9
ø5
30
34 21.5
427
ø4.2
2.2
58
(TOP VIEW)
8
7 6 5
4
9
1110 1 2
334
33.5 when using BAA
DIN Rail (BAA)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
(cannot use ring terminal)
SR3P-05C Fingersafe
Style 11-pin octal, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp, fingersafe (9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RR3PA, *RR2KP (*latching relay)
Compatible Timer GT3 (11-pin), RTE-P2
Hold-Down Spring SR3B-02F1 for RR3PA; SR3P-06F3 for RR2KP
Hold-Down Clip SFA-203 (Timers)
2-ø4.2 Mounting Hole(M4 screw hole)
M3.5TerminalArrangement
Mounting Hole
Screw
25.5 when using BAA
DIN Rail (BAA)
ø3.6min.
7.9max.
ø4.2
(TOP VIEW)
8 7 6 5 4
9 1110 1 2 3
33
4.9max. 5min.
8
59
33
601 22
18
ø27
SR3P-06
Style 11-pin octal, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RR3PA, *RR2KP (*latching relay)
Compatible Timer GT3 (11-pin), RTE-P2
Hold-Down Spring SR3B-02F1 for RR3PA; SR3P-06F3 for RR2KP
Hold-Down Clip SFA-202 (Timers)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SR Series: DIN Rail Snap-Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-11
F
So
ckets
SR3B Sockets
SR3B-05
Style 11-blade, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 15A (10A)* (*denotes CSA rating)
Compatible Relay RR1BA, RR2BA, RR3B
Compatible Timer RTE-B
Hold-Down Spring SR3B-02F1 (relays)
Hold-Down Clip SFA-202 (relays and timers)
Ø 0.137"(M3.5)
(14.5mm)0.566"
(8mm)0.315"
Ø 0.164" (4.2mm)
0.078"(2mm)
6 5 4
3 2 1
B A
9 8 7
(28.5mm)1.122"
(56mm)2.184"
(25mm)0.975"
1.404"(36mm)
(37mm)1.456"
(43mm)1.677"
(76mm)2.964"
0.172"(4.4mm) 0.195"(5mm)
Ø 0.140"(3.6mm)
(7.9mm)0.311"
1.456"(37mm)
Ø 0.164"(4.2mm)2 Holes
DINRail
TerminalArrangements
(top view)
Panel Cutout for Surface Mounting
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
SH Series: DIN Rail Snap-Mount Sockets
F-12 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SH Series: DIN Rail Snap-Mount Sockets
SH1B Sockets
M3 BindingScrew
M3.5 Screw
17
4.2
672.
5 20
16
8
5.9max.
ø3.2min.(TOP VIEW)
ø3.6min.
7.9max.
5
1
9
good for terminals 14 13 5 1 9
14 13
16
25
4max.
4.8min.
47
18
14.5
4.4max.
5.5min.
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
28.5 when using BAA
DIN Rail (BAA)
good for terminals
SH1B-05
Style 5-blade, snap-mount/surface mount
Terminal/Torque(Coil) M3 screws/(5.5 - 9 in•lbs) (contact) M3.5 screws (9 - 11.5 in•lbs)with captive wire clamp
Wire Size Maximum up to 2–#12AWG
Electrical Rating 250V, 10A
Compatible Relay RH1B
Hold-Down Spring SY2S-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
5
1414
12
1
1A
31
2A
41
9
11M3 Binding Screw
M3.5 Screw
ø5
16
25
1.7
29.518.7
48
177
69
20
4.2
(TOP VIEW)
5
1
9
14 13
16
(cannot use ring terminal)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
33 when using BAA
DIN
Rai
l (B
AA
)
SH1B-05C Fingersafe
Style 5-blade, snap-mount/surface mount
Terminal/Torque(Coil) M3 screws/(5.5 - 9 in•lbs) (contact) M3.5 screws with captive wire clamp, fingersafe (9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 250V, 10A
Compatible Relay RH1B
Hold-Down Spring SY2S-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SH Series: DIN Rail Snap-Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-13
F
So
ckets
SH2B Sockets
M3.5 Screw
22
4.2
672.
5
8
(TOP VIEW)ø3.6min.
7.9max.
8
4
5
1
12
14
9
13
26
25
47
18
14.5
4.4max. 5.5min.
26
30
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
28.5 when using BAA
DIN Rail (BAA)
SH2B-05
Style 8-blade, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RH2B
Hold-Down Spring SY4S-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
912
14 13
1141
A2 A1
1242
44 14
4 1
8 5
M3.5
ø525
29.518.71
.76
9
49
4.2
227
3026
(TOP VIEW)
8
4
5
1
12
14
9
13
26
(cannot use ring terminal)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
33 when using BAA
DIN
Rai
l (B
AA
)
SH2B-05C Fingersafe
Style 8-blade, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp, finger-safe (9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RH2B
Hold-Down Spring SY4S-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
SH Series: DIN Rail Snap-Mount Sockets
F-14 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SH3B Sockets
(TOP VIEW)
M3.5 Screw
ø3.6min.7.9max.
5
1
12
14
10
13
8
4
6
2
9
36
25
32
4.2
672.
5
47
18
14.5
8
4.4max. 5.5min.
36
40
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
28.5 when using BAA
DIN Rail (BAA)
SH3B-05
Style 11-blade, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RH3B, RH2LB
Hold-Down Spring SH3B-05F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
14
5
1
12
12
41
910
14 13
1121
A2 A1
2242
44 24
4 2
8 6
M3.5 Screw 25
1.7
29.518.7
32
49
4.2
7
4036
ø5
(TOP VIEW)
5
1
12
14
10
13
8
4
6
2
9
36
(cannot use ring terminal)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
33 when using BAA
DIN
Rai
l (B
AA
)
SH3B-05C Fingersafe
Style 11-blade, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp, fingersafe (9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RH3B, RH2LB
Hold-Down Spring SH3B-05F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SH Series: DIN Rail Snap-Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-15
F
So
ckets
SH4B Sockets
(TOP VIEW)
M3.5 Screw
ø3.6min.
7.9max.
5
1
9
13
10
14
8
4
7
3
6
2
12 11
46
25
42
4.2
672.
5
47
18
14.5
8
4.4max. 5.5min.
46
50
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
28.5 when using BAA
DIN Rail (BAA)
SH4B-05
Style 14-blade, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp(9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RH4B
Hold-Down Spring SH4B-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
4 3 2 1
8 67 5
32
31
22
41
A2 A1
12
142434
12 11 10 9
14
44
21 11
42
13
ø5
25
4.2
1.7
69
46
42
7
18.729.5
50
49
(TOP VIEW)
5
1
9
13
10
14
8
4
7
3
6
2
12 11
46
(cannot use ring terminal)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
33 when using BAA
DIN Rail (BAA)
SH4B-05C Fingersafe
Style 14-blade, snap-mount/surface mount
Terminal/Torque M3.5 screws with captive wire clamp, fingersafe (9 - 11.5 in•lbs)
Wire Size Maximum up to 2–#12AWG
Electrical Rating 300V, 10A
Compatible Relay RH4B
Hold-Down Spring SH4B-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
SY Series: DIN Rail Snap-Mount Sockets
F-16 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SY Series: DIN Rail Snap-Mount Sockets
SY2S Sockets
M3 Screw
5.9max.
ø3.2min.(TOP VIEW)
8
4
5
1
12
14
9
13
16
25
4max. 4.8min.
6
17
4.2
622
45
18
20
16 14.5
28.5 when using BAA
DIN Rail (BAA)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
SY2S-05
Style 8-blade, snap-mount/surface mount
Terminal/Torque M3 screws with captive wire clamp(5.5 - 9 in•lbs)
Wire Size Maximum up to 2–#14AWG
Electrical Rating 300V, 7A
Compatible Relay RY2S, RY22S
Hold-Down Spring SY2S-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
12
1
5
14
8
14
A2
44
9
11
12
41
13
42
A1
4
M3 Screw
ø5
25
46
2918.2
4.2
1.6
64
617.2
1620
2
(TOP VIEW)
8
4
5
1
12
14
9
13
16
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
32.5 when using BAA
DIN
Rai
l (B
AA
)
(cannot use ring terminal)
SY2S-05C Fingersafe
Style 8-blade, snap-mount/surface mount
Terminal/Torque M3 screws with captive wire clamp, fingersafe (5.5 - 9 in•lbs)
Wire Size Maximum up to 2–#14AWG
Electrical Rating 300V, 7A
Compatible Relay RY2S, RY22S
Hold-Down Spring SY2S-02F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SY Series: DIN Rail Snap-Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-17
F
So
ckets
SY4S Sockets
M3 Screw
5.9max.
ø3.2min.(TOP VIEW)
1
13
9
14
12 11 10
5678
4 3 2
26
18.5
25
4max. 4.8min.
6
30
26
4.2
623
0.7
45
18
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
28.5 whenusing BAA
DIN Rail (BAA)
SY4S-05
Style 14-blade, snap-mount/surface mount
Terminal/Torque M3 screw with captive wire clamp(5.5 - 9 in•lbs)
Wire Size Maximum up to 2–#14AWG
Electrical Rating 300V, 7A
Compatible Relay RY4S, RY42S, RU4S, RU42S, RM2S, *RY2KS, *RY2LS (*latching relay)
Compatible Timer GT5Y
Hold-Down Spring SY4S-51F1 for all relays; SY4S-51F3 for RY2KS only
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch) for all relays and timers
9
11
12
13
A1
10
21
5
12
1
14
42
4
8
44
A2
23
14
31
6
11
24
32
34
41
22
7
M3 Screw
ø5.5 18
25
2.0
306
64
26
46
1.6
4.2
2918.2
(TOP VIEW)
1
13
9
14
12 11 10
5678
4 3 2
26
(cannot use ring terminal)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
32.5 when using BAA
DIN
Rai
l (B
AA
)
SY4S-05C Fingersafe
Style 14-blade, snap-mount/surface mount
Terminal/Torque M3 screw with captive wire clamp, fingersafe (5.5 - 9 in•lbs)
Wire Size Maximum up to 2–#14AWG
Electrical Rating 300V, 7A
Compatible Relay RY4S, RY42S, RM2S, RU4S, RU42S, *RY2KS, *RY2LS (*latching relay)
Compatible Timer GT5Y
Hold-Down Spring SY4S-51F1 for all relays; SY4S-51F3 for RY2KS only
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch) for GT5Y timer and relays
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
SM Series: DIN Rail Snap-Mount Sockets
F-18 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SM2S Sockets
M3 Screw
5.9max.
ø3.2min.
14
13
9
14
12
58
26
18.5
25
4max. 4.8min.
45
186
30
26
4.2
623
0.7
(TOP VIEW)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
28.5 when using BAA
DIN Rail (BAA)
SM2S-05
Style 8-blade, snap-mount/surface mount
Terminal/Torque M3 screw with captive wire clamp(5.5 - 9 in•lbs)
Wire Size Maximum up to 2–#14AWG
Electrical Rating 300V, 10A
Compatible Relay RU2S, RM2S
Compatible Timer —
Hold-Down Spring SY4S-51F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
9
11
12
13
A1
10
21
5
12
1
14
42
4
8
44
A2
23
14
31
6
11
24
32
34
41
22
7
M3 Screw
ø5.5
25
18
2
306
64
26
46
1.6
4.2
2918.2
26
14
13
9
14
12
58
(TOP VIEW)
(cannot use ring terminal)
2-ø4.2 Mounting Hole(M4 screw hole)
TerminalArrangement
32.5 when using BAA
DIN
Rai
l (B
AA
)
SM2S-05C Fingersafe
Style 8-blade, snap-mount/surface mount
Terminal/Torque M3 screw with captive wire clamp, fingersafe (5.5 - 9 in•lbs)
Wire Size Maximum up to 2–#14AWG
Electrical Rating 300V, 10A
Compatible Relay RU2S, RM2S
Compatible Timer —
Hold-Down Spring SY4S-51F1
Hold-Down Clip SFA-101 (top notch), SFA-202 (side notch)
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SR Series: Panel Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-19
F
So
ckets
SR Series: Panel Mount Sockets
SR3B-51
Style 11-blade, panel mount
Terminal Solder
Electrical Rating 300V, 10A
Compatible Relay RR1BA, RR2BA, RR3B
Compatible Timer RTE-B
Hold-Down Spring SR3B-02F1 (for relays only)
1.496"(38mm)
2.02
7" (5
2mm
)
1.38
"(3
5.3m
m)
0.866" (22.2mm)
1.69
" (43
.4m
m)
0.138" (3.54mm)
1.38" (35.3mm)
0.118"(3mm) 0.256"
(6.56mm)
1.26
" (32
.3m
m)
0.295"(7.56mm)
0.433"(11.1mm)
1 2 34 5 67 8 9A B
TerminalArrangement
As Viewedfrom the Bottom
1.73
2" (4
4.4m
m)
0.266"(6.82mm)
0.866"(22.2mm)
*1.40" (35.9mm)
1.28
" (32
.8m
m)
1.69
4" (4
3.4m
m)
2-Ø0.165"Mounting Hole
(4.23mm)
Tolerance ±0.01(±0.31mm)
*More than 2 Sockets are MountedSide by Side L=1.496"(n-1)+1.40"(38.4mm (n-1)+35.9mm)n=Number of Sockets Mounted
Panel Cutout for Surface Mounting
SR2P-51
Style 8-pin octal, panel mount
Terminal Solder
Electrical Rating 300V, 10A
Compatible Relay RR2P
Compatible Timer RTE-P1, GT3 (8-pin), GT5P
Hold-Down Spring SR3P-01F1 (for relay only)
Hold-Down Clip SFA-402 (for GT3 8-pin)SFA-302 (for GT5P)
0.234"(6mm)
0.164"
1.13"(29mm)
PanelSurface
HD SpringSFA-402
0.429"(11mm)
0.39"(10mm)
0.1"(2.5mm)
0.1"(2.5mm)
(4.2mm)
1.48"(38mm)
1.95"(50mm)
1.33"(34mm)
Ø 1.17"Ø 0.137" Drilled
or Ø 0.118" Tapped(30mm)
1.48"
6
Terminal
Bottom View
123 4 5
78
Arrangement
(3.5mm)
(M3), 2 Holes
(38mm)Panel Cutout for Surface Mounting
SR3P-51
Style 11-pin octal, panel mount
Terminal Solder
Electrical Rating 300V, 10A
Compatible Relay RR3PA, *RR2KP (*latching relay)
Compatible Timer GT3 (11-pin), RTE-P2
Hold-Down Spring SR3P-01F1 for RR3PA SR3P-51F3 for RR2KP
Hold-Down Clip SFA-402 (for GT3 11-pin, RTE-P2)
Ø 1.17"Ø 0.137" Drilled
or Ø 0.118" Tapped(30mm)
1.48"
PanelSurface
HD SpringSFA-402
0.429"(11mm)
0.39"(10mm)
0.1"(2.5mm)
6
Terminal
Bottom View
0.234"(6mm)
0.164"
12345 78
91011
1.13"(29mm)
Arrangement
(3.5mm)
(M3), 2 Holes
(4.2mm)
1.48"(38mm)
1.95"(50mm)
1.33"(34mm) 0.1"
(2.5mm)
(38mm)Panel Cutout for Surface Mounting
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SH Series: Panel Mount
F-20 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SH Series: Panel Mount Sockets
SH1B-51
Style 5-blade, panel mount
Terminal Solder
Electrical Rating 300V, 10A
Compatible Relay RH1B
Hold-Down Spring SY4S-51F1
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1.22
" (31
mm
)
0.707" (18mm)
0.138"(3.54mm)
0.102"(2.62mm)
0.48" (12.3mm)
Panel Thickness0.04" to 0.079"
(1 to 2mm)
1.0"
(25.
6mm
)
0.118"(3mm)
0.433"(11.1mm)
0.728" (18.7mm)
0.736" (18.7mm)
159
13 14
TerminalArrangement
As Viewedfrom the Bottom 0.707"(n-1)+0.488"+0.02"
(18.3(n-1)+12.5mm+0.51) - 0- 0
1.00
8"+0
.008
"- 0
(25.
9mm
+0.2
1mm
)- 0
n=No. ofSockets
*0.2
12" M
in.
(5.4
mm
)
*0.41" Minimum (10.5mm) when Hold-Down Spring is Used
Panel Cutout for Surface Mounting
SH2B-51
Style 8-blade, panel mount
Terminal Solder
Electrical Rating 300V, 10A
Compatible Relay RH2B
Hold-Down Spring SY4S-51F1SY4S-02F1 for RH2B-4C
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1.22
" (31
.3m
m)
1.063" (27.3mm)
0.138"(3.54mm)
0.835" (21.4mm)
Panel Thickness0.04" to 0.079"
(1 to 2mm)
1.0"
(25.
4mm
)
0.118"(3mm)
0.433"(11.1mm)
0.707" (18.7mm)
1 45 89 12
13 14
As Viewedfrom the Bottom
TerminalArrangement
1.063"(n-1)+0.842"+0.02"(27.3(n-1)+21.6mm+0.51) - 0
- 0
1.00
8"+0
.008
"- 0
(25.
9mm
+0.2
1mm
)- 0
n=No. ofSockets
*0.2
12" M
in.
(5.4
mm
)
*0.41" Minimum (10.5mm) when Hold-Down Spring is Used
Panel Cutout for Surface Mounting
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SH Series: Panel Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-21
F
So
ckets
SH3B-51
Style 11-blade, panel mount
Terminal Solder
Electrical Rating 300V, 10A
Compatible Relay RH3B, *RH2LB (*latching relay)
Hold-Down Spring SY4S-51F1SY4S-02F1 for RH3B-4C
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1.22
" (31
mm
)
1.417" (36mm)
0.138"(3.54mm)
1.189" (30.2mm)
Panel Thickness0.04" to 0.079"
(1 to 2mm)
1.0"
(25.
6mm
)
0.118"(3mm)
0.433"(11.1mm)
0.736" (18.7mm)
1 45 89 12
13 14
As Viewedfrom the Bottom
TerminalArrangement
26
10
1.417"(n-1)+1.181"+0.02"(36.3(n-1)+30.3mm+0.51) - 0
- 0
1.00
8"+0
.008
"- 0
(25.
9mm
+0.2
1mm
)- 0
n=No. ofSockets
*0.2
12" M
in.
(5.4
mm
)
*0.41" Minimum (10.5mm) when Hold-Down Spring is Used
Panel Cutout for Surface Mounting
SH Series: Panel Mount Sockets, continued
SH4B-51
Style 14-blade, panel mount
Terminal Solder
Electrical Rating 300V, 10A
Compatible Relay RH4B
Hold-Down Spring SY4S-51F1, SY4S-02F1
Hold-Down Clip SFA-301, SFA-302
1.771"(n-1)+1.551"+0.02"(45.4(n-1)+39.8mm+0.51) - 0
- 0
1.00
8"+0
.008
"- 0
(25.
9mm
+0.2
1mm
)- 0
n=No. ofSockets
*0.2
12" M
in.
(5.4
mm
)
*0.41" Minimum (10.5mm) when Hold-Spring is Used
1.22
" (31
mm
)
1.771" (45mm)
0.138"(3.54mm)
1.535" (39.2mm)
1.0"
(25.
6mm
)
0.118"(3mm)
0.433"(11.1mm)
0.736" (18.7mm)
1 45 89 12
13 14
As Viewedfrom the Bottom
TerminalArrangement
26
10
37
11
Panel Cutout for Surface Mounting
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
SY Series: Panel Mount Sockets
F-22 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SY Series: Panel Mount Sockets
SY2S-51
Style 8-blade, panel mount
Terminal Solder
Electrical Rating 300V, 7A
Compatible Relay RY2S, RY22S
Hold-Down Spring SY4S-51F1
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
0.707"(n-1)+0.488"+0.02"(18.3(n-1)+12.5mm+0.51) - 0
- 0
1.00
8"+0
.008
"- 0
(25.
9mm
+0.2
1mm
)- 0
n=No. ofSockets
*0.2
12" M
in.
(5.4
mm
)
*0.41" Minimum (10.5mm) when Hold-Down Spring is Used
1.22
" (31
mm
)
0.709" (18mm)
0.138"(3.54mm)
0.102"(2.62mm)
0.48" (12.3mm)
Panel Thickness0.04" to 0.079"
(1 to 2mm)
1.0"
(25.
6mm
)
0.118"(3mm)
0.433"(11.1mm)
0.736" (18.8mm)
13 14
TerminalArrangement
As Viewedfrom the Bottom
5 89 12
1 4
Panel Cutout for Surface Mounting
SY4S-51
Style 14-blade, panel mount
Terminal Solder
Electrical Rating 300V, 7A
Compatible RelayRY4S, RY42S, RM2S, RY2KS, RY2LS, RU4S, RU2S, RU42S
Compatible Timer GT5Y
Hold-Down SpringSY4S-51F1 for all relays except;SY4S-02F3 for RY2KS relay
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1.063"(n-1)+0.842"+0.02"(27.3(n-1)+21.6mm+0.51) - 0
- 0
1.00
8"+0
.008
"- 0
(25.
9mm
+0.2
1mm
)- 0
n=No. ofSockets
*0.2
12" M
in.
(5.4
mm
)
*0.41" Minimum (10.5mm) when Hold-Down Spring is Used
1.22
" (31
mm
)
1.063" (27mm)
0.102"(2.62mm)
0.835" (21.2mm)
As Viewedfrom the Bottom
TerminalArrangement
0.189"(4.85mm)
13 14
5 89 12
1 46
10
27
11
3
Panel Thickness0.04" to 0.079"
(1 to 2mm)
1.0"
(25.
4mm
)
0.118"(3mm)
0.433"(11.1mm)
0.63" (16.2mm)
0.736" (18.8mm)
Panel Cutout for Surface Mounting
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SH Series: PCB Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-23
F
So
ckets
SH Series: PC Board Mount Sockets
SH1B-62
Style 5-blade
Terminal Solder/PCB mount
Electrical Rating 250V, 10A
Compatible Relay RH1B
Hold-Down Spring SY4S-51F1
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1.22
" (31
mm
)
0.707" (18.1mm)
0.079"(2mm)
0.059"(1.5mm)
0.48" (12.3mm)
159
13 14
TerminalArrangement
As Viewedfrom the Bottom
1.0"
(25.
mm
)
0.118"(3mm)
0.433"(11.1mm)
0.59" (15.1mm)
0.707" Minimum(18.1mm)
0.173" (4.4mm)3-Ø0.094"(2.4mm)
0.185"(4.7mm)
0.228"(5.8mm)
0.461"(11.8mm)
*1.2
2" m
in.
(31.
3mm
)
2-Ø0.079"(2mm)
(tolerance ±0.004")(±0.1mm)
*1.417" (36.3mm) Minimum whenHold-Down Spring is Used
PCB Layout
SH2B-62
Style 8-blade
Terminal Solder/PCB mount
Electrical Rating 300V, 10A
Compatible Relay RH2B
Hold-Down Spring SY4S-51F1, SY4S-02F1
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1 45 89 12
13 14
As Viewedfrom the Bottom
TerminalArrangement
1.14
2" (2
9mm
)
0.835" (21.2mm)
1.0"
(254
mm
)
0.118"(3mm)
0.433"(11.1mm)
0.59" (15.1mm)
0.079"(2mm)
0.846" Minimum(21.5mm)
0.185"(4.7mm)
0.254"(6.6mm)
0.486"(12.5mm)
*1.1
42" m
in.
(29.
3mm
)
8-Ø0.094"(2.4mm)
(tolerance ±0.004")(±0.1mm)
*1.338" (34mm) Minimum whenHold-Down Spring is Used
0.634" min.(15.5mm)
0.394"(10mm)
0.317" (8.1mm)PCB Layout
SH3B-62
Style 11-blade
Terminal Solder/PCB mount
Electrical Rating 300V, 10A
Compatible Relay RH3B, *RH2LB (*latching relay)
Hold-Down Spring SY4S-51F1, SY4S-02F1
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1.417" Minimum(36.3mm)
0.185"(4.7mm)
0.25
4"(6
.6m
m)
0.486"(12.5mm)
*1.2
2" m
in.
(31.
3mm
)
11-Ø0.094"(2.4mm)
(tolerance ±0.004")(±0.1mm)
*1.417" (36.3mm) Minimum whenHold-Down Spring is Used
0.85" min.(21.8mm)
0.394"(10mm)
0.317" (8.1mm)
0.315"(8.1mm)
1 45 89 12
13 14
As Viewedfrom the Bottom
TerminalArrangement
26
10
1.22
" (31
mm
)
1.447" (36mm)
0.079"(2mm)
1.189" (30.2mm)
1.0"
(25.
4mm
)
0.118"(3mm)
0.433"(11.1mm)
0.59" (15.1mm)
PCB Layout
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
SH/SY Series: PCB Mount Sockets
F-24 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SH Series: PC Board Mount Sockets, continued
SH4B-62
Style 14-blade
Terminal Solder/ PCB mount
Electrical Rating 300V, 10A
Compatible Relay RH4B
Hold-Down Springs SY4S-51F1, SH4B-02F1
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1 45 89 12
13 14
As Viewedfrom the Bottom
TerminalArrangement
26
10
37
11
1.22
" (31
mm
)
1.771" (45mm)
0.079"(2mm)
1.535" (39.2mm)
1.0"
(25.
4mm
)
0.118"(3mm)
0.433"(11.1mm)
0.59" (15.1mm)
1.77" Minimum(45mm)
0.185"(4.7mm)
0.25
4"(6
.6m
m)
0.486"(12.5mm)
*1.2
2" m
in.
(31.
3mm
)
14-Ø0.094"(2.4mm)
(tolerance ±0.004")(±0.1mm)
*1.417" (36.3mm) Minimum whenHold-Down Spring is Used
1.23" min.(31.3mm)
0.394"(10mm)
0.317" (8.1mm)PCB Layout
SY Series: PC Board Mount Sockets
SY2S-61
Style 8-blade
Terminal Solder/PCB mount
Electrical Rating 300V, 7A
Compatible Relay RY2S, RY22S
Hold-Down Spring SY4S-51F1
Hold-Down Clip SFA-301 (top notch), SFA-302 (side notch)
1.22
" (31
mm
)
0.709" (18mm)
0.059"(1.51mm)
0.48" (12.3mm)
1.0"
(25.
4mm
)
0.118"(3mm)
0.433"(11.1mm)
0.59" (15.1mm)0.535" Minimum
(13.6mm)0.173" ±0.004"
0.161"(4.1mm)
0.228"(5.8mm)
0.661" ±0.004"(17mm±0.1mm)
*0.559" Min.(14.2mm) 8-Ø0.079"
(2mm)
(tolerance ±0.004")(±0.1mm)
*0.756" (14.2mm) Minimum whenHold-Down Spring is Used
(4.4mm ± 0.1mm)
13 14
TerminalArrangement
As Viewedfrom the Bottom
5 89 12
1 4
PCB Layout
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets SY Series: PCB Mount
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-25
F
So
ckets
SY Series: PC Mount Sockets, continued
SY4S-61
Style 14-blade
Terminal Solder/PCB mount
Electrical Rating 300V, 7A
Compatible RelayRY4S, RY42S, RM2S, *RY2KS, *RY2LS, RU4S, RU42S, RU2S (*latching relay)
Compatible Timer GT5Y
Hold-Down Spring SY4S-51F1, SY4S-02F1
Hold-Down ClipSFA-301 (top notch; except GT5Y and RY2KS)SFA-302 (side notch for all)
As Viewedfrom the Bottom
TerminalArrangement
13 14
5 89 12
1 46
10
27
11
3
1.22
" (31
mm
)
1.063" (27mm)
0.059"(1.51mm)
0.835" (21.4mm)
1.0"
(25.
4mm
)
0.118"(3mm)
0.433"(11.1mm)
0.59" (15.1mm)
1.061" Minimum(27.2mm)
0.354"(9.1mm)
0.66
1" ±
0.00
4"(1
7mm
±0.
1mm
)
*0.559" Min.(14.3mm) 15-Ø0.079"
(2mm)
(tolerance ±0.004")(±0.1mm)
*0.756" (19.4mm) Minimum whenHold-Down Spring is Used
0.518" Min.(13.3mm)
0.173"(4.4mm)
0.055"(1.4mm)0.
409"
(10.
5mm
)
0.161"(4.1mm)
0.346"(8.9mm)
PCB Layout
SY4S-62
Style 14-blade
Terminal Solder/PCB mount
Electrical Rating 250V, 7A
Compatible RelayRY4S, RY42S, RU4S, RU42S, *RY2LS, *RY2KS (*latching relay)
Compatible Timer GT5Y
Hold-Down Spring
SY4S-51F1, SY4S-51F3, SY4S-51F4, *SY4S-02F1, *SY4S-02F3 (*when mounting a relay with check button)
As Viewedfrom the Bottom
TerminalArrangement
13 14
5 8
9 12
1 4
6
10
2
7
11
3
1.13
" (29
mm
)
0.83" (21.2mm)
0.059"(1.51mm)
0.118"(3mm)
0.433"(11.1mm)
0.59" (15.1mm)
0.3" (0.01mm)
**0.
32" M
in.
(8.1
mm
)
0.354"(9.1mm)
0.66
1"(1
7mm
)
*0.48" Min.(12.2mm) 15-Ø0.079"
(2mm)
(Tolerance ±0.004")(±0.1mm)
*0.67" (17.2mm) Minimum whenHold-Down Spring is Used
0.518" Min.(13.3mm)
0.173"(4.4mm)
0.055"(1.4mm)0.
409"
(10.
5mm
)
0.346"(8.9mm)
**0.51 (13.2mm) Minimum when Usinga Hold-Down Spring for the RelayCheck Button
PCB Layout
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Other Sockets Sockets
F-26 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
SH Series: Surface Mount Sockets
SH2B-02
Style 8-blade, snap-mount/surface mount
Terminal M3.5 screws with captive wire clamp
Electrical Rating 300V, 10A
Wire Size Maximum up to 2-#12AWG
Compatible Relay RH2B
Hold-Down Spring SY4S-02F1
0.985"(25mm) 0.57"
(14.5mm)
1.89"(48mm)
2.64"(67mm)
1.418"(36mm)
1.142"(29mm)
0.867"(22mm)0.315"
(8mm)
0.165"(4.2mm)
1.142"(29mm)
Ø 0.164"(4.2mm)2 Holes
Ø 0.137"(M3.5)
14 13
12 9
8 5
4 1
Panel Cutout for Surface Mounting
SR Series: Socket for Panel Mounted Timers
SR6P-M08G
Style 8-pin
Terminal M3.5 screws with captive wire clamp
Electrical Rating 300V, 10A
Wire Size Maximum up to 2-#12AWG
Compatible Timer GT3 (8-pin), RTE-1, GE1A
Hold-Down Spring SY4S-02F1
ø3.6min.
8-M3.5
2 1 8 7
3 4 5 6
6.9max.30.4
44.6
0.8~5mm
80.5
7
9.8x3
44.6
3.5max. 5.6min.
SR6P-M11G
Style 11-pin
Terminal M3.5 screws with captive wire clamp
Electrical Rating 300V, 10A
Wire Size Maximum up to 2-#12AWG
Compatible Timer GT3 (11-pin), RTE-2
Hold-Down Spring ------
ø3.6min.
11-M3.5
6.9max.
92
4 3 8 9 10
2 115
1 7 63.5max. 5.8min.
30.5 7
8.5x4
16.745
3445
1. For socket mounting accessories, see page F-27.2. For hold-down clip/spring selections, see page F-4.
Sockets Accessories
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-27
F
So
ckets
Description Appearance Use with Part No. Remarks
Aluminum DIN Rail (1 meter length)
All DIN rail sockets BNDN1000
IDEC offers a low-profile DIN rail (BNDN1000). The BNDN1000 is designed to accommodate snap-mount sockets. Made of durable extruded aluminum, the BNDN-1000 measures 0.413" in height and 1.37" (35mm) in width (DIN standard). Standard length is 39" (1,000mm).
DIN Rail End Stop BNDN1000 DIN rail BNL5 9.1 mm wide.
Surface Mount End Connector
SY2S, SY4S, SR3B, SH1B, SH2B, SH3B, SH4B
SA-203 For use on ends of socket groupings when surface mounting.
SA-204 For use between adjoining sockets when surface mounting.
Surface Mount Connector
SY2S, SY4S, SR3B, SH1B, SH2B, SH3B, SH4B SA-405 For use between adjoining sockets
when surface mounting.
DIN Rail Spacer All DIN rail sockets SA-406
Steel Mounting Plates (for panel mount sockets)
SY4S-51, SH2B-51 SA-402 11.42" length with 10 holes.
SY4S-51, SH2B-51 SA-403 23.33" length with 21 holes.
Relay Holders
RH2B, RM2S, RY4S, RY42S, RY2LS, RAMB, RBMB, RU4S, RU42S
RH-01For diagram, see next page.
RY2S, RH1B RH-03
Replacement Hold-Down Spring Anchor
Horseshoe clip for all DIN rail sockets except SR*P-05(C)
Y778-011For use with hold-down springs (bale wire types).or DIN rail mount sockets.2 pieces included with each socket.
Hold-Down Spring for SR*P-05(C) Chair clip for SR*P-05(C) Y703-102 For SR2P-05, SR2P-05C,
SR3P-05, SR3P-05C
Accessories
SA-203SA-203 SA-204
M4 screwwasher
hold-down spring
18mm
5mm
Instructions Sockets
F-28 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
Mounting Snap-Mount Sockets
Mounting Relay Holders
Mounting Hold-Down Springs
Mount directly onto panel boards in two alternate positions: A and B (see Figure 1).
To mount the relay into the holder, hook the bottom edge of the relay case (coil terminal side) onto the relay holder (see Figure 2).
Push down until the relay snaps into place.
Take the two anchor clips (horseshoe / U-shaped piece) that come with the socket and insert into the slits on both sides of the socket. Make sure the raised notches on the anchor clip face into the socket.
Plug relay into socket
Insert the open ends of the hold-down spring into either the first or second hole of the anchor clip. The relay-spring combination will determine which hole should be used.
Slide spring over relay.
Hold-Down Spring
Instructions
Snap-mount sockets are designed to mount on the BNDN-1000 mounting rail. The built-in mounting clip eliminates mounting hard-ware and reduces mounting time by 80%.
To mount see Figure 1. Place the end of the socket (end opposite of mounting clip against the outer edge of the rail). Press the socket down firmly until the clip snaps onto the mounting rail. To remove see Figure 2. Pull out the mounting clip with a screwdriver, and lift the socket.
For spacing between adjoining sockets, use the SA-406 DIN rail spacer. Spacers are 0.195" wide. Spacing can be adjusted accord-ing to the number of spacers added. Spacers snap on and off easily like snap-mount sockets.
To prevent side-to-side movement, use a BNL-5 end clip at each end of every socket row.
Remove
Mount
Figure 1
Figure 2
Figure 1
RH-01 or -03
Figure 2
Sockets Dimensions
www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC F-29
F
So
ckets
Surface Mount Sockets (SH2B-02)
Snap-Mount Sockets
Dimensions
IDEC surface mount sockets (SH2B-02) are also designed to mount individually or collectively on a flat surface without the use of a DIN rail. Use the mounting screw between adjoining sockets and at the outer ends of the row of sockets.
Dimension Table
Socket Part No. Dimension A
SH2B-02 1.14"
A A A
1. Drawing is not to scale.
Snap-mount sockets are designed to mount individually or collectively without using a rail. Use a SA-405 connector or SA-204 connector between adjoining sockets (see Figures 1 and 2). Use the SA-203 end connector at the outer ends of each socket row when using the SA-204 connector (see Figure 2).
Dimension Table
Socket Part No. Dim. B Dim. C Dim. D
SY2S-05, SY2S-05C 0.669" 0.826" 0.866"
SY4S-05, SY4S-05C 1.024" 1.181" 1.220"
SR3B-05 1.496" 1.693" 1.732"
SH1B-05, SH1B-05C 0.630" 0.787" 0.827"
SH2B-05, SH2B-05C 1.024" 1.181" 1.220"
SH3B-05, SH3B-05C 1.417" 1.575" 1.614"
SH4B-05, SH4B-05C 1.811" 1.969" 2.008"
B C CC C
D D D
0.165" Holeor M4 Tapped
Using an SA-406 Connector
Using SA-203 or SA-204 Connectors
2. Drawings are not to scale.
Dimensions Sockets
F-30 www.idec.com USA: (800) 262-IDEC or (408) 747-0550, Canada (888) 317-IDEC
F
So
ckets
Collective Panel Mounting
Mounting Plate
Dimensions, continued
How to Calculate Cutout Length (L)
Cutout L = A (Total Overall Width of Each Socket) – 0.221" (+ 0", – 0.020")
Example:
L = [0.709" + 1.063" + 1.063" + 0.709" + 1.063" + 0.709" + 1.063" + 1.063"] – 0.221" = 7.93"
L = 7.93" (+ 0", – 0.020")
SH and SY series panel mount sockets are designed to mount collec-tively in panel cut-outs. Insert socket with mounting springs facing the top and bottom edge of the panel cut-out. Push the socket until the mounting spring clips onto the panel. (See Figure 1.)
Dimension Table
Part No. Width Relay
SY4S-51 1.063" RY4S, RY42, RY2KS, RY2LS, RM2S
SH4B-51 1.772" RH4B
SH3B-51 1.418" RH3B, RH2LB
SH2B-51 1.063" RH2B, RAMB, RBMB
SH1B-51 0.709" RH1B, RAHB, RBHB
SY2S-51 0.709" RY2S, RY22S
SY4S-51
RM2SRH1B
RH2B RY2KS
Figure 1
SH1B-51SY2S-51
SY4S-51SY4S-51
SY2S-51
SY4S-51
SH1B-51 SH2B-51
SY4S-51
A = Total Overall Width of Each SocketCutout L = A – 0.221" (+ 0", – 0.020")