Download - Schneider ACB

Transcript
  • A-

    Functionsandcharacteristics

    ThischapterdescribesallthefunctionsofferedbyMasterpactNTandNWdevices.Thetwoproductfamilieshaveidenticalfunctionsimplementedusingthesameordifferentcomponentsdependingonthecase.

    Circuitbreakersandswitch-disconnectors pageA-4

    PB

    007

    6-6

    0

    ratings:Masterpact NT 60 to 600 AMasterpact NW 800 to 600 Acircuit breakers type N, H, H, H, Lswitch-disconnectors type NA, HA, HF or polesfixedordrawoutversionsoption with neutral on the rightprotection derating.

    bvvbbbbbb

    Micrologiccontrolunits pageA-10AmmeterA.0 basic protection5.0 selective protection6.0 selective + earth-fault protection7.0 selective + earth-leakage protectionPowermeterP5.0 selective protection6.0 selective + earth-fault protection7.0 selective + earth-leakage protectionHarmonicmeterH5.0 selective protection6.0 selective + earth-fault protection7.0 selective + earth-leakage protectionexternalsensorforearth-faultprotectionrectangular sensor for earth-leakage protectionsetting options (long-time rating plug):lowsetting0.4to0.8xIrhighsetting0.8to1xIrwithout long-time protectionexternalpower-supplymodulebattery module.

    bbbvvvbb

    DB

    0

    DB

    0

    Portabledataacquisition 0 pageA-22Masterpact and GetnSetb

    Communication pageA-24

    PB

    007

    6-5

    6

    COM option in MasterpactMasterpact in a communication networkMasterpact and the Micro Power Server MPS00.

    bbb

    Connections pageA-30rear connection (horizontal or vertical)front connectionmixedconnectionsoptional accessoriesbare-cable connectors and connector shieldsterminal shieldsvertical-connection adapterscable-lug adaptersinterphase barriersspreadersdisconnectable front-connection adaptersafety shutters, shutter locking blocks, shutter

    position indication and locking.

    bbbbvvvvvvvv

    DB

    0

    56D

    B0

    7

    DB

    0

    9D

    B0

    50

    Generaloverview 0Detailed contents

    Livre_EN.indb 2 17/04/2008 11:38:35

  • A-

    Functionsandcharacteristics

    PB

    007

    6-5

    6

    Locking pageA-34pushbutton locking by padlockable transparent coverOFF-position locking by padlock or keylockchassis locking in disconnected position by keylockchassis locking in connected, disconnected

    and test positionsdoor interlock (inhibits door opening with breaker

    in connected position)racking interlock (inhibits racking with door open)racking interlock between crank and OFF pushbuttonautomatic spring discharge before breaker removalmismatch protection.

    bbbb

    b

    bbbb

    DB

    0

    0

    D

    B0

    09

    Indicationcontacts pageA-36

    DB

    007

    66-5

    6

    standard or low-level contacts:ON/OFF indication (OF)fault trip indication (SDE)carriage switches for connected

    (CE) disconnected (CD) and test (CT) positions

    programmable contacts: contacts (MC)6 contacts (M6C).

    bvvv

    bvv

    DB

    0

    M2Ccontact.

    DB

    0

    OFcontact.

    Remoteoperation pageA-38

    DB

    007

    65-5

    6

    remote ON/OFF:gear motorXF closing or MX opening voltage releasesPF ready-to-close contact

    options: RAR automatic or Res electrical remote reset- BPFE electrical closing pushbutton

    remote tripping function:MN voltage release

    - standard- adjustable or non-adjustable delay

    or second MX voltage release.

    bvvv

    bv

    v

    D

    B0

    D

    B0

    Gearmotor.

    MX,XFandMNvolagereleases.

    Accessories pageA-42auxiliaryterminalshieldoperation counterescutcheontransparent cover for escutcheonescutcheon blanking plate.

    bbbbb

    DB

    0

    5

    Generaloverview 0Detailed contents

    Livre_EN.indb 3 17/04/2008 11:38:37

  • A-

    Functionsandcharacteristics

    MasterpactNT06toNT16installationcharacteristicsCircuitbreaker NT06,NT08,NT10 NT12,NT16Type H1 H2 L1 H1 H2Connection

    Drawout FC b b b b bRC b b b b b

    Fixed FC b b b b bRC b b b b b

    Dimensions(mm)HxWxDDrawout P 322x288x277

    P 322x358x277Fixed P 301x276x196

    P 301x346x196Weight(kg)(approximate)

    Drawout P/P 0/9Fixed P/P /8

    MasterpactNW08toNW63installationcharacteristicsCircuitbreaker NW08,NW10,NW12,NW16 NW20 NW25,NW32,NW40 NW40b,NW50,NW63Type N1 H1 H2 L1 H10 H1 H2 H3 L1 H10 H1 H2 H3 H10 H1 H2Connection

    Drawout FC b b b b - b b b b - b (1) b (1) b (1) - - -RC b b b b b b b b b b b b b b b b

    Fixed FC b b b - - b b - - - b (1) b (1) - - - -RC b b b - - b b - - - b b - - b b

    Dimensions(mm)HxWxDDrawout P 439x441x395 479x786x395

    P 439x556x395 479x1016x395Fixed P 352x442x297 352x767x297

    P 352x537x297 352x997x297Weight(kg)(approximate)

    Drawout P/P 90/0 5/00Fixed P/P 60/80 0/60

    (1) Except4000(1) Except4000

    Circuitbreakersandswitch-disconnectors 0NT06 to NT6 and NW08 to NW6

    NTandNWselectioncriteriaMasterpactNT MasterpactNWStandardapplications Standardapplications SpecialapplicationsNT06,NT08,NT10,NT12,NT16 NT06,NT08,NT10 NW08...NW16 NW08...NW40 NWH10 NWH2withanti-

    corrosionprotection

    NW10...NW40 NWearthingswitchH1 H2 L1 N1 H1 H2 H3 L1 NDC HDC

    Type of application Standard applications with low short-circuit currents

    Applications with medium-level short-circuit currents

    Limiting circuit breaker for protection of cable-type feeders or upgraded transformer ratings

    Standard applications with low short-circuit currents

    Circuit breaker for industrial sites with high short-circuit currents

    High-performance circuit breaker for heavy industry with high short-circuit currents

    Incoming device with very high performance for critical applications

    Limiting circuit breaker for protection of cable-type feeders or upgraded transformer ratings

    000 V systems, e.g. mines and wind power

    Environments with high sulphur contents

    DC system DC system Installation earthing

    Icu/Ics at 0 V kA 50 kA 0 kA kA 65 kA 00 kA 50 kA 50 kA - 00 kA - - -Icu/Ics at 000 V - - - - - - - - 50 kA - - - -Icu/Ics at 500 V DC L/R < 5 ms - - - - - - - - - - 5 kA 85 kA -

    Position of neutral Left Left Left Left Left or right Left or right Left Left Left Left or right - - -Fixed F F F F F F - - - - F F -Drawout D D D D D D D D D D D D DSwitch-disconnector version Yes No No Yes Yes Yes Yes No Yes Yes Yes Yes YesFront connection Yes Yes Yes Yes Yes up to 00 A Yes up to 00 A Yes up to 00 A Yes up to 00 A No Yes up to 00 A No No Yes up to 00 ARear connection Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes YesType of Micrologic control unit A, P, H A, P, H A, P, H A, P, H A, P, H A, P, H A, P, H A, P, H A, consult us

    for P and HA, P, H DC Micrologic DC Micrologic -

    Livre_EN.indb 4 17/04/2008 11:38:38

  • A-5

    MasterpactNT06toNT16installationcharacteristicsCircuitbreaker NT06,NT08,NT10 NT12,NT16Type H1 H2 L1 H1 H2Connection

    Drawout FC b b b b bRC b b b b b

    Fixed FC b b b b bRC b b b b b

    Dimensions(mm)HxWxDDrawout P 322x288x277

    P 322x358x277Fixed P 301x276x196

    P 301x346x196Weight(kg)(approximate)

    Drawout P/P 0/9Fixed P/P /8

    MasterpactNW08toNW63installationcharacteristicsCircuitbreaker NW08,NW10,NW12,NW16 NW20 NW25,NW32,NW40 NW40b,NW50,NW63Type N1 H1 H2 L1 H10 H1 H2 H3 L1 H10 H1 H2 H3 H10 H1 H2Connection

    Drawout FC b b b b - b b b b - b (1) b (1) b (1) - - -RC b b b b b b b b b b b b b b b b

    Fixed FC b b b - - b b - - - b (1) b (1) - - - -RC b b b - - b b - - - b b - - b b

    Dimensions(mm)HxWxDDrawout P 439x441x395 479x786x395

    P 439x556x395 479x1016x395Fixed P 352x442x297 352x767x297

    P 352x537x297 352x997x297Weight(kg)(approximate)

    Drawout P/P 90/0 5/00Fixed P/P 60/80 0/60

    (1) Except4000(1) Except4000

    NTandNWselectioncriteriaMasterpactNT MasterpactNWStandardapplications Standardapplications SpecialapplicationsNT06,NT08,NT10,NT12,NT16 NT06,NT08,NT10 NW08...NW16 NW08...NW40 NWH10 NWH2withanti-

    corrosionprotection

    NW10...NW40 NWearthingswitchH1 H2 L1 N1 H1 H2 H3 L1 NDC HDC

    Type of application Standard applications with low short-circuit currents

    Applications with medium-level short-circuit currents

    Limiting circuit breaker for protection of cable-type feeders or upgraded transformer ratings

    Standard applications with low short-circuit currents

    Circuit breaker for industrial sites with high short-circuit currents

    High-performance circuit breaker for heavy industry with high short-circuit currents

    Incoming device with very high performance for critical applications

    Limiting circuit breaker for protection of cable-type feeders or upgraded transformer ratings

    000 V systems, e.g. mines and wind power

    Environments with high sulphur contents

    DC system DC system Installation earthing

    Icu/Ics at 0 V kA 50 kA 0 kA kA 65 kA 00 kA 50 kA 50 kA - 00 kA - - -Icu/Ics at 000 V - - - - - - - - 50 kA - - - -Icu/Ics at 500 V DC L/R < 5 ms - - - - - - - - - - 5 kA 85 kA -

    Position of neutral Left Left Left Left Left or right Left or right Left Left Left Left or right - - -Fixed F F F F F F - - - - F F -Drawout D D D D D D D D D D D D DSwitch-disconnector version Yes No No Yes Yes Yes Yes No Yes Yes Yes Yes YesFront connection Yes Yes Yes Yes Yes up to 00 A Yes up to 00 A Yes up to 00 A Yes up to 00 A No Yes up to 00 A No No Yes up to 00 ARear connection Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes YesType of Micrologic control unit A, P, H A, P, H A, P, H A, P, H A, P, H A, P, H A, P, H A, P, H A, consult us

    for P and HA, P, H DC Micrologic DC Micrologic -

    Functionsandcharacteristics

    Circuitbreakersandswitch-disconnectors 0NT06 to NT6 and NW08 to NW6

    Livre_EN.indb 5 17/04/2008 11:38:39