SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 3 L&T Automation Confidential

3 SYSTEM DESCRIPTION  

We have offered SCADA system for 5 MWp PV Solar Power Plant at Bap, Jodhpur. Our solution includes data collection from the Solar PV field via Ethernet Switches and providing SCADA for Plant monitoring, String Monitoring & power evacuation monitoring. 

3.1 Proposed System architecture for 5 MWp PV Solar Power Plant  

  

Page 2: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 4 L&T Automation Confidential

4 SCOPE OF WORK 

Design, Engineering, Supply, Installation Testing and Commissioning of Data acquisition system for 5MW Solar PV Plant. 

4.1 Scope of Supply 

Proposed Bill of Material for various systems offered for the SCADA & Control are as under:   4.1.1 Central Control system  5MW Solar PV plant with Grid connect Inverters 

 

Sr. No.  Item Description  Unit  Qty 

  Central Station  

1   EWS with 21” TFT Monitor Nos.  1 

2   SCADA Server   Nos.  1 

3   iVision SCADA – Software  Nos.  1 

4   Web Server + 1 Client Set.  1 

5   Furniture for Control Station (1 Table & 1 Chair)  Set  1 

6   A4 B/W Laser Printer for alarm & report   Nos.  1 

7   GPS for Time Synchronization 1 sec accuracy  Nos.  1 

8   RS 485 Cable  Mtrs.  100 

9   Industrial Ethernet switch  Nos.  1 

10   RJ 45 Ethernet cable  Mtrs.  100 

11   4 Core Multimode Fiber Optic cable (Jelly Filled Armoured) 

Mtrs.  1800 

12   2 KVA UPS System  Set  1 

13   LIU with FO Patch‐cords  Set  1 

14   Local controller (PLC/RTU) with I/O for Local HT Panels, Energy Meters, HT Transformers, C&R Panels, Meteorological Station Data. 

Nos.  1 

 IO List for Central control Station Controller:  

Equipment  DI  DO  AI  Modbus 

33 kV HT Panel (5 I/C & 2 O/G, MFMs, TVMs) 

56  14  14  16 

Weather Station        1 

Auxiliary Power (Availability Status, water Monitoring System, Plant Lighting ON/OFF) 

  3     

Transformer  6       

   

Page 3: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 5 L&T Automation Confidential

4.1.2 Local substations – 5 Nos.  

Sr. No.  Item Description Unit  Qty 

  Local Station     

1   Local controller (PLC/RTU) with I/O for Local LT Panels. 

Nos.  1 

2   Ethernet switch Nos.  1 

3   Ethernet cable Mtrs.  100 

4   1 kVA UPS system Nos  1 

5   RS 485 cable  Mtrs.  580 

6   LIU with FO patch cords  Nos.  1 

 IO List per Sub‐station for Local control Station Controller:  

Equipment  DI DO AI  Modbus

Inverter  10 6 6  2 

Standalone VCB Panel  3  2     

ACB  6  4     

Transformer  6       

SJBs        14 

Page 4: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 6 L&T Automation Confidential

5  (SOLAR PV CONTROL SYSTEM) SCADA SYSTEM DESCRIPTION 

The SCADA (Solar PV Control) System proposed is based on iVisionmax.  iVisionmax  Solar  is  an  advanced  energy monitoring &  control  system  covering  typical  SCADA functionality such as data acquisition, monitoring and control of  the solar photovoltaic plants plus  advanced  features  such  as  alarm  generation,  yield  reports,  performance  ratios  and operation  and maintenance  calendars which will  provide  the  ideal  and  best  in  class  tool  to manage your solar photovoltaic plant. 

  

 

 

 

 

 

 

 

 

 

 

iVisionmax ‐ Screenshot 

A dynamic Solar Power Plant Control System, on iVisionmax platform is an essential, control for cost effective plant operation, especially in Solar Power plants where annual energy generation costs sum up to Cr of Rupees and even small improvement can have a dramatic impact on their bottom  line.  iVisionmax  enables  centralized  control  &  operation  from  a  single  point.  It incorporates all the basic features available in a high‐end Generation SCADA system.  

The plant  is modeled  in such a way so the data acquired can range  from only the most basic ones; such as meteorological data and energy production data to an exhaustive acquisition data scheme, where sensors are connected to the strings, to the input of the inverters and to all the switchgears  of  the  plant,  giving  full  visibility  of  the  solar  photovoltaic  plant  and  enabling immediate reaction in the event of a fault. 

Page 5: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 7 L&T Automation Confidential

   

   

iVisionmax  Solar  Features : 

Controlling with day’s climate conditions 

  Power Evacuation 

Basic features 

 Advanced Features 

Dashboard with KPIs of the solar photovoltaic plant in real time and at a glance 

Inverter parameter Monitoring 

String parameter Monitoring 

Weather Monitoring 

Electrical Network Monitoring & Control 

 Alarms & Events logging 

 Trends & Reporting 

 Data Storage  

         

         

         

Page 6: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 8 L&T Automation Confidential

Solar Field Monitoring            

                                            

Inverter Parameters such as Current, Voltage, Power, Frequency, Power Factor, Cumulative energy etc. (All Parameters which are communicable over RS‐485 Modbus Protocol)    

PV String Parameters ‐ String Current, Voltage & power etc. (All Parameters which are communicable over RS‐485 Modbus Protocol)   

 

Weather Data –Solar Irradiance, Wind Speed, Ambient Temperature, Relative humidity. 

 

Communication Health 

Extract operating values of the plant, compare signals and graphically represent the obtained 

l

Page 7: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 9 L&T Automation Confidential

                  

Electrical Network Monitoring & Control  Real time monitoring and Control of various Electrical equipments (LV, MV & HV) 

LT/MV/HT Switch Boards 

 Incomers 

 Outgoing feeders 

 Transformer feeders 

Transformer Protection 

 Bus couplers 

 Electrical Network (SLD) preparation using standard     Electrical Object Library (as per IEC standard 60617) 

Alarms & Events monitoring  

Page 8: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 10 L&T Automation Confidential

Power Evacuation            

        

     

Yield Reports  

Accurate information of the performance of the 

plant daily, weekly and monthly, including 

production ratios, performance ratios and 

availability. 

 Annual/Daily/Hourly Generation  

 Energy Tracking 

 Total consumption 

 Assist  to minimize plant operational cost 

Assist user to identify areas for energy saving and minimize plant operational cost  

Monitoring and 

Protection of Substation  Grid Tie‐up system 

Energy Management & Accounting System 

Page 9: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 11 L&T Automation Confidential

 

Asset Management 

Inventory management system   

 Detailed asset registry, combined with detailed parts and support descriptions. 

 Support for complex inventory relationships for repair and overhaul, such as maintenance, repair and operations (MRO) – goods that are associated with forecasts of planned and unplanned work on installed assets 

 Extensive warranty tracking to component levels  Advanced Maintenance management system  

Remote electronic monitoring of asset health and performance 

 Maintenance scheduling 

 Asset running hours tracking 

Improves maintenance performance

Page 10: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 12 L&T Automation Confidential

  

Trends 

Real time trends for operating parameter of Plant 

 Historical trends for operating Parameter of plant 

 Direct printing   Export to CSV 

Events & Alarms logging 

Alarms generation and treatment, direct alarms from the acquisition equipment, range alarms, connectivity alarms and performance alarms  

Configurable alarms 

 Alarms & Event filtering and commenting 

 Authorized acknowledgement of alarms  

Email and/or SMS to the recipients. 

Configurable receiving groups, frequency and category of the alerts to be transmitted 

Page 11: Scada Detail

SCADA and Control System for 5 MWp Solar PV Plant M/s Rays Solar Energy

QN-RaysSolar-PBP-11/Rev3 P a g e | 13 L&T Automation Confidential

    iVisionmax Solar enables Data Monitoring, Electrical Control in a plant. Deployed hardware and iVisionmax Solar enable clear overview of the electrical network in the plant and provide means for monitoring and managing Load. Tight integration of all subsystems ensures system stability and helps avoid system collapse.   (iVisionmax Solar  in essence,  is designed to be hierarchical, distributed, and modular based on internationally  recognized "open" standards. The Redundant architecture used at  the Central Control,  incorporates computer and LAN  redundancy. Failures at any  levels of  the  system do not  impact  other  levels.  Open  architecture  allows  easy  upgrading  to  new  technology,  as  it becomes available.   

Extensive Reports

MS Excel Reporting 

 Configurable Reports  User defined templates 

 Daily  Weekly 

 Monthly 

 Yearly  User defined time slot 

Secured User Administration 

Specified: 

 Users  Groups  Areas  Different authorization levels