�AN028-Quick-Guide�ThySetter-ThyVisor-04-2017
Quick-guide connection to
thytronic relays
This�application�note�describe�procedure�for�setting:Communication�Ethernet�parameters�(IP�address)Relay�reference�name
This�application�note�make�use�of�software�Thysetter�and�Thyvisor,�freely�downloadable�from�the�website�www.thytronic.com�.For�proper�installation�be�sure�also�to�download�and�execute�the�file�“ThytronicTemplates”�availa-ble�in�2�versions�(IT�and�EN�or�IT,�EN,�RU,�ES�and�TR)
••
2�
AN028-Quick-Guide�ThySetter-ThyVisor-04-2017
t h y s e t t e rSince�fw�version�3.40�on�device�of�family�Pro-N�and�since�version�1.50�for�device�of�the�family�Pro-NX�settings�of�Ethernet�communication�parameters�(IP�address)�and�the�relay�reference�namecan�be�changed�only�inside�menu�commands \ set Params \ set no resettable parameters.For�earlier�versions�relay�reference�name�could�be�changed�from�menu�set \ Base while�Ethernet�communication�parameters�could�be�changed�from�the�menu�communication \ ethernet.
relay reference nameRelay�reference�name�can�be�changed�from�menu�commands \ set Params \ set no resettable pa-rameters.
After�inserting�the�name�and�press�the�OK�button�you�need�to�place�the�mouse�cursor�on�the�menu�set no resettable parameters�and�send�the�command�(right�click�on�it)�to�store�the�configuration�in�the�relay�memory.
communication parameters
ETHERNETInside�of�menu�is�possible�to�read�and�change�settings�regarding�Ethernet�parameters:IP host address � � Relay�IP�addressIP net mask � � � Relay�netmask�addressIP gateway� � � � Relay� gateway� adress� (usefull� for� connection� to� external�� � � � network�or�between�2�or�more�network).
With�the�same�procedure�just�now�described�to�change�the�relay�reference�name,�after�inserting�data�and�confirming�with�OK�button�you�need�to�place�the�mouse�curso�on�the�menu�set no resetta-ble parameters�and�send�the�command�(right�click�on�it)�to�store�the�changed�configuration�in�relay�memory.
—
—
•••
�3AN028-Quick-Guide�ThySetter-ThyVisor-04-2017
Checking IP-address
To�check�an�IP�address�is�possible�to�execute�these�commands:Start�a�DOS�session:�“Start�->�Programs�->�Prompt�MS-Dos”�or�“Start�->�Run�->�CMD”Type�the�command�“ping�-n�10�200.1.1.225”�->�Enter[1]
The�communication�is�working�properly�if�you�get�the�message�“Reply�from...”;�otherwise,�if�you�get�a�message�as�“Request�time�out”,�you�need�to�change�configuration.
Close�the�DOS�session�typing�the�command�“exit”.
setting the serial numberThe�serial�number�of�relay�is�changable�from�the�menu�command \ set Params \ set serial number.
After�changing�the�serial�number�and�confirm�with�“Enter”�key,�you�need�to�put�the�cursor�on�the�menu�set serial number�and�send�the�command�(right�mouse�click)�to�save�the�modificed�configu-ration�in�the�relay�memory.
Note � In the example you are checking the transmission of pocket with a device with IP adress 200.�.2.24�.
••
—
4�
AN028-Quick-Guide�ThySetter-ThyVisor-04-2017
t h y V i s o rsetting up iP address over ethernet using thyVisor software
Starting configuration:Relay�IP�address:�127.0.0.1�(default�setting)Relay�directly�linked�to�PC�using�cross�network�cable�or�è�collegato�al�PC�direttamente�tramite�cavo�incrociato�o�indirectly�through�network�switch.
Desired IP address:200.1.2.186
The�sequence�of�actions�to�be�made�is:Take�note�of�the�relay�serial�number,�in�this�example:�183247Take�note�of�the�model�and�of�the�software�version,�in�this�example:“PRON-NV10P-E00-s”;�infor-mation�are�available�on�display�in�menu�read / infoRun� Thyvisor� (properly� installad� together� with� corrisponding� or� most� recent� version� of� Thytro-nicTemplates.exe)
Click�on�the�button�“Manage”�in�the�group�“Network”
Click� on� the� button� “Add� Device”� and� select� the� relays� family� and� the� software� version�(as�per�point�2);�in�this�example:�“PRON”�and�device�“NV10P-EXO-s”.[1]
Note � In case of relay with code E00 select EX0, in case of relay with code E02, select EX2, in case of relay with code M00 or C00 select CX0, in case of relay with code M02 or C02 select CX2, in case of relay with code D00 select DX0,
in case of relay with code D02, select DX2
—
••
•
1)2)
3)
4)
5)
�5AN028-Quick-Guide�ThySetter-ThyVisor-04-2017
Click�on�the�button�“Add”
Keep�default�name�and�press�the�button�“Ok”
Select�the�relay�just�now�added�and�press�the�button�“Modify”
After�inserting�the�desired�IP�address�(200.1.2.186)�and�serial�number�(183247)�confirm�data�pres-sing�the�“OK”�button
6)
7)
8)
9)
sede: 20139�Milano�-�Piazza�Mistral,�7�-�Tel.�+39�02�574�957�01�ra�-�Fax�+39�02�574�037�63stabilimento: 35127�Padova�-�Z.I.�Sud�-�Via�dell’Artigianato,�48�-�Tel.�+39�049�894�770�1�ra�-�Fax�+39�049�870�139�0
www.thytronic.it [email protected] www.thytronic.com
��Click�on�“Update�Ip”
��The�error�message�is�not�importand�and�can�be�ignored.
10)
11)