Technology for energy efficiency
OPTIMAutomatic Capacitor Banks
Power Factor correctionand harmonic filtering
Since 1973, CIRCUTOR has specialised in the design, manufacture and marketing of energy efficiency equipment: measurement and control equipment for electricity, supply quality, industrial electrical protection, reactive energy compensation and harmonic filtration.The production capacity of CIRCUTOR is based on six production centres throughout Spain and the Czech Republic.
CIRCUTOR has committed itself to following the latest technological advances in order to add them to its products. It has its own test technology and laboratories that enable it to guarantee the quality of all its products. The company is present in over 100 countries, with offices in Argentina, Mexico, Germany, France, Shanghai, Singapore, Dubai etc. CIRCUTOR holds certification in: • Quality (ISO 9001) • The Environment (ISO 14001) • Safety (OHSAS 18001) • Hazardous substances (RoHS RSC MS) • Energy Management System (ISO 50001)
CIRCUTOR Profile
Measurement
Quality and Metering
Protection and Control
Power Factor Correction and Harmonic Filtering
Smart Electrical Vehicles Recharging
What are reactive power and reactive energy? The reactive power is the power used by some receivers to create electric and magnetic fields, such as electrical motors, lighting systems, etc.
This power is not converted into useful work, instead of increases the total power to be transmitted and distributed by the utilities, therefore it’s overloading the electrical power systems.The reactive energy is the reactive power consumed per hour.
What is power factor?Power Factor is the proportion that exists between active and apparent power, as it`s shown in diagram:
What is power factor correction?It’s the decrease of the reactive power by connecting capacitor banks in the electrical installation. This fact is shown in the previous diagram.
Benefits of power factor compensation1. Reduction of the electricity bill. The cost of electrical bill is reduced by the elimination of the reactive penalty, or the cost of reactive energy. That depends on the different electrical tariff systems existing in the countries.
2. Technical improvements y Reduction of the demanded apparent power of the facilities, so that, it allows
an increase of the capacity of the electrical installations. y Decrease the level of electrical losses throughout the electrical system y Increase the voltage levels. y As a result, extension of installation lifetime
3. Care of environmentThe Power Factor Compensation helps to reduce the Greenhouse Emissions by reducing the amount of primary energy needed.
Why to use CIRCUTOR’s PFC products y Designed and manufactured in EUROPE y State-of-the-art technology y Wide product range for:
y Fix capacitors y Automatic Capacitor Banks (OPTIM) y Detuned Capacitor Banks (FR) y Quick delivery
kVA - Apparent Power
kVA
kW - Active Power kW
kvarL
kvarL - Inductive Reactive Power
kvarC - Capacitive Reactive Power
WITH Capacitor BankWITHOUT Capacitor Bank
cos j = 0,8cos j = 0,98
Regulated capacitorsOPTIM 1 / 1A
The regulated capacitors of the OPTIM 1 / OPTIM 1A series are power factor com-pensation units operated by a computer one reactive relay.
Application
Their simple installation, high-technology and robustness make OPTIM 1 and OPTIM 1A re-gulated capacitors an ideal compact unit for compensating reactive energy in low power installations or loads where the load levels are not subject to major fluctuations such as:
}} Small businesses}} Restaurants}} Lifts}} Irrigation pumps}} etc.
FeaturesDescription
Electrical features
Operating voltage 400 V (other voltages: please ask)
Support voltage 440 V
Frequency 50 Hz (other frequencies: please ask)
Capacity tolerance -5%...+10%
Insulation level 3 kV a 50 Hz
Impulse test 15 kV, ray type wave 1.2/50 µs
Current transformer input 250 mA
Contactor operating voltage 230 V
Unit composed of • CLZ capacitors • Appropriate contactors for capacitive currents • Circuit breaker protection • Computer One PF relay
Residual discharge voltage 75 V / 3 minutes
Total losses < 0,5 W / kvar
Overvoltage • 10% 8 over 24 hours • 15% up to 15 minutes over 24 hours • 20% up to 5 minutes over 24 hours • 30% up to 1 minute over 24 hours
Environmental conditions
Class D according to IEC-60831
TemperatureDaily meanAnnual meanMaximumMinimum
45 ºC35 ºC55 ºC-25 ºC
Humidity 80% non-condensing
Altitude < 1000 m above sea level.
Mechanical features
Enclosure material Thermoplastic
Protection Degree IP 21
Colour RAL 7035 Grey
Assembly conditions
Type of assembly Wall-mounted
Position Vertical
Ventilation Natural or forced, in accordance with options
Standards
IEC 60831-1, UNE 60831-1, IEC 61921, IEC 60439, IEC 61439
OPTIM Automatic Capacitor Banks
Regulated capacitorsOPTIM 1 / 1A
Dimensions
References
500
215 166
140
ENTRADA CABLESCABLE INPUT 270
500
166
140
ENTRADA CABLESCABLE INPUT
OPTIM 1 OPTIM 1A
Automatic Capacitor Banks
Type Codekvar
Composition Switch (A)Optional
Cable section (mm2)
Weight (kg)
Dimensions (mm) width x height x depth440 V 400 V
OPTIM 1, automatic capacitor bank with Power Factor relay. Requires one measuring transformer - MC series 250 mA (see. M.7)
OPTIM 1-2,5-440 [*] R3Q631EN 2,5 2 1 x 2,5 Included 6 4 215 x 500 x 140
OPTIM 1-5-440 [*] R3Q641EN 5 4 1 x 5 Included 6 4,5 215 x 500 x 140
OPTIM 1-6,25-440 [*] R3Q651EN 6,25 5 1 x 6,25 Included 6 5 215 x 500 x 140
OPTIM 1-10-440 [*] R3Q671EN 10 8 1 x 10 Included 6 5 215 x 500 x 140
OPTIM 1-12,5-440 [*] R3Q681EN 12,5 10 1 x 12,5 Included 6 5 215 x 500 x 140
OPTIM 1-15-440 [*] R3Q691EN 15 12,5 1 x 15 Included 6 5 215 x 500 x 140
OPTIM 1A-18,2-440 [*] R3Q6E1EN 18,2 15 1 x 18,2 Included 6 6 270 x 500 x 140
OPTIM 1A-25-440 [*] R3Q6F1EN 25 21 1 x 25 Included 10 7 270 x 500 x 140
OPTIM 1A-30-440 [*] R3Q6D1EN 30 25 1 x 30 Included 10 7 270 x 500 x 140
years of warrantyjust because we are entirely sure
OPTIM Automatic Capacitor Banks
The OPTIM series automatic capacitor banks have been designed for the automatic compensation of reactive energy in networks with fluctuating loads and power variations during seconds, by switching operations ca-rried out by contactors.
Application
Their simple installation, high-technology and robustness make the OPTIM series the ideal unit for compensating reactive energy in insta-llations with fluctuating load levels.
Description
Automatic capacitor banksOPTIM
Features
Electrical features
Operating voltage 400 V (please ask about other voltages)
Voltage 440 V
Frequency 50 Hz (please ask about other frequencies)
Capacity tolerance -5%, +10%
Impulse test 15 kV, lighting impulse type wave 1.2 / 50µs
Current transformer input
• 250 mA in OPTIM 2 model
• 5 A in OPTIM 3, OPTIM 3A, OPTIM 4, OPTIM 6, OPTIM 8, OPTIM SC8, OPTIM SC12 and OPTIM SC16 models
Contactor operating voltage 230 V
Unit composed of
CAPACITORS:
• CLZ Cilindrival type capacitor in OPTIM 2, OPTIM 6, OPTIM 12 and OPTIM 8 models
• CEUB type capacitor in OPTIM 3, OPTIM 3A and OPTIM 4 models
• CSB Prismatic type capacitor in OPTIM SC8, OPTIM SC12 and OPTIM SC16 models
• Appropriate contactors for capacitive currents
PROTECTION:
• Circuit breaker protection incorporated in OPTIM 2, OPTIM 3 and OPTIM 3A models
• Fuses with high cut off power (APR): NH-00 type in OPTIM 4, OPTIM 6, OPTIM 12, OPTIM 8, OPTIM SC8,OPTIM SC12 and OPTIM SC16 models
POWER FACTOR REgULATOR:
• Computer TWO, with 2 relay outputs, in OPTIM 2 model
• Computer MAX with digital indication and 6 or 12 relay outputs in accordance with type, in OPTIM 3, OPTIM 4, OPTIM 6, OPTIM 8, OPTIM SC8, OPTIM SC12 and OPTIM SC16 models
Add-ons (optional)
• Manual capacitor bank header switch • Bank header circuit breaker • Bank header circuit breaker + earth leakage protection
• Forced ventilation unit + thermostat • Polycarbonate sheet to protect against direct contacts
• 400/230 V autotransformer • Computer SMART regulator with built-in power analyzer and single-phase measuring
• Computer PLUS regulator with built-in power analyzer and three-phase measuring
Residual discharge voltage 75 V / 3 minutesCapacitor losses < 0.5 W / kvarOverload 1.3 times the nominal hold current
Overvoltage10% 8 over 24 hours15% up to 15 minutes over 24 hours20% up to 5 minutes over 24 hours30% up to 1 minute over 24 hours
Temperature
Class D according to IEC-60831:Daily mean: 45 ºCAnnual mean: 35 ºCMaximum: 55 ºCMinimum: -50 ºC
Environmental conditionsHumidity 80% non-condensingAltitude < 2,000 m above sea level.Mechanical features
Enclosure material Thermoplastic in OPTIM 2 modelSheet metal in all other models
Protection Degree IP 21
Colour RAL 7035 GreyRAL 3005 Maroon
Assembly conditions
Type of assembly
Wall mounted in OPTIM 2, OPTIM 3, OPTIM 3A and OPTIM 4 modelsFreestanding in OPTIM 6, OPTIM 12, OPTIM 8, OPTIM SC8, OPTIM SC12 and OPTIM SC16 models
Positioning the unit Vertical
Ventilation Natural or forced, in accordance with the options
Standards
IEC 60831-1, UNE 60831-1, IEC 61921, IEC 60439, IEC 61439
Automatic Capacitor Banks
OPTIM, automatic capacitor banks, 2.5 to 1600 kvar
Type Codekvar
Composition Switch (A)Optional
Cable section (mm2)
Weight (kg)
Dimensions (mm) width x height x depth440 V 400 V
OPTIM 2, automatic capacitor banks with Power Factor regulator without display. Requires one measuring transformer - MC series 250 mA (see. M.7)OPTIM 2-7,5-440 [*] R3Q761EN 7,5 6,25 2,5 + 5 Included 6 7 362 x 500 x 166OPTIM 2-10,5-440 [1] R3Q771EN 10,5 8,5 3 + 7,5 Included 6 7 362 x 500 x 166OPTIM 2-12,5-440 [*] R3Q781EN 12,5 10 5 + 7,5 Included 6 7 362 x 500 x 166OPTIM 2-17,5-440 [1] R3Q7E1EN 17,5 14 5 + 12,5 Included 6 7 362 x 500 x 166OPTIM 2-20-440 [1] R3Q7F1EN 20 16,5 7,5 + 12,5 Included 6 7 362 x 500 x 166OPTIM 2-22,5-440 [*] R3Q7g1EN 22,5 18,5 7,5 + 15 Included 6 7 362 x 500 x 166OPTIM 2-25-440 [1] R3Q7H1EN 25 20 10 + 15 Included 10 8 362 x 500 x 166OPTIM 2-30-440 [1] R3Q7J1EN 30 25 15 + 15 Included 10 8 362 x 500 x 166
OPTIM 3, automatic capacitor banks with Computer Max regulatorOPTIM 3-7,5-440 [*] R3J105 7,5 6,25 2,5 + 5 Included 6 28 290 x 464 x 170OPTIM 3-12,5-440 [1] R3J110 12,5 10 2,5 + 5 + 5 Included 6 28 290 x 464 x 170OPTIM 3-17,5-440 [*] R3J115 17,5 14 2,5 + 5 + 10 Included 6 30 290 x 464 x 170OPTIM 3-25-440 [*] R3J120 25 20 5 + 10 + 10 Included 10 31 290 x 464 x 170OPTIM 3-31,25-440 [*] R3J130 31,25 26 6,25 + 12,5 + 12,5 Included 10 32 290 x 464 x 170OPTIM 3A-37,5-440 [1] R3J135 37,5 31,25 7,5 + 15 + 15 Included 16 33 335 x 560 x 170OPTIM 3A-43,75-440 [*] R3J140 43,75 36 6,25 + 12,5 + 25 Included 25 36 335 x 560 x 170OPTIM 3A-50-440 [1] R3J145 50 41 10 + 20 + 20 Included 25 37 335 x 560 x 170OPTIM 3A-62,5-440 [1] R3J150 62,5 51 12,5 + 25 + 25 Included 35 40 335 x 560 x 170OPTIM 4, automatic capacitor banks with Computer Max regulatorOPTIM 4-52,5-440 [*] R3J204 52,5 43 7,5 + 15 + 30 125 35 40 460 x 930 x 230OPTIM 4-55-440 [*] R3J205 55 45 5 + 10 + 20 + 20 125 35 40 460 x 930 x 230OPTIM 4-70-440 [*] R3J210 70 58 10 + 3 x 20 125 50 41 460 x 930 x 230OPTIM 4-75-440 [1] R3J220 75 62 15 + 30 + 30 200 70 42 460 x 930 x 230OPTIM 4-90-440 [*] R3J230 90 74 15 + 15 + 30 + 30 200 70 43 460 x 930 x 230OPTIM 4-105-440 [*] R3J240 105 87 15 + 30 + 30 + 30 200 70 46 460 x 930 x 230OPTIM 4-120-440 [1] R3J250 120 99 4 x 30 250 95 48 460 x 930 x 230
OPTIM 6, automatic capacitor banks with Computer Max regulatorOPTIM 6-135-440 [*] R3J320 135 112 15 + 4 x 30 250 95 81 615 x 1330 x 400 OPTIM 6-150-440 [1] R3J330 150 124 5 x 30 400 120 82 615 x 1330 x 400OPTIM 6-165-440 [*] R3J340 165 136 15 + 5 x 30 400 120 83 615 x 1330 x 400OPTIM 6-180-440 [1] R3J350 180 149 6 x 30 400 150 87 615 x 1330 x 400OPTIM 12, automatic capacitor banks with Computer Max regulatorOPTIM 12-195-440 [*] R3J520 195 161 15 + 6 x 30 400 150 117 1180 x 1340 x 360OPTIM 12-210-440 [1] R3J530 210 173 7 x 30 400 185 119 1180 x 1340 x 360OPTIM 12-225-440 [1] R3J540 225 186 15 + 7 x 30 400 185 121 1180 x 1340 x 360OPTIM 12-240-440 [1] R3J545 240 198 8 x 30 630 185 124 1180 x 1340 x 360OPTIM 12-255-440 [*] R3J550 255 210 15 + 8 x 30 630 240 127 1180 x 1340 x 360OPTIM 12-270-440 [*] R3J560 270 223 9 x 30 630 240 130 1180 x 1340 x 360OPTIM 12-285-440 [1] R3J565 285 235 15 + 9 x 30 630 240 133 1180 x 1340 x 360OPTIM 12-300-440 [1] R3J570 300 248 10 x 30 630 240 136 1180 x 1340 x 360OPTIM 12-315-440 [*] R3J575 315 260 15 + 10 x 30 630 240 139 1180 x 1340 x 360OPTIM 12-330-440 [1] R3J580 330 273 11 x 30 630 2x150 142 1180 x 1340 x 360OPTIM 12-345-440 [*] R3J585 345 285 15 + 11 x 30 630 2x150 145 1180 x 1340 x 360OPTIM 12-360-440 [1] R3J590 360 298 12 x 30 630 2x150 155 1180 x 1340 x 360
Switch and cable section for installations with Un= 400 V. The installation company must ensure compliance with the low voltage directive at all times, in accordance with the particularities of each installation and type of cable.
years of warrantyjust because we are entirely sure
OPTIM 3
OPTIM 4
OPTIM Automatic Capacitor Banks
OPTIM 2
OPTIM 3A
500
166
140
362
335 170
560 40
534
5OPTIM, automatic capacitor banks, 2.5 to 1600 kvar
Type Codekvar
Composition Switch (A)Optional
Cable section (mm2) Weight (kg) Dimensions (mm)
width x height x depth440 V 400 V
OPTIM 8, automatic capacitor banks with Computer Max regulatorOPTIM 8-330-440 [1] R3J405 330 273 30 + 5 x 60 630 2x150 232 1180 x 1650 x 360OPTIM 8-360-440 [1] R3J410 360 298 6 x 60 630 2x185 240 1180 x 1650 x 360OPTIM 8-390-440 [*] R3J420 390 322 30 + 6 x 60 800 2x185 245 1180 x 1650 x 360OPTIM 8-420-440 [1] R3J430 420 347 7 x 60 800 2x240 250 1180 x 1650 x 360OPTIM 8-450-440 [*] R3J440 450 372 30 + 7 x 60 800 2x240 255 1180 x 1650 x 360OPTIM 8-480-440 [1] R3J445 480 397 8 x 60 1000 2x240 260 1180 x 1650 x 360OPTIM SC8, automatic capacitor banks with Computer Max regulatorOPTIM SC8-450-440 [2] R3J640 450 372 50 + 4 x 100 800 2x185 270 1180 x 1805 x 460 OPTIM SC8-500-440 [2] R3J650 500 413 5 x 100 1000 2x240 275 1180 x 1805 x 460 OPTIM SC8-550-440 [*] R3J655 550 454 50 + 5 x 100 1000 2x240 280 1180 x 1805 x 460 OPTIM SC8-600-440 [2] R3J660 600 496 6 x 100 1250 2x240 285 1180 x 1805 x 460 OPTIM SC8-650-440 [*] R3J665 650 537 50 + 6 x 100 1250 3x150 290 1180 x 1805 x 460 OPTIM SC8-700-440 [2] R3J670 700 579 7 x 100 1250 3x150 295 1180 x 1805 x 460 OPTIM SC8-750-440 [*] R3J675 750 620 50 + 7 x 100 1600 3x185 300 1180 x 1805 x 460 OPTIM SC8-800-440 [2] R3J680 800 661 8 x 100 1600 3x185 305 1180 x 1805 x 460 OPTIM SC12, automatic capacitor banks with Computer Max regulator
OPTIM SC12-900-440 [2] R3J765 900 744 9 x 100 1250 / 400 3x150 / 185 525 1930 x 1805 x 460OPTIM SC12-950-440 [2] R3J770 950 785 50 + 9 x 100 1600 / 400 3x185 / 185 535 1930 x 1805 x 460OPTIM SC12-1000-440 [2] R3J775 1000 826 10 x 100 1600 / 400 3x185 / 185 545 1930 x 1805 x 460OPTIM SC12-1050-440 [2] R3J780 1050 868 50 + 10 x 100 1600 / 630 3x185 / 240 555 1930 x 1805 x 460OPTIM SC12-1100-440 [2] R3J785 1100 909 11 x 100 1600 / 630 3x185 / 2x120 565 1930 x 1805 x 460OPTIM SC12-1150-440 [2] R3J790 1150 950 50 + 11 x 100 1600 / 800 3x185 / 2x150 575 1930 x 1805 x 460OPTIM SC12-1200-440 [2] R3J795 1200 992 12 x 100 1600 / 800 3x185 / 2x185 585 1930 x 1805 x 460OPTIM SC16, automatic capacitor banks with Computer Max regulatorOPTIM SC16-1300-440 [2] R3J880 1300 1074 100 + 6 x 200 1250 / 1250 3x185 / 2x240 590 2460 x 1805 x 460OPTIM SC16-1400-440 [2] R3J885 1400 1157 100 + 100 + 6 x 200 1600 / 1250 3x185 / 3x120 595 2460 x 1805 x 460OPTIM SC16-1500-440 [2] R3J890 1500 1240 100 + 7 x 200 1600 / 1600 3x185 / 3x150 600 2460 x 1805 x 460OPTIM SC16-1600-440 [2] R3J895 1600 1322 100 + 100 + 7 x 200 1600 / 1600 3x185 / 3x185 605 2460 x 1805 x 460
Switch and cable section for installations with Un= 400 V. The installation company must ensure compliance with the low voltage directive at all times, in accordance with the particularities of each installation and type of cable.
Automatic Capacitor Banks
OPTIM 6
OPTIM SC8
OPTIM 8
OPTIM SC12
13
40
12
40
10
0
1180 360
1650
1550
100
1180 360
18
05
1 180
460
years of warrantyjust because we are entirely sure
OPT
IM
R 3 X X X X 0 0 X X X
Code Internal code
Delivery time
Options
Standard (*) 0 -Autotransf. maniobra 1 (a)
Fan 2 ConsultPolicarbonate 3 1
Autotransf. + Fan 4 (a) Autotransf. + Policar-
bonate 5 Consult
Policarbonate + Fan 6 (c)
Autotransf. + Policarbonate + Fan 7
Choose the Regulator
that is better for you
Estándar 0 -computer PLUS T8 3computer PLUS T14 4computer PLUS T8 - C (*1) Acomputer PLUS T14 - C (*1) B (b)computer PLUS T8 - CDI (*2) E (c)
computer PLUS T14 - CDI (*2) F (c)
computer SMART 6 (*1) Icomputer SMART 12 (*1) J
Switch
without switch 0 -Manual switch 63 A 1 ConsultManual switch 125 A 2 ConsultManual switch 200 A 3 ConsultManual switch 250A 4 -Manual switch 400 A 5 -Manual switch 630 A 6 -Manual switch 800 A 7 -Manual switch 1000 A 8 -Manual switch 1600 A 9 -Automatic switch 63 A A -Automatic switch 125 A B -Automatic switch 160A C -Automatic switch 250A D -Automatic switch 400 A E -Automatic switch 630 A F -Automatic switch 800 A G -Automatic switch 1000 A H -Automatic switch 1250 A I -Automatic switch 1600 A J -
Automatic switch 63 A + Earth leakage K -Automatic switch 125 A + Earth leakage L -Automatic switch 160 A + Earth leakage M -Automatic switch 250 A + Earth leakage N -Automatic switch 400 A + Earth leakage O -Automatic switch 630 A + Earth leakage P -Automatic switch 800 A + Earth leakage Q -Automatic switch 1000 A + Earth leakage R -Automatic switch 1250 A + Earth leakage SAutomatic switch 1600 A + Earth leakage T
(*1) With communications(*2) With communications, earth leakage current and capacitor current
Codification table
Computers Power Factor Smart Relays for OPTIM Series
computer Top features, accuracy and technology at the best price
User-friendly and fully intuitive installationcomputer max provides the “phase selection” function, that allows the user choosing the power line phase where the measuring current transformer (C.T.) has been placed in. This option eliminates the difficulty in placing the C.T. in a specific phase of the power line. phase
selectionfunction
CLZ / CSB Capacitors for OPTIM Series
The CLZ tubular capacitor range is composed of capacitors with a tubular casing, of the dry-type, covering a wide range of power and voltage ratings, at 50 and 60 Hz. The design, manufacturing and testing processes of CLZ tubular capacitors guarantee the production of top quality and long lasting capacitors.
CIRCUTOR GuaranteesDurability guarantee y Top quality polypropylene with a European origin guarantee. y Dielectric thickness designed to offer a greater capacitor durability.
Continuity of the service guarantee y Self-regeneration technology that guarantees the minimum loss of the capacity. y Internal fuse technology. Assuring the whole disconnection of the capacitor before hazardous situations.
Safety guarantees yOver-pressure safety system, in order to guarantee the correct disconnection of the damage capacitor piece. yGas technology system. Complete elimination of oil leaks and also of fire risk.
Power Factor Smart Relays for OPTIM Series
Voltage measurement Current measurement
THD(I) measurement Voltage maximum valueCurrent maximum value
Measurement of basic electrical parameterscomputer max shows by display: cos φ, voltage, current, THD(I) and, besides, records in memory maximum values for voltage and current.
Built-in alarmscomputer max automatically assigns the alarm conditions to the last output relay (relay 6 or 12), provided that this is not used for switching a capacitor step.
Indication by display or through relay output of following alarm conditions: y Compensation failure y Over-compensation y Over-voltage y Over-current y C.T. not connected or open y Line current below measurable value
Capacitors for OPTIM Series
CIRCUTOR GuaranteesDurability guarantee y Top quality polypropylene with a European origin guarantee. y Dielectric thickness designed to offer a greater capacitor durability.
Continuity of the service guarantee y Self-regeneration technology that guarantees the minimum loss of the capacity. y Internal individual fuse that guarantees the disconnection exclusively of the damaged element
Safety guarantees yOver-pressure disconnection, isolating the damaged element. y Anti-deflagration system, by means of compacting coils with inert and fireproof materials.
Innovation within your reachThe application of new technologies and the use of printed circuit boards to manu-facture prismatic capacitors have allowed CIRCUTOR to reinvent the classic CS capacitor, manufactured for over 35 years. The spirit of innovation and proprietary technology used during the design of the new CSB capacitor have increased the lifespan of traditional prismatic capacitors by over 60%. This new series has im-proved all aspects of the previous models, offering our customers a longer-lasting, safer and more profitable capacitor.
PatentedDesign
CIRCUTOR, SA reserves the right to modify the information contained in this catalogue.Code: C2R333-01
CIRCUTOR, SA - Vial Sant Jordi, s/n 08232 Viladecavalls (Barcelona) Spain Tel. (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14 [email protected]
www.circutor.com Des
igne
d by
: Im
age
and
Com
mun
icat
ions
Dep
artm
ent -
CIR
CU
TOR
, SA
+ information: [email protected]
OPTIMAutomatic Capacitor Banks
Top Related