Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 1of 14
Page 1 of 14
Inspected by: Juber Anwar Khan (Asst. Maint. Engineer)
Sl.No Picture Remarks
1.
2 & 3
Rusted tapchanger leaver in Tx1
Breather not in good condition in Tx- 1 Cooling fan is missing in Tx -1
8/13/2019 Mudhaibi Grid Station
2/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 2of 14
Page 2 of 14
4 & 5
6.
Transformer Oil leak in Tx 1 Rusted cooling fan in Tx - 1
Oil on the top of tapchanger oil filter system in Tx 1
8/13/2019 Mudhaibi Grid Station
3/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 3of 14
Page 3 of 14
7 & 8
9 &10
Fire fighting system paint removed in Tx
1 Proper padlocks should be use in Tx - 1
Transformer climbing lader is not locked in Tx - 1 Broken cable clids in Earthing TFR1
8/13/2019 Mudhaibi Grid Station
4/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 4of 14
Page 4 of 14
11&12
13.
Temporary sealing of cable box in Earthing TFR 1 Rusted pad locks in Earthing TFR 1
Oil leak in Earthing TFR 1
8/13/2019 Mudhaibi Grid Station
5/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 5of 14
Page 5 of 14
14&15
16.
Control Cable dressing is not proper in EAT 1 Rusted Handle of NER 1
Rusted body of NER 1
8/13/2019 Mudhaibi Grid Station
6/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 6of 14
Page 6 of 14
17.
18&19
Bird nest on Circuit Breaker
Damage Tx1 Oil drainage pump switch Damage Gland Shrouds
8/13/2019 Mudhaibi Grid Station
7/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 7of 14
Page 7 of 14
20.
21.
Damage Cable Gland Shrouds
Damage Cable Gland Shrouds
8/13/2019 Mudhaibi Grid Station
8/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 8of 14
Page 8 of 14
22&23
24.
Bird nest in the centre of busbar Damage earth pit
Damage Cable Gland Shrouds Damage Cable Gland Shrouds
8/13/2019 Mudhaibi Grid Station
9/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 9of 14
Page 9 of 14
25.
26.
Damage Cable Gland Scroud
Oil leak in CT ( PhaseB )
8/13/2019 Mudhaibi Grid Station
10/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 10of 14
Page 10 of 14
27.
28&29
Rusted transformer cooling fans in Tx - 2
Damage gland scroud at MK box in Tx - 2 Old breathers in Tx - 2
8/13/2019 Mudhaibi Grid Station
11/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 11of 14
Page 11 of 14
30&31
32&33
Cable cleats missing in Tx2 Paint removed in EAT- 2
Temporary seald Cable box in EAT2 Rusted body in NER2
8/13/2019 Mudhaibi Grid Station
12/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 12of 14
Page 12 of 14
34.
35&36
Missing foundation in fire
Broken Earth pit Broken wall foundation
8/13/2019 Mudhaibi Grid Station
13/14
Visual Inspection Report (RAY)Region: Sharqyia
Location: Mudhaibi Grid station
Ref. OETC/2013
March 2013
Page 13of 14
Page 13 of 14
37.
Faded Phase plates Faded Phase plate