Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Module 5
Lighting Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
ContentsContents
Determining Average Illuminance
Average Illuminance Equation
The Lumen Method
Determining the Illuminance at a Point-Direct Component (Point-by-Point Method)
Computer-Aided Lighting Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Determining Average IlluminanceDetermining Average Illuminance
The standard lumen method formula is also used to calculate average illuminance levels when the Coefficient of Utilization (CU’s) are taken from a utilization curve.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Average Illuminance EquationAverage Illuminance Equation
Φ(TOTAL) x CU x LLF
Awp
Ewp
General equation for illuminance in space
Ewp = average maintained illuminance on the work plane
Φ(TOTAL) = total system lamp lumen output
CU = coefficient of utilization
LLF = light loss factor
Awp = area of the work plane
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
The Lumen MethodThe Lumen Method
Means of determining the average workplane illuminance within a space with a given number of luminaires
ComponentsTotal system lamp lumen output
Coefficient of utilization
Loss factor determination
Calculated illuminance
Spacing criteria
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Total System Lamp OutputTotal System Lamp Output
Lamp lumen output is the total initial luminous flux that the lamps emit as specified by the manufacturer.
Example 1: In an office space 3m x 4.6m with a 2.6m ceiling height, there are 2 recessed fluorescent luminaires. Each luminaire has three (3) 32W 48” T8 fluorescent lamps. Manufacturer’s data shows that the initial lumen output of the lamp is 2900 lumens. What is the total lamp lumen output Φ(TOTAL)?
Φ(TOTAL) = 2 luminaires x 3 lamps/luminaire x 2900 lumens/lamp
= 17,400 lumens
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Coefficient of Utilization (CU)Coefficient of Utilization (CU)
Factors influencing coefficient of utilization:
The efficiency of the luminaire
The luminaire distribution
The geometry of the space
The reflectances of the room surface
Each luminaire has its own CU table specific to that luminaire’s light distribution and efficiency. CU values are listed in tables for different room geometries and room surface reflectances.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Coefficients of Utilization (CU)Coefficients of Utilization (CU)
Coefficient of utilization is based on room cavity ratio (RCR)RCR is five (5) times the ratio of total vertical surface area to total horizontal surface area within the room cavity, and therefore indicates the relative space proportions.
Where, hRC = Room cavity height L = Length of the room W = Width of the room
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Coefficients of Utilization (CU)
Cavity ratios :Ceiling cavity ratio – is the space between the ceiling and luminaire plane computed using the equation below in relation to room cavity ratio:
Floor cavity ratio – is the space between the workplane and the floor computed using the equation below in relation to room cavity ratio:
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Coefficients of Utilization (CU)Coefficients of Utilization (CU)
Cross section of a room showing room cavities.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Coefficients of Utilization (CU)For a given room, the cavity ratios are in direct proportion to their respective cavity heights. For the case where the luminaires are mounted on the surface of the ceiling or are recessed into the ceiling, the ceiling cavity ratio is zero.
Since the coefficient of utilization is based on the room cavity ratio, it is necessary to treat this cavity as if there were a ceiling surface at the luminaire plane and a floor surface at the workplane level.
It is necessary to convert the actual ceiling reflectance into an effective ceiling cavity reflectance (pCC) and the actual floor reflectance must be converted to an effective floor cavity reflectance (pFC).
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
CU DeterminationCU DeterminationUsing Example 1 above, the following steps should be followed in calculating the coefficient of utilization.
Step 1. Determine the room cavity ratio using the equation below
Room cavity height (hRC) = Luminaire height – Workplane height
Assuming a workplane height of 0.76m (typical desk height)
hRC = 2. 59 m – 0.76m
= 1.83m
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
CU DeterminationCU DeterminationIn this example, the luminaires are recessed in the ceiling so the luminaire height is the as the ceiling height. Computing the room cavity ratio, we have:
RCR = 5 x Room cavity height (Length + Width)
Length x Width
RCR = 5 x 1.83m (3.05m + 4.57m)
3.05m x 4.57m
RCR = 5
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
CU DeterminationCU DeterminationStep 2. Since the Lumen Method considers what occurs only within the room cavity, the ceiling and floor cavities are replaced with their effective reflectances.
To find the effective reflectance of a floor or ceiling cavity, find the floor cavity ratio and ceiling cavity ratio using the equations below
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
CU DeterminationCU Determination
Step 3. Find the effective cavity reflectances using cavity surface reflectances. The surface that is opposite the opening to the cavity is called the base cavity. The base reflectance, the wall reflectances, and the cavity ratio determine the effective cavity reflectance. Using the IESNA Lighting Handbook, look for the cavity reflectances and cavity ratios.
For the ceiling cavity, the base reflectance is the actual ceiling surface reflectance while the floor cavity, the base reflectance is the actual floor surface reflectance.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
CU DeterminationCU Determination
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
CU DeterminationCU Determination
Step 4. Once all room cavity reflectances and the room cavity ratio are known, the CU value can be determined by selecting the appropriate value from the luminaire’s CU table.
Continuing with Example 1, the following assumptions are made after consulting the IES Lighting Handbook Table on Effective Reflectances:
Effective Ceiling Cavity Reflectance, CC = 0.70
Wall Reflectance, W = 0.50
Effective Floor Cavity Reflectance, FC = 0.20
RCR = 5 (calculated in Step 1)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
CU DeterminationCU Determination
CU = 0.50, which means that 50% of the lumens given off by the lamps reach the workplane and the other 50% are absorbed by the luminaire or the room surfaces and never reach the workplane.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Coefficients of Utilization for Some LuminaireCoefficients of Utilization for Some Luminaire
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Light Loss Factor
Two types of Light Loss Factor (LLF)Recoverable
Non-recoverable
Total Light Loss Factor (LLF) is the product of the individual light loss factors, recoverable and non-recoverable
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Light Loss FactorLight Loss Factor
Recoverable LLFLamp Lumen Depreciation (LLD)
Lamp Burnout Factor (LBO)
Luminaire Dirt Depreciation Factor (LDD)
Room Surface Dirt Depreciation Factor (RSDD)
Area of workplane (AWP)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Lamp Lumen DepreciationLamp Lumen Depreciation
The lamp lumen depreciation factor is the fraction of initial lumens at a specific time during the life of the lamp
Lamp lumen depreciation comes from aging and dirt accumulation on lamps, reflectors, lenses and room surfaces.
Most lighting designs base calculations on “maintained” as opposed to “initial” lamp lumens
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Lamp Burnout FactorLamp Burnout Factor
If lamps are not replaced immediately after burnout, a lamp burnout factor should be applied to any analysis of the system.
Unreplaced burned-out lamps will vary in quantity, depending on the kind of lamps and the relamping program used.
This factor is simply the ratio of the number of lamps that would be burning o the total number of lamps in the system.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Room Surface Dirt Depreciation
Room Surface Dirt Depreciation Factor (RSDD) is influenced by:
The amount of dirt in the environment
The room cavity ratio (proportions of the room)
Type of lighting equipment used
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Room Surface Dirt DepreciationRoom Surface Dirt Depreciation
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminaire Dirt Depreciation
Luminaire Dirt Depreciation Factor (LDD) depends on three (3) aspects of the situation:
The amount and type of dirt in the environment (a clean office environment compared to a dirty manufacturing facility)
The type of luminaire used
The expected cleaning cycle for the equipment
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminaire Dirt DepreciationLuminaire Dirt Depreciation
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Area of WorkplaneArea of Workplane
Is the area of the entire workplane, which is typically the same as the floor area
Illuminance will be greatest near the center of the room and slightly less toward the walls for a given uniform layout of luminaires
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Light Loss FactorLight Loss Factor
Non-Recoverable LLFLuminaire Ambient Temperature Factor
Heat Extraction Thermal Factor
Voltage to Luminaire Factor
Ballast Factor
Ballast Lamp Photometer Factor
Equipment operating Factor
Lamp Position (Tilt) Factor
Luminaire Surface Depreciation Factor
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminaire Ambient TemperatureLuminaire Ambient Temperature
Variations in temperature, above those normally encountered in interiors, have little effect on the output of incandescent and high intensity discharge (HID) lamps, but can have a significant effect on light output of fluorescent lamps
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Heat Extraction Thermal FactorHeat Extraction Thermal Factor
Heat extraction factor is the fractional lumen loss or gain due to airflow
Airflow has an effect on lamp temperature and lamp lumens especially those air handling fluorescent luminaires which are integrated with the HVAC system as a means of introducing or removing air from the room
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Voltage to Luminaire FactorVoltage to Luminaire Factor
High or low voltage at the luminaire will affect the lumen output of lamps
High voltage condition will increase the lumen output of lamps over their rated output
Low voltage condition will reduce the lumen output
The rate of change of lumen output with a voltage change varies with each light source, but has the greatest effect on incandescent lamps
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Ballast FactorBallast FactorBallast used for a specific application is usually different from the ballast used to determine the rated lumen output for a lamp
Ballast factor corrects this difference to maintain the arc within the lamp
Ballast factor is the ratio of the lamp lumens generated on commercial ballasts to those generated on the test quality ballasts . The ballast factor for good quality fluorescent ballast is nominally is 0.95while electronic ballasts can have ballast factors ranging from 0.70 to 1.28
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Ballast Lamp Photometer FactorBallast Lamp Photometer Factor
Ballast Lamp Photometer Factor adjusts the lumen output when a different lamp ballast combination is used other than the manufacturer’s set-up
Temperature effects within the luminaire may cause the lamp to operate at less than the rated output and should be considered in the determination of the luminaire’s coefficient of utilization
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Equipment Operating FactorEquipment Operating Factor
Effects on the lumen output of lamps caused by the ballast, the lamp operating position and the effect of power reflected from the luminaire back onto the lamp are collectively incorporated into the equipment operating factor
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Lamp Position FactorLamp Position Factor
Lumen output is sensitive to the lamp orientation especially for high intensity discharge (HID) lamps when they are tilted from their rated horizontal or vertical position
Lamp position factor adjusts the lumen output and is defined as the ratio of luminous flux in the given operating position to that in the test position
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminaire Surface DepreciationLuminaire Surface Depreciation
Luminaire surface depreciation results from adverse changes in metal, paint and plastic components that result in permanently reduced light output
Luminaire surface depreciation factor adjusts light output to original reflectance
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Loss Factor DeterminationLoss Factor DeterminationExample 2. LLF Determination
Detailed description of the determination of the light loss factors can be found in the IESNA Lighting Handbook. The product of the recoverable factors and the non-recoverable factors will give us the total light loss factor.
Recoverable Factors
Lamp Lumen Depreciation (LDD) 0.90
Lamp Burnout Factor (LBO) 1.00
Luminaire Dirt Depreciation Factor (LDD) 0.94
Room Surface Dirt Depreciation Factor (RSDD) 0.96
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Loss Factor DeterminationLoss Factor Determination
Nonrecoverable Factors
Ballast Factor 0.93
Other Non Recoverable Factors 1.00
LLFTOTAL = Recoverable Factors x Nonrecoverable Factors
LLFTOTAL = 0.90 x 1.00 x 0.94 x 0.96 x 0.93 x 1.00
LLFTOTAL = 0.75
Total Light Loss Factor (LLF) is 0.75, which means that 25% (100%-75%) of the luminous flux that might otherwise reach the workplane is lost due to ballast factor, dirty luminaires, room surfaces, and aged lamps.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Calculated IlluminanceCalculated Illuminance
Φ(TOTAL) x CU x LLF
Awp
Ewp
At this point it is possible to calculate the illuminance on the workplane:
Ewp = average maintained illuminance on the work plane
Φ(TOTAL) = total system lamp lumen output
CU = coefficient of utilization
LLF = light loss factor
Awp = area of the work plane
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Calculated IlluminanceSubstituting all the computed values in Example 1and using the equation for average illuminance on the workplane, we have:
EWP = 17,400 lm x 0.50 x 0.75
3.05m x 4.57m
= 468 lm/m2 or 486 lux (Maintained)
The average initial illuminance on the workplane can be determined by substituting only the non-recoverable light loss factors for the total light loss factor.
EWP = 17,400 lm x 0.50 x 0.0.93
3.05m x 4.57m
= 581 lm/m2 or 581 lux (Initial)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Calculated IlluminanceCalculated Illuminance
An average maintained illuminance of 468 lumens per square meter will strike the area covered by the workplane in a completely empty space
Some points on the workplane will have an illuminance higher than 468 while others will have an illuminance lower than this value
During first time that this system will be turned on, wherein the lamps are new and the surfaces are clean, the average initial illuminance will be greater than the maintained value, which is computed as 582 lumens per square meter (lux)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Calculated IlluminanceBy rearranging the Lumen Method equation, it is possible to find the number of luminaires required to meet a specific average illuminance level:
(lumens/lamp) x (lamps/luminaire) x (no. of luminaires)x CU x LLFTOTAL
EWP = AWP
AWP x EWP
No. of = luminaires (lumens/lamp) x (lamps/luminaires)
x CU x LLFTOTAL
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Calculated IlluminanceCalculated IlluminanceExample 2. Find the number of luminaires needed in a room given the following:
Room dimensions: 9.15m by 9.15m by 3.5m
Target Illuminance: 300 lux average maintained
Working Plane Height: 0.76m
Luminaire: Recessed round
Lamp: 70 watt metal halide, 5600 lumen initial output
Reflectances (): Ceiling cavity 0.70
Walls 0.30
Floor Cavity 0.20
Assume LLFTOTAL = 0.75
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Calculated IlluminanceCalculated IlluminanceStep 1. Calculate RCR
Using the equation for RCR, we get 3 as the answer.
Step 2. Determine Cavity ratios for ceiling and floor
Step 3. Obtain Effective Ceiling Cavity Reflectance (CC) using Tables in CU determination for metal halide lamps
Step 4. Obtain Effective Floor Cavity Reflectance (FC) using Tables in CU determination for metal halide lamps
Step 5. Obtain Coefficient of Utilization (CU) from Manufacturer’s Data
The CU based on calculated value of RCR and the given reflectances, we get 0.55 as the answer.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Calculated IlluminanceCalculated IlluminanceUsing the equation below, and substituting all the known values:
Number of luminaires = AWP x EWP
lumens/lamp x lamps/luminaires x CU x LLFTOTAL
Number of luminaires = 9.15m by 9.15m by 3.5m x 300 lux
5600 lumen x 1 x 0.55 x 0.75
Number of luminaires = 10.9
In this example, 12 fixtures can be spaced uniformly in a 3 by 4 pattern. Although 12 is more than the calculated value of 10.9 fixtures, results within a 10% margin is generally acceptable for meeting this target criterion
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Spacing CriteriaSpacing Criteria
Spacing Criteria is the maximum ratio of spacing to mounting height of the luminaire above the workplane that provides reasonable uniformity of illumination within the space
Spacing ratios for specific luminaires are given in the data sheets published by each manufacturer. This number, usually between 0.5 to 1.5, when multiplied with the mounting height, gives the maximum distance that the luminaires maybe separated and provide uniform illuminance on the workplane
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Spacing CriteriaSpacing CriteriaFor luminaires using essentially point sources of light, such as incandescent or HID lamps, the number of luminaires per row should be in proportion to the width-to-length ratio of the room
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Spacing CriteriaSpacing Criteria For fluorescent luminaires, it is necessary to first establish the
maximum number that can be installed in one row. the maximum number is calculated by subtracting at least 0.3 meter from the room length and then dividing by the length of the luminaire.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Spacing CriteriaSpacing Criteria
The exact spacing between rows is calculated by dividing the room width by the number of rows
Spacing between luminaires in each row is calculated by dividing the room length by the number of luminaires per row.
spacing between the outer luminaires and the adjacent wall is one-half of the luminaire spacing
If desks or other work areas are to be located alongside the walls, then the wall-to-luminaires spacing should be reduced to one-third of the luminaire spacing
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Spacing CriteriaSpacing Criteria
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Illuminance at a Point-Direct ComponentIlluminance at a Point-Direct Component
Examples:What is the illuminance on a wall display from a spotlight aimed at the display?
How much light is striking a point on the façade of a building or in a parking lot from a floodlight?
Factors to considerLuminous intensity
Distance
Orientation of the surface
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminous IntensityLuminous Intensity
I
w
dw
Luminous Flux in a certain direction, radiated per unit of solid angle
Unit : Candela
Symbol : II = Luminous flux
Solid Angle=
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminous IntensityLuminous Intensity
Rotational symmetrical
Light distribution same in all planes
Usually Circular or ‘Bowl shaped’ luminaire
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminous IntensityLuminous Intensity
Planar symmetrical
Luminaire distribution is confined to two vertical planes separately
Typical distribution for Fluorescent Lamp luminaires and Road Lighting
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Luminous IntensityLuminous Intensity
Asymmetrical
Asymmetry present in one of the Planes of measurement.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
DistanceDistance
Distance between a surface and the source affects the illuminance (luminous flux per unit of area) striking that surface
Surface of a given area that is closer to the source captures a larger portion of the flux in the cone than a surface of the same given area that is further away
Considering the luminous intensity as the luminous flux (lumens) leaving a source in a cone traveling in a specific direction, as the area increases the iluminance decreases while the luminous flux remains the same
Inverse Square Law states that the cross-sectional area of the cone increases with the square of the distance from the source. Therefore, the illuminance on this surface varies inversely with the square of the distance from the source
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
DistanceDistance
PA
w
Light Source
Solid Angle
Plane
Distance
d
E = I/ d2
I
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
DistanceDistance
Inverse Square Law
E = I/ d2
Where:
E = Illuminance on the surface
I = Luminous intensity of the source in the direction
of the surface
d = Distance from the source to the surface
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Orientation of the SurfaceOrientation of the Surface
Surface orientation is included in the Inverse Square Law by adding a cos term:
E = I/ d2 cos
is the angle between the light ray coming from the source to the point, and a line that is perpendicular (normal) to the plane or surface on which the illuminance is being measured or calculated
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Orientation of the SurfaceOrientation of the Surface
P
Light Source
Plane
Distance, dCosine LawCosine Law
IE = I / d2 cos E = I / d2 cos
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Illuminance at a Point-Direct ComponentIlluminance at a Point-Direct Component
Example 1. This example will consider the illuminance at a single point on a horizontal surface from a single luminaire straight down. An assumed LLF of 0.85 will be used.
D = 2.13 m
= 15°
LLF = 0.85
I = 2200 candelas
The luminous intensity (I) is determined using the photometric data for the specific luminaire used and the angular relationship between the luminaire aiming direction and the direction from the luminaire to the calculation point.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Illuminance at a Point-Direct ComponentIlluminance at a Point-Direct Component
Using the equation;
E = I/ d2 x cos x LLFTOTAL
E = 2200 cd x cos 15° x 0.85
2.13 m2
E = 398 lux (maintained)
This tells us that 398 lux will strike the point in question directly from the luminaire and no reflected light is calculated. The answer is a maintained illuminance level since a light loss factor of 0.85 was included to account for the loss of light over time due to reduced lumen output of the lamp and dirt on the luminaire surfaces.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Illuminance at a Point-Direct ComponentIlluminance at a Point-Direct Component
Example 2. This example will consider the illuminance at a single point on a horizontal surface from two luminaires aimed straight down. An assumed LLF of 0.85 will be used and Luminaire #1 is the same in Example 1.
D1 = 2.13m 1 = 15°
D2 = 2.29m 2 = 25°
1 = 15° I1 = 2200 cd
2 = 25° I2 = 2000 cd
E1 = 398 lux (from previous calculation)
E2 = 291 lux (from calculations)
ETOTAL = E1 + E2 = 689 lux
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Illuminance at a Point-Direct ComponentIlluminance at a Point-Direct Component
Example 3. This example will consider the illuminance at multiple points on a vertical surface from a luminaire aimed at the surface. An assumed LLF of 0.85 will be used.
Table 1. Components of Example 3
The luminaire is now aimed at the vertical surface so is no longer measured from straight down, and and are no longer equal. Illuminance is calculated using the same equation as the prior examples.
Point Distance, m C C I LLF Emaintained
1 1.74 45 0 2300 0.85 463 lux
2 1.37 27 18 2225 0.85 893 lux
3 2.29 56 11 2100 0.85 194 lux
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Illuminance at a Point-Direct Component
In Table 1, illuminance at point 2 is greater than at point 1 and illuminance at point 3 is the least. This is because the distance at point 2 is less than point 1 and the angle theta ( ) at point 2 is less than at point 1, despite the fact that the intensity in that direction is less.
Similar reasoning can be used with regard to point 3. These two factors cause the illuminance at point 2 to be greater than the illuminance at point 3.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
The calculations presented using various tables and figures are only meant to give the user of this module a general overview of the design of lighting system, showing individual steps from the selection of the recommended luminance level, to the design of lighting layout.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsSample Calculation 1:
The room to be lighted is as follows:
Type of building : Commercial
Area/activity : Drafting/tracing paper, low contrast
Average age of worker : 35 years
Demand for speed and/or accuracy : Important
Task background reflectance : 75%
Size of room : 10.0 by 13.25 meters; 2.91 m ceiling
Height of work plane : 0.91 m
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Reflectance factors : Ceiling 80%, walls 50%, and floor 30%
Luminaire type : Type 2, IES Lighting Handbook Table ; 300 mm
wide with two lamps
Lamps : 430 mA, 40 W, 1200 mm, warm white, rapid start tubular
fluorescent lamps
Atmosphere : Clean
Interval between cleaning : 12 months
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsSolution:
Step 1: Determine the recommended illuminance level:
From Illuminance Table (IES Lighting Handbook) , the illuminance category is F.
From the IES Lighting Handbook Table, the recommended level is 1000 lux
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 2: Draw a cross section of the room and determine cavity
heights. Note there is no ceiling cavity.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 3: Calculate the cavity ratios using Equations and indicate dimensions.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 4: Determine the effective floor cavity reflectance (pFC) from
IES Lighting Handbook Table. Note that the effective ceiling cavity reflectance is the same as the actual ceiling reflectance.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 5: Determine the coefficient of utilization:
It is necessary to interpolate for RCR = 1.75
For luminaire 2, ñCC= 80% and ñW = 50%
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
30% 1.070 (from above)
28% (interpolate) 1.056
20% 1.00
- Multiply by factor 0.9 as per note on IES Lighting Handbook Table for luminaire 2, 300 mm wide using two lamps.
Final Coefficient of Utilization
(CU) = 0.61 x 1.056 x 0.9 = 0.58
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 6: Calculate the light loss factor (LLF):
- Ballast factor = 0.95
- LLD from IES Lighting Handbook Table is 84% (use 0.84)
- From IES Lighting Handbook Table, luminaire 2 is category V.
- LDD is 0.88
- RSDD: the light output is all down (direct distribution) the luminaire is direct. From the graph in IES Lighting Handbook Table , for a clean atmosphere at 12 months, the percent expected dirt depreciation is 12%(use10%) and RSDD is 0.98.
LLF = 0.95 x 0.84 x 0.88 x 0.98 = 0.69 (two figure accuracy is acceptable)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 7: Calculate the total initial lamp lumens (TILL) using the
equation below:
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 8: Calculate the required number of luminaires using
equation below. From IES Lighting Handbook Table, the initial lumens are 3175 and there are two lamps per luminaire.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 9: Select a practical layout for the luminaire:
- Assume continuous rows are required
- Calculate the maximum number per row lengthwise in the room as in figure below for 1200-mm long luminaires.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
- Number of rows required is 52/10 = 5
- Select 5 rows of 10 = 50
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 10: Calculate the luminaire spacing using the figure below:
Sw = 10/5 = 2.0 m
Total length of each row = 10 x 1.2 = 12.0 m
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 11: Check the maximum spacing allowed between rows:
- From the IES Lighting Handbook Table, for luminaire 2, SC is 1.4 for crosswise spacing.
- Maximum spacing = 1.4 x hRC = 1.4 x 2.0 = 2.8 m
- 2.0 m is within the limits
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 12: Draw plan of the room and indicate the locations of
luminaires
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 13: Calculate the actual minimum maintained lighting level:
(within 4% of target value)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 14: Calculate the unit power density (UPD); From the IES Lighting Handbook table, the power input to the ballast for each luminaire (two 430 mA, 1200 mm lamps) is 95 watts.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
The unit power density (UPD) of 35.85 W/m2 (3.33 watts per square foot) is high. Before the advent of the energy shortage, this value was accepted as normal. Today’s practices, however dictate that the lighting load be kept as low as possible by using energy-saving lamps and ballast.
In this example, the designer should start over with F32T8 or F36T8 lamps operated with electronic ballasts and go through the calculations again to reduce the UPD.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Sample Calculation 2. Illustrations in calculating illumination levels (Lux) on certain lighting layout configurations:
Illumination of a conference room with OSRAM DULUX CARRÉ EL/D
2 x 24 W, with two DULUX L 24 W compact fluorescent lamps.
Room dimensions:
L = 15.00 m (length)
W = 8.00 m (width)
H = 3.40 m (ceiling-to-floor height)
h = 2.55 m (luminaire-to-work plane height)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsRequired quality of light:
Conference room: Light color ww or nw, Ra group 2A
Illuminance
E = 300 lux
Selected lamp:
2 DULUX L 24 W,
Light color LUMILUX Warm
(LF 31/830), Ra group 1B,
Luminous flux per lamp
ƒn= 1800 lumen
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Lighting design data is available in EULUMDAT format for most OSRAM luminaires. EULUMDAT data can be read by a wide range of programs for lighting design, including DIALUX (Version 2.0 and higher), RELUX, SPECTRAL ƒn LUMAGIC and RADEMACHER BELWIN.
The table below shows the room utilization factor for numerous combinations of room factors and reflectances (always assuming ideal dispersion).
The illuminance E required in a room of area L x W is achieved with n luminaires that have an efficiency çLB and with lamps with a luminous flux .
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsLuminaire efficiency and light distribution:
OSRAM DULUX CARRÉ EL/D 2 X 24 W
Light distribution A40.2 hLB = 0.58
Reflectances:
ñ Ceiling = 0.8
ñ Wall = 0.5
ñ Work surface = 0.3
Room utilization factor:
From the LiTG Table
For A40.2 (Table 1)
çR = 0.91
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsCalculation:
Result:
24 luminaires (ç is rounded up)
Recommended arrangement:
3 rows of 8 luminaries
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Sample Calculation 3. Given are the following :
Width = 15 m
Length = 100 m
Ceiling height = 3.5 m
Desired Illumination = 400 lux
Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
General Information:
Project Identification: Shopping Mall
Average maintained Illuminance: 400 lux or 400 lux /1lux x 10.76fc
= 37.17 fc
Lamp data: 26W TC-D (compact fluorescent lamp)
Lamp flux: 1800 lumen (as per manufacturer’s data)
Luminaire data:
Manufacturer: Zumtobel Staff (Fumaco)
Model No: Panos HG 2/26W TC-D VVG 200
ñw = 50%
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsSelection of Coefficient of Utilization:
Step 1: Fill in all information in sketch
L (Length) = 100 m
W (width) = 15 m
h (height) = 3.5 m
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 2: Determine Cavity Ratio
If from manufacturer’s data, CU table are given based on Room Cavity Ratio
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsIf from manufacturer's data, CU table are given based on Room Index
where:
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 3: Obtain effective cavity reflectance:
Ceiling : cc = 70%
Wall : w = 50%
Floor : fc = 20%
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 4: Obtain Coefficient of Utilization from manufacturer's data: Based on Fig. 9-28 of IESNA Handbook @ RCR 1.34 @ 70/50/20 reflectance
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
by interpolation CU @ 1.34:
RCR = 0.64
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 5: Compute for the Light Loss Factor (LLF)
LLF = Ballast factor x LLD x LDD x RSDD
Ballast Factor = 0.95
LLD (as per Figure 6.3 of IESNA Handbook) = Lumen maintenance (LLD) of compact fluorescent lamp double Biax (TC-D) is LLD =
85%
LDD under luminaire maintenance category I @ very clean room using Table 6-2 where maintenance frequency is every 12 months LDD = 0.96
Since luminaire is Direct downlight (as per Figure 6.4 of ELI handbook) % Room Surface Dirt Depreciation (RSDDF) is = 12%
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
by Interpolation, x = 0.976 (RSDD)
LLF = 0.95 x 0.85 x 0.96 x 0.976
LLF = 0.76
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 6: Compute for Initial Lamp Lumens (TILL) using equation below:
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 7: Calculate the required no. of luminaries using equation below. From table lamp manufacturer’s data, the initial lamp lumens of 26W TC-D lamp = 1,800 lumens
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 8: Select a practical lay out for the luminaire.
Spacing Criterion, SC = spacing distance/mounting height
As per Figure 9-28 of IESNA Handbook, for 8" open reflector using 2-26 CFL, SC = 1.5
Spacing distance = 1.5 x 3.5 m = 5.25 m
For this distance, 343 luminaires required to achieve 400 lux illumination cannot be placed for the given area.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsStep 9: Calculate Luminaire Spacing
Number of luminaires per row = (15m-5.25m)/5.25 = ~ 2
Number of luminaires per column = 343/2 = 172 luminaires x 5.25 m (spacing) = 903 m which exceeded 150 m.
Spacing criterion with this case is not applicable
Assuming spacing at end rows = 1 m
Number of luminaires/row = 15-2(1)/2 = 6.5 ~ 7 luminaires/row
Transverse spacing = 15-2(l)/6= 2.17 m
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Total length at each row = 6 x 2.17 m = 13 m
Space at end rows = 15-13/2 = 1 m
Number of luminaires/column = 343/7 = 49 luminaires/column
Longitudinal spacing = 100-2(1)/48 = 2.04 m
Total length at each column = 48 x 2.04 m = 98 m
Space at end rows = 100m-98m/2 = 1 m
Total luminaires = 7 x 49 = 343 luminaires
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 10: Draw plan of the room and indicate the locations of luminaries:
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 11: Calculate the actual minimum maintained lighting level:
E = 343/343 x 400 lux = 400 lux (within the target value)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Step 12: Calculate the power density (UPD) or connected load.
From manufacturers data, the power consumption of 2 x 26W TC-D lamp using conventional ballast = 90watts, in using electronic ballast = 70 watts
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Sample Calculation 4. Given the following data:
Width = 15 m
Length = 100 m
Ceiling height = 3.5 m
Desired Illumination = 400 lux
Type of Luminaire = 200mf Downlight w/ 26W TC-D Lamp
Luminaire : 8" Downlight with 70W Metal Halide Lamp
Lamp Flux : 6600 lumens (from manufacturer’s data) from Table (Figure 9-28) of IESNA handbook CU of metal halide downlight #10 @ 70/50/20 reflectance & RCR of 1.34
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Compute for the Light Loss Factor (LLF)
LLF = Ballast factor x LLD x LDD x RSDD
Ballast factor = 0.95
LLD of metal halide lamp = 0.85
LDD = 0.96
RSDDF = 0.976
LLF = 0.95 x 0.85 x 0.96 x 0.976
LLF = 0.76
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Compute for the the total initial lamp lumens (TILL)
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Compute for the number of luminaires
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Compute for the number of luminaires/row
Spacing Criterion = 1.2, does not apply since total of 179 luminaires cannot be placed on the given area.
Assuming spacing criterion = 0.9
Spacing distance between luminaries = MH x SC
Spacing (Longitudinal) = 3.5 m x 0.9 = 3.15
Number of luminaires/column = 100/3.15 = 31 luminaires
Total length of column = 31 x 3.15 = 97.65 m
Space at end of column = (100-97.65)/2 = 1.175 m
Total luminaires at each row = 179/31 = 5.7 ~ 6 luminaires
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample CalculationsTransverse spacing = 15m - 2(1.175m)/5
= 2.53 m
Total length of each row = 5 x 2.53m
= 12.65 m
Space at ends of row = (15 - 12.65)/2
= 1.175m
Total number of luminaries = 6 x 31
= 186 luminaires
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Draw plan of the room and indicate the locations of luminaries.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Calculate the actual maintained lighting level.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Sample CalculationsSample Calculations
Calculate the unit power density (connected load), from lamp manufacturer’s data, the power input of 70W metal halide lamp
= 81.5 Watts.
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
A wide variety of computer programs are available from lighting manufacturers to perform interior and exterior lighting calculations
Some programs are very simple, while others are complex and can even interface with computer-aided design
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
The following is a list of some of the software available but are not intended as a substitute for creating design but as an aid to the design process
General Electric PhilippinesA GE Lighting Application Design and Analysis (ALADAN)EUROPIC
OSRAM PhilippinesDiaLuxLight@work
Philips Lighting and ElectronicsCalcuLux
FUMACO IncorporatedRELUX 1 (Version 2.4 and 3.0)DiaLux
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramIndoor
Area
Road
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramIndoor
Calculux Indoor is a software tool which can help lighting designers select and evaluate lighting systems for office and industrial applications
Speed, ease of use and versatility are features of the package from Philips Lighting, which runs under the Microsoft Windows operating system
Calculux Indoor is part of the Philips Calculux line, covering indoor, area and road applications
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramWhat Calculux Indoor does
Calculux is a very flexible system which offers lighting designers a wide range of options:You can use the package to simulate real lighting situations and analyse different lighting installations until you find the solutions which suits your technical as well as your financial and aesthetic requirements bestCalculux not only uses luminaires from an extensive Philips database, but can also use photometric data which is stored in the Philips Phillum external formatSimple menus, logical dialogue boxes and a step by step approach help you to find the most efficient and cost-effective solutions for your lighting applications
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramWhat you can do with Calculux Indoor
Perform lighting calculations (including direct, indirect, total and average illuminance) within orthogonal rooms
Predict financial implications including energy, investment, lamp and maintenance costs for different luminaire arrangements
Select luminaires from an extensive Philips database or from specially formatted files for luminaires from other suppliers
Specify room dimensions, luminaire types, maintenance factors, interreflection accuracy, calculation grids and calculation
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramWhat you can do with Calculux Indoor
Compile reports displaying results in text and graphical formats
Support Switching modes and Light regulation factors
Support multiple languages
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
After installing the Calculux program in your PC, create an indoor lighting project by entering general project data, specify a room, perform a calculation and print a report
Example: General lighting for an office given the following room dimensions:
– Width 3.5 m– Length 5.6 – Height 2.7 m
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Select Project Luminaires from the Data menu
Select Indoor Lighting
Select the housing and light distributor of the luminaire– Housing TBS 600/135– Light Distributor C7-60
Select Arranged Luminaires from the Data menu
Click Add and select Room Block– In the UF Method box you can see that 3.5 luminaires
is sufficient for the requested illuminance level of 300 lux as general lighting
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Click Generate
– A Room Block arrangement of 4 luminaires will be generated
In the Definition box enter the name of the arrangement, enter:
– Name General
Define a (calculation) grid– Before a calculation can be performed a (calculation)
grid has to be defined– You can define your own grid, define a grid according
to a rule or use a preset grid
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Select Grids from the Data menuPerform a calculation
– Select Show Results from the Calculation menu– The calculation will be performed
Printing the report– Select Print Report from the File menu
Saving the project– Select Save from the File menu– Enter the file name– Click OK to save the project
Select Exit from the File menu to close the program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Sample printouts of the program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Sample printouts of the program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Sample printouts of the program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Sample printouts of the program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Sample printouts of the program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramSample Indoor Project
Sample printouts of the program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramArea
Calculux Area is a software tool which can help lighting designers select and evaluate lighting systems for sports fields, parking places, areas for general use, industrial applications and even road lighting calculations.Calculux Area is part of the Philips Calculux line, covering indoor, area and road applicationsSame principles and procedures apply as when using Calculux Indoor
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
PHILIPS Calculux ProgramRoad
Calculux Road is a software tool which can help lighting designers select and evaluate lighting systems for road lighting installations
Calculux Road is part of the Philips Calculux line, covering indoor, area and road applications
Same principles and procedures apply as when using Calculux Indoor and Calculux Area
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
OSRAM DiaLux Program
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
OSRAM DIALux ProgramCalculates the light exchange between luminaires and any other surfaces (direct lighting) and the light exchange between illuminated surfaces (indirect lighting)
Lighting from the sky (daylight) or direct sunlight can also be calculated
Calculation based on the radiosity method
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
Advanced Lighting ProgramsCapable of extreme accuracy in spaces of complex geometry
Most generate high quality semi-photorealistic images depicting interior and exterior lighting, including daylight
Radiosity
Ray-tracing programs
Some programs combine the computational speed of radiosity with the accuracy and realism of ray tracing
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
Advanced Lighting ProgramsRadiosity
Advanced radiosity programs have greater capabilities than basic programs, including:
– Analysis of rooms of any shape– Rooms can have sloping and complex ceilings– Realistic objects in space– Faster execution time– Much more realistic renderings
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
Advanced Lighting ProgramsRay-tracing programs
Much less common since it requires more computer time, data entry time and operator expertiseProduce superior visual results making them worth the time and expense for critical lighting designs and evaluationsCapable of demonstrating effects and issues caused by specular surfaces and are the only programs that render highlights, such as reflections in polished surfaces or glassDisplay lighted rooms in full color with accurate light patterns on room surfaces and partitions, and realistic shadows from realistic furniture
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
Advanced Lighting ProgramsSome programs, such as Lightscape, use radiosity for calculations then add a ray-tracing “layer” for realism of specular reflections and highlights
Module 5 – Lighting Calculations Philippine Efficient Lighting Market Transformation Project (PELMATP)
Computer-Aided Lighting Calculations
Other Lighting Software Programs
Top Related