8/13/2019 M&E spc 8 ER-R
1/4
Page 1 of 4 ER
ER: Page 1 of 4
8. ENGINE ROOM
8/13/2019 M&E spc 8 ER-R
2/4
Page 2 of 4 ER
ER: Page 2 of 4
8.1 Diesel Daily Fuel Tank 1 Unit
Arrangement : To store and supply diesel to the diesel generator sets.
Type : Elevated m.s tank with steel structure support.
Capacity : 2m3
Dimesion : 1500x1200x1200 mm(to suit)
Construction : The tank shall be of 4.5mm thick mild steel plates and
supported by angles with a service platform.
Accessories : a) Inlet, outlet and drain pipes.
b) Air Vents and manhole at top.
c) Plastic sight tube with steel tube as guard c/w isolating
cocks level indicators.
8.2 Diesel Skid Tank x 1 unit
Arrangement : To receive diesel delivery by diesel tanker.
Capacity : 10m3
Dimension : 1.9 dia x 3.6m S/L(to suit)
Construction : Mild Steel cylindrical Skip tank m/d 6mm MS plate
Accessories : a) Inlet, outlet and drain pipes.
b) Air Vents and manhole at top.
c) Plastic sight tube with steel tube as guard c/w isolating
cocks level indicators
d) Saddles m/o MS pipe
8.3 Diesel Skid Pump x 1 unit
Capacity of Pump : one unit of pump, 5m3/hr at 5m head
Make : KEW-KSSR 32 c /w 1.5 kw motor.or eq.
Material : CI/CI/SS
8/13/2019 M&E spc 8 ER-R
3/4
Page 3 of 4 ER
ER: Page 3 of 4
8.6 Turbine Water Tank 1 Unit
Arrangement: To receive turbine hot water
Capacity 1.5m3
Dimension 1.2x1.2x1.2m(to suit)
Construction: The tank shall be fabricated from 4.5mm thick MS
plate suitably stiffened by angles. Cover plate 3mm MS
Accessories: Vent, Inlet, outlets and overflow pipes.
8.6a Turbine water tank Pump 1 Unit
Accessories : a) 1 unit water pump of capacity 5 m3/hr At 15m head. .
KEW-KSSR40
b) Necessary inlet/outlet valves, overflow piping & fittings.
c) CI/CI/SS
Motor : 2.2 kW at 2900 rpm mounted on a rigid common base plate
8/13/2019 M&E spc 8 ER-R
4/4
Page 4 of 4 ER
ER: Page 4 of 4
8.7 Back Pressure Steam Receiver 1 Unit
Arrangement : A pressure vessel to receive exhaust steam from the steamturbine as well as to provide steam for mill process andsterilisation.
Type : Horizontal cylindrical type of 9.5mm thk x915mm diameter x
3,400mm long design & fabricated accordance with theregulation for unfired Vessel & using Design Code: ASME
SEC. VIII. DIV 2001 Edition.
Construction : The vessel shall be fabricated from 9.5mm thick ASTM516-
Gr70, for a working pressure of 3.8 bars & temperature 200C.
The vessel shall be insulated with 50mm thick 60 kg/m3
rockwool and covered with 22 SWG plain aluminums sheeting.
Saddles for support the receiver shall be one Fixed and the
other shall be free rollers to Take up expansion.
Ports to be provided as shown in the Drawing. Pipe nozzles for
all ports shall be Schedule 40 seamless steam pipes.
A set of 4.5mm thk chequered plate/4.5 t expanded metal sheet
Operating Platform c/w hand railing 38 dia and kicking angle
Plate and staircase at both ends shall be installed.
Accessories : 0-7 bars, 100 diameter SS body diaphragm gauge c/w fittings.
Local Authority Dept : Arrangement and submission to local authorities for approval
Top Related