Chapter 4
AC Machinery Fundamentals
Contents
Simple Loop in a uniform Magnetic Field
The Voltage Induced in a Simple Rotating Loop
Alternative way to express induced voltage
Torque Induced in a Current-Carrying Loop
The Rotating Magnetic Field
Induced Voltage in AC Machines
AC Machine Power Flows and Losses
Power Flow Diagram
Voltage Regulation and Speed Regulation
8/7/2019 machinery fundamentals
2/16
[email protected] Ch4 - Electrical Machines by Chapman Page 2 of 16
Simple Loop in a uniform Magnetic Field
Front view View of coil.
(a) Velocities and orientations of the sides of the loop with respect to the magnetic field.
(b) The direction of motion with respect to the magnetic field for side ab.
(c) The direction of motion with respect to the magnetic field for side cd.
(a) (b)
(c)
8/7/2019 machinery fundamentals
3/16
[email protected] Ch4 - Electrical Machines by Chapman Page 3 of 16
The Voltage Induced in a Simple Rotating Loop
eind = (v x B) l1. Segment ab: The velocity of the wire is tangential to the path of rotation, while the magnetic field B points to
the right, as shown in Figure 4-2 b. The quantity v x B points into the page, which is the same direction as seg-
ment ab. Therefore, induced voltage on this segment of the wire is eba = (v x B) l = vBl sin ab into the page
2. Segment bc: In the first half of this segment, the quantity v x B points into the page, and in the second half ofthis segment, the quantity v x B points out of the page. Since the length l is in the plane of the page, v x B is per-
pendicular to l for both portions of the segment. Therefore, the voltage in segment be will be zero: ecb = 0
3. Segment cd: The velocity of the wire is tangential to the path of rotation, while the magnetic field B points to
the right, as shown in Figure 4-2c. The quantityv x B points into the page, which is the same direction as segment
cd. Therefore, the induced voltage on this segment of the wire is
edc = (v x B) I = vBIsin cd out of the page
4. Segment da. Just as in segment bc, v x B is perpendicular to l. Therefore, the voltage in this segment will be
zero too: ead = 0
Total induced voltage on the loop eind is the sum of the voltages on each of its sides: vBl sin ab + vBl sin ad
Note that ab = 180 - cd and recalling the trigonometric identity sin = sin (180 -).
Therefore, the induced voltage becomes eind = 2vBL sin
The resulting voltage eind is shown as a function of time in Figure 4-3.
8/7/2019 machinery fundamentals
4/16
[email protected] Ch4 - Electrical Machines by Chapman Page 4 of 16
Alternative way to express induced voltage
= wtAlso, tangential velocity v of the edges of the loop can be expressed as
v = rw (4-7)
where ris the radius from axis of rotation out to the edge of the loop, and
w
is the angular velocity of the loop.Substituting these expressions into Eq. (4-6) gives
eind = 2rwBI sin wt(4-8)
Notice also that the area A of the loop is just equal to 2rl,
Therefore, eind = AB w sin wt (4-9)
Finally, note that the maximum flux through the loop occurs when the loop is
perpendicular to the magnetic flux density lines. This flux is just the product of
the loop's surface area and the flux density through the loop.
max = AB (4-10)Therefore, the final form of the voltage equation is
eind = maxw sin wt (4-11)
8/7/2019 machinery fundamentals
5/16
[email protected] Ch4 - Electrical Machines by Chapman Page 5 of 16
Torque Induced in a Current-Carrying Loop
Figure 4-5:
(a) Derivation of force and torque on segment ab.(b) Derivation of force and torque on segment bc.
(c) Derivation of force and torque on segment cd.
(d) Derivation of force and torque on segment da.
Figure 4-4:
A current-carrying loop in a uniform
magnetic field.
(a) Front view;
(b) view of coil
(a) (b)
ab = ilB.rSinab
cd= ilB.rSincd
8/7/2019 machinery fundamentals
6/16
[email protected] Ch4 - Electrical Machines by Chapman Page 6 of 16
cont
Force on each segment of the loop will be given by Equation (1-43),
F = i(l x B) (1-43)where i = magnitude of current in the segment
l = length of segment, with direction of l in direction of current flowB = magnetic flux density vector.
The torque on that segment will then be given by
T = (force applied) (perpendicular distance)
= (F) (r sin ) = rF sin (1-6)where is the angle between the vectorr and the vectorF. The direction of the
torque is clockwise if it would tend to cause a clockwise rotation and counter-
clockwise if it would tend to cause a counterclockwise rotation.
8/7/2019 machinery fundamentals
7/16
[email protected] Ch4 - Electrical Machines by Chapman Page 7 of 16
cont
Total induced torque on the loop ind is sum of the torques on each of its sidesind = rilB sin ab + rilB sin cdNote that ab = cd, so the induced torque becomes
ind = 2rilB sin (4-17)
The resulting torque ind is shown in Figure 4-6. Note that the torque is maxi-
mum when the plane of the loop is parallel to the magnetic field, and the torque
is zero when the plane of the loop is perpendicular to the magnetic field.
8/7/2019 machinery fundamentals
8/16
[email protected] Ch4 - Electrical Machines by Chapman Page 8 of 16
The Rotating Magnetic Field
If two magnetic fields are present, then a torque will be created which will tend to line up the
two magnetic fields.
If one magnetic field is produced by the stator of a machine and the other one is produced by
the rotor of the machine, then a torque will be induced in the rotor which will cause the rotor
to turn and align itself with the stator magnetic field.
The fundamental principle of ac machine operation is that if a 3-phase set of currents, each of
equal magnitude and differing in phase by 120, flows in a 3-phase winding, then it will pro-
duce a rotating magnetic field of constant magnitude.
FIGURE 4-8
(a) A simple 3-phase stator, Currents
in this stator are assumed positive if
they flow into the unprimed end and
out the primed end of the coils.The
magnetizing intensities produced by
each coil are also shown.
(b) The magnetizing intensity vector
Haa(t) produced by a current flowing
in coil aa'.
8/7/2019 machinery fundamentals
9/16
[email protected] Ch4 - Electrical Machines by Chapman Page 9 of 16
Concept of the rotating magnetic field
Since B =H
Coil currents
Magnetic field
Flux densities
Intensities
8/7/2019 machinery fundamentals
10/16
[email protected] Ch4 - Electrical Machines by Chapman Page 10 of 16
cont
8/7/2019 machinery fundamentals
11/16
[email protected] Ch4 - Electrical Machines by Chapman Page 11 of 16
cont
Although the direction of the magnetic field has changed, the magnitude is constant.
Magnetic field is maintaining a constant magnitude while rotating in a counterclockwise
direction.
If the current in any of two of the windings is reversed, the direction of rotation of the
magnetic field will be reversed
where fe = frequency of the field (current) in Hz (typically 60 Hz)
nm = mechanical speed of rotation in revs per minute
P = number of poles pairs
Relationship between Electrical frequency and speed of rotation of magnetic field
8/7/2019 machinery fundamentals
12/16
[email protected] Ch4 - Electrical Machines by Chapman Page 12 of 16
Magnetomotive Force and Flux Distribution On AC Machines
(a) AC machine with a cylindrical rotor.
(b) AC machine with a salient-pole rotor FIGURE 4-14
(b) The magnetomotive force distribu-
tion resulting from the winding, com-
pared to an ideal distribution.
8/7/2019 machinery fundamentals
13/16
[email protected] Ch4 - Electrical Machines by Chapman Page 13 of 16
Induced Voltage in AC Machines
8/7/2019 machinery fundamentals
14/16
[email protected] Ch4 - Electrical Machines by Chapman Page 14 of 16
AC Machine Power Flows and Losses
The efficiency of an ac machine is defined by
The losses that occur in ac machines can be divided into four categories:
1. Electrical or copper losses (I2R losses)
2. Core losses
3. Mechanical losses
4. Stray load losses
The mechanical power that is converted is given by:
8/7/2019 machinery fundamentals
15/16
[email protected] Ch4 - Electrical Machines by Chapman Page 15 of 16
Power Flow Diagram
(a) The power-flow diagram of a 3-phase ac generator.
(b) The power-flow diagram of a 3-phase ac motor.
8/7/2019 machinery fundamentals
16/16
[email protected] Ch4 - Electrical Machines by Chapman Page 16 of 16
Voltage Regulation and Speed Regulation
Voltage regulation(VR) is a measure of the ability of a generator to keep a
constant voltage at its terminals as load varies.
where Vnl is the no-load terminal voltage of the generator and
Vfl is the full-load terminal voltage of the generator
Speed regulation (SR) is a measure of the ability of a motor to keep a constant
shaft speed as load varies.
or
Top Related