Showrooms and Training Centers
Building Analysis Project – AENG321
Group members: Amira Abdel Rahman
Aya Fayez
Hadeer
Salma Samir
Sarah Mokhtar
To the attention of: Dr. Ahmed Sherif
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 2 of 74
Table of contents
Title page Table of contents Introduction Literature Review
A. Lecture Halls
B. Showrooms
Analyses
A. Local Showroom Case Study BMW Showroom, Cairo-Alexandria Road
B. International Showroom Case Study I Autostella Showroom, Thailand
C. International Showroom Case Study II BMW Showroom, Netherlands
D. Local Lecture Hall Case Study Mansour Hall, AUC campus Comparative Analysis Conclusion: Checklists of Optimum Designs Works Cited Appendices Appendix 1: Sections of BMW Showroom, Cairo-Alexandria Road Appendix 2: Construction phases of BMW Showroom, Cairo-Alexandria Road
1 2 3 4
12
27
35
42
53
63
65
67
69 70
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 3 of 74
Introduction:
The purpose of this report is to investigate the different aspects that should affect the
design of both a showroom and a lecture hall. Consequently, analyses of existing showrooms
and lecture halls were carried out while investigating both local and international cases.
Several design issues were discussed such as the site plan analysis, the plan analysis,
circulation, zoning, lighting, acoustics, landscape, ventilation, parking, security and safety,
structure and interior. Showroom case studies included the BMW Showroom on Cairo-
Alexandria Road, BMW Showroom in Netherlands and Autostella showroom in Bangkok. The
lecture hall case study considered was that of Mansour hall at the American University in Cairo.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 4 of 74
Literature Review: Lecture Hall A. General characteristics:
Location
1. The location of the lecture hall in the building should ensure the easy access and flow of students, faculty and equipment (“Lecture Hall Design”).
2. It should be isolated from possible noisy spaces such as dining facilities (“Lecture Hall Design, General Assignment and Yale and Classroom Design”).
3. It should be located within the lower floors of the buildings to make it easier for students to access it (“Lecture Hall Design and Guidelines for Yale”).
4. Direct air paths should be taken into account while choosing the location of the lecture hall (“Lecture Hall Design”).
5. The location of the lecture hall should be near the entrances of the main building in order to decrease the students’ travel through the building (“General Assignment”).
6. Restrooms should be located as close as possible to the lecture hall but with no common wall (“General Assignment”).
Entrances
1. The student traffic areas should be set away from the location of entrances (“Lecture Hall Design”). 2. Quick and efficient changeover between lecture halls could be achieved by providing few double-
swing doors with at least one near the rear of the theatre. This should allow for a maximum clearance time of 5 minutes (“Lecture Hall Design”). The possible organization of doors’ locations is shown below in figure 1.
Figure 1: Entrances to the lecture hall
(Design Requirements)
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 5 of 74
3. Doors should be recessed into the room, but it should swing into the hallway not to cause any kind of obstruction of traffic in the hallway (“Guidelines for Yale”).
4. One entrance should be in the front to allow for wheelchair access (“Large lecture”).
The following diagram shows the plan for a good 200 seat lecture hall in which nearly all the factors and characteristics of a good lecture hall is applied. Regarding the entrance, it is wide enough to allow the access of a large number of people at the same time. Regarding the disabled, there is a ramp that leads directly to the places where they are supposed to sit.
Figure 2: Good Example of a Lecture Hall
Materials:
Colors of walls and furnishing should be sui table for the eye to have the most comfortable vision and keep the
audience in the comfort zone. Front walls are the areas of highlight and
demonstration, a white color would be the best. As for side walls and furni ture they are preferred to be of darker color
and finally the back wall of bright color. That’s to have contrast between the i tems in the hall and for the eye not to mix them up. That also helps in improving the lighting of the hall.
Ceiling is preferred to be of a sound reflecting material , since in most cases
i t is being used to reflect sound, amplify i t and spread i t on the hall.
The side and the back walls should do the same job plus that they should be of a sound absorbing material as well , to prevent the sound produced from the activi ty in the hall to reach outside and harm others .
Reflecting material should be chosen such that the di fference between the original sound beam and i ts echo is less than 0.2 sec, so as that people won’t
feel the repetition of sound.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 6 of 74
Seating, Capacity
1. The number of expected occupants should be reflected in the size of the room (Lecture Hall Design). The amount of space that should be provided per student is on average 60x80cm=55x75cm, and for additional comfort is 70x65cm (Neufert).
2. Additional space should be provided that allows for audio-visual equipments, circulation space, etc… (“Lecture Hall Design”). The area needed per student including all spaces in the lecture hall is 0.60 meters squared (Neufert).
3. Lectures halls are generally spaces having sloping floor surface with tablet arm chairs (“Lecture Hall Design”).
4. An unobstructed view to the board, the screens and the lecturer should be present from all seats located in the lecture hall (“Lecture Hall Design and Classroom Design”).
5. The riser height is recommended to be in-between 6” and 12” while the riser depth should include the minimum row-to-row spacing in addition to around 8” to 12” (“Lecture Hall Design and Hall Planning”).
6. Arm chair tablets usually follow one of the following illustrated dimensions. However, it is recommended to use the oversized tablet for note taking and laptop use.
Figure 3: Arm Chair Tablets Dimensions
(Hall Planning) B. Space planning and layout:
Proportions and Physical Access
1. No columns should be included in the lecture hall (“Lecture Hall Design and Classroom Design”). 2. The size and proportions of the hall should take into account the flow of students within the room in
addition to the need for the lecturer to move around in the front part of the lecture hall ( “Lecture Hall Design”).
3. The location of all seats should be within a 90 degree viewing angle from the screen’s center, i.e. within 45 degrees from both sides of the perpendicular to the screen’s center (“General Assignment, Large Lecture and Guidelines for Yale”).
4. There are two types of possible learning spaces, “wide and shallow” shape and the most used in lecture halls being the “long and skinny” shape of the room. The “long and skinny” should be narrow enough to ensure that a 90 degree viewing angle to the front wall is present for all seats. On the other hand, narrow learning spaces decrease the student-lecturer interaction and may create visibility challenges (“General Assignment and Guidelines for Yale”).
5. The lecture hall’s slope should be lower than a one twelfth ratio (“Large lecture”) as shown in the diagram below.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 7 of 74
Figure 4: Maximum slope of lecture hall
C. Architectural and environmental standards:
Floors, Walls, Ceiling
1. Colors used for the finishes should be neutral and should suit the space (“Lecture Hall Design”).
2. Because of the use of projection screens in lecture halls, the ceiling height should be higher than the
standard 8 feet (“Lecture Hall Design and General Assignment”). A table 1 below shows the relation
between the distances to the last row to the ceiling heights of the lecture hall as shown below.
Table 1: Ceiling heights Distance to last row Rear of lecture hall Front of lecture hall
50 ft 10 ft 17 ft 75 ft 10 ft 22 ft
100 ft 10 ft 28 ft
(Yale) 3. To project the lecturer’s voice from the front to the rear of the lecture hall, the ceiling section over
the sending end should be inclined toward the students, and should be as well angled upward from the sending end (“Lecture Hall Design”). This is shown in the diagram below.
Figure 5: Section of a Lecture Hall/Bent Ceiling
(Neufert)
4. If moveable seats are used; corridors, cross aisles and rows should be covered or made from non-
slip surfaces (“General Assignment”).
5. The painted walls should be washable and resistant (“General Assignment”).
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 8 of 74
Furniture
1. Approximately 10% of the total number of tablet arm chairs should be made for left-handed
(“Lecture Hall Design, General Assignment and Large Lecture”).
2. Seat numbers should be visible in all fixed seats (“Lecture Hall Design”), and seat dimensions are
shown in the following diagram.
Figure 5: Dimensions of Seats
(E. Neufert and P. Neufert)
3. A lecture hall usually includes writing boards. However, as the size of the room increases, the use of
writing boards would not be useful because distant students might not be able to read (“Lecture Hall
Design”).
4. Windows are not required in a lecture hall. However, if present, they should be placed at the sides
of the room and effective control of natural lighting should be achieved through thick curtains for
example. A complete blackout should be possible to achieve (“Lecture Hall Design and General
Assignment”).
5. Lecture hall doors should be placed at the rear of the hall, must be noise-free and must control
sound (“General Assignment”).
6. Furniture item should suit a wide range of people, hence should be comfortable for use “from the
5th
percentile female (4’ 11” tall, 113 pounds) to the 95th
percentile male (6’2” tall, 246 pounds)”.
Accordingly, the required seat width is between 23” and 24” (“General Assignment”).
7. If tables are used within the lecture halls, their depth should be at least 18” (“General Assignment”).
8. The door leaf’s width should be not less than 36” and should include a vision panel, with a maximum
area of glass of 100 square inches (“Guidelines for Yale”).
Lighting
1. In the case of using projection screens, the lighting system should provide darkening while keeping
sufficient light for note taking (“Lecture Hall Design, General Assignment and Classroom Design”).
2. Lighting should be provided in a minimum of four zones: full lighting for general use (adequate for
reading), note taking lighting (should not shine on screens or on students’ eyes), controlled lighting
for writing boards and lighting highlighting lecturer’s area (“Guidelines for Yale”).
3. Lighting’s controls should be present at the room’s entrance and neat the lecturer’s area. Both
controls should not lock out each other (“Classroom Design”).
4. Natural lighting is not desirable in lecture halls, because most of the times it causes glaring which leads to decreasing the concentration level of the audience (“Guidelines for Yale”).
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 9 of 74
The following diagram shows an example of indirect light rays from one of the light sources to one of the audience.
Figure 6: Dimensions of Seats
5. “Generally, there certain things that come up when talking about lightening in lecture halls: a) Glare: direct glare definitely annoy the audience, and combating glare; because of the color of the
spot lights. b) Modeling: A case where a speaker is made to look grotesque due to the bad modeling. This may
be solved by adding luminaries which have the ability to direct light towards the speaker and not down on him.
Figure 7: Dimensions of Seats
c) Direct light on the board or the projecting screen is not recommended since it may cause blare and inaccurate sight” (“Classroom Design”)
Acoustics
1. Heavy curtains or roman blinds contribute to acoustic insulation by damping sound reflections in the space itself (“Lecture Hall Design”).
2. Room materials should provide the reflection of the sound from the front to the rear (General Assignment).
3. Walls should be treated to insulate from noise coming from adjacent corridors (“General Assignment and Classroom Design”)
4. Effective voice amplification should be considered and could be provided by audio speakers and wireless microphones (Large Lecture).
5. Sound isolation from adjacent classrooms and corridors (“Classroom Design”)
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 10 of 74
Electrical supplies and Technologies
1. The position of the projection screen should follow the following rules shown in figure 8 below:
i. The projection screen should not be placed further than six times the height of the screen
(Lecture Hall Design, Guidelines for Yale, Classroom Design and General Assignment).
ii. It should not be placed closer than two times the height of the screen (“Lecture Hall Design
and Large Lecture”).
iii. A 45 degree horizontal viewing angle should be provided for students starting from the
centerline of the screen (“Lecture Hall Design”).
iv. The screen’s base should be placed above 1.35 meters from the ground level (“Lecture Hall
Design”).
v. The vertical viewing angle should be limited to 15 degrees head tilt excursion over the
horizontal (“Lecture Hall Design”).
vi. The top of the screen should not rise more than 35 degrees from the students’ sight lines
(“Guidelines for Yale and Large Lecture”)
Figure 8: Positioning of the projection screen
2. The writing boards should be positioned with a sufficient distance from the screen so that the light
targeting the writing board would not be spilling on the screen (“Guidelines for Yale”). 3. The projection screen’s size should have a ratio of 1:4 (“Large Lecture”). 4. The lecturer’s consoles should be placed such that they do not obscure the students’ sight lines
(“Classroom Design”).
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 11 of 74
Ventilation
1. The climate of the lecture hall should be controlled in order to provide the students with an
appropriate environment that promotes learning (“Lecture Hall Design”).
2. Natural ventilation could be provided through the process of cross ventilation.
3. The AC should provide the lecture hall with similar temperatures at different places of the room.
Safety and Security
1. The design should take into account some aspects of safety in the Building Code requirements such
as distance from seats to escape routes, lighting of emergency exits, aisle widths, exit doors, etc…
(“Lecture Hall Design”).
2. For permanently installed multimedia equipment within lecture halls, a security system must be on,
keeping the room secured and monitoring the air flow, climate and use of windows (“Classroom
Design”).
Special planning issues for the disabled:
1. The entry doors should be on the same level as well as adjacent to the front row of seats for the disabled people (“Lecture Hall Design”).
2. For less than 800 seats, at least four wheelchair spaces should be provided (“Design requirements”). 3. Wheel chair seats should be placed in pairs and not entirely separated from the other ordinary seats
in order to promote interaction between all (“Design requirements”). 4. The passage that links the entrance to the seats should have a minimum width of 1500mm (Design
requirements). Some of the required dimensions for lecture halls for the disabled are shown in figure 9 below:
(Design requirements)
5. Sight lines for wheelchair seats should be similar to the normal ones. 6. Tablet arm chairs should contain a minimum of 5% that are ADA (Americans with Disabilities Act)
accessible (Large Lecture).
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 12 of 74
Literature Review: Showrooms Introduction: Car showrooms should be a Universal high space with special form having contemporary finishing and complicated structure/ glazing system. It should accommodate different zones with different levels to display cars in different categories and classes; the more expensive cars always have the prime and higher exposed locations. Other than cars, the main showroom should accommodate floating desks for sales persons, insurance companies’ representatives, bank auto loan officers in addition to a desk for vehicles registration officer. Showroom for branded cars always include display cabins for small gift items such as key chains, small car models, glass and crystal souvenirs, belts, T shirts, etc… that people can buy. Also car accessories display units are provided such as 4X4 bumpers, special lights, seat covers, floor mats, etc. Car Showrooms should be carefully illuminated, use of intensive white illumination is recommended at evening. Each showroom should have separate entrance doors for customers and vehicles. Usually having colorful showrooms should be avoided in order to leave the colors for the cars, since the target is to show and sell the car not the space. Demographics: The daytime and nighttime population within the determined trade area indicates the sales
potential that operate within the showroom (Wiley).
Pedestrian flows: the numbers and movement of people on the streets, in different parts of the centre at different times of the day and evening, who are available for businesses to attract into showrooms. To be effective this indicator should be monitored regularly as it is the relative values (rather than absolutes), which are important together with clear evidence of changes over time (“Retail Planning”).
Location
Easily accessible to at least one existing or shortly to be constructed major highway, preferably to two or more major highways. A location literally bordering on one or more major highways is desirable for its advertising impact on passing cars, but this is not necessary if suitable access roads exist between the highway and the site (Callender and Chiara).
Figure 10
Figure 11
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 13 of 74
Attractions supports the place by consisting of the range and diversity of shopping and other activities, which draws in customers and visitors (“Retail Planning”).
A healthy town centre should be a pleasant place to be in. It should be attractive in terms of environmental quality and urban design, safe, and it should have a distinct identity or image (“Retail Planning”).
For car showrooms, the ideal would be a wide, level, rectangular lot on the corner of a primary thoroughfare. If an interior lot must be used, it should have wide frontage for display purposes and sufficient depth for future expansion (Callender and Chiara).
Access:
If a site is not easy to enter and safe to leave it must have the potential to be made so (Wiley).
Successful showrooms need both to be accessible to the surrounding catchment area via a good road network and public transport facilities, and to encompass good local linkages between car parks, public transport stops and the various attractions within the centre (“Retail Planning”).
Visibility:
Car showrooms need to be located on highly visible sites with good access to main transport routes and an eye-catching frontage. Display of the car range is paramount and the layout and orientation of sites and display areas will have a major impact on sales (“Cost Model”).
Heavy traffic also prevents potential shoppers from easily seeing tenant signage and points of access
(Wiley).
The desire for the forecourts to be illuminated for as long as possible, especially relevant in
suburban locations (“Cost Model”).
For car showrooms, the showroom should be located in a position of unobstructed visibility-one
that will readily attract the attention of people passing by (Callender and Chiara).
Figure 12
Figure 13: Sample of a Car Showroom Access
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 14 of 74
If the building site is on a corner, the showroom should be on the corner facing both streets for
maximum visibility of its interior. On an inside lot the showroom should be projected in front of the
major portion of the facilities to increase visibility and exposure time (Callender and Chiara).
Additional new unit display, if desired, can be provided outside the showroom under a canopy or
roof extension, adjacent to the customer service reception area or through use of a landscaped
patio display area (Callender and Chiara).
Shape:
Adequate size and suitable shape to permit proper planning of the merchandising area and a proper number of parking spaces (Callender and Chiara).
The site should be regular in shape and unified, undivided by highways of dedicated streets. Very few successful centers exist on divided sites (Wiley).
A site with a regular shape- no acute angles, odd projections, or indentations- is most amenable to an efficient layout. If an irregularly shaped site is used, it still needs adequate frontage so that the center is visible from Thoroughfares (Wiley).
Figure 14
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 15 of 74
Shading Devices:
Additional new unit display, if desired, can be provided outside the showroom under a canopy or
roof extension, adjacent to the customer service reception area or through use of a landscaped
patio display area (Callender and Chiara).
These types of new unit display areas are relatively inexpensive to provide and can be very
effective. The minimum space guide for inside showroom display is 500 square feet per unit. Leave
at least 5 ft open around each car. This will allow space so that the customer may walk around and
open the hood, doors, and trunk freely. Allow as much extra space as possible around the display,
so that customers can stand back and get a good view of the car from all angles (Callender and
Chiara).
Parking Space:
The standard car parking space is 4.8m x 2.4m.
The minimum space for wheelchair and car is 4.8m x 3.6m.
The precise amount of car parking will be determined according to the specific characteristics of the showroom and its location.
Specific parking limitations should apply to the location of the showroom.
The parking place of the showroom should provide for maneuvering space to enable vehicles to exit the site in forward gear.
The parking space should also serve as a pedestrian access.
The parking area should provide 0.75 spaces per 100m2
site area plus 6 spaces per service bay. Topography:
The ideal site has minimal subsoil complications, neither solid rock nor a high water table, and a slope of less than 3 percent (Wiley).
Ground that is fairly level of gently sloping to the street is easily adaptable to showrooms (Wiley).
Noise:
In order to reduce noise we could have walls, solid fences, plantings of evergreens to buffer the showroom’s sound and illumination level (Wiley).
Figure 15
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 16 of 74
Security:
With the value of the stock on display, security is a major concern. Showrooms should have comprehensive access control, alarms and sophisticated Closed-circuit television (CCTV) (“Cost Model”).
Discreet physical security measures such as forecourt bollards and perimeter fencing are also
necessary to prevent unauthorized vehicle entry and exit, but must not interfere with customer
views of vehicles on display (“Cost Model”).
Design Concept:
“One of the significant challenges in the designing
large scale, multitenant, mixed used projects is the
difference in the goals undertaken by both
developers and architects to create a project that is
both unique and distinctive, as well as one that
complies with all the tied-and-true formulaic rules
of the industry.
Much of what makes a project distinctive lies in the
basic design concept or the main idea behind the
project. The designer has to search for a key idea or
story that will help him shape the design and
thereby give the project its own character.
If concept design is compelling and evocative
enough, it can inform most of the key decisions for
the project, from the smallest architectural details
to overall layout and leasing.
The architect has to begin by looking at the context
of the site as the starting point for your concept
design.
If a designer wants to create the quintessential
“there” of a place, it is best to start with what is unique about the site, its history, geography,
culture, scale, and so forth-its essence.
For instance, if a location is known for its brick architecture, try to make use of the material in the
project, which may be realized in a contemporary interpretation of a historic style.
Sometimes, there is no physical or historical feature of a site to use as the basic concept. Then it is
the best to create a sense of character.
These design concepts can be categorized by two types; formative and transformative:
Formative Design Concepts: They come from various sources of inspiration, for instance
nature is an important informing concept. Projects that are often sited in Greenfield
areas or very recent habitation and development follow formative design concepts.
Transformative Design Concepts: Retail and mixed-used architecture reaches its highest
and best purpose when used to transform dilapidated underused or economically
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 17 of 74
depressed urban areas. Architects look forward to working on these types of projects
because they can reanimate a vacant and derelict downtown into a vital center of social
and commercial interaction. With a city as a context, there is usually a wealth of
inspiration for a transformative design concept” (Wiley).
Basic floor planning Guidelines:
Six basics plans:
Curved Plan: The curved theme can be emphasized with walls, ceiling, and corners. To complete the look, specify circular floor fixtures (Wiley).
Varied Plan: The varied plan is highly functional. Typical of the varied plan is a "below" effect, a tapering of the space that focuses on a special purpose area in the rear (Wiley).
Straight plan: The straight plan is economical and can be adapted to any type of showroom. The straight plan lends itself well to pulling customers to the back of the showroom, to define transition from one section of the showroom to another; displays can be placed to help lead shoppers. For a change of pace. Floor levels can be elevated (Wiley).
Pathway plan: Applicable to virtually any type of showroom, the pathway plan is particularly suited to showrooms of more than 5000 sq ft and on one level. A good architectural organizer, it pulls shoppers smoothly from the front to the rear without interruption by the floor fixtures. The floor and ceiling can be used as directional elements off the path (Wiley).
Diagonal plan: It permits angular traffic and design interest around the showroom's perimeter and encourages movement to all areas (Wiley).
Geometric plan: The geometric plan is the most exotic of the six basic plans. The designer created forms and shapes derived from showcases, racks, or gondolas and can use wall angles to restate the shapes dominating the sales floor. Ceilings and floors can be lowered or raised to create different zones (Wiley).
Figure 16: Different Floor Plans
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 18 of 74
Layout planning tips:
Use 100 percent of the space allocated in the lease (Wiley).
Do not sacrifice function to aesthetics. Successful plans combine both to the fullest (Wiley).
Do not create a maze (Wiley).
As part of the fit-out, additional space may be given over to financial services companies providing loans, insurance and similar products (“Cost Model”).
The site selected should contain sufficient usable space to provide for an adequate building and the necessary outside lot area. Ordinarily, the space allocation is approximately 60 percent outside area and 40 percent inside or under roof area. The inside space of a dealership is ordinarily apportioned into four major areas approximately as shown in the following table:
Space Analysis: The illustrated building layout was prepared as an example for an automobile dealer center, in accordance with recommendations for a conventional dealership building design.
Figure 17
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 19 of 74
The Entrance:
In air-conditioned showrooms, in order to maintain the conditioning systems efficiency at a maximum, a seal between indoor and outdoor air may be needed (Callender and Chiara).
Vestibules offer such protection, and may be made removable in summer months (Callender and Chiara).
Revolving doors are often essential where wind pressures are high, when volume of traffic is great, or when air conditioning is used (Callender and Chiara).
Show Windows
The current trend is for a double-height display area with the main frontage in full-height glazing, providing high visibility (“Cost Model”).
Patented systems, which eliminate reflections, are available; so are types of glass suited to special conditions, such as heat resisting glass (Callender and Chiara).
Show windows attract passersby. They may be opened up to display the shop's interior. Door locations require study in relation to pedestrian traffic flow, grades of sidewalks and store floors, and interior layout of the shop (Callender and Chiara).
Show windows must be induced to enter the shop (Callender and Chiara).
Figure 18
Figure 19
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 20 of 74
Show-Window Lighting
Showroom lighting – which reinforces brand identity, displays cars in the best light and creates the right mood – is a useful sales tool (“Cost Model”).
For exterior lighting distributing light in order to produce a semicircular light meant for mounting on the sides of the showroom and walls. The intensity of this distribution lighting has the same intensity at angles from 90 degrees to 270 degrees (Fiorentino).
Employing highly specialized lighting techniques such as fiber optics, the artificial lighting or neon to energize the space (Fiorentino).
Adding daylight via simple skylights or more complex architectural expressions (Fiorentino). Interior Lighting
For interior lighting, using architectural lighting techniques like cove lighting and wall washing to reveal or reinforce the merchandise (Fiorentino).
Recessed lighting is very popular and if chosen correctly is excellent for display. (Jewelry of Architecture)
Wall washing produces a flat, even wash of light for a wall. (Jewelry of Architecture)
Showroom Ventilation
In ventilation systems, operators must understand the variations to know how to provide occupants with adequate outdoor air in all spaces throughout the year (“HVAC”).
It should be that a portion of ventilation air supplied to occupied spaces is outdoor air and a portion
is recalculated air (“HVAC”).
It can be that variations in the thermal requirements of a space are satisfied by varying the
temperature of a constant volume of air delivered to the space at a constant (“HVAC”).
Figure 20
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 21 of 74
Organizing Showroom Spaces: Interiors
Easy circulation and exposing the customer to the maximum amount of merchandise are part of good design (Callender and Chiara).
Avoid monotony in circulation and display of merchandise (Callender and Chiara).
Determine what customer accessories are required: seating in general.
Location of stock rooms, or of reserves, must be carefully considered so that the salesperson does not have to leave a customer for too long a period (Callender and Chiara).
The choice of materials, such as timber flooring in lieu of tiling, is a way
for a manufacturer to reinforce the showroom’s visual image (“Cost
Model”).
Departmentalization :
Impulse, or luxury, cars are usually high in price, so they shall have the prime and higher exposed locations.
Leave at least 5 ft open around each car in order to allow space so that the customer may walk around and open the hood, doors, and trunk freely.
Classifications may overlap; dividing the showroom or having different levels is possible in order to differentiate between the different categories.
Signs are not always necessary (Callender and Chiara).
Customer Flow (circulation)
What a customer sees is more influenced by the arrangement of the space and the walking habits of customers, than by the intrinsic quality of the objects exhibited (Callender and Chiara).
Figure 21
Figure 22
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 22 of 74
Tendencies to turn to the right, to be attracted by doorways, to choose the wider of two aisles are all of utmost importance to the showroom planning. Offices must also be analyzed in relation to customer flow (Callender and Chiara).
The most common pattern for the direction of the flow of customers are:
Entrance to exit, front to back, side to side, diagonal (Wiley). Showroom Sizes
Heights: Basements 8 to 9 ft high, in the clear, permit economical stock storage. Ground floors are preferably approximately 12 ft high if no mezzanine is included; mezzanine at least 7 ft 6 in. above floor level will accommodate most fixture heights. Height from mezzanine floor to ceiling may be as low as 6 ft 6 in., if used for service space only 7 ft is the preferred minimum for public use (Callender and Chiara).
The minimum space guide for inside a car showroom display is 500 square feet per unit. Typical Counter and Case Layouts
Center Island Type illustrated, L = 13 ft avg. min. ; W = 9 ft 6 in . to 13 ft . Islands composed of showcases only, L = 10 ft min. ; W = 5 ft 10 in . t o 6 ft 3 in . For floor tables, L = 4 to7ft; W=2ft6in.to 3ft. (Callender and Chiara).
Aisle Widths For clerks, min. = 1 ft 8 in. ; Desirable, 2 ft to 2 ft 3 in . For main public aisles, min. ~= 4 ft 6 in.; avg., 5 ft 6 in. to 7 ft; usual max., 11 ft. Secondary public aisles, 3 ft to 3 f t 6 in. See Figs. 2 and 3. (Callender and Chiara).
Figure 23
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 23 of 74
Displays
Staple items are often placed at the rear to draw the traffic from the front to the back of the store. Merchants count on customers getting to view additional (Callender and Chiara).
Locating display surfaces perpendicular to the line of entrance may result in angular plans, or in the use of screens or freestanding display cases (Callender and Chiara).
Structure:
Always avoid having structural columns in this hall and depending on other structure systems such as space frames, space trusses, tension tent structure, glazed domes, etc.
Space frames: A three-dimensional steel building frame which is stable against wind loads.
Benefits:
“Minimum structure weight.
Accommodates concentrated loads.
Suits irregular supports or plan geometry. Frame can be a feature without ceiling” (“Space
Frames”).
Figure 24
Figure 25
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 24 of 74
Space trusses: It is used like a plate or slab, particularly for long span roofs where the plan shape is square or rectangular, and is most efficient when the aspect ratio (the ratio of the length and width) does not vary above 1.5. A space truss can support weight and loads in any direction. Scale
An important factor in display is the relation between the possible viewing distance and the scale of the merchandise (Callender and Chiara).
It is possible to dramatize objects on display, to make them stand apart from their neighbors and in this way suggest that they are more desirable (Callender and Chiara).
Work Areas
Car showrooms should accommodate floating desks for sales persons, insurance companies’ representatives, bank auto loan officers in addition to a desk for vehicles registration officer (Callender and Chiara).
Most dealers have their own preference for the
location offices (Callender and Chiara).
Figure 26
Figure 27
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 25 of 74
Service department:
Overall organization and appearance determines the operating efficiency of the service department. Dealers have to create a balanced service environment that serves the customer's needs as well as the dealer’s (Callender and Chiara).
The following are features that should be considered basic elements in the service environment: the covered, out-of-the-weather reception area, well-positioned signs that spell out traffic flow, the service tower that provides visual control, including a view through the service entrance and into the street and over the reception area and into the work areas, the customer lounge and cashier at one location, convenient access to the lounge without the need to wander through the service department to find it, wide entrance and exit lanes, and uncrowned write -up areas with
sufficient room for customer convenience (Callender and Chiara).
The type of building shown in the following figure requires 120 sq ft per stall for access area which
results in an average of 420 sq ft per stall. (Work area plus access area.) An average of an additional 80 sq ft per stall is required for other nonproductive service-related areas such as a tool room, locker room, service manager's office, and other utility areas (Callender and Chiara).
The reception area should be immediately inside the service entrance, decorated, well lighted, and equipped to create the best possible impression and selling atmosphere (Callender and Chiara).
It is strongly recommended that the customer reception area be removed from the productive service area (Callender and Chiara).
This concept has the following advantages :
(1) keeping vehicles out of the productive area until they are ready to be worked on ;
(2) outside (canopy) reception area can be considered, which is less expensive than inside
roof area ;
(3) customers prefer a clean, quiet atmosphere to the normal noise, dirt and congestion of
the shop area (Callender and Chiara).
Figure 28
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 26 of 74
Climate control
Today virtually all commercial spaces are maintained the year round within certain limits as to temperature and relative humidity (Callender and Chiara).
In most climates this means heating and humid. The problem of cooling is proportionately more important than heating, even in relatively cold climates, because of the necessity to compensate for the body heat and moisture emitted by crowds of people and the heat from electric lighting, especially the incandescent type (Callender and Chiara).
The developer would supply the minimum heating required by the code (Callender and Chiara). For most motor dealerships, sustainability is not a major business driver, but delivering buildings
that meet manufacturers’ design codes could be a challenge. Although occupancy-related cooling loads are not a major issue, loads related to solar gain are.(“Cost Model”).
Measures taken to mitigate loads, energy use and carbon emissions include:
Use of roof lights to provide basic levels of illumination without adding to cooling loads
Enhanced insulation for solid cladding and roofs
Lighting control
Offsetting relatively high carbon emissions in a mechanically cooled showroom across the total
floor area of the scheme, which includes areas such as workshops with lower loads. (Cost Model)
Stairs:
In a car showroom, if only the first floor is used for displaying cars while the second floor is for the offices then the stairs are better placed where they aren’t seen by the client; away from the entrance.
Fire and building codes devote a lot of space to stairs. (Stairs)
The 1996 Council of American Building Officials (CABO) and the 2000 International Code Council recommendations call for unit runs to be not less than 10 inches and unit rises not more than 7¾ inches. (Stairs)
Most fire codes do not allow stairs to rise more than 12 feet without providing a landing. The length of the landing should be at least equal to the width of the stair tread. (Stairs)
According to the 1996 CABO code, the openings between balusters are to be no greater than 4 inches. (Stairs)
According to 2008 New York State Stair Code the minimum [stair] tread depth shall be 9 inches (229 mm). (Building Code Guide to Stairways)
Fire stopping for stairs is required to slow the spread of building fires between floors and to assist in emergency exit. (Building Code Guide to Stairways)
Figure 29
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 27 of 74
Emergency Exit:
“Exit discharges must lead directly outside. Exit stairs that continue beyond the level on which the exit discharge is located must be interrupted
at that level by doors, partitions, or other effective means that clearly indicate the direction of travel leading to the exit discharge.
Exit route doors must be unlocked from the inside.
Ceilings of exit routes must be at least 7 feet, 6 inches high. An exit access must be at least 28 inches wide at all points.
Exits must be separated by fire resistant materials” (Occupational Safety).
The entrance door for the customer reception area should be 16 ft wide and 12 ft high. Two-lane traffic door should have a minimum width of 24 ft. Wide doors make it easier to move cars into the
stalls just inside the entrance. Single exit doors should be 14 ft wide and 12 ft high.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 28 of 74
Local Case Study: BMW Showroom
A. Site Analysis:
i. Climate
The showroom is located in the desert on Cairo-Alexandria Road. The temperatures are very high during day time. The architect placed the building in the south-west direction prioritizing the availability of natural lighting and the show windows on the high way side over the possible increase in temperatures within the showroom and the consequent increase in the use of artificial cooling systems. However, to minimize these risks, the show windows were not used extensively in the façade.
ii. Site Accessibility
The location of the showroom in relation to the high way and surroundings is shown in the map
below. Figure 30: Showroom and surroundings
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 29 of 74
Accordingly, the site is accessible by one major high way in Egypt, the Cairo-Alexandria road. The showroom is as well placed near other car showrooms and a popular megastore and mall. Private parking areas are well present.
B. Architectural aspects:
i. Plan Analysis:
Analysis of different aspects related the use of spaces in the ground floor is shown in the diagram below.
Figure 31: Ground Floor Plan analyzed
The depth of the showroom makes the customers feel the wideness of the space and makes the visit of the showroom longer, and thus increasing the time that the customers spend on thinking consequently increasing the probability of them buying something.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 30 of 74
Analysis of different aspects related the use of spaces in the basement and first floors is shown in the diagram below.
Figure 32: Basement and First Floor Plans analyzed
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 31 of 74
ii. Circulation and Zoning:
Spaces of the showroom were well designed taking into account the relationships between all the different elements as shown below in diagram below.
Figure 33: Relations between spaces, Ground Floor Plan
Although not clear on the plan, the circulation spaces between cars within the showroom are
appropriate allowing the customers to move freely in all directions. This is shown in the photos below.
Figure 34: Circulation within the showroom
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 32 of 74
The randomness of cars’ locations makes the circulation within the showroom a multi-paths space because it does not direct the customer to specific spaces, but gives him the freedom of moving around in all directions according to their preferences. This means that customers may skip some of the cars displayed.
The different zones of the space are shown in the diagram below, showing that each floor targets a certain function of the building.
Figure 35: Zoning
iii. Entrance and Show Windows:
The entrance to the showroom is placed on the side of Cairo-Alexandria highway which makes it very likely to be noticed while driving beside it.
The use of show windows was not extensively used because of the location of the showroom in the desert in which the temperature can rise really high. However, show windows were used partially to show some of the displayed cars in order to attract customers as shown below.
Figure 36: BMW Showroom facade
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 33 of 74
Few stairs were placed leading to the showroom and the entrance was protruded to cause self shading thus decrease the amount of sun rays entering the building.
The complete façade of building is shown in the main elevation below.
Figure 37: BMW Showroom main elevation
iv. Interior:
The interior of the showroom is quite simple with the dominant color being the white to put emphasis on the cars rather than the building itself. Few illustrations are hung in different locations within the building to break the monotony, but all illustrate BMW cars again to make customers focus on the displayed cars. This is shown in the photos below.
Figure 38: Interior of the showroom
Unlike Autostella showroom, the relation between the scale of the product and the viewing distance is appropriate because of the big surface area of the showroom.
v. Structure: Car showrooms in general try to avoid the presence of columns if possible in order to facilitate
the placement of cars within the showroom. In this showroom, there are only few columns within the showroom space for structural purposes.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 34 of 74
C. Environmental aspects:
i. Lighting:
The showroom was intended to use natural lighting during daytime through the use of show windows. However, since the show windows are not large enough and the showroom is deep, the lighting within the space was not successfully achieved in a way that values the cars displayed. This is shown below in the photo.
Figure 39: Insufficient lighting in the showroom
Artificial lighting is used for night time use as well as to increase the intensity of light when
natural lighting appears to be insufficient.
ii. Acoustics:
The building is placed near a highway which could cause a significant level of noise; however, background noise does not represent a major problem as visiting showrooms is not an activity that requires high concentration levels.
Placing the offices in the upper floor in complete isolation from the showrooms may be an attempt to minimize the noise to offices in which some concentration is necessary. On the other hand, sales offices were placed in the ground floor because the designer prioritized the availability of workers to customers over the possible drawback in concentration levels.
iii. Landscape:
The showroom is located within the desert on a highway making it impossible to provide an
appropriate view. This is why few spots of greenery were created to attenuate the sense of dryness as shown below.
Figure 40: Greenery spots
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 35 of 74
iv. Climate control/Ventilation:
The climate control is provided by air conditioning within all rooms of the building. The need for cooling systems is maximized here because of the hot weather, the use of show windows and the desert location of the building.
D. Security and safety:
Alarms and surveillance cameras are used to ensure the security of the showroom.
E. Parking
A wide parking area is provided in front of the showroom building. This parking has two
functions: provide park areas for customers and provide park areas for BMW cars that will not be displayed within the building as shown below.
Figure 41: Parking area
Overall analysis: The design successfully planned both the circulation and the zoning within different spaces in the building. Different relations were forms according to the nature of showrooms. Environmental features were moderately taken into consideration. Since the desert makes it impractical to use natural lighting and ventilation, the design should have emphasized these through the use of preventative elements. Parking area was provided while security of the building was not complexly designed.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 36 of 74
International Case Study I: Autostella Showroom, Bangkok, Thailand
A. Site Analysis:
iii. Land and Topography:
The showroom is located in Bangkok, Thailand around Eakamai-Ramintra expressway. The
site area is 1565 square meters while the project area is 496 square meters (archi).
The city of Bangkok is located in the basin of the Chao Phraya River and has no mountains.
The land is crisscrossed with canals and rivers. It is situated 2 meters above the sea level
which could lead sometimes to floods (info).
This high level of water makes the availability of underground parking impractical. The
showroom does not provide a formal parking area, but provides a space in front of the
entrance for cars to park. This limits the number of possible customers; but this may be
compensated by free parking spaces within the showroom nearby streets.
iv. Climate
“There are three seasons: rainy (from June to October), hot (from March to May), and cool
(from November to February). The annual average temperature is about 29° C with the
monthly averages ranging from 35° C in April to 26° C in December” (info).
The design of the space allowed for high temperature as the use of windows was limited,
limiting the heat entering the space. However, this meant that the use of natural lighting
was limited.
Rainfalls were taken into account in the design as walls were tilted pushing rain away from
windows.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 37 of 74
v. Site Accessibility
The showroom is located near a high way (Eakamai-Ramintra expressway), making it faster to
reach the showroom. It is as well located in a corner of two streets making it easily noticed by potential customers.
vi. Cultural implications and Surroundings
Bangkok became nowadays a mixture of traditional architecture and high tech/fancy architecture, making the showroom a normal part of such a heterogeneous city.
B. Architectural aspects:
iii. Plan Analysis:
Analysis of different aspects related the use of spaces is shown in the diagram below.
Figure 42: Floor Plan analyzed
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 38 of 74
The spaces are organized in a way that does not keep the customer during a long time. From the entrance door, the customer can scan all the cars presented in the showroom. This was due to space constraints. On the other hand, the customers will be able to access all cars easily and quickly, which may consequently make them at ease and give them enough time to think about the products displayed.
iv. Circulation and Zoning:
Spaces of the showroom were well designed taking into account the relationships between all
the different elements as shown below in diagram.
Figure 43: Circulation Analysis and Zoning
The circulation within the showroom allows for a maximum of two paths from which one is most
likely. A regular customer is pushed to take his right then visit showroom 1 then 2 then 3 then rests sometime in the sitting area. The exact opposite path could as well be taken. Customers usually like to have alternatives, which may frustrate the customer. However, a one-path design ensures that the customer will take a look at all the cars.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 39 of 74
vi. Entrance, Façade and Windows:
The entrance to this showroom takes place at the opposite side to the road. One has to go up stairs to access it. A fish pond is present besides the entrance adding nature to the already present greenery. This could lead to sense of relaxation and comfort to customers. This is shown in the figure below.
Figure 44: Entrance to showroom
No entrance doors are available at the side of the road but instead stand large windows that allow customers to see the cars displayed and attract them to visit the showroom. This is shown in figure below.
Figure 45: Façade (street side)
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 40 of 74
vii. Interior:
The organization of the spaces allows for minimal about of flexibility in terms of changing of interior design, movement of cars, etc… However, there is an extremely efficient use of spaces and no space is wasted as shown below. Display cars consist of all the cars present within the showroom.
Figure 46: Interior of the Showroom
Yellow, orange, red, black and grey colors are used in a way that accentuates the architectural style of this showroom that is very modern. However, the white color is the dominant color used as it helps the customer concentrate on the traits of the cars and not be distracted by the design of the showroom.
The bathroom follows the same architectural style of the building hence gives the customer a sense of homogeneous space.
Spot lighting is extensively used to highlight the cars displayed and sitting areas are placed at different places in the building.
An important relation that is lacking in this building is the adequate relation between the possible viewing distance and the scale of the product. Cars are relatively big products which could not be seen entirely in details if the viewing distance is small, which is the case in this showroom because of its small size.
viii. Structure:
The showroom is not an open space but rather separate spaces that are linked to each other. This semi-closed space gives the customer the feeling of narrowness, but made the structural design easier as it didn’t require steel structures to keep the space open with no columns.
ix. Concept and Shape The project was “accessed *…+ by neglecting the stereotype aspects of automobile that people
connect themselves with, which is “Speed” and its “Dynamic” look. But it is designed like a small bakery and cafe’ that has small cars park right in the middle of the shops. Imagine a car is one of the furniture in the living room…Their potential clients are those lifestyle concerned people (who sometimes emotional buy rather than logical buy things.) Cars become part of people’s lifestyle, like mobile phone. They are not only transportations like when they were invented anymore” (archi).
The concept can be easily observed within the space: scattered sitting areas, a homogeneous interior design that unifies the toilet, showrooms, cars and sitting areas.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 41 of 74
The shape of the building is non-uniform adding to the uniqueness of its design. “The flat and long red box is pushed-pulled, deformed and divided in to 4 different (but connected) rooms. Each room has windows in different sizes facing the street. Each of the windows is different in size according to the size of the room” (archi). This is well observed in the elevations of the building below.
Figure 47: Elevations of Autostella Showroom
C. Environmental aspects:
v. Lighting:
The design of the building does not put emphasis on natural lighting. Unlike other showrooms,
large windows are not extensively used to show products. Even in the side facing the street, the windows are not large enough to lighten the showroom. This could be due to climate issues discussed earlier.
There is extensive use of spot lighting as mentioned before in the interior section.
vi. Acoustics:
The building is placed at the corner of two streets and near a highway which could cause a significant level of noise; however, background noise does not represent a major problem as visiting showrooms is not an activity that requires high concentration levels.
Placing the offices in the upper floor in complete isolation from the showrooms may be an attempt to minimize the noise to offices in which some concentration is necessary.
vii. Landscape:
As already mentioned in previous sections, the greenery around the building as well as the fish
pond help maintain a good view to customers. viii. Climate control/Ventilation:
There is no available information about that issue.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 42 of 74
D. Security and safety:
A safety rail is placed near the fish pond in order to avoid possible accidents to customers. Because of the small scale of the building, a lower number of surveillance cameras will be
needed. There is only one entrance and exit door which could make it difficult to escape in case of
emergencies.
E. Parking
As mentioned earlier, the high levels of water make it impractical to build an underground parking so this could not be used in this design. However, no formal parking space is available.
Overall analysis: The design planned reasonably acceptable both the circulation and the zoning within different spaces in the building, despite the small area constraint of the showroom. Major components of showrooms are existent within the building. Environmental features were moderately taken into consideration as well. Natural lighting was prevented within the space due to climatic reasons. Sound and ventilation were not significantly considered by the designer. Formal parking area was not provided while security of the building was not complexly designed.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 43 of 74
International Case Study II: BMW Showroom, Utrecht, Netherlands
A. Site Analysis:
i. Climate
Generally, the weather is rather cold in Utrecht,
Netherlands. All over the year the temperature varies from 0 to 25 degree Celsius; ranging from 0 to 12 degree Celsius in winter and reaches 25 degree in its hottest summer days. That makes the use of the glass facades very convenient to the climate.
The Netherlands is located in the northern half of the
earth, which means that the maximum intensity of the sunlight would be on the southern part of the building. And since the building is located in the
north west quadrant, the sun hits its the southern part, which is the glass façade in the indicate building, allowing direct sun rays in most of the day for natural heat and lighting purposes.
ii. Site Accessibility
A customer could access the showroom through the main entrance overlooking the Proostwetering Street (Fig.49) or the garage staircase. The Staircase on the northern part of
the basement is the one for customers.
Employees parking is also in the basement but they have their own staircase right next the Security office and it directs towards the offices
zone
It’s an advantage to separate the customers’ path from the employees’.
iii. Location
The twin headlight showrooms are seen from the A2 highway near Leidsche Rijn behind the Acoustic Barrier and the Hessing Cockpit, but seen from the commercial area itself placed in front of the Cockpit building.
Figure 48, Sunrays Direction.
Figure 49. Pedestrians Entrance
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 44 of 74
B. Architectural Analysis
i. Plan Analysis
Zoning
- Parking
- Maintenance
- Outdoor Display
- Indoor Display
- Offices: The offices are located on both the ground and first floor. They’re not in a quiet zone but rather overlooking the showroom, which could
be the loudest area.
- Wet Zones
Figure 501, Basement Floor Plan
Figure 22, Ground Floor Plan Figure 51, First Floor Plan
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 45 of 74
Customers Circulation
As shown in Figure 55 and 56, the customers’ circulation starts on the ground floor from the pedestrians’ entrance. The customer could head in two directions; he will also find a large number of cars distributed on the floor. However, the distribution is not even as the right side has more cars than the left one. This could confuse the customer and make him concentrate more on one part more than the other. But this is also a technique to
emphasize special or rare edition products.
On the first floor plan, the cars are places right in front of the staircase causing a very narrow circulation.
The arrangement of cars in both showrooms is the same. It’s shown in the ground and first plan of right headlight building (Fig. 51 and 52).
Figure 56, Ground Floor circulation.
Figure 54, Products Display.
Figure 55, First Floor Circulation.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 46 of 74
The cars are spaced enough to allow an easy circulation and examination of the products. They’re also assembled according to types (Fig. 56)
However, the cars are not placed in a technique that directs the customer into a certain way.
Cars Circulation
There are ramps surrounding the building to allow an easy circulation for cars.
The cars enter from the Proostwetering Street to a wide lane that separates the twin buildings. This is the only entrance for both cars and pedestrians. It would’ve been better if the main entrance
were located on the highway to attract more customers.
Figure 57, Display of Products According to Type.
Figure 58, Cars Circulation.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 47 of 74
There’s a service zone at the northern part of the building on the ground level (Fig.59). As shown in figure 9 the circulation for the cars passageway is rather narrow and could only accommodate one car
at a time.
The outdoor cars display is located between the two buildings (Fig.60). The lanes are wide enough to accommodate both product display and cars
circulation in and out of the parking.
ii. Show Windows
The entrance of both Headlight showrooms is overlooking the street and a commercial area (Fig.61)
so it’s highly noticeable. Revolving doors are used because wind pressures are high.
The main façade is partly glazed curtain walls and partly steel, forming the headlight shape and allowing catching display. In addition to that the difference in materials allows direct sunrays access only in the products display area. But the glass facades have a slight blue shade, which causes color distortion and could mislead the
customer.
Figure 3, Maintenance Service.
Figure 61, Show Window.
Figure 60, Outdoor Display.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 48 of 74
The cockpit’s show window displays the cars through a glass façade Stretched along 150 meters of the A2 highway in the direction of the cars’ flow. This technique allows the display of a huge number of cars just by passing next to the showroom’s glass façade. The glass facades are facing north; this is a drawback, as it doesn’t benefit from natural heat meanwhile, the region has a very
low temperature throughout the year.
C. Structural Analysis
Given that auto showrooms cannot have columns in the display area, the architects used space frame trusses (Fig.64) to support the ground and first level then used columns in the basement (Fig.63) because it’s only used for parking thus, it doesn’t obstruct the display or circulation.
Figure 62, Hessing Showroom from Highway.
Figure 64, Space frame Trusses. Figure 4, Parking Structure.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 49 of 74
D. Environmental Analysis
i. Lighting
The headlight twin buildings have their main elevations facing south. These southern elevations are in all glass curtain walls, allowing direct sunrays penetration to
provide natural lighting and heating. (Fig.65)
In order to decrease energy consumption, the architects used the Revit model for lighting analysis. They placed the lights on the steel connectors of the curtain system (Fig.66) and then examined on the model the lighting levels. The designers were ascertained that the lighting levels are sufficient and avoided installation of a secondary lighting grid for the showroom lighting.
However, the architects failed to use sunrays for natural lighting in the cockpit building. They used steel facades on their southern elevation and glass on the northern. This is not beneficial energy wise but had they done the opposite the view on the highway would’ve been obstructed which would’ve
ruined the building’s concept. (Fig.67)
Figure 65, Southern Elevation.
Figure 5, Close Up View of The Supporting Structure.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 50 of 74
ii. Climate Control/Ventilation
The showroom is located in averagely low temperature region throughout the whole year. Therefore, we assume that the glass facades transmit heat. There should also be a heating system installed. It’s also very windy in Utrecht, Netherlands, that’s why it’s not possible to use natural ventilation. There should be a ventilation system all over the building and the glass facades should have a very small number of open able windows. Revolving doors are used because wind pressures are high.
Figure 67, Cockpit showroom Different Material Use.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 51 of 74
iii. Acoustics
In order to decrease the intensity of the noise coming from the A2 highway, an acoustic
barrier was built on both sides of the cockpit to work as a buffer.
Figure 69, Acoustic Barrier.
Ventilation
Figure 68
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 52 of 74
However, the offices are not placed these in a quiet zone. They’re actually overlooking the showroom, which could decrease the concentration needed for office employees to do their work during the presence of a big number of employees in such a big showroom.
Furthermore, the first floor is overlooking the floor below making it more harder to create quite zones.
Yet, This could be an advantage for salesman whose job is focused on interaction with clients.
iv. Landscape
Since the building overlooks a main street and is seen from a major highway, it’s located in a highly commercial area. Thereby, it needs a catching frontage to match the significance of the location. Some green spaces were added to give a pleasing view (Fig.71). The layout shows how the lanes between the three buildings are properly planned
Figure 70, Greenery Spots
Figure 71, Project Layout.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 53 of 74
E. Security and Safety
Due to the expensive value of the cars displayed, there should be an intense security system, including surveillance cameras and alarm systems on entrances and for each car.
F. Parking
Both of the headlight buildings offer a wide space for parking in their basement floor (Fig.74). The plan shows the spacing between each car and an easy passage giving enough space for two cars to move in the main lane. There are other parking slots all around the building but they’re all designated for cars on sale display.
Concept: This built project is a twin-facility car showroom for Ekris Utrecht, the largest BMW dealership in the Netherlands. ONL, the design office, named the project “Ekris Headlights” because the design was inspired by the shaped headlights of a car, which over the years have been transformed from a non-integrated element in the grille of the car to an integral part of the shaped body. The two volumes together form a coherent image that is reminiscent of two BMW grilles with slightly tilted bars. The glass facade literally rounds the corner of the building, just like the headlights of a new BMW. There’s a Rolls Royce and Bentley car showroom at the back of the Ekris Building, it’s called the cockpit Hessing Showroom. It’s inspired from the shape of the plane’s cockpit. The Cockpit lies on the A2 highway and show its products for 150 meters. The analysis was made for both showrooms as they were both affected by the same site issues and were related in some key factors.
Figure 72, Products Display.
Figure 73, Parking
Figure 74, Parking Entrance.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 54 of 74
Local Lecture Hall Case Study: Mansour Hall, AUC campus
A. General characteristics:
Location
1. Mansour Hall is located at the ground floor the back of a building, 14 meters from the main
entrance of the building. That means that it is isolated from any noisy caused by students’
activities at the main entrance of the building, however, that would increase the students’
travel through the building.
2. Being at the ground floor makes it easy access to the hall and facilitates the task of locating it.
3. The corridor leading to the lecture hall is relatively a wide one, allowing the follow of a couple
of students at a time.
4. Also, the hall can be accessed via a stair leading to a different part of the university it is in,
which allows access from different parts and decrease the conjunction at a part.
5. The bathroom is 11 meters away from the hall which is a suitable distance and convenient for
the users of the lecture hall, since it means a 2 minute walk.
Sun
direction
Afternoon sunrays
North
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 55 of 74
Entrances
1. There is one entrance for the hall, the entrance have three doors in the middle the re is a double
door which allows access to wheel chaired persons and one the side two single door for the access
of the maximum number of people at the same time.
2. The doors are designed so as that they open to the outside, which facilitates access to the hall,
since the audience won’t find something that would obstruct their way while they are
Seating, Capacity
1. Mansour Hall has 15 rows; the first two of it have 14 chairs while the other rows have 15, which
give us a total capacity of the hall of 223 persons.
2. The standards mention that the row-to-row distance should be from 20.4 cm to 30.5 cm. the row-
to-distance in Mansour hall is 55 cm, which gives extra space for the user and can be considered
as a waste of space.
Notice … the arrangement of the
chairs, here they are arranged in a way that they are all aligned with
each other, unlike other hall that have chairs having different aligned. Different is good because
it allows a person to see through the distance between the shoulders
of those in front of him. However, alignment in Mansour is due to its
shape of the
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 56 of 74
3. Arm chair tablets usually follow one of the dimensions previously illustrated at the literature
review of the lecture halls. However, it is recommended to use the oversized tablet for note
taking and laptop use. While that in the Mansour hall is relatively small and is not that
convenient in usage, there is a difference of 3 cm from the standards.
B. Space planning and layout:
1. Plan Analysis:
21 cm
Distance between back to back for
each row is 1 m
Distance between the
rows 50 cm
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 57 of 74
2. Proportions and Physical Access:
There are no columns in the Mansour hall, since it is not preferable to have columns in any
lecture hall.
According to the standard design, to project the lecturer’s voice from the front to the rear of the
lecture hall, the ceiling section over the sending end should be inclined toward the students,
and should be as well angled upward from the sending end. However, that wasn’t applied at
Mansour Hall since the ceiling is a straight one not having any inclination in it.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 58 of 74
3. Furniture
There is no special seat s for the left-handed.
The seats are not numbered.
It doesn’t have a white board, sine it is relatively a bid lecture hall and thus students at the back
would be able to see what’s written on the board.
There are no windows in Mansour hall; however a window is not required at a lecture hall.
The doors are at the back of the hall, to avoid interruptions for possible late comers.
The seat distance is 42 cm which is below the standard which is 48 cm.
4. Materials:
The ceiling’s material: there were two materials on the ceiling tiled and plaster in order to reflect
either light or sound.
The side’s material was wood having circular openings in it, when looking in it foam like material
would be noticed, most probably used to isolate the sound produced by the hall’s activities.
7 cm
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 59 of 74
The floor has two materials as well, the first one is the is the one used for the stairs and which is
wood (smoothed one ) and the other one is a paint like material, there is something that should
be taken into consideration which is that these materials are slippery and could cause a serious
problems in the future.
5. Stairs:
The stairs in the lecture hall are even greater than the normal standards. The length of the step extended to reach almost 50 cm, but the depth and the nose were of normal measurements.
6. Lighting
Generally, nature light is not desirable at the lecture halls, but at sometimes of the day sunlight
penetrates into the hall and that causes glare and decreases the concentration level of the
students sitting at the back rows of the hall.
Pores in the wooden side of the hall
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 60 of 74
Lighting must provide a level of room darkening to view projections on the front screen that also
provides sufficient lighting for note taking and Mansour hall have different zones of lightening
controlled by a unit.
In the picture below, it is shown how the sunlight penetrating the hall through the glass on its
window annoys the rows at the back.
7. Acoustics
Mansour hall is very good and efficient regarding sound proof and isolation from the outside.
The kind of glass that is used on the doors and the structure of its walls make the hall totally
sound proof.
Regarding the sound system within Mansour hall itself, there are several speakers in the hall,
exactly 3 speakers on each side and 6 on the ceiling. These acoustical devices help in providing
the best sound for students.
One zone controls the hall’s general-use fluorescent lights to provide full brightness for general activities.
One zone controls low level lights for note taking. These lights don’t shine on the screens and don’t shine in the eyes of the audience. These should be fully dimmable.
A zone controls incandescent spot lights that highlight the stairs, for people not to slip if the room is dark and there is something projected.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 61 of 74
This is an attempt to simulate the possible case of the sound reflection in the room,
the only trick is the angle of incidence and the angle of reflection.
8. Safety and Security
There are two emergency exists at the front of the hall, near the area where the lecturer stands,
which lead to the plaza.
That supposes that if a person is sitting at the back of the hall and an emergency happened,
such as it is not possible for him to exit from the back / main entrance, it would be risky and
rather hard for him to try to escape through an exit door located at the front and vice versa,
since that would mean running more than 10 meters on a highly sloped ground and entering a
narrow emergency exist.
Speakers
Ceiling Speakers
Side speakers
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 62 of 74
The architect tried to overcome that problem by having two emergencies exists one of which
has a double door which allows the flow of a bigger number of people.
Suggested Solutions: since there are boundaries around Mansour hall, an emergency exist on
the left side of the hall would be another possible solution leading directly to the plaza.
There is a fire extinguisher for fire emergencies near the door (main entrance)
The main entrance can be used as an emergency exit beside the other two ones at the front.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 63 of 74
9. Electrical Supplies and technologies:
Mansour hall is supplied with a large number of technologies and electrical devices.
To begin with it has a huge projector screen and a very sophisticated projector, there is an IT
unit that has access to the internet and can work as a control unit for the sound and the
projector as well.
Some Problems regarding Mansour Hall: During our research about Mansour hall and aiming at critically analyzing it, some of the group members attended a movie that was shown on Mansour hall’s screen. It was noticed that sight from the first four rows is terrible and hurts the back to a great extent that one gets aches from the first couple of minutes he sits there. Sight only begins to improve starting the fifth row and above, since that’s the height at which the standard is fulfilled and the Screen Position is correct compared to the eye sight. The base of the screen should generally be at least 1.35 m clear of the floor at the front of the lecture screen. Also, regarding the Vertical Viewing Angle, Students should be limited to 15 degrees maximum head tilt excursion above horizontal, to reference the center of the projection screen. Another point is the sound, although Mansour hall theoretically has all the qualifications to have a good sound, the sound of the movie wasn’t good at all. To proof our theory, we tried to watch different types of movie to attain the credibility of our analysis and they all showed that sound were not as good as expected. Light was another thing, since the movie was project at 5:00 pm and at that time the sun is at the west which means that it is facing the entrance of the hall and glaring would be a disastrous problem. What they did was that the stuck papers on the windows of the door to prevent light. But a possible solution for that is putting shading portions or simply curtains on the windows.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 64 of 74
Comparative Analysis:
Factors BMW, Cairo Autostella, Bangkok BMW, the
Netherlands
Site Accessibility
1 car access to the site.
1 car access to the site, close to a highway, corner of two streets.
1 car access through the underground parking, to the upper floors. An employee access and guests access
Land and Topography
Desert. High levels of water within the land.
On a side of a high way, of dry nature.
Cultural implications and surroundings
Quite considerate. Minimal use of windows, entrance shading, similar surrounding buildings.
Fitting within Bangkok which is a heterogeneous city.
Usage of curtain walls due to cold weather and need for sun
Circulation
Appropriate spaces for customers’ circulation. Multi-paths plan.
Appropriate spaces for customers’ circulation for mostly all spaces. Two paths plan.
Not all the display cars have appropriate spacing between them
Zoning
Acoustics
Noise coming from the near highway. Admin offices separated from showroom for minimum noise levels.
Noise coming from the near highway. Offices separated from showroom for minimum noise levels.
Near the high way, put the services area facing it and showroom and offices away from it. Offices in the middle.
Lighting
Natural lighting partially used as: windows face the SW direction while the building is deep so does not allow light access to the entire floor. Natural lighting is prevented from the entrance by a protrusion. Artificial lighting used in day and night time.
Limited use of natural lighting because of little use of show windows. Tilted exterior walls for sun shading and protection from rainfalls. Artificial lighting used in day and night time.
The main display window faces the S direction, thus benefits from the sunlight most of the day. Artificial lighting used day and night.
Interior
Simple white interior Viewing angle vs. cars’ size relation is appropriate.
Mostly white interior, but multiple colors are used for minor areas. Viewing angle vs. cars’ size relation is inappropriate.
Mostly grey interior with a clear look of the main material steel and glass. Viewing angle vs. cars’ size relation
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 65 of 74
differs from a place to another.
Structure
Rounded supporting columns utilized, but do not obstruct cars’ transportation.
Semi-open space, almost divided into spaces making the structure easy with no need of columns within.
Having the shape of quarter a circle, no columns used within but rather space frame trusses
Landscape
Desert, artificial greenery.
Natural greenery, artificial fish pond.
Greenery and a twin building giving the shape of a car’s high lights
Climate control
No use of natural ventilation systems because of the hot location. Only artificial ventilation by air conditioning.
No use of natural ventilation systems because of the hot location. Only artificial ventilation by air conditioning.
No use of natural ventilation systems because of the cold location. Only artificial ventilation by air conditioning.
Security and safety
Regular security precautions (video surveillance cameras, alarms). Only one entry/exit.
Regular security precautions (video surveillance cameras, alarms). Only one entry/exit.
Regular security precautions (video surveillance cameras, alarms). two entry/exist, one for cars and other for pedestrians
Parking
Wide parking space for customers’ cars and informal cars’ display.
No formal parking space, only limited space for few cars.
A fairly big underground parking for employee and some guests are allowed. A parking space outside beside it for customers’ cars and informal cars’ display.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 66 of 74
Checklist for Optimum Car Showroom Design:
A showroom is best located on two or more major highways in order to be accessed easily.
It needs to be accessible to the surrounding via good road network and public transport facilities
and to have good local linkages between car parks and public transport stops.
For car showrooms, the showroom should be located in a position of unobstructed visibility.
The site selected should contain sufficient usable space to provide for an adequate building and
the necessary outside lot area.
In car showrooms, the show windows are better a double-height display area with the main
frontage in full-height glazing, providing high visibility.
The showroom should be designed providing easy circulation and exposing the customer to the
maximum amount of merchandise.
The space of the car showroom should accommodate different zones with different levels to
display cars in different categories and classes; the more expensive cars always have the prime
and higher exposed locations.
Always avoid having structural columns in this hall and depending on other structure systems
such as space frames, space trusses, tension tent structure, glazed domes, etc.
Car showrooms should accommodate floating desks for sales persons, insurance companies’
representatives, bank auto loan officers in addition to a desk for vehicles registration officer.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 67 of 74
Checklist for Optimum Lecture Hall Design:
1. Being easily reached and smoothly accessed.
2. Presence of enough isolation from the outside whether from light or sound perspective.
3. Achieving a human’s ease and keeping him in the comfort zone; through taking care of the affecting
environmental factors such as the lightening, the temperature and the ventilation of the hall.
4. Offering a comfortable seating facility, with careful dimensions with which almost anyone can sit
comfortably.
5. Projection screen should be of a particular height to achieve suitable angle between the audience
and the screen.
6. Sound and technological facilities plays a very important role in the success and the failure of any
lecture hall, since a lecture hall’s main aim is to present something the people ought to see and
listen to well.
7. Emergency exists: like any other facility there must be emergency exists in case a something went
wrong during one of the lectures.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 68 of 74
Works Cited
Benya, James. "Jewelry of Architecture." Home. Benya Lighting Design, 2005. Web. 04 Oct. 2010.
<http://www.benyalighting.com>
"Building Code Guide to Stairways, Railings, Landing Construction & Stair Safety Inspections."
InspectAPedia.com Building & Environmental Problem Diagnostic & Repair Encyclopedia. Web.
02 Oct. 2010.
Callender, J. H., and J. De. Chiara. Time-saver Standards for Building Types. New York: McGraw-Hill,
1973. Print.
Classroom Design Standards. Publication. University of Connecticut. Web. 19 Sept. 2010.
<http://fas.uconn.edu/Masterplan/10.%20Classroom%20Design%20Standard/Classroom%20Fin
al%20rev11.%20033005.pdf>.
"Cost Model: Car Showrooms | Magazine Features | Building." Construction Industry
News from the UK's Leading Construction Magazine - Building. Web. 29 Sept. 2010.
DeChiara, Joseph, Julius Panero, and Martin Zelnik. Time-saver Standards for Interior Design and Space
Planning. New York: McGraw-Hill, 2000. Print.
Design Requirements. Publication. Web. 19 Sept. 2010.
<http://www.bd.gov.hk/english/documents/code/bfa2008/Division1.pdf>.
"Emergency Exit Routes." Occupational Safety and Health Organization (OSHA) . U.S. Department of
Labor, 2003. Web. 3 Oct. 2010.
Fiorentino, Catherine. "Lighting Distribution Types | EHow.com." EHow | How To Do Just About
Everything! | How To Videos & Articles. Web. 30 Sept. 2010.
General Assignment Classroom Design Standards. Publication. University of Iowa. Web. 19 Sept. 2010.
<http://www.facilities.uiowa.edu/pdc/designstandards/ClassroomDesignStandards.pdf>.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 69 of 74
Guidelines for Yale Learning Spaces. Publication. Yale University, 16 May 2007. Web. 19 Sept. 2010.
<http://www.yale.edu/its/media/classroom/classroom_guidelines.pdf>.
"Heating, Ventilation, and Air-conditioning (HVAC) | Text Modules | US EPA." US Environmental
Protection Agency. Web. 30 Sept. 2010.
Karlen, Mark, and James Benya. Lighting Design Basics. Hoboken, NJ: John Wiley, 2004. Print.
"KI Education - Auditorium/Lecture Hall Planning." KI Education. Web. 19 Sept. 2010.
<http://www.kieducation.com/issues.aspx?ar=106>.
"Large Lecture Hall Design." CRLT : Center for Research on Learning and Teaching. University of
Michigan. Web. 19 Sept. 2010.
<http://www.crlt.umich.edu/learningspaceguidelines/largelecture.php>.
Lecture Hall Design Standards. Publication. University of Maryland, Baltimore County, 29 Aug. 2000.
Web. 19 Sept. 2010.
<http://www.umbc.edu/oit/classroomtechnology/about_files/LH_Standard.pdf>.
Neufert, Ernst, and Peter Neufert. Architects' Data. Oxford: Blackwell Science, 2008. Print.
"Parking Requirement Guidelines." Wagga Wagga City Council Internet. Wagga Wagga Development
Control Plan 2005, Dec. 2005. Web. 04 Oct. 2010. <http://www.wagga.nsw.gov.au>.
Retail Planning Guidelines for Planing Authorities. Ireland. January 2005. Print.
"Space Frames." Triodetic. Web. 03 Oct. 2010.
"Stairs" Sizes of Things and the Units Used to Describe Them. Web. 02 Oct. 2010.
"Wiley::Building Type Basics for Retail and Mixed-Use Facilities." Wiley::Home. Web. 25 Sept. 2010.
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 70 of 74
Appendices
Appendix 1: Side Elevation and Sections of the BMW showroom, Cairo-Alexandria Road
Section B-B
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 71 of 74
Appendix 2: Construction Phases of the BMW showroom, Cairo-Alexandria Road
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 72 of 74
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 73 of 74
AENG 321 Project 1 Building Analysis Project
Showrooms and Lecture Halls
Fall 2010 AENG 321
Page 74 of 74