Job Name:
System Reference: Date:
Indoor Unit:
PEAD-A36AA7
Outdoor Unit:
□ PUZ-A36NKA7
□ PUZ-A36NKA7-BS
INDOOR UNIT FEATURES• Unobtrusive ceiling-concealed design for short-run ductwork.• Wide ranging external static pressure• Built-in condensate lift mechanism• Auto fan speed mode• Optional FB Series filter boxes for easy access and service• Ideal for residential homes,retail shopping centers, larger classrooms, office complexes, conference ballrooms,
fitness centers, and more
OUTDOOR UNIT FEATURES• Variable speed INVERTER-driven compressor• Suction accumulator pre-charged with refrigerant volume for piping length up to 100 ft (70 ft. for A12/18/24/30)• 24-hour continuous operation (cooling mode)• High pressure protection• Fast restart due to bypass valve make it ideal for equipment cooling applications, such as data centers• Superior energy and operational efficiency
SUBMITTAL DATA: PEAD-A36AA7 & PUZ-A36NKA7(-BS)36,000 BTU/H HORIZONTAL-DUCTED HEAT PUMP SYSTEM
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
P-SERIES
Model number Indoor unit PEAD-A36AA7
Outdoor unit PUZ-A36NKA7
PUZ-A36NKA7-BS
Cooling*1 Maximum Capacity Btu/h 36,000
Rated Capacity Btu/h 36,000
Minimum Capacity Btu/h 16,000
Maximum Power Input W 3,000
Rated Power Input W 3,000
Moisture Removal Pints/h 8.10
Sensible Heat Factor 0.75
Power factor % 93.8
Heating at 47° F*2 Maximum Capacity Btu/h 40,000
Rated Capacity Btu/h 38,000
Minimum Capacity Btu/h 18,200
Maximum Power Input W 3,020
Rated Power Input W 2,410
Power factor % 92.7
Heating at 17° F*3
Maximum Capacity Btu/h 24,200
Rated Capacity Btu/h 20,800
Maximum Power Input W 2,400
Rated Power Input W 2,350
Efficiency SEER 19.1
EER *1 12.0
HSPF (IV) 9.9
COP at 47° F *2 4.62
COP at 17° F *3 2.60
Electrical Voltage, Phase, Frequency 208 / 230V, 1-phase, 60 Hz
Guaranteed Voltage Range V AC 187 - 253
Voltage: Indoor - Outdoor, S1-S2 V AC 208V / 230
Voltage: Indoor - Outdoor, S2-S3 V DC 24
Voltage: Indoor - Remote controller V DC 12
Recommended Fuse/Breaker Size A 30
Recommended Wire Size (Indoor - Outdoor) AWG 14
Indoor unit MCA A 3.30
MOCP A 15
Fan Motor Full Load Amperage A 2.64
SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
Model number Indoor unit PEAD-A36AA7
Outdoor unit PUZ-A36NKA7
PUZ-A36NKA7-BS
Fan Motor Output W 244
Airflow Rate, Dry CFM 847-1024-1201
Airflow Rate, Wet CFM 807-984-1161
External Static Pressure in.WG 0.14-0.20-0.28-0.40-0.60
Sound Pressure Level dB(A) 33-38-42
Drain Pipe Size In. (mm) 1-1/4 (32)
Condensate Lift Mechanism, Max. Distance Ft. (m) 27-9/16 (700)
Heat Exchanger Type Plate fin coil
External finish color Galvanized
Unit Dimensions // Grille Dimensions W: In. (mm) 55-1/8 (1400)
D: In. (mm) 28-7/8 (732)
H: In. (mm) 9-7/8 (250)
Package Dimensions // Grille Dimensions W: In. 65
D: In. 34-11/16
H: In. 13-7/16
Unit Weight Lbs. (kg) 86 (39)
Package Weight Lbs. 101
Indoor unitoperatingtemperature range
Cooling Intake Air Temp (Maximum /Minimum)
°F 90 DB, 73 WB / 66 DB, 59 WB
Heating Intake Air Temp (Maximum /Minimum)
°F 82 DB / 50 DB
Outdoor unit MCA A 25
MOCP A 31
Fan Motor Full Load Amperage A 0.5 + 0.5
Fan Motor Output W 74
Airflow Rate CFM 3,880
Refrigerant Control Electronic Expansion Valve
Defrost Method Reverse Cycle
Heat Exchanger Type Cross fin
Sound Pressure Level, Cooling*1 dB(A) 52
Sound Pressure Level, Heating*2 dB(A) 53
Compressor Type INVERTER-driven twin rotary
Compressor Model MNB33FBRMC-L
Compressor Rated Load Amps A 8
SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
Model number Indoor unit PEAD-A36AA7
Outdoor unit PUZ-A36NKA7
PUZ-A36NKA7-BS
Compressor Locked Rotor Amps A 13
Compressor Oil Type // Charge oz. FV50S // 45
External finish color Ivory Munsell 3Y 7.8/1.1
Base pan heater n/a
Unit Dimensions W: In. (mm) 1050 [41-5/16]
D: In. (mm) 330 + 30 [13+1-3/16]
H: In. (mm) 1338 [52-11/16]
Package Dimensions W: In. 42-15/16
D: In. 17-11/16
H: In. 56-4/16
Unit Weight Lbs. 214 (97)
Package Weight Lbs. 243 (110)
Outdoor unitoperatingtemperature range
Cooling *5 Intake Air Temp (Maximum /Minimum)
°F 115 DB / 0* DB
Heating Intake Air Temp (Maximum /Minimum)
°F 70 DB, 59 WB / -4 DB, -4 WB
Thermal Lock-out / Re-start Temperatures** °F -8 / -4 DB
Refrigerant Type R410A
Charge Lbs, oz 10 lbs, 6 oz
Piping Gas Pipe Size O.D. (Flared) In.(mm) 5/8 (15.88)
Liquid Pipe Size O.D. (Flared) In.(mm) 3/8 (9.52)
Maximum Piping Length Ft. (m) 165 (50)
Maximum Height Difference Ft. (m) 100 (30)
Maximum Number of Bends 15
AHRI RatedConditions
*1 Cooling (Indoor // Outdoor) °F 80°F DB, 67°F WB // 95°F DB, 75°F WB
*2 Heating at 47°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // 47°F DB, 43°F WB
*3 Heating at 17°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // 17°F DB, 15°F WB
Conditions *4 Heating at 5°F (Indoor // Outdoor) °F 70°F DB, 60°F WB // -4°F DB, -5°F WB
Notes
*Wind baffles required to operate below 23°F DB in cooling mode. PUZ with wind baffle: 0°F - 115°F.
**System cuts out in heating mode to avoid thermistor error and automatically restarts at these temperatures
SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
SEACOAST PROTECTION
External Outer Panel: Phosphate coating + Acrylic-Enamel coating
Fan Motor Support: Epoxy resin coating (at edge face)
Separator Assembly; Valve Bed: Epoxy resin coating (at edge face)
“Blue Fin” treatment is an anti-corrosion treatment that is applied to the condenser coil to protect it against airbornecontaminants.
Notes:
SPECIFICATIONS: PEAD-A36AA7 & PUZ-A36NKA7(-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
PEAD-A36AA7
Filter Box with Filters (MERV 13) □ FBM2-4
3-Pole Disconnect Switch (30A/600V/UL) [fits 2" X 4" utility box] □ TAZ-MS303
Drain Pan Level Sensor (Control for indoor unit shut off to prevent drain pan overflow) □ DPLS2
Advanced Blue Diamond Mini-Condensation pump w/ Resevoir & Sensor (110V) □ X87-711 - 110
Advanced Blue Diamond Mini-Condensation pump w/ Resevoir & Sensor (208/230V) □ X87-721 - 208/230
Extension Cord for Blue Diamond Pump □ C13-103
MegaBlue Blue Diamond Condensate Pump (110-230V) □ X87-835
Remote Sensor (extensible) □ PAC-SE41TS-E
Connector Cable for Remote Display □ PAC-SA88HA-EP
□ PAC-725AD-E (10pcs)
Connector for CN32 (remote ON/OFF) □ PAC-SE55RA-E
Connector for CN24 (Back up heating) □ PAC-SE56RA-E
Connector for CN30 (LLC) □ PAC-SE57RA-E
Remote Operation Adapter (with wire terminals for remote ON/OFF and operation status/error)
□ PAC-SF40RM-E*1
External Fan / Heater Control Relay Adapter □ CN24RELAY-KIT-CM3
Backlit, Wall-mounted, Wireless □ MHK1
Wireless Adapter □ PAC-USWHS002-WF-1
BACnet® and Modbus Interface □ PAC-UKPRC001-CN-1
Wall-mounted, Wired □ PAC-YT53CRAU-J
T-STAT Interface □ PAC-US444CN-1
Wired Remote Controller □ PAR-32MAA
Signal Receiver □ PAR-SA9CA-E
Wireless Remote Controller □ PAR-FL32MA-E
Wireless Signal Receiver □ PAR-FA32MA-E
Wire for Remote ON/OFF with CN32 connector □ PAC-715AD
Lockdown Bracket for Wireless, Hand-held, Remote Controllers □ RCMKP1CB*1 Unable to use with wireless remote controller
PUZ-A36NKA7(-BS)
Twinning Distribution Pipe (50:50) □ MSDD-50TR-E
Air Outlet Guide □ PAC-SH96SG-E
Front Wind Baffle □ WB-PA
Drain socket □ PAC-SG61DS-E
Centralized Drain Pan □ PAC-SH97DP-E
M-NET Converter □ PAC-SF83MA-E
ACCESSORIES: PEAD-A36AA7 & PUZ-A36NKA7(-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
PUZ-A36NKA7(-BS)
Control/Service Tool □ PAC-SK52ST
Wall mounting bracket (powder-coated steel) □ QCWB2000M-1
Wall mounting bracket (316 Series Stainless Steel) □ QCWBSS
M-NET control adapter for Building Management System □ PAC-SF83MA-E
Outdoor Unit Mounting Pad 24" x 42" x 3" □ ULTRILITE2
Outdoor Unit 3-1/4 inch Mounting Base - Pair (Plastic) □ DSD-400N
MiniSplit Mounting Stand-Dual Fan models - 12" □ QSMS1202M
MiniSplit Mounting Stand-Dual Fan models - 18" □ QSMS1802M
MiniSplit Mounting Stand-Dual Fan models - 24" □ QSMS2402M
3/8 x 5/8 x 10' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-10
3/8 x 5/8 x 15' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-15
3/8 x 5/8 x 30' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-30
3/8 x 5/8 x 50' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-50
3/8 x 5/8 x 65' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-65
3/8 x 5/8 x 100' / 1/2" Lineset (Twin-Tube Insulation) □ MPLS385812T-100
ACCESSORIES: PEAD-A36AA7 & PUZ-A36NKA7(-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
PEAD-A36AA7
21H
WE
16080
OU
TLINE
S &
DIM
EN
SIO
NS
6.OU
TLINES &
DIM
ENSIO
NS
IND
OO
R U
NIT
PEAD
-A12, 18, 24, 30, 36, 42A
A7
200(
7-7/
8)
120°
120°ø125
135
378(14-15/16) 153(6-1/16)
B(S
uspe
nsio
n bo
lt pi
tch)
23(1
5/16
)
CA
40(1
-5/8
)
15(5/8)
40(1
-5/8
)
58(2
-5/1
6)
20(1
3/16
)D
(Duc
t)
30(1
-3/1
6)10
0(3-
15/1
6)X
(E-1
)=F
100(
3-15
/16)
10(7/16)
57(2-1/4) 643(25-3/8)
18(3/4) 210(8-5/16)
21(7
/8)
G
732(28-7/8)32(1-5/16) 700(27-9/16)
238(9-3/8)10(7/16)
33(1
-5/1
6)
40(1
-5/8
)10
0(3-
15/1
6)
122(
4-13
/16)
178(
7-1/
16)
136 67
356(14-1/16)
217(
8-9/
16)
41(1
-5/8
)
250(
9-7/
8)
23(1
5/16
)
H±3
(H±1
/8)
J±3(
J±1/
8)
(4-15/16)
(5-3
/8)
3-ø2.9(1/8) mount hole
Drain pipe(O.D ø32(1-1/4))Fresh air intake ø100(3-15/16)knock out hole
2XE-ø2.9(1/8)
(Suspension bolt pitch)
Air filter
Drain pipe(Integral lift pump outlet)
Drain pump
(DU
CT)
1Refrigerant piping (gas) (5-3/8) (2-11/16)
(Emergency drain)
2Refrigerant piping(liquid)
Drain pipe(O.Dø32(1-1/4))(Gravity drain)
Terminal block(Power source)
Terminal block(Transmission)
Note 4
Control box
(O.Dø32(1-1/4))
Top
Top
Bottom
view
Top
Bottom
Inlet airside view
Outlet airside view
Opposite pipingside view
Pipingside view
2X2-ø2.9(1/8)
(43-5/16)
(55-1/8)
(45-7/16)
(57-1/4) (59-1/16) (53-9/16)
(47-1/4) (41-3/4) (39-3/8)
(51-3/16)
(41-11/16)
(53-1/2)
2Liquid pipe1Gas pipe
1058
13581300
Model
1200 1110601100 1154
1400
ø15.88 (5/8)
1454 1500
ø9.52 (3/8)
1360 14
1000PEAD-A24,30AA7
PEAD-A36,42AA7
Unit:mm(in.)
Airinlet
Airoutlet
Note 1.Use an M10 screw for the suspension bolt (field supply).
2.Keep the service space for maintenanceat the bottom.
3.This drawing is for PEAD-A24·30·36·42AA7 models,which have 2 fans. PEAD-A12·18AA7 models have 1 fan.
4.If the inlet duct is used,remove the airfilter (supplied with the unit), theninstall the filter (field supply) at thesuction side.
5.Heat air to 0˚C (32˚F) or higher whentaking fresh air with a fresh air intake.
PEAD-A24,30AA7
PEAD-A36,42AA7
PEAD-A12,18AA7
Model A EDCB F G
Unit:mm(in.)
(35-7/16) (37-9/16) (39-3/8) (33-7/8) (31-1/2) (33-13/16) 8581000 9 860 900 954 800PEAD-A12,18AA7
ø12.7 (1/2)
ø6.35 (1/4)
(3-1/8)78
H
(2-7/8)72
J
(2-5/8)66
(2-1/2)62
Unit:mm(in.)
DIMENSIONS: PEAD-A36AA7 & PUZ-A36NKA7 (-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.
PUZ-A36NKA7(-BS)
16
PUZ-A
36NK
A7
PUZ-A
42NK
A7
PUY-A
36NK
A7
PUY-A
42NK
A7
PUZ-A
36NK
A7-B
S PU
Z-A42N
KA
7-BS
PUY-A
36NK
A7-B
S PU
Y-A42N
KA
7-BS
Bottom piping hole(Knockout)
Drain hole(5-ø33<1-5/16>)
154
<6-1
/16>
136
<5-1
1/32
>
81 <3-3/16>
45 <1-25/32>
110 <14-11/32>160
<6-5/16>160
<6-5/16>160
<6-5/16>
86<3
-3/8
>
Rear Air Intake
Handle for moving
Handle for moving
Side Air Intake
12
Handle for moving
Handle for moving
Service panel
Earth terminal Terminal connectionLeft ... Power supply wiringRight ... Indoor/Outdoor wiring
*1 4
42<1
7-2/
5>
1063
<41-
7/8>
632
<24-
7/8>
*1 4
50<1
7-23
/32>
26<1
-1/3
2>36
9<1
4-17
/32>
1338
<52-
11/1
6>
362 <14-1/4>1050 <41-11/32>
Air intake
Front piping cover
Rear piping cover
2-12×36 Oval holes(Foundation Bolt M10<W3/8>)
Installation Feet
2-U Shaped notched holes(Foundation Bolt M10<W3/8>)
225 <8-27/32>
42 <1-21/32>60 <2-3/8>
25<3
1/32
>33
0<1
3>
225 <8-27/32>600 <23-5/8>
70 <2-3/4>
417
<16-
13/3
2>
28<1
-3/3
2>37
0<1
4-9/
16>
19<3
/4>
40 <1-9/16> 53 <2-3/32>
56 <2-7/32>
0
Conduit hole(ø 24<15/16>knockout)
Conduit hole(ø 37<1-15/32>knockout)
Rear trunking hole(Knockout)
Rear piping hole(Knockout)
75 <2-15/16>
92 <3-5/8>
73<2
-7/8
>60
<2-3
/8>
5<3/
16>
26<1
-1/3
2>
27<1
-1/1
6>55
<2-3
/16>
55 <2-3/16> 60 <2-3/8>
ø 92<3-5/8>
Conduit hole(ø 24<15/16>knockout)
Front piping hole(Knockout)
Front trunking hole(Knockout)
Conduit hole(ø 37<1-15/32>knockout)
26<1
-1/3
2>
92 <3-5/8> 27<1
-1/1
6>55
<2-3
/16>
73<2
-7/8
>
75 <2-15/16>
55 <2-3/16>60 <2-3/8>
ø 92<3-5/8>
Right trunking hole(Knockout)
Conduit hole(ø 37<1-15/32>knockout)
Conduit hole(ø 24<15/16>knockout)
Right piping hole(Knockout)
73<2
-7/8
>61
<2-3
/8>
5<3/
16>
29 <1-5/32>
27<1
-1/1
6>26
<1-1
/32>
92<3
-5/8
>
53 <2-3/32> 60 <2-3/8>
55 <2-3/16>
92 <3-5/8>
ø 92<3-5/8>
Min.
Min.
Min.
Min.
Service space Min.
150
<5-2
9/32
>50
0<1
9-11
/16>
500<19-11/16>
15 <3/5>
50<2> Ma
x.30
<1-3
/16>
( )
21 ... Refrigerant GAS pipe connection (FLARE) ø15.88(5/8F)
... Refrigerant LIQUID pipe connection (FLARE) ø9.52(3/8F)
*1 ... Indication of STOP VALVE connection location.
Piping Knockout Hole Details
Example of Notes
FREE
Min. 15mm<3/5>
Min. 15mm<3/5>
Min. 1000mm<39-3/8>
Min. 150mm<5-29/32>
Piping and wiring connectionscan be made from 4 directions:FRONT, Right, Rear and Below.
4 PIPING-WIRING DIRECTIONS3 FOUNDATION BOLTS2 SERVICE SPACE1 FREE SPACE (Around the unit)Please secure the unit firmlywith 4 foundation (M10<W3/8>) bolts.(Bolts and washers must be purchased locally.)
Dimensions of space neededfor service access areshown in the below diagram.
The diagram below shows a basic example.Explantion of particular details aregiven in the installation manuals etc.
<Foundation bolt height>
Air Discharge
Rear Air Intake
Side Air Intake
1/2 Conduitattachment
ø 22.2<7/8>ø 27.8<1-3/32>
When installing the conduit.Set the attachment to the inner side of each panel.
3/4 Conduitattachment
Scale 1:5
60 <2-3/8> 22.5 <7/8>
5<3/
16>
24.7
<31/
32>
100<3-15/16>
FOUNDATION
OC
H636
Unit: mm<in>
FORM# PEAD-A36AA7 / PUZ-A30NKA7(-BS) -201702Ver2
1340 Satellite Boulevard. Suwanee, GA 30024Toll Free: 800-433-4822 www.mehvac.com
DIMENSIONS: PEAD-A36AA7 & PUZ-A36NKA7 (-BS)
Specifications are subject to change without notice. Copyright © 2017 Mitsubishi Electric US, Inc.