S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
1. CABLE LAYING IN HUME PIPE & MANHOLE
1.1 Providing, laying and fixing following dia RCC pipe
NP2 class (light duty) in ground complete with RCC
collars, jointing with cement mortar 1:2 (1 cement : 2
fine sand) including trenching (75 cm deep) and
refilling etc as required.
1.1.1 450 mm dia 5.00 RM
1.1.2 300 mm dia 30.00 RM
1.1.3 100 mm dia. 10.00 RM
1.2 Providing & making of MAN HOLE chambers of
various sizes as detailed below with 230/ 345 mm
thick brick work plaster inside and outside both, PCC
flooring including providing and fixing of heavy duty
ISI mark SFRC cover with frame complete with RCC
slab and as approved by the Engineer.
1.2.1 450mm X 450 mm (depth 0.700 mtr) - 230mm Thick 1.00 Nos
1.2.2 750mm X 750 mm (depth 0.900mtr) - 230mm Thick 1.00 Nos
1.2.3 1200mm X 1000 mm (depth 1.0mtr) - 230mm Thick 1.00 Nos
2 LT PANELS, SWITCHGEARS AND METERS
Defination : LT Panels are used for LT power
distribution to all Distribution Boards / Sub
Panels.This section covers the following items
INDIAN INSTITUTE OF TECHNOLOGY KANPUR
Tender Notice No. 63 /Elect/2019
SCHEDULE OF QUANTITY
Name of the Contractor
Name of Work: Construction of 5th, 6th, 7th & 8th floor of National Aerosol Facility Building Phase-II (SH:
Electrical Works).
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
2.1 Design , fabrication, wiring, Supply, Installation,
Testing and Commissioning of following Wall
mounted / Floor mounted(including base stand),
415V,3PH, 50Hz extensible and fully
compartmentalized panels complying to IS 8623/93.
The indoor panels shall be IP 42 and outdoor panels
shall be IP 54 type.The Panel shall have proper space
with required clearance for cables, incoming /
outgoing switchgear, CTs, PTs, Ammeter, Voltmeter,
selector switches, Insulated and properly supported
compartmentalized bus bars with heat shrinkable
sleeves along with the other control circuit
accessories within the panel and any other electrical
component mentioned in the Panel SLD.The panel
shall be fabricated out of CRCA not less than 2.0 mm
thick for load bearing members and 1.6mm for the
doors of LT panel.The Panel shall have seven tank pre
treatment process comprising of degreasing, rinsing,
de-rusting, rinsing, phosphatising, rinsing and
passivation followed by powder coat painting having
a paint thickness of 60 microns or as specified.The
Panel shall be Dust/Vermin poof with earth studs as
per
2.1.1 LNP (Lighting Distribution Panel) :
Incomer : 1 Nos. x 2kVp, 50kA, Surge arrestor
Incomer : 1 Nos. x 250 A, Four pole , MCCB, 25kA,
Microprocessor based
Incomer : 1 set. x R,Y,B indication lamp with 2A
control MCB
Incomer : 1 Nos. x Multi Function meter
Incomer : 3 Nos. x CT 250/5A, CL:1, 15VA, Ring type
Bus bar : 1 set. x 415V, 50HZ, 300 A, Four pole , 25kA
aluminium busbar.
Outgoing : 2 Nos. x 100 A, Four pole , MCCB, 25kA,
Microprocessor based
Outgoing : 2 Nos. x 40 A, TPN, MCB, B type,10kA
Outgoing : 2 Nos. x 25 A, TPN , MCB, B type,10kA
Outgoing : 2 Nos. x 32 A, Double pole , MCB, B
type,10kA
Outgoing : 3 sets. x R,G On-Off lamp with 2A control
MCB
5.00 Nos
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
2.2 Supplying and fixing following rating, Dual Pole / four
pole, (three phase and neutral), 230/415 volts, MCB,
quick make and break type with connections, testing
and commissioning etc. as required.
2.2.1 16 Amp, FP MCB , 10kA, C Type (For Air washer) 1.00 Each
2.2.2 25 Amp, FP MCB , 10kA, C Type (For Air washers) 3.00 Each
2.2.3 40 Amp, FP MCCB , 10kA, C type (For 10KVA UPS) 1.00 Each
2.3 S & F metal enclosure suitable for DP/FP MCB/ on
surface or recessed etc as reqd.
5.00 Each
2.4 Supplying and fixing 25Amp rating, Four pole, (Three
phase and neutral), 415 volts, residual current break
over circuit breaker (RCBO), having a sensitivity
current upto 300 milliamperes and breaking capacity
of 10kA in an enclosure complete with connections,
testing and commissioning etc. as required.
1.00 Nos
SAFETY TOOLS & EQUIPMENTS
2.5 Providing & fixing in position 1000 mm wide ,
Electrical Insulating Mats as per IS 15652:2006, 2mm
thick, suitable upto 3.3 KV , fire retardant,no effect of
acids, alkalies and transformer oils, moisture proof,
high tensile strength and texture finish / cloth
impression (Anti slip , marking on top)
10.00 SqM
2.6 Supply & fixing in position approved shock treatment
chart written in English Hindi and Local language.
These charts shall be framed in wooden frame &
covered with clear glass.
3.00 Nos.
3 CABLES, END TERMINATIONS
Defination : The item in this section refers to
incoming and outgoing cabling of sub Panels and
outgoing cabling of main panel along with its end
termination requirements.
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
3.1 Supply of following armoured/Unarmoured/flexible
cables from main panel to sub panels and from sub
panels to final DBs. All the below mentioned cables
shall be 1.1kV grade, XLPE insulated, FRLS type
armoured cables of Al / Cu, whichever applicable
with inner and outer PVC sheath.The said cables shall
confirm IS 7098-1, BS 5467, IEC 60502-1, BS 7889 all
supplymentary.The rate shall include complete
Supply, Installation, testing and commissioning rates
including cost of all tools and accessories required to
Complete the job in full respect.
3.1.1 3.5C x 150 SQMM Armoured AL Cable 200.00 RM
3.1.2 3.5C x 120 SQMM Armoured AL Cable 180.00 RM
3.2 Supplying and drawing following sizes of FRLS PVC
insulated copper conductor, single core cable in the
existing surface/recessed steel/PVC conduit as reqd.
3.2.1 1C x 70 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
40.00 RM
3.2.2 4C x 25 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
290.00 RM
3.2.3 2C x 16 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
100.00 RM
3.2.4 3C x 16 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
100.00 RM
3.2.5 3C x 10 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
80.00 RM
3.2.6 2C x 10 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
150.00 RM
3.2.7 3C x 1.5 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
100.00 RM
3.2.8 3C x 2.5 SQMM PVC INS. PVC SH. FRLS CU. FLEX.
CABLE
100.00 RM
3.2.9 3C x 4 SQMM PVC INS. PVC SH. FRLS CU. FLEX. CABLE 150.00 RM
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
3.2.10 3C x 6 SQMM PVC INS. PVC SH. FRLS CU. FLEX. CABLE 100.00 RM
3.3 Wiring for circuit/ submain wiring alongwith earth
wire with the following sizes of FRLS PVC insulated
copper conductor, single core cable in surface/
recessed steel conduit as required
3.3.1 2 X 4 sq. mm + 1 X 4 sq. mm earth wire 204.00 RM
3.3.2 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 94.00 RM
3.3.3 2 X 10 sq. mm + 1 X 6 sq. mm earth wire 431.00 RM
3.3.4 4 X 4 sq. mm + 2 X 4 sq. mm earth wire 137.00 RM
3.3.5 4 X 6 sq. mm + 2 X 6 sq. mm earth wire 245.00 RM
3.3.6 4 X 10 sq. mm + 2 X 6 sq. mm earth wire 443.00 RM
3.3.7 4 X 16 sq. mm + 2 X 6 sq. mm earth wire 298.00 RM
3.4 Laying of on number PVC insulated and PVC
sheathed/XLPE power cable of 1.1 kv grade of size
following sizes direct in ground including excavation,
snd cushioning, protective covering and refilling the
trench etc as required.
3.4.1 less than 35sqmm 120.00 Mtr.
3.4.2 exceeding 35 sq.mm.but not exceeding 95 sqmm 250.00 Mtr.
3.4.3 exeeding 95 sq.mm.but not exceeding 185 sqmm 120.00 Mtr.
3.5 Laying of on number additional PVC insulated and
PVC sheathed/XLPE power cable of 1.1 kv grade of
size following sizes direct in ground in the same
trench in one tier horizontal formation including
excavation, snd cushioning, protective covering and
refilling the trench etc as required.
3.5.1 less than 35sqmm 120.00 Mtr.
3.5.2 exceeding 35 sq.mm.but not exceeding 95 sqmm 250.00 Mtr.
3.5.3 exeeding 95 sq.mm.but not exceeding 185 sqmm 120.00 Mtr.
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
3.6 Laying of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 KV grade of
following size in the existing RCC/ HUME/ METAL
pipe as required.
3.6.1 Upto 35 sq. mm 30.00 Mtr.
3.6.2 Above 35 sq. mm and upto 95 sq. mm 40.00 Mtr.
3.6.3 Above 95 sq. mm and upto 185 sq. mm 15.00 Mtr.
3.7 Laying of one number PVC insulated and PVC
sheathed / XLPE power cable of 1.1 KV grade of
following size in the existing masonry open duct as
required.3.7.1 Upto 35 sq. mm 30.00 Mtr.
3.7.2 Above 35 sq. mm and upto 95 sq. mm 40.00 Mtr.
3.7.3 Above 95 sq. mm and upto 185 sq. mm 15.00 Mtr.
3.8 Laying and fixing of one number PVC insulated and
PVC sheathed / XLPE power cable of 1.1 KV grade of
following size on wall surface as required.
3.8.1 Upto 35 sq. mm (clamped with 1mm thick saddle) 10.00 Mtr.
3.8.2 Above 35 sq. mm and upto 95 sq. mm (clamped with
25x3mm MS flat clamp)
20.00 Mtr.
3.8.3 Above 95 sq. mm and upto 185 sq. mm (clamped
with 25/40x3mm MS flat clamp)
10.00 Mtr.
3.9 S/F, copper cable lug suitable for following size of
conductor.
3.9.1 2.5 Sqmm 24.00 Nos.
3.9.2 4 Sqmm 24.00 Nos.
3.9.3 6 Sqmm 24.00 Nos.
3.9.4 10 Sqmm 24.00 Nos.
3.9.5 16 Sqmm 24.00 Nos.
3.9.6 25 Sqmm 24.00 Nos.
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
3.9.7 70 Sqmm 12.00 Nos.
3.10 Supplying and making end termination with brass
compression gland with aluminium lugs for following
size of PVC insulated & PVC sheathed/XLPE
aluminium cable of 1.1kV grade as reqd.
3.10.1 3.5C x 150 SQMM A2XFY 4.00 Each
3.10.2 3.5C x 120 SQMM A2XFY 6.00 Each
3.10.3 3.5C x 95 SQMM A2XFY 10.00 Each
3.10.4 3.5C x 70 SQMM A2XFY 2.00 Each
3.10.5 3.5C x 50 SQMM A2XFY 2.00 Each
3.10.6 3.5C x 35 SQMM A2XFY 8.00 Each
3.10.7 3.5C x 25 SQMM A2XFY 4.00 Each
3.10.8 2C x 6 SQMM A2XFY 14.00 Each
4 CABLES TRAYS & RACEWAYS
Supply and fixing of factory fabricated GI perforated
type hot dip galvanised cable trays, with radial bends,
suspenders and supports as per specification and of
the following sizes.
4.1.1 100 mm width X 50 mm depth X 1.6 mm thickness 45.00 RM
4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness 30.00 RM
4.1.3 300 mm width X 50 mm depth X 1.6 mm thickness 40.00 RM
4.1.4 450 mm width X 50 mm depth X 2.0 mm thickness 35.00 RM
4.2 Supply and fixing of factory fabricated ladder type
hot dip galvanised cable trays, with necessary bends,
cross arms and supports as per specification and of
the following sizes.
4.2.1 300 mm width X 50 mm depth X 2.0 mm thickness 10.00 RM
4.2.2 450 mm width X 50 mm depth X 2.0 mm thickness 12.00 RM
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
RACEWAYS
4.3 Supply, Installation testing and commissioning of
metallic adaptable raceway system ,
compartmentalised of following mentioned sizes
suitable for passing through walls and floors as per
the layout ,suitable for FRLS wires confirming to
IS:694 and extra low voltage cables for data
/AV/telephone. The raceway shall have Z- section,
hole with thread for cover screw, coupler plate,
cover, junction box, fly cover , inspection box flushed
to the finished floor at suitable distances etc as
required. The screw for cover fixing shall be counter
sunk type.The cover shall have a thickness of
2mm.The cost shall also include the cost of bends
couplers and any other suporting accessories.
4.3.1 75 mm x 40 mm x 1.6 mm 24.00 RM
4.3.2 100 mm x 40 mm x 1.6 mm 20.00 RM
4.3.3 150 mm x 40 mm x 1.6 mm 40.00 RM
4.3.4 200 mm x 40 mm x 1.6 mm 260.00 RM
4.3.5 300 mm x 40 mm x 2 mm 121.00 RM
4.4 Supplying, installation DLP mini- trunking 32mm x
20mm and accessories white-system with
independent cover- without central partion etc. as
reqd.
100.00 RM
4.5 Supply and fixing of following items for plastic
trunking accessories suitable for size 32 mm x 20 mm
4.5.1 End cap 10.00 Nos.
4.5.2 Internal angle/ External angle 20.00 Nos.
4.5.3 Changeable flat angle 20.00 Nos.
4.5.4 Flat Junction 10.00 Nos.
4.6 Providing and fixing DLP plastic trunking of size 105
mm x 50 mm without cover on surface as reqd.
150.00 RM
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
4.7 Providing and fixing 85 mm width flexible cover of
DLP plastic trunking. (size 105 mm x 50 mm.)
150.00 RM
4.8 Supply and fixing of following items for plastic
trunking accessories suitable for size 105 mm x 50
mm.4.8.1 End cap 8.00 Nos.
4.8.2 Internal angle. 12.00 Nos.
4.8.3 External angle 10.00 Nos.
4.8.4 Flat Junction 4.00 Nos.
4.8.5 Changeable flat angle 8.00 Nos.
4.8.6 Separation partitions 130.00 RM
4.8.7 cover joint 20.00 Nos.
4.8.8 Base joint 40.00 Nos.
5 DISTRIBUTION BOARDS
5 Supplying and fixing following way, single pole and
neutral, sheet steel, MCB distribution board, 240
volts, on surface/ recess, complete with tinned
copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing
etc. as required. (But without MCB/RCCB/Isolator)
5.1.1 2 + 8 Way Double door 4.00 Each
5.1.2 2 + 12 Way Double door 4.00 Each
5.2 Supplying and fixing following way, horizontal type
three pole and neutral, sheet steel, MCB distribution
board, 415 V, on surface/ recess, complete with
tinned copper bus bar, neutral bus bar, earth bar, din
bar, interconnections, powder painted including
earthing etc. as required.(But without MCB/ RCCB/
Isolator)
5.2.1 8 way ( 4 + 24 ), Double door 4.00 Each
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
5.3 Supplying and fixing following way prewired vertical
type TP&N MCB distribution board of steel sheet for
415 volts on surface/ recess complete with loose wire
box of sheet steel, dust protected, duly powder
painted, inclusive of 200 amps tinned copper bus bar,
common neutral link, earth bar, din bar for mounting
MCB's, terminal connectors for all incoming and
outgoing circuits, duly prewired with adequate size of
FR PVC insulated copper conductor upto the terminal
connector/ neutral link, earthing etc as required (But
without MCB/ RCCB/ Isolator).
5.3.1 8 way Double door 1.00 Each
5.3.2 12 way Double door 2.00 Each
5.4 S & F following rating and pole, 240 volts 'C' curve 10
kA, lexic MCB of following pole in the existing MCB
DB complete with connection, testing &
commissioning etc as reqd. 5.4.1 Single Pole ( 5 Amp to 32 Amp ) 213.00 Each
5.4.2 Double Pole ( 5 Amp to 32 Amp ) 2.00 Each
5.4.3 Tripple Pole ( 5 Amp to 32 Amp ) 7.00 Each
5.4.4 Tripple pole & Neutral ( 5 Amp to 32 Amp ) 1.00 Each
5.4.5 Single Pole ( 40 Amp to 63 Amp ) 5.00 Each
5.4.6 Double Pole ( 40 Amp to 63 Amp ) 8.00 Each
5.4.7 Tripple pole ( 40 Amp to 63 Amp ) 7.00 Each
5.4.8 Tripple pole & Neutral ( 40 Amp to 63 Amp ) 5.00 Each
5.5 Supplying and fixing following rating, double pole,
(single phase and neutral), 240 volts, residual current
circuit breaker (RCCB), having a sensitivity current
upto 300 milliamperes in the existing MCB DB
complete with connections, testing and
commissioning etc. as required.
5.5.1 63 amps 12.00 Each
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
5.6 S & F metal box of following sizes ( nominal ) on
surface or recess with suitable size of MS sheet cover
in the front I/c painting etc as reqd.
5.6.1 375 mm x 175 mm x150 mm deep 2.00 Each
5.6.2 450 mm x 175 mm x175 mm deep 3.00 Each
5.6.3 675 mm x 175 mm x175 mm deep 1.00 Each
5.6.4 900 mm x 175 mm x175 mm deep 1.00 Each
5.6.5 975 mm x 175 mm x175 mm deep 1.00 Each
5.6.6 1675 mm x 175 mm x175 mm deep 1.00 Each
5.7 Providing and fixing following rating and breaking
capacity four pole 415V 50Hz MCCB in existing
cubicle panel board including drilling holes in cubicle
panel, making connections, etc as required.
5.7.1 125 Amp, 25KA 2.00 Each
55.8 S&F connecting and commissioning indipendent
mounting of 125/200 Amp MCCB enclosure make
legrand or its equivalent approved make in
surface/recess I/c cutting the wall and making good
the same in case of recessed as reqd.
2.00 Each
6 POINT WIRING AND SWITCH SOCKETS
6.1 Wiring for light point/ fan point/ exhaust fan point/
call bell point with 1.5 Sq.mm FRLS PVC insulated
copper conductor single core cable in surface /
recessed steel conduit, with modular switch, modular
plate, suitable GI box and earthing the point with 1.5
Sq.mm. FR PVC insulated copper conductor single
core cable etc as required.
6.1.1 Group C 575.00 Nos.
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
6.2 Wiring for twin controlled Light point with1.5 sq.mm
FRLS PVC insulated Copper Conductor single core
cable in surface / recessed steel conduit, 2 way
modular switch, modular plate, suitable GI Box and
earthing the point with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable etc as reqquired.
6.2.1 Group C 5.00 Nos.
6.3 Supplying and fixing suitable size GI box with
modular plate and cover in front on surface or in
recess, including providing and fixing 3 pin 5/6 amps
modular socket outlet and 5/6 amps modular switch,
connection etc as required. (for light plugs to be used
in non reseidential buildings).
216.00 Nos.
6.4 Supplying and fixing suitable size GI box with
modular plate and cover in front on surface or in
recess, including providing and fixing 6 pin 5/6 &
15/16 amps modular socket outlet and 15/16 amps
modular switch, connection etc as required.
178.00 Nos.
6.5 Supplying and fixing 20 amps, 240 volts, SPN
industrial type, socket outlet, with 2 pole and earth
metal enclosed plug top along with 20 amps ' C '
series SP, MCB, in the sheet steel enclosure, on
surface or in recess, with chained metal cover for the
socket outlet and complete with connections, testing
and commissioning etc as required.
44.00 Nos.
6.5 Supplying and fixing of following sizes of steel conduit
along with accessories in surface/recess including
painting in case of surface conduit, or cutting the wall
and making good the same in case of recessed
conduit as reqd.
6.6.1 20 mm dia 1000.00 RM
6.6.2 25 mm dia 1500.00 RM
6.6.3 32 mm dia 300.00 RM
6.6.4 40 mm dia. 200.00 RM
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
6.7 S & L following size of GI pipe in ground after digging
the trench & refilling the same ramming the loose soil
and making good the same as reqd.
6.7.1 40 mm dia. 40.00 RM
7 LIGHT FIXTURES, CEILING FANS/EXHAUST/WALL
FANS 7.1 Supply, Installation, Testing and Commissioning of
following LED Lighting fixtureswith as per the
technical specifications and all accessories including
electronic drivers, dffiusers and all tools and
accessories required to complete the job in full
respect
7.1.1 18w LED surface mounted Light 107.00 Nos.
7.1.2 18w LED recess mounted Light 107.00 Nos.
7.1.3 12w LED surface mounted Light 200.00 Nos.
7.1.4 12w LED recessed Light 20.00 Nos.
7.1.5 5W LED Mirror Light 20.00 Nos.
7.1.6 20W LED Batten Light 50.00 Nos.
7.1.7 40W 4 feet lon surface mounting/ceiling suspeneded
LED Light
50.00 Nos.
7.1.8 10w Bulk Head Fittings 12.00 Nos.
7.1.9 1x9/10WLED Wall mounted Light 30.00 Nos.
7.1.10 36W 2'X2' Sqaure Recessed Light 250.00 Nos.
7.2 Supply, Installation, Testing and Commissioning of
following fans as per the technical specifications and
all accessories including hanging pendent, fully
painted with inbuilt motor and capacitor. and all tools
and accessories required to complete the job in full
respect
7.2.1 1200 mm Sweep ceiling fan 75.00 Nos.
7.2.2 400 mm Sweep Wall Fan 15.00 Nos.
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
7.2.3 300 mm Exhaust fan 20.00 Nos
7.3 Supply and fixing ceiling fan box 150 mm dia x 75 mm
deep fabricated from 16 SWG MS sheet with cover
for the top and 3 mm hylam sheet with brass screw,
cover for the bottom having suitable holes for fan
hook & conduit entry including 12 mm dia MS rod
hook duly bend in shape and projecting 150mm on
either side of box , complete as reqd.
75.00 Nos
8 EARTHING INSTALLATIONS
8.1 Earthing with GI earth electrode 50mm dia x 3 mtr
length including earth enhancing compound (Jam Fill
quality product) and PIT cover for earthing pit etc as
reqd. (193GI JMV)
4.00 Nos.
8.2 Earthing with Copper bonded earth electrode 50mm
dia x 3 mtr length including earth enhancing
compound (Jam Fill quality product) and PIT cover for
earthing pit etc as reqd. (503 CBE JMV).
4.00 Nos.
Earth conductors
8.3 Providing and fixing 25 mm X 5 mm copper strip in 40
mm dia G.I. pipe from earth electrode including
connection with brass nut, bolt, spring, washer
excavation and re-filling etc. as required.
150.00 RM
8.4 Supply, Installation, Testing and Commissioning of
following Earth strips/wire on surface or in recess ats
as required.
8.4.1 25 x 5 sqmm GI strip 200.00 RM
8.4.2 25 x 5 sqmm CU strip 150.00 RM
8.4.3 6 SWG GI Wire 200.00 RM
9 LIGHTNING PROTECTION SYSTEM
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
9.1 Supply, Design & Testing of Prevectron type 3rd
Generation Controlled Early Streamer Emission
(CESE) lightning conductor equipped with a tinned
copper central pick up rod. Full electrical continuity
between the tip and the earth point shall be ensured.
Fully autonomous (no battery, no external power
supply required) which shall collect ambient energy
through a lower series of electrodes. Timing of the
streamer emission controlled with an electronic
device that detects the lightning and triggers a
streamer (3.5 KV and 20 A). Manufactured as per NFC
17-102.
A tester/ testing process corresponding specifically to
the airterminal shall be available for the maintenance
and ensure the healthiness of the unit.
Protection Radius = 26 meters
1.00 Set
9.2 Elevation pole made of GI with a dia of 35mm to
50mm with a thread at the top to fix the unit. Base
plate, mounting bracket, clamps and all required
fixing accessories . (The base of the down conductor
should be protected from accidental knocks and
other damage by means of a 2 meters stainless-steel
or PVC protection sheath fixed to the structure.)
(5meter ht. considered)
1.00 Set
9.3 Supply of Wireless Remote Control unit required only
for testing the Prevectron air terminal.
1.00 Set
9.4 Down Conductor :Supply of Test Clamp to connect
the down conductor to the earth termination and
disconnect the down conductor from the earth
termination for regular checks of the earth
termination resistance value.
2.00 Set
9.5 Performance Recording Equipment : Supply of
Lightning Flash Counter. Electronically controlled,
register every strike between 1000 A to 100 KA for a
8/20 microsecond peak current. Tested in High
Voltage Laboratory (CPRI).
1.00 Set
9.6 Supply, Installation testing and commissioning of
conventional type franklin rod with itss PCC base
support to be mounted on the highest point of the
building structure along with downleads.
1.00 Set
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
10 TEL. & DATA SYSTEM
Defination : This includes the provisions for
Telephone, Intercom, Data. This includes following
items
10.1 Supplying and drawing following pair 0.5 Sq.mm FR
PVC insulated copper conductor, unarmoured
telephone cable in the existing surface/recessed
steel/PVC conduit as reqd.
10.1.1 2 Pair 500.00 RM
10.2 S&L, connecting and commissioning 50 pairs jelly
filled un-armoured telephone cable PVC insulated
and PVC sheathed annealed tinned copper
conductor.
10.2.1 Direct in ground I/c excavation, sand cushioning,
protective covering and refilling the trench etc. as
reqd.
80.00 RM
10.2.2 On surface with MS clamp 10.00 RM
10.2.3 In pipe 5.00 RM
10.2.4 In open duct 5.00 RM
10.3 S & F following rating moduler RJ-11 telephone jack
(1M) complete with moduler base & cover plate etc
as reqd.
20.00 Each
10.4 Fixing, Internet Box of size 75mm x 75mm x 40 mm
including brass screw on surface / recessed as reqd.
50.00 Each
10.5 Drawing of computer network cable in existing pipe /
casing and capping as reqd including numbering the
wires at both the ends.
1400.00 RM
10.6 Fixing of telephone DP/network rack ( HUB ) on wall
floor with suitable brick foundation on bolts and nut
etc. as reqd.
3.00 Nos.
11 FIRE ALARM SYSTEM
Note: Colour coding for conduits to be done for
different systems. The whole length of conduits to
be painted.
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
All AC's and fire Escape VTPN DB shall be integrated
with main fire panel so that in case of fire signal, all
the AC's will be switched off and fire escape VTPN DB
will work.
2 Layer For above false ceiling and below false ceiling
11.1 Supply, installation, connecting, testing and
commissioning of addressable photoelectric type
Smoke Detectors with mounting base, blinking LED
etc. complete as required.
8.00 Nos
11.2 Supply, installation, connecting, testing and
commissioning of addressable Type Multi Sensor
Smoke Detectors with mounting base etc. complete
as required.
99.00 Nos
11.3 Supply, installation, connecting, testing and
commissioning of addressable rate of rise cum fixed
temperature Heat Detectors with mounting base,
blinking LED etc. complete as required.
2.00 Nos
11.4 Supply, installation, connecting, testing and
commissioning of Addressable Hooters cum strobe
min. 95 db output , the cost includes of control
module if required
8.00 Nos
11.5 Supply, installation, connecting, testing and
commissioning of Addressable Manual Call Box in
ABS plastic as required complete.
8.00 Nos
11.6 Supply, installation, connecting, testing and
commissioning of addressable fault Isolator
11.00 Nos
11.7 Supply, installation, connecting, testing and
commissioning of addressable control module for
A.C. & Access Control System
4.00 Nos
11.8 Supply, installation, connecting, testing and
commissioning of addressable monitor module for
integration of builder panel to main fire panel
4.00 Nos
11.9 Supply, installation, connecting, testing and
commissioning of UL Listed Addressable Beam
Detector with Receiver, transmitter including all
accessories as required.
2.00 Set
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
11.10 Supply, installation, connecting, testing and
commissioning of Control Relay Module
4.00 Nos
11.11 Supply, installation, connecting, testing and
commissioning of Response indicator.
2.00 Nos
11.12 Supply Installation, Testing & Commissioning of UL
listed, 9th edition 32 bit Fire alarm control panel
having microprocessor based 2 loop cards
expandable upto 4 loops with 252 intelligent points /
loop cards in any flexible combination (detectors/
devices ) . The panel have 6 inch long LCD touch
screen and LED's for displaying system status. In
addition to the digital screen, the user can view a
graphics map which can show a simple building floor
plan. The panel shall provide the user with 40
programmable macro or function buttons, which can
be programmed for a variety of usages like
controlling AHU's, Pressurisation fans, fire pumps,
monitoring of flow switches in fire pipe line etc. The
panel shall have 240 V AC power supply, automatic
battery charger, 24 V SMF batteries sufficient for 24
hour in standby and 15 minutes in alarm complet as
per specification. The panel shall be able to give
relay outputs to the PA system if applicable.
1.00 Nos
11.13 Providing and fixing in position the following G.I.
flexible conduits including all accessories
11.13.1 1.6mmwall thickness 20mm dia 50.00 RM
11.13.2 1.6mm wall thickness 25 mm dia 60.00 RM
11.14 Providing and fixing in position 1.2mm thick M.S.
outlet boxes for housing smoke detectors/heat
detectors including providing 3 mm thick hylam sheet
cover as required11.14.1 75mm x 75mm x 75mm 4.00 Nos
11.15 Supplying and drawing following sizes of FRLS PVC
insulated copper conductor, single core cable in the
existing surface/recessed steel/PVC conduit as reqd.
11.15.1 2 core x 1.5 sq. mm 1500.00 RM
S. No Description of Items Qty Unit Rate in Figures
in Rupees
Amount
12 PUBLIC ADDRESS SYSTEM
12.1 Supply,installation,testing and commissioning of
following Philips (BOSCH) make Music
Accessories/Equipments.12.1.1 Ceiling Speaker Unit 6 Watts LHM 0606/10 45.00 Nos.
12.1.2 Wall mounted Speaker Unit 6 Watts 19.00 Nos.
12.1.3 Power Amplifier, 480 Watts with output transformer
etc. complete.
1.00 Nos.
12.1.4 Power Amplifier, 120 Watts with output transformer
etc. complete.
1.00 Nos.
12.1.5 System pre-amplifier with suitable size of PA
controller, Router, console, call station and call
station keypad for above system
1.00 Nos.
12.1.6 Single DVD player Philips/Samsung. 1.00 Nos.
12.1.7 6 Zone call station ( Bosch Make LBB 1946/10) 1.00 Nos.
12.1.8 Control Unit (with volume and on/off switch) Philips
(Smooth stepless control, but the control shall be
through dimmer switch, the make of which will be
same as the make of light control switches)
1.00 Nos.
12.1.9 Philips Microphone unit Cat no. LBD 8292 1.00 Nos.
12.1.10 Equipment Rack complete with monitor unit,
speaker, power supply control etc. President make
Suitable for above system
1.00 Nos.
12.1.11 Main Termination Box 1.00 Nos.
12.1.12 Supply and drawing of 1.5 sq. mm Twin Core
shielded Speaker Cable in existing conduit.(Fusion
/Excel/BonTon)
700.00 RM
Total Rs.
Top Related