Thumb rules for HVAC design
36 | P a g e
Thumb rules for HVAC design
1 | P a g e
HEAT LOAD DETAILS
1. DBT, WBT, RH and daily range from ISHRAE handbook P. No – 1.1 to 1.3
Outside Conditions Month DBT WBT RH GR/LB
BangaloreSummer April 96 78 45 116Monsoon September 82 78 82 140Winter January 58 54 78 56
ChennaiSummer May 103 82 41 132Monsoon November 83 80 88 152Winter January 65 57 60 58
MumbaiSummer April 95 83 60 151Monsoon July 85 82 88 162Winter January 65 58 65 60
HyderabadSummer May 106 78 28 100Monsoon September 85 81 82 154
Winter December 55 48 60 39
New DelhiSummer May 110 75 20 75.81Monsoon Aug 95 83 60 154.37Winter January 45 41 70 31.93
Kolkatta
Summer May 100 83 49 144Monsoon July 90 83 85 161
Winter December 56 48 55 37
2. Eq. temp diff for wall (∆T F) = 4 PM eq. temp value (ISHRAE handbook table 9 in P. No – 1.14) +
correction to eq. temp (Table 11P. No – 1.15)
3. Q wall(BTU/Hr) = U x A x ∆T 1
4.
Solar heat gain through glass (BTU/Hr Sft) = 4 PM value (ISHRAE handbook table 7 in P. No – 1.8
to 1.10)
5. QGlass(BTU/Hr) = (U x A x ∆T) + (SHG x A x SF) where (∆T = OA Temp – IA Temp)
6. Fresh air CFM can be derived with the sample sheet attached (ASHRAE Ventilation Standard
62_1_2004 Table 6.1)
7. Fresh Air CFM = (Volume x ACPH) / 60
8. Sensible Fresh air infiltration load = Fresh Air CFM x ∆T x 1.08 x Coil BF (ISHRAE handbook
table 14 in P. No – 1.16)
9.
Latent Fresh air infiltration load = Fresh Air CFM x ∆G x 0.68 x Coil BF (ISHRAE handbook table14 in P. No – 1.16)
10. Typical bypass factors - Three Row coil BF=0.176 (17.6 %), Four Row coil BF=0.12 (12 %), Six
Row coil BF=0.06 (6%)
11. Optimum velocity of air through coil is 450 fpm
12. HRW ηηηη = (OSA Temp – Temp after HRW) / (OSA Temp – Return Air Temp)
13. Sensible lighting load = W/sft x Area
8/20/2019 HVAC Thumprule Handbook
3/19
8/20/2019 HVAC Thumprule Handbook
4/19
Thumb rules for HVAC design
34 | P a g e
6. Various types of camera were used for monitoring as per the requirement for 24 x 365. Namely
Fixed dome, Varifocal, PTZ(Pan Tilt Zoom) Camera.
7.
CCTV also can be linked with FPCP in modern system to know exactly how the fire or smokecondition.
Public addressable system
1. Also a security system runs all the floors and parking’s and used for announcements etc….
2. Systems consist of various models of speakers, amplifiers and micro phones.
3. System can be integrated with FACP and CCTV
4. Three type of speaker namely ceiling mounted, wall mounted, horn speaker can be used.
Access Control System
1. Smart card reader, Proximity card reader or Biometric card reader can be used. Biometric can be
retina or finger print reader
2. From card reader signal is sent to controller, which can be connected to software for monitoring
and for report generation using access control software.
3. Controllers to PC cat 5 cables are used. Controller to reader / push button 4c x 0.75 sq mm cable
is used
Building Management System
1. Field devices are connected to DDC (Digital Direct Controller), which has digital or analog input
and output. Analog input is for sensors and digital input is for switches.
2. DDC can be 16 or 32 bits. Various inputs are connected to it. It acts as a interface and converts
them into binary language which a system can understand.
3. This is then transferred to Router using RS 485 cable, which is then connected to PC using RS
232 cable.
This also provides facility for third party integration such as electrical, plumbing, DG, energy meter, ups, VFD etc .
SITE ACTIVITIES
1. Duct size as per dwg
2. Duct supports for every 8 to 10 feet
3. Duct to duct flange gap should be arrested properly
Thumb rules for HVAC design
3 | P a g e
P a r t i c u l a r s
N O R T H
S O U T H
E A S T
W E S T
N E
S E
S
N W
B A N G A L O R E
S u m m e
r
S o l a r H e a t G a i n T h
r o u g h G l a s s ( B T U / H r S f t )
3 9
1 1
1 1
1 6 3
1 1
1 1
9 4
1 3 0
M o n s o
o n
1 1
1 3
1 1
1 6 4
1 1
1 1
1 2 7
1 0 3
W i n t e r
9 6 5 9
1 4 3
9 9 1 5 3
3 7
C H E N N A
I S u m m e
r 3 9
1 1
1 1
1 6 3
1 1
1 1
9 4
1 3 0
M o n s o o n
1 1
1 3
1 1
1 6 4
1 1
1 1
1 2 7
1 0 3
W i n t e r
9 6 5 9
1 4 3
9 9 1 5 3
3 7
M U M B A I S
u m m e
r 1 1
1 1
1 1
1 6 5
1 1
1 1
1 1 3
1 1 8
M o n s o
o n
1 1
2 2
1 1
1 6 3
1 1
1 1
1 3 6
8 7
W i n t e r
8 6 9 8
1 2 8
8 8 1 4 4
2 6
H Y D R A B A D
S u m m e r 1
1 1 1
1 1
1 6 5
1 1
1 1
1 1 3
1 1 8
M o n s o
o n
1 1
2 2
1 1
1 6 3
1 1
1 1
1 3 6
8 7
W i n t e
r 8 6 9 8
1 2 8
8 8 1 4 4
2 6
N e w D e l h i S
u m m e r 1
4 1 2
1 2
1 6 4
1 2
1 2
1 0 0
1 2 3
M o n s o
o n
1 1
1 3
1 1
1 6 5
1 1
1 1
1 2 7
1 0 0
W i n t e r
6 6 8 6 1 0 9 6 6 1 2 7 1 6
K o l k a t t a
S u m e r 2
3 1 2
1 2
1 6 3
1 2
1 2
8 5
1 3 8
M o n s o
o n
2 3
1 2
1 2
1 6 3
1 2
1 2
8 5
1 3 8
W i n t
e r 7 7 4 7
1 1 8
7 7 1 3 9
1 8
8/20/2019 HVAC Thumprule Handbook
5/19
8/20/2019 HVAC Thumprule Handbook
6/19
8/20/2019 HVAC Thumprule Handbook
7/19
Thumb rules for HVAC design
6 | P a g e
40 sq.ft/person for Corridors in other floors & Hypermarket
Lighting :
5 Watts/sq.ft for Shops, Hypermarket
3 Watts/sq.ft for Common areas, Foodcourt,Café, Restaurant
1 Watts/sq.ft for Theatres & Projector rooms.
Equipment load :
1 Watts/sq.ft for Shops
1.2 Watts/sq.ft for Café, Restaurant, Foodcourt
2 Watts/sq.ft for Anchor Shops & Departmental store
3.7 Watts/sq.ft for Hypermarket
10 kW/projector
Fresh Air CFM :
15 cfm/person for Hypermarket & Theatres
1 ACPH for others
1200 cfm/projector for Projector room
Hotels :
Occupancy :
- 2 person/room
- 25 sq.ft/person - for Dining rooms, Training Rooms, GYM, SPA & Business Center
- 12 sq.ft/person - for Banquet Hall & Pre function & Bar.
- 100 sq.ft/person - for Corridor.
Lighting :
1.5 Watts/sq.ft
Equipment :
- 1.2 Watts/sq.ft for Coffee shop&Gym
- 5 kW for Banquet hall
- 3 kW for Pre function
- 150 Watts/Computer for Offices
Fresh Air CFM :
25 cfm/person - for Rooms,GYM
Thumb rules for HVAC design
31 | P a g e
11. Human comfort chart
ELECTRICAL
1. For electrical load calculation – Lighting 1.5 W/sft, Power load – 0.75 W/sft, Socket power (5 A)
-100 W and for 15A – 500 W
8/20/2019 HVAC Thumprule Handbook
8/19
8/20/2019 HVAC Thumprule Handbook
9/19
8/20/2019 HVAC Thumprule Handbook
10/19
Thumb rules for HVAC design
28 | P a g e
21 20 2 3 24 21 23 27 1 2525 20 49 3 16 25 23 25 2 1729 21 30 2 51 29 23 17 3 7
DeclinationEquationof time Declination
Equationof time
Date Deg Min Min Sec Date Deg Min Min SecJuly 1 23 10 -3 31 Aug 1 18 14 -6 17
5 22 52 4 16 5 17 12 5 599 22 28 4 56 9 16 6 5 33
13 21 57 5 30 13 14 55 4 5717 21 21 5 57 17 13 41 4 1221 20 38 6 15 21 12 23 3 1925 19 50 6 24 25 11 2 2 1829 18 57 6 23 29 9 39 1 10
Declination Equationof time Declination Equationof timeDate Deg Min Min Sec Date Deg Min Min SecSep 1 8 35 0 15 Oct 1 -2 53 10 1
5 7 7 1 2 5 4 26 11 179 5 37 2 22 9 5 58 12 27
13 4 6 3 45 13 7 29 13 3017 2 34 5 10 17 8 58 14 2521 1 1 6 35 21 10 25 15 1025 0 32 8 0 25 11 50 15 4629 2 6 9 22 29 13 12 16 10
Declination
Equation
of time Declination
Equation
of timeDate Deg Min Min Sec Date Deg Min Min Sec Nov 1 -14 11 16 21 Dec 1 -21 41 11 16
5 15 27 16 23 5 22 46 9 439 16 38 16 12 9 22 45 8 1
13 17 45 15 47 13 23 6 6 1217 18 48 15 10 17 23 20 4 4721 19 45 14 18 21 23 26 2 1925 20 36 13 15 25 23 25 0 2029 21 21 11 59 29 23 17 -1 39
5. The position of the sun is generally given as azimuth and altitude angle
6.
Azimuth represents horizontal angle of the sun relative to the north.
7. Altitude represents the vertical angle the sun makes with the horizontal ground plane.
Thumb rules for HVAC design
9 | P a g e
8/20/2019 HVAC Thumprule Handbook
11/19
8/20/2019 HVAC Thumprule Handbook
12/19
8/20/2019 HVAC Thumprule Handbook
13/19
Thumb rules for HVAC design
12 | P a g e
SHAFT SIZING
1. Pipe sizing can be done both using Chart and formula.
2.
Pipe dia (mm) = Sqrt (Gpm x 0.000011) x 2000 for 6 fps velocity3. Pipe dia can be calculated using ∆P = (4 x f x L x V2) / 2 x g x D, Where f is the friction
factor, L is the Equivalent Length, g is the acceleration due to gravity 9.8 m/s2 and V is the
velocity in m/s
4. Pipes going outside the building, Underground and diameter greater than 350mm should be
provided the insulation thickness of 3”. Others should be insulated by 2”.
5. For example, if the pipe dia is 14”, shaft size required will be 14”+6”(insulation on pipe
dia)=20” (supply) + 20” (return) + 18”(Space in between). So shaft length will
be(6”+20’+6”+20”+6”)=58”. (20”+6”+6” )= 32” will be the width of the shaftAHU SIZING
1. Select AHU Size for the given CFM & TR
2. Provide 1.5m space in piping side and 1m space in filter side. Minimum of 150mm in all
other sides.
3. CFM = Velocity x Area
4. Coil face velocity is limited to 500 FPM
VENTILATION AIR CHANGES
1.
Toilet, Electrical – 15ACPH
2. Basement – 6 ACPH (normal) 30 (Fire mode)
3.
Kitchen – 45 to 60 for big – 15 for small 15 ACPH is sufficient
4. Fresh air has to be supplied at 80% of exhaust air in order to maintain negative pressure
5.
For kitchen hood exhaust, CFM = Hood Area x 120 fpm. 80% of exhaust will be ducted as
a fresh air into the kitchen
Thumb rules for HVAC design
25 | P a g e
8/20/2019 HVAC Thumprule Handbook
14/19
Thumb rules for HVAC design
24 | P a g e
2. Primary pump head = Pipe eq. length till secondary pump + primary pump outlet valves +
chiller evaporator valves + secondary pump inlet valves + evaporator pressure drop
3.
Secondary pump head = pipe length till farthest AHU + AHU coil pressure drop + AHUvalves + Secondary pump outlet valves + Pipe length till Primary pump + Primary pump
inlet valves
4. Condenser pump head = Pipe length till cooling tower + Nozzle pressure loss + clearance
height + chiller condenser + condenser pump valves + Chiller condenser side valves
5. Valve Losses
Isolation Valve Balancing/ 2way valve NRV Y Strainer
Diameter EquivalentLength Diameter EquivalentLength Diameter EquivalentLength Diameter EquivalentLength25 29 25 15 25 10 25 1032 38 32 20 32 14 32 1440 43 40 24 40 16 40 1650 55 50 30 50 20 50 2065 69 65 35 65 25 65 2580 84 80 43 80 30 80 30100 100 100 50 100 35 100 35125 120 125 58 125 40 125 40150 140 150 71 150 50 150 50200 170 200 88 200 60 200 60
250 220 250 115 250 80 250 80300 280 300 145 300 100 300 100350 320 350 165 350 120 350 120400 360 400 185 400 135 400 135450 410 450 210 450 150 450 150500 460 500 240 500 165 500 165550 520 550 275 550 200 550 200600 610 600 320 600 240 600 240
6. Closed circuit friction loss
Thumb rules for HVAC design
13 | P a g e
8/20/2019 HVAC Thumprule Handbook
15/19
Thumb rules for HVAC design
14 | P a g e
LIGHTING LOAD TO BE CONSIDERED AS PER ECBC
ELECTRICAL LOAD
1. Air cooled chiller – 1.3KW/TR
2.
Water cooled centrifugal chiller – 0.65KW/TR, Water cooled screw chiller – 0.75 Kw/TR
3. Primary Pump = TR x GPM x Head x 0.745
3960 x Efficiency
4. AHU = CFM x Static x 0.745
6356 x Fan Efficiency
5.
Cooling tower = TR x 300 x 1x 0.745
Thumb rules for HVAC design
23 | P a g e
PUMP HEAD CALCULATION
1. Pipe friction can be calculated from the chart below
8/20/2019 HVAC Thumprule Handbook
16/19
Thumb rules for HVAC design
22 | P a g e
11. Where hv = (V / 4005) ^ 2
Thumb rules for HVAC design
15 | P a g e
6356 x 0.6
=TR x 0.117
6. Split AC, Ductable split, Package unit = 1.2KW/TR
7. Ventilation (inlet fan) = Vent.Cfm x 1.2 x 0.745
6356 x 0.6
8. Kitchen (supply) = Vent.Cfm x 1.5 x 0.745
6356 x 0.6
9. Kitchen (exhaust) = Vent.Cfm x 4 x 0.745
6356 x 0.6
GENERAL APPLIANCES LOAD
8/20/2019 HVAC Thumprule Handbook
17/19
Thumb rules for HVAC design
16 | P a g e
DUCT STATIC PRESSURE CALCULATION
1. Filter pressure drop can be calculated from the table below
2. Coil side pressure drop can be calculated from the table
3. Volume Control Damper – 7.5 mm
4.
Grill – 2.5 mm
5. Silencer – Max allowable pre drop is 7.5 mm
6. Diffuser – 2.5 mm
7. Nozzle – From catalogue
Thumb rules for HVAC design
21 | P a g e
8/20/2019 HVAC Thumprule Handbook
18/19
Thumb rules for HVAC design
20 | P a g e
Thumb rules for HVAC design
17 | P a g e
8. VAV – 2 mm
9. Duct pressure from the chart below or using duct sizer
10. Equivalent bend length and taper length can be calculated from the chart below
8/20/2019 HVAC Thumprule Handbook
19/19
Thumb rules for HVAC design
18 | P a g e
Thumb rules for HVAC design
19 | P a g e