125/250/500 WATT
Occupant Warning & System
Installation, Commissioning & Operation
MAN1549-2
125/250/500Watt Occupant Warning System
TABLE OF CONTENTS Page No.
1 About This Manual ............................................................................................................... 1
1.1 Introduction ................................................................................................................ 1
1.2 Symbols ..................................................................................................................... 1
2 Evacuation Control............................................................................................................... 2
2.1 EV20 Audio Line Driver .............................................................................................. 2
2.2 Features ..................................................................................................................... 2
2.3 Operation ................................................................................................................... 3
2.4 Options ...................................................................................................................... 3
2.4.1 Public Address ............................................................................................... 3
2.4.2 Verbal Message ............................................................................................. 4
3 Control & Indicator Card ...................................................................................................... 5
3.1.1 Controls ......................................................................................................... 5
3.1.2 Indicators ....................................................................................................... 5
4 125/250/500Watt Amplifier.................................................................................................... 7
4.1 Features ..................................................................................................................... 7
4.2 Audio Connections ..................................................................................................... 8
4.3 Speaker Connections ................................................................................................. 8
4.4 Power Supply ............................................................................................................. 8
4.5 Battery Charging Function .......................................................................................... 8
4.6 Operation ................................................................................................................... 8
4.7 Trouble Shooting ........................................................................................................ 9
5 Line Montoring Unit ............................................................................................................ 10
5.1 Features: .................................................................................................................. 10
5.2 Connection ............................................................................................................... 10
5.3 Speaker Connection ................................................................................................. 11
6 Typical Application............................................................................................................. 13
7 Specifications 20W amplifier ............................................................................................. 14
8 Specifications 250W amplifier ........................................................................................... 15
Page 1
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
1 About This Manual
1.1 Introduction
This manual uses the 250Watt amplifier configuration to out line AMPAC’s high powered, stand alone Occupant Warning System.
1.2 Symbols
Note: Configuration considerations
Observe antistatic precautions
Page 2
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
2 Evacuation Control
The EV20 is a compact single zone occupant warning module that produces
Alert and Evacuation signals
An output that will drive up to 20-watts of speaker load
Is supplied with a switch control card; and
Can be installed into most fire alarm control panels or used as a stand-alone unit in its own enclosure
Driver Stage 20Watt Amplifier Stage
Figure 1: Complete EV20
2.1 EV20 Audio Line Driver
The EV20 is also supplied in a modified form for use as an audio line driver for larger amplification systems. Supplied in this form the 20watt amplification stage is not populated on the PCB.
2.2 Features
Open and short circuit speaker line monitoring and protection
Fault indication
Adjustable ALERT and EVAC level control
FACP input
“Alert” / “Evacuation” changeover time out – 0, 30, 60, 120, 180, 240 or 300 seconds
2.5mm terminals for field wiring
P. A. microphone input (optional)
Verbal messaging (optional)
Page 3
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
2.3 Operation
If an FACP input is received when the rotary switch is in the AUTO position the EV20 will begin to output the Evacuation signal as the factory default setting of the Alert “time out” period is 0. If the alert signal is required the “time out” duration of the “time out” is determined by the setting of the 4 way DIL switch SW1.
The set duration is termed the changeover timeout and ranges from 0 seconds to a maximum of 300 seconds. If the time out is set to 0 sec then the alert tone is bypassed and the evacuation signal commences immediately. The operator can manually stop the signal sequence by turning the rotary switch to the ISOLATE position.
ON
EXAMPLE OFSETTING - 30SECS
0 ( EVAC ONLY - FACTORY SETTING )
30
60
120
180
240
300
ALERT ONLY NO CHANGE OVER
1 2 3 4
SW 1 2 3
SW1 TIMEOUT TABLE
4
SECONDS
MUST ALWAYSBE SET TO OFF
Figure 2: Time Out Setting
Note: SW1/4 MUST ALWAYS be set to “OFF’
2.4 Options
2.4.1 Public Address
An optional microphone and pre-amplifier (Product code 222-0007) is used to provide the public address capabilities.
Figure 3: Microphone Pre-Amplifier
Page 4
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
2.4.2 Verbal Message
The optional verbal message board (Product code 222-0026) is mounted on standoffs to the main board. Audio and control interconnection to the main board is by way of a 5 way IDC cable.
Message
“Emergency Evacuate Now”
Figure 4: Verbal Message Board
0 1 2 3 4Time in seconds
OFF
500Hz
1200Hz
0.5
sec
0.5
sec
"EMERGENCYEVACUATE NOW"
1.5
secs
0.5
sec
0.5
sec
0.5
sec
0.5
sec
Figure 5: Evacuate Signal Timing
Page 5
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
3 Control & Indicator Card
Figure 6: Front Control Card
3.1.1 Controls
When the control switch is in;
AUTOMATIC - occupant warning signals, and if applicable the verbal message, is outputted to the amplifier system in use when it receives a “warning system” signal from the FACP.
ISOLATE – the occupant warning system is isolated from the FACP “warning system” signal and even if the signal is present there will be no output.
PUBLIC ADDRESS – the occupant warning system can be used locally as an optional PA system. The “press to talk” switch is mounted into the side of the microphone.
MANUAL EVACUATION – the occupant warning signal/s will be transmitted over the system.
3.1.2 Indicators
- In the event of an open or short circuit speaker line the LINE FAULT indicator (yellow) will be illuminated
- The LED will be illuminated (yellow) when the occupant warning system is isolated
Page 6
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
2 CORE AUDIO TERMINATED ONE ENDWITH 3 WAY PANDUIT CONNECTOR
+27V
SHEILD
2 CORE AUDIO FITTED WITH 3 WAY PANDUIT CONNECTORS
RED
BLACK
GREY
WHITE
AP
I-7
18
CN
1C
N2
CN
3RL1
8
9CA
1011
12
1
2
3
4 56
7B
SW1
0V
Pin
1
+27V
Pin
2
Sh
ield
P
in 3
Sig
nal P
in 1
Shield
Signal(Red)
VERBAL MESSAGEBOARD PLACEMENT
F1 1A GN
D
OU
T
IN
AUDIO
TO VERBALMESSAGEBOARD
FAULT
+ I
N -
CO
ME
VD
C-
DC
+
341
2
AM
PA
C
TIM
ER
BR
D4
2E
TG
-01
O/P
TO
NE
VO
ICE
CN2
CN1
CN3RV1 RV2
SW
1
C1
4
TB1
TX
1
5 WAYPANDUITEVAC/ALERT CONTROL
PUBLIC ADDRESSPRE-AMP
NOTE: IF THE P.A. OPTION IS NOT FITTED. FIT LINK ACROSSCN3 PINS 1(IN) AND PIN 2(OUT)
SYSTEM POWER
WARNING SYSTEM
-0V
FireFinder (* 302-673)
ZoneSense Plus
TB5/1 TB5/2
+ -WARN SYS
PANEL TERMINAL No
FireFinder (* 302-673)
ZoneSense Plus
TB2/1 TB2/2
CN10/1 CN10/2
PANEL TERMINAL No
47K
+-
PANEL CONNECTIONS
5 WAY CABLEMESSAGE CONTROL
FRONT PANEL
CN2
D090 PHILIPS
ON
1
2
3
4
TX1
TX2
RV1
LE
D1
O/P
O/P
AP
I-4
75
/2
O/P
O/P
TB1
CN1CN3
ET
H
MIC I/PShield
- + + -
IF THE OPTION IS USED THE BOARDIS MOUNTED ON STANDOFFSONTO THE MAIN BOARD IN THEPOSITION INDICATED ABOVE
FRONT PANEL PCB
Sig
nal P
in 2
TONEVOLUME
NOTE: "WARNING SYSTEM" IS AMONITORED FACP O/P.THE EOL IS ONBOARD THE EV20AND IS EFFECTIVELY MADE TO BEO/C (AT TB1) DURING AN EV120FAULT CONDITION.THIS PRODUCES THE FAULTINDICATION AT THE FACP
THE ALERT & EVAC OUTPUTLEVELS ARE SET BY ADJUSTINGRV1 & RV2 RESPECTIVELYFOR 100VAC.* 302-673 - BRIGADE PSU MONITOR BRD
VOICEVOLUME
ISOLATE
LINE FAULT
CN2
CTRL
1
1
1
OCCUPANT WARNING SYSTEM
AUTOMATIC
PUBLIC ADDRESS
MANUAL EVACUATION
LINE FAULT
ISOLATED
TO
EV
AC
DIS
AB
LE
EN
AB
LE
RE
CO
RD
ING
RE
CO
RD
AU
DIO
IN
AM
PA
C
12
/01
/11
BR
D42V
OM
2-
U3
U2
U4
U1 R15
R1
4
R13
R12
R11
R1
0
R9
R8
R7
R6R
5
R4
R3
R2
R1
CN
2
C1
0
C9
C8
C7
C6
C5
C4
C3
C2
C1
C11
C1
2
C1
3
C1
4
C1
5C16
C1
7
CN3
CN
4
R1
6
R17R
18
SW
1
CN
1
R1
9
Figure 7: Typical Wiring Diagram of an EV20 Single Zone OWS complete with P.A and Verbal Message Brd Fitted
Page 7
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
4 125/250/500Watt Amplifier
Note: For the purposes of this manual the 250W amplifier is highlighted in this explanation. Both
models have the same specifications and wiring configurations except for power output.
Figure 8: RedBack Phase 4 Amplifier Front
The output power stage is thermally monitored enabling automatic operation of a long life computer style cooling fan to "off", "low" or "high" air flow through a specially designed tunnel Heatsink. In quiescent or ordinary cycle paging mode the fan is inoperative.
Over temperature sensing is employed to shut down the amplifier in extreme over heat conditions, e.g. extreme over load and /or over drive misuse. Re–start is automatic once normal temperatures are attained.
The output voltage is limited to 110V maximum RMS voltage irrespective of load impedance to prevent damage to speaker load. Standard 100V line PA amplifiers can deliver up to 180 volts or more under conditions of high drive and very light loading. This output over voltage can quickly destroy any loudspeakers connected. In the event of an overload, the output current is limited by the internal circuitry, thus reducing the output voltage at the speaker terminals. The front panel ‘Overload’ LED flashes, indicating a fault with the speaker circuit.
240VAC
4-16Ohm
70V 100VVolume
Line In
Line Out
D CFuse
+-
Input24VDC
ChargingTerminals
+-
Figure 9: RedBack Phase 4 Amplifier Rear
4.1 Features
Multi-stage thermally cued fan cooling
LED bar graph VU meter
Input signal presence indicator
Output peak limited
2U 19" rack mount
pin XLR input, 3 pin XLR loop out
Level control rear mounted
100V, 70V and 4 - 16Ω outputs
Thermal and overload protection
240V AC, or 24V DC operation
300mA 24V battery trickle charge
Australian made
Page 8
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
4.2 Audio Connections
The audio Line Input is via the 3 pin XLR socket on the rear panel. This is a 320mV line level balanced signal. Pin out is printed on the rear of the amplifier.
A balanced, Line Out XLR plug is also available for passing the audio signal on to more amplifiers.
4.3 Speaker Connections
Speakers with a total impedance of 4 to 16 ohms, or speakers fitted with a line transformer may be connected.
Always ensure that the total load of the fitted speakers does not exceed the rated output of the amplifier otherwise damage may result.
Always be especially careful to avoid any short circuits and connections to the wrong terminals.
4.4 Power Supply
Ensure power is switched off at the front panel of the amplifier. Connect either mains power to the IEC socket with the supplied lead, or 24V DC to the terminal connections. As high currents may be drawn (possibly 18 amps) when operating from a 24V DC power supply, confirm the capacity of the DC power supply used.
4.5 Battery Charging Function
To operate the battery charging function a link must be made between the two terminals on the back of the unit (marked as “Charging resistor”). This activates the charging circuit and provides a nominal 24VDC 300mA trickle charge to the battery connected when 240V mains is present. When the mains fails, the amplifier is seamlessly powered from the battery.
4.6 Operation
Confirm all connections are correct. Turn volume on the rear panel of amplifier down. Switch on the power at the front panel. Slowly increase the volume on the amplifier to a suitable audio level.
The Overtemp LED on the front panel indicates the amplifier has shutdown due to excessive heat build-up and/or excessive load on the speaker outputs. The Overload LED indicates excessive load is connected to the amplifier.
The Peak LED indicates when the peak limiting is in operation and the Signal LED is provided to indicate when an input signal is present.
Adequate ventilation is required for the amplifier to work within its rated limit. Ensure the vents and fans are free of obstructions at all times. For the 250W model we recommend that a 1U Vented panel be placed between amplifiers to aid air flow.
Page 9
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
4.7 Trouble Shooting
If the REBACK Phase 4 amplifier fails to deliver the rated performance, check the following:
No Power, No Lights
Make sure amplifier power switch is on. Make sure mains power switch is on at the wall. Check the mains and DC fuse. Replace with only the correct type and rating.
Distorted Output
Check that the speaker type is correct for the output that you are using (i.e. 4-16Ω, 70V or 100V line). Check for any short circuits on the speaker line. Check speaker line impedance. Note: you must use an impedance meter to measure this. See table below for load details.
100V Line Legend
Load Reading
0.5W 20kΩ
0.66W 15kΩ
1W 10kΩ
1.25W 8kΩ
2W 5kΩ
2.5W 4kΩ
5W 2kΩ
7.5W 1.3kΩ
10W 1kΩ
15W 666Ω
20W 500Ω
30W 333Ω
40W 250Ω
60W 166Ω
100W 100Ω
125W 80Ω
250W 40Ω
500W 20Ω
Very Low Output Volume
Make sure that the input is the correct level (check for shorted connectors). Check for any short circuits on the speaker line.
Continually Blows Fuses
Make sure that the speaker line is not shorted. Check speaker types, ratings and if on correct output.
Amplifier Keeps on Cutting In & Out
Make sure that there is adequate ventilation around the amplifier. Check the vent slots on the front are not covered or blocked and the fan on the rear is functioning correctly. Check also speaker types, ratings and for any short circuits on the speaker line.
Page 10
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
5 Line Montoring Unit
This module has been designed to monitor the integrity of 100V Line speaker circuits. It is connected between the amplifier output and the speaker circuit. The module will detect one of three speaker line conditions. (Normal, Short Circuit or Open Circuit). LED indication is provided for each condition. A switched output is provided for each of the fault conditions. These may be used for sounding an alarm or muting the input of the amplifier to prevent excessive current draw in the event of a short circuit. Several modules may be connected to one amplifier for multi-zone installations. To function correctly, the speaker circuit must be wired on a loop-in, loop-out basis with a 100K Ohm end-of-line resistor fitted across the speaker line at the last transformer.
Note: All speakers must be fitted with a 22µF Bi-Polar capacitor fitted on the input of the
transformer.
5.1 Features:
LED Status Indicators
Two switched outputs Operates from a wide supply voltage (15-35 volts DC)
Screw Terminals for all connections
Compact design
Includes Spike protection
No setup or calibration required
Figure 10: Line Monitor Card
5.2 Connection
Mount the module within the amplifier or an appropriate enclosure.
Connect a nominal 24V DC supply (15 - 35V DC) positive pin 1, negative pin 2. The output of the amplifier is connected to the “IN” terminals pins 3 + 4. The speaker line is connected to pins 5 + 6. Pins 7, 8 and 9 are used for monitoring an alarm condition.
PIN 7. Switched negative out in OPEN CIRCUIT condition
PIN 8. Positive 12V
PIN 9.Switched negative out in SHORT CIRCUIT condition
Note: pins 7+9 are only rated at 100mA. For driving loads larger then 100mA use a 12V
interface relay.
Page 11
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
5.3 Speaker Connection
For correct operation the speakers must be wired in a “loop in” “loop out” basis. “T” connections are not permitted. Each speaker must be fitted with a 22µf bipolar capacitor to prevent DC flowing through the speaker transformer. See PDS218-0008 and 0028 for suitable speakers for this application. At the last speaker, the speaker line must be terminated with an end of line (EOL) resistor valued at 100K.
The module continuously sends a DC signal down the speaker line looking for the 100K EOL resistor. If this is present the OK (green) LED lights.
If the 100K is not found i.e.: open circuit the OPEN CIRCUIT (Red) LED lights.
If the EOL resistor is lower than 100K the SHORT CIRCUIT (Yellow) LED lights.
This signal will not interfere with any audio program being sent to the speakers.
When a fault develops the appropriate LED lights and an output appears at either pin 7 or 9. When either pin 7 or 9 receives an output, this could be used to sound an alarm or operate a relay etc.
Several modules can be connected to the output of one amplifier where several speaker circuits are installed. This way each speaker line can be monitored independent of the others.
Relay coil for externalswitched contacts
Short -
Com +
Open -
Output -
Output +
Input -
Input +
-ve 24VDC
+ve 24VDC
OPEN(Red)
SHORT(Yellow)GREEN(Good)
Figure 11: Line Monitor Card (connections)
Wiring pin outs for the Line Monitor. Take care to note the polarity of the wiring as reversing them may cause damage to the amplifier and / or Line Monitor.
100KEOL
LineMonitor
24VDC
100VAmp
+
-
+
-
+
-
Figure 12: Line Monitor Card (wiring)
Correct Speaker Wiring.
Note: the 100KΩ End of Line Resistor, this must be installed on the last speaker in the run
otherwise the Line Monitor will not operate correctly.
Note: the 100Volt tapped line transformers and the 22μF capacitors
Page 12
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
Figure 13: Line Monitor Card Circuit Diagram
Page 13
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
6 Typical Application
30
2-7
18
0
EV
20
CO
NT
RO
L
BR
D4
2E
TG
1-B
CN
12 31
CN
1C
N3
30
2-4
75
C
321C
N1
31
TB
1
MIC
PR
E-A
MP
CN
2321 4 5
1 2
TB
1
43
CN
3C
N2
3
+V
E
-VE
PO
WE
R
FIB
21
10
0V
LIN
EO
/P
TB
1
65 43
97T
B1
LIN
E M
ON
ITO
RIN
G U
NIT
A 2
06
5
TB
1
RL
12 218
12
V
TB
1
+2
4V
0V
I/P
O/P
100K
25
0W
AM
P
LIN
EL
EV
EL
INP
UT
1 2 3
SH
IEL
D
0V
+2
4V
24
0V
PO
WE
RIN
24
VP
OW
ER
IN
10
0V
LIN
EO
/P
C5
& C
647
0uF
63V
(-)
C1
0
(-)
C1
3 (
SH
LD
)W
HIT
E
BLU
E
SH
IELD
2 C
OR
E S
HIE
LD
ED
PIN
1P
IN 2
PIN
3P
IN 4
PIN
5
PIN
1P
IN 2
PIN
3P
IN 4
PIN
5
RL
1/2
EV
AC
UA
TIO
NS
YS
TE
M
EV
20
-B
47K
TB
3
211
00
VO
/P
PS
U
TB
4
(0V
)(+
27
V)
(+B
AT
)
TB
1
(-V
E)
(+V
E)
(+V
E)
(+V
E)
(-V
E)
(-V
E)
BR
D8
5C
LF
B1
CU
RR
EN
T L
IMIT
ER
FU
SE
BO
AR
D
TO
BA
TT
S
CN
1
CN
2
CN
3
CN
4
CN
5
3 4
WA
RN
ING
SY
ST
EM
MO
NIT
OR
ED
33
0-0
03
1
SP
-15
0-2
7
TB
1
5A
PO
WE
R S
UP
PLY
3 2 1
TB
1
6 4
GN
D
N(A
C)
L(A
C)
24
0V
AC
IN
PU
T
VE
+
VE
-F
RO
M P
DL
BL
OC
K
RL
2/2
Figure 14: Typical Application
Page 14
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
7 Specifications 20W amplifier
SUPPLY VOLTAGE 27VDC (nominal)
QUIESCENT CURRENT 41 mA
MAX. CURRENT DRAW 650 mA
MAX. SPEAKER LOAD 20 Watt RMS (100V line)
ALERT SIGNAL
0 1 2 3 4
0.625sec
0.625sec
ON
OFF
420Hz 420Hz 420Hz
Time in seconds
Australian AS1670.4 Alert Signal
AS1670.4: 420Hz pulsed on and off for 0.625 of a second at 1.25 second intervals
EVACUATION SIGNAL
0 1 2 3 4Time in seconds
OFF
500Hz
1200HzAustralian AS1670.4 Evacuate Signal
0.5
sec
0.5
sec
1.5
secs
0.5
sec
0.5
sec
0.5
sec
0.5
sec
AS1670.4: 0.5 of a second sweep signal 500-1200 Hz pulsed on and off 3 times in 2.5 seconds at 4 second intervals
SPEAKER EOL RESISTOR 47k ohms
FACP INPUT Monitored
DIMENSIONS (mm)
Main EV20 Board 180H x 82W x 55D
Control Card 90H x 35W x 40D
P.A. Input Board (Opt.) 63H x 35W x 18D
Microphone Pre-amplifier Board
SUPPLY VOLTAGE 27VDC (nominal)
QUIESCENT CURRENT 21mA
Voice Messaging Board
SUPPLY VOLTAGE Regulated +5VDC
QUIESCENT CURRENT 1.4mA
Page 15
OCCUPANT WARNNG SYSTEM INSTALLATION, COMMISSIONING & OPERATION
8 Specifications 250W amplifier
Power output 250 watts RMS
Distortion < 0.5%, @ 1kHz
Frequency response 50Hz - 15kHz, -3dB
Output line 100V, 70V, or 4 - 16Ω
Input sensitivity 500mV balanced
Signal to noise ratio (peak limiting bypassed) > 90 dB
Line output 600Ω balanced, 0dBV
Output Connectors
Speakers Screw terminals
Line out 3 pin XLR
Trickle charge Screw terminals
Input Connectors
Inputs 3 pin XLR balanced
24VDC – 30VDC power Screw terminals
240VAC power IEC power connector
Controls / indicators / Power / Protection / Mechanical
Master Volume (on rear panel)
Power On / Off switch
Indicators Power, Fault, VU meter, Signal Present, Output Peak Limiting and Over Current
Power supply 240VAC or 24VDC (nominal)
Fuse Protection
5A AC and 10A DC (125W)
7.5A AC and 20A DC (250W)
10A AC and 2 x 10A DC (500W)
UNCONTROLLED DOCUMENT
NOTE: Due to Ampac’s commitment to continuous improvement specifications may change without notice.