BORGER VACUUM / COKER ELECTRICAL LOAD LISTNON-MOTOR LOADS
File: document.xlsTab: NonMotorLoad
Sheet 1 of 14 Printed: 21:51:32 04/07/2023
Equipment QUANTITY POWER_REQ Plant Area Bus ID VFD Y/N EST_ACT Priority RUN_INT_SP Description Load Load % PF 1-PHASE Phase Cont Interm Spare Delta-Wye-Grd Grounding Operating Service Type Comment Cable ID Cable 1 or 3 No per Cable Cable Cable Length
ID Voltage kVA Y/N Conn DF DF DF Connection Type Load (kVA) 1 = In Service Voltage Cond Phase Size Length Unit280-EE-0750AKS 1 Y 280-EE-0700A N EST 0 C POWER FACTOR CORRECTIONCAPACITOR 11000 2000 90 100 30 10 0 1
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD1
23456789
1011121314151617181920212223242526272829303132333435363738394041424344454647484950515253545556575859606162636465666768697071727374757677787980818283848586
BORGER VACUUM / COKER ELECTRICAL LOAD LISTNON-MOTOR LOADS
File: document.xlsTab: NonMotorLoad
Sheet 2 of 14 Printed: 21:51:32 04/07/2023
ID Voltage kVA Y/N Conn DF DF DF Connection Type Load (kVA) 1 = In Service Voltage Cond Phase Size Length Unit
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD4
8788899091
BORGER VACUUM / COKER ELECTRICAL LOAD LISTHEATER LOADS
File: document.xlsTab: Heater
Sheet 3 of 14 Printed: 21:51:32 04/07/2023
Equipment QUANTITY POWER_REQ Plant Area Bus ID EST_ACT Priority RUN_INT_SP Description Heater Heater % PF 1-PHASE Phase Cont Interm Spare Delta-Wye-Grd Grounding Operating Service Type Comment Cable ID Cable 1 or 3 No per Cable Cable Cable Length
ID Voltage kW Y/N Conn DF DF DF Connection Type Load (kW) 1 = In Service Voltage Cond Phase Size Length UnitS-110-TRACE 1 Y 4A1 280-EE-0700A EST 0 Run Caustic Line Heat Tracing 480 15.00 100 100.00 50.00 0.00 15.00 1 600 3 1 6 450 Feet
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD1
2
345
Secondary Bus ID Tertiary Bus ID Temp Rise Transformer Primary Rating
Transformer Primary Rating
UOM
Primary Voltage
Primary Voltage UOM
Secondary Voltage
Secondary Voltage UOM
Tertiary Voltage
Tertiary Voltage UOM
Secondary Rating
Secondary Rating UOM
Tertiary Rating
Cooling Code Pri-Sec X/RTertiary Rating UOM
Pri-Sec Impedance
Pri-Sec Impedance
UOM
Pri-Ter Impedance
Pri-Ter Impedance
UOM
Sec-Ter Impedance
Sec-Ter Impedance
UOM
Equipment QUANTITY Description POWER_REQ Primary Bus ID
ID280-ET-0511A 1 33/11.5KV SUB 5 Y 280-EE-0500A280-ET-0700A 1 33/11.5KV SUB 7 Y 280-EE-0500A
Secondary Bus ID Temp Rise
280-EE-0501A 65 450000 1 33000 V 11000280-EE-0700A 65 450000 1 33000 V 11000
Transformer Primary
Rating
Transformer Primary
Rating UOM
Primary Voltage
Primary Voltage UOM
Secondary Voltage
K Factor Standard
V 10 OhmV 10 Ohm
Secondary Voltage UOM
Pri-Sec Impedance
Pri-Sec Impedance
UOM
Basic Impulse
Level
Basic Impulse
Level UOM
Cooling Code
Max Transforme
r Rating
BORGER VACUUM / COKER ELECTRICAL LOAD LISTMOTOR LOADS
File: document.xlsTab: Motor
Sheet 13 of 14 Printed: 21:51:32 04/07/2023
Equipment QUANTITY POWER_REQ VFD Y/N Plant Area Bus ID EST_ACT Priority Description Motor Motor NP Brake 1-PHASE Phase Cont Interm Spare %PF %PF %PF %EFF %EFF %EFF % Locked % Starting Starting Delta-Wye Grounding Grd Device Rated % Slip Service Stall Time Stall Time Service Type Comment Cable ID Cable 1 or 3 No per Cable Cable Cable Length
ID Voltage kW kW Y/N Conn DF DF DF 100% 75% 50% 100% 75% 50% Rotor Current PF Device Connection Type Amp Rating RPM Factor Hot Start Cold Start 1 = In Service Voltage Cond Phase Size Length Unit
141-CM-101A 1 Y N 280-EE-0501A EST 0 C BOOSTER COMPRESSORAFTERCO 415 37 26.3 100 30 10 86 91 20 0 0 1 1500 2 1 1 INFO FROM HEAT EXCHANGER DATA SHEET262-PM-201A 1 Y N 280-EE-0700A EST 0 C CONDENSATE COLLECTION PUM 415 22 15 100 30 10 88 90 20 0 0 1 1500 1 1 1 ESTIMATED ABSORBED LOAD262-PM-201B 1 Y N 280-EE-0501A EST 0 C CONDENSATE COLLECTION PUM 415 22 15 100 30 10 88 90 20 0 0 1 1500 1 1 1 ESTIMATED ABSORBED LOAD
RUN_INT_SP
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AD AE AF AG AH AI AJ AK AL AM AN AO AP AQ AR1
2
3
456789
10111213141516171819202122232425262728293031323334353637383940414243444546474849505152535455565758596061626364656667686970717273747576777879808182838485
BORGER VACUUM / COKER ELECTRICAL LOAD LISTSWITCHGEAR AND MCC BUS LIST
File: document.xlsTab: Bus
Sheet 14 of 14 Printed: 21:51:32 04/07/2023
Equipment POWER_REQ Bus Initial Description Upstream Bus Min % DF Max % DF ANSI or IEC Bus Type Cont Bracing Bracing Bracing Bracing Comment
ID Voltage % Voltage ID Rating (A) Crest (kA)
280-EE-0500A YES 33000 100 SUB 5 33KV BUS A 80 100 1 2 2500 1
280-EE-0501A YES 11000 100 SUB 5 11KV BUS A 80 100 1 2 2500 1
280-EE-0700A YES 11000 100 SUB 7 11KV BUS A 80 100 1 2 1600 1
Service Type
Symm RMS (kA)
ASymm RMS (kA)
Peak kA (IEC)
1 = In Service
A B C D E F G H I J K L M N O P Q12
3
4
56789
1011121314151617181920212223242526272829303132333435363738394041424344